Você está na página 1de 2

FireFightingQCDExamQuestions

Totalquestion:25
Time:90Minutes
PassMark:70%&above
1.DrawFireFightingRaiserDiagramandmark20pointsof2b+G+10HighRaiseBuilding
2.MinimumrequiredseparationdistanceofnonfireratedconstructionPumproomfromBuilding.(50
ft)
3.RangeofmeasuringinstrumenttocomparewithPumprating(Double)
4.whatistheuseofvalveusedsuctionlineofJockeyPump(Isolation)
5..PressuregaugeusedtocheckPumpPerformance(New&Calibrated)
6.MinimumcalibrationperiodofPressureGauge(1Year)
7...:Equipment,materials,orservicesincludedinalistpublishedbyan
Organizationthatisacceptabletotheauthorityhavingjurisdictionandconcernedwith
Evaluationofproductsorservices,thatmaintainsperiodicinspectionofproductionoflisted
Equipmentormaterialsorperiodicevaluationofservices,andwhoselistingstatesthat
Eithertheequipment,material,orservicemeetsappropriatedesignatedstandardsorhas
Beentestedandfoundsuitableforaspecifiedpurpose.(Listed)
8isAnorganization,office,orindividual
Responsibleforenforcingtherequirementsofacodeorstandard,orforapproving
Equipment,materials,aninstallation,oraprocedure.(AHJ)
9Indicatesamandatoryrequirement.(Shall)
10..isAnautomaticvalveinstalledonthedischargesideofapositive
Displacementpumptorelievepressurepriortothepumpdriverreachingoperatingspeed.(
DumpValve.)
11.Adevicethatallowsthediversionofliquidtolimitexcesspressure
inasystem(ReliefValve)
12.Pipewithfilledwatercapacitytakingforseismicdesign(5Times)
13.Drainconnectionrequiredfor4StandPipe(2)
14.Equipmentormaterialstowhichhasbeenattachedalabel,symbol,orother
identifyingmarkofanorganizationthatisacceptabletotheauthorityhavingjurisdiction
andconcernedwithproductevaluation,thatmaintainsperiodicinspectionofproductionof
labeledequipmentormaterials,andbywhoselabelingthemanufacturerindicates
compliancewithappropriatestandardsorperformanceinaspecifiedmanner(Labled)
15.Apilotoperatedvalveinstalledindischargepiping
thatmaintainspositivepressureinthesuctionpiping,whilemonitoringpressureinthe
suctionpipingthroughasensingline.(LowSuctionThrottlingValve.)
16.Avalvethatisdesignedtorelieveexcessflowbelowpump
capacityatsetpumppressure.(UnloaderValve.)
17.Acentrifugalfirepumpforfireprotectionshallbeselectedtooperateatlessthanor
equaltopercentoftheratedcapacity.(150%)
18.Asinglesuctionpumphavingitssuctionnozzleonthe
oppositesideofthecasingfromthestuffingboxandhavingthefaceofthesuctionnozzle
perpendiculartothelongitudinalaxisoftheshaft.(EndSuctionPump.)
19.Themotorcapacityinhorsepowershallbesuchthatthemaximummotorcurrentin
anyphaseunderanyconditionofpumploadandvoltageunbalanceshall..the
motorratedfullloadcurrentmultipliedbytheservicefactor.(notexceed)
20.Eachfireextinguishershallhaveatagorlabel
securelyattachedthatindicatesthe(monthandyearthemaintenancewas
performed,thepersonperformingthework,nameoftheagencyperforming
thework)
21.CodeusedforCleanAgentFireExtinguishingSystems(NFPA2001)
22.Minimumnumberofsparesprinklerrequiredsprinklerinthesystemhaving250Nos
sprinkler(Atleast6Nos)
23.SprinklerBulbcolorforExtraHighHazardzone(Purple)
24. The maximum service factor at which a motor shall be used is..(1.15)
25. The horsepower capability of the engine, when equipped for fire pump service,
shall not be less than percent greater than the listed horsepower on the engine
nameplate.(10%)

Você também pode gostar