Você está na página 1de 11

Shell and tube heat exchangers

Model series

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
Quality shell and tube exchangers from specialists
ViFlow has the exclusive right to sell FUNKEs products in Finland. The company was founded in
1974 and focus on designing and manufacturing of heat exchangers for nearly all industrial
applications as well as also for the HVAC sectory.
The partnership with FUNKE broadens ViFlows product base, we can now offer the right heat
exchanger type for every customer.

In the area of shell and tube heat exchangers we can offer a mature product range of special models
for almost all requirements in machine and plant enginering. Maximum quality requirements and
customer-oriented solutions characterise the brand FUNKE. Customised process gas coolers with
operating pressure of 400 bar and above are nothing unusual. However, with the series models we
already offer our customers in our standard programme a comprehensive and high quality range of
products for all current requirements in international machine and plant engineering.
The customer receives thermodynamically optimised units which are manufacture in defined
graduations e.g. with regard to shell diameter and shell and tube length and which are available at
short notice.

Shell and tube exchangers - the model series

TDW, BCF, CCFA, SWF, Basic technical data


CPS, WRA 200 Performance 1 KW-30 MW

Transfer surface 0,11 m2 - 2000 m2


Preselected apparatus geometries provide for:
Shell diameter 60 mm - 2000 mm
short delivery periods
excellent price/performance ratio Operating temperature -20 C - 500 C
assurance of models proven over years
Operating pressure max. 600 bar

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
Shell and tube exchanger -structure and functioning
The shell and tube heat exchanger is a non-
fired pressure system consisting of two
separate pressure chambers (shell chamber
and tube chamber). Separated by the internal
tube wall, two media flow past one another
with such alignment that, if there is a
temperature difference, they will mutually
exchange heat without mixing in the process.
One medium flows through the shell chamber
and the second medium flows through the
tube chamber. The flow through the shell
chamber will be controlled by baffles such that
there is as much cross-flow to the tubes as
possible. The form and spacing of the baffles
will be adapted to the relevant operational use.
Depending on effectiveness, speed and
pressure loss the flow through the tube
chamber will be effected by a single pass or
by multiple passes. With the exception of
radiation losses, the input heat quantity is the
same as the output heat quantity.

Components of the shell and tube heat exchanger


3 5 1 4 6 5 2
7 7 7 7 However, an effective heat exchange can only
occur if there is a sufficient temperature
difference. The greater the temperature
difference is the smaller will be the re-quired
heat transfer surface. The heat transfer
performance of a heat exchanger is the
product calculated from the mean logarithmic
temperature difference, the heat transfer
surface and the heat transfer coefficient. The
latter will be largely determined by the flow
1. Heat exchanger shell 5. Tubesheets characteristics of the media, that is by the
2. Connection shell 6. Baffles geometric design.
3. Guide chamber 7. Apparatus seal
4. Internal tubes On the other hand, the supplier of heat
exchangers must have a wide application
know-how with regard to the thermodynamic
properties of special media at pertinent
pressures and temperatures. This also
concerns the issues of fouling factor and
material compatibility.

The calculation and design of FUNKE heat


exchangers is effected with worldwide leading
programs (e.g. HTRI, Heat Transfer Research
Institute, USA) as well as with FUNKE-
Software which is already used
internationally.
Design of a CP standart unit using 3D software

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
TDW
Compact heat Exchanger for the cooling of hydrauric oils and hydraulic oils and hydraulic oils
replacement liquids

TURBO-SPIN HEAT EXCHANGER

removable tube bundle


surface 0.15-4.00 m2

Two versions available:

O-version for liquid oils


W-version for viscocid oils

sealing with o-rings


multi-pass design
easy to integrate in in oil supply system or
drive and control units
according to PED (97/23/EG)
article 3, paragraph 3 => No CE-mark

COMPONENT MATERIAL STANDARD MATERIAL OPTIONAL MATERIAL HYDRAULIC


REPCAMENT FLUIDS

Internal tubes Cu-DHP-R250, tin-plated on CuNi10Fe, tin-plated on the oil


the oil contact side contact side

Tubesheets Syntetic material with AI


composite material

Helical screws GD-ZnAI4Cu1 Tin plated

Shell AIMgSi0, 0,5F22

Connection chamber B-AISi10Mg

Seals NBR

Coat of paint RAL 5012, light blue

Clamp type feet St 37

MEDIA ROUTING MAX. OPERATING TEST OVERPRESSURE MAX. OPERATING


OVERPRESSURE TEMPERATURE

Shell side 16 bar 21 bar 100 C

Tube side 8 bar 11 bar 100 C

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
BCF/CCF/SSCF
Modular system construction for universal use. Primarly used as fluid cooler for oil, water or other
operating fluids

UNIVERSAL HEAT EXCHANGER

BCF Brass, fixed tube bundle


CCF Carbon steel, fixed tube bundle
SSCF Stainless steel, fixed tube bundle
BCP Brass, removable tube bundle
CCP Carbon steel, removable tube bundle
SSCP Stainless steel, removable tube bundle

O-versions for close baffle spacing


W-version for wide baffle spacing
horizontal or vertical installation
fluid cooler for oils, waters or other
operating medias
surface 0.11-11.45 m2

PED in accordance with article 3,


paragraph 3 => No CE-mark
Only for BCF horizontal version PED module B

COMPONENT MATERIAL STANDARD

BCF/BCP CCF/CCP SSCF/SSCP

Internal tubes CuZn28Sn1 F32 St35, St35.8I 1.4571

Tubesheets CuZn40Pb2 (CW617N) GS 45 1.4408

Baffles CuZn37 (CW508L) 1.4571 1.4571

Shell CuZn37 Pb0.5 (CW604N) St35.8I 1.4571

Connection chambers, Stand EN-GJL-200 EN-GJL-200 1.4408

Seals Klinger C4400 Klinger C4400 Klinger C4400


Arostat 6204 Arostat 6204 Arostat 6204

Coat of paint RAL 5012, light blue RAL 5012, light blue pickled and passivized

Angular feet S235JRG2 S235JRG2 1.4571

Insulation Mineral wool, Mineral wool, Mineral wool,


galvanized with steel sheet galvanized with steel sheet galvanized with steel sheet

MEDIA ROUTING MAX. OPERATING TEST MAX. OPERATING TEMPERATURE


OVERPRESSURE OVERPRESSURE

Shell side 16 bar 24 bar BCF/P CCF/P SSCF/P

Tube side 10 bar 15 bar 150 C 110 C 230 C

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
CCFA/SSCFS
Further development of the BCF-series for usage as gas cooler.
Manifold usage as air and gas cooler. May also be used as intermediate cooler or after cooler.

GAS COOLING HEAT EXCHANGER

CCFA
Carbon steel with fixed tube bundle

SSCFA
Stainless steel version

tube side only one-pass


(gas flowing through the tubes)
can be integrated into the gas pipe work

horizontal or vertical installation


air or gas cooler
gas pre-heating is also possible
higher operating pressure possible

PED (97/23/EG) in accordance with the


AD 2000 regulations

COMPONENT MATERIAL CCFA MATERIAL SSCFA OPTIONAL

Internal tubes 1.4571 1.4571 CuNi30Fe

Tubesheets or connection P 265 GH 1.4571 CCFA mating flanges, seals


flange and bolts

Baffles 1.4571 1.4571

Shell St35.8I 1.4571

Coat of paint RAL 5012, light blue pickled and passivized other RAL shades /CCFA

Clamp type feet S235JRG2 1.4571

MEDIA ROUTING MAX. OPERATING TEST OVERPRESSURE MAX. OPERATING


OVERPRESSURE TEMPERATURE

Shell side 16 bar 24 bar 230 C

Tube side 8 bar 15 bar 230 C

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
SWF/SWP/SSWF/SSWP
Safety heat exchanger for usage where leakage or mixing of operating media is not acceptable.
In case of leakage of the shell or tube side the corresponding change in pressure is detected by the
pressure control device in the safety space and is signalled accordingly.

SAFETY HEAT EXCHANGER

Three chamber devices with straight internal


tubes and fixed ( F ) or removable ( P ) tube
bundle.

Each individual tube has a smaller internal


tube, which prevents a mixing of the following
operating media.

Double tube sheets produce the enclosed


safety space, wich is filled with a special
barrier fluid and is checked for pressure
changes.

This type is used when following issues have


special importance:
Environmental protection
Health protection
Cost of operating resources

PED 97/23/EG AD 2000 Chemical reactions between operating


medias can be dangerous.
Contaminated liquid removal from surface
water or boiler water.
Closed circles for refilling media.

COMPONENT MATERIAL SWF/P MATERIAL SSWF/P OPTIONAL

Shell St35.8I 1.4571 possible

Tubesheets P 265 GH 1.4571 possible

Angular feet RSt37-2 1.4571

Coat of paint RAL 5012, light blue pickled and passivized other RAL shades at SWF/P

MEDIA ROUTING MAX. OPERATING TEST OVERPRESSURE MAX. OPERATING


OVERPRESSURE TEMPERATURE

Shell side 16 bar 24 bar 150 C

Tube side 10 bar 15 bar 150 C

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
CPS
The operational use of this heat exchanger as a fluid cooler is wide and varied. It is predominantly
used as a standard oil cooler or water cooler.

STANDARD HEAT EXCHANGER

PED (97/23/EG) in accordance with the


AD 2000 regulations, close to TEMA type
BEW.

Heat exchanger surface 0.47-104.02 m2

Straight internal tubes and a removable


floating tube bundle.

Two sealing rings and a leakage ring


between the device flanges protects
against a mixing of the shell side and
tube side media.

Two versions of the connection and guide


chambers are available.

Common type for different kind of liquids.

COMPONENT MATERIAL OPTIONAL REMARKS

Internal tubes CuZn28Sn1F32 Refined steel, 1.4571

Tubesheets CuZn38SnAIF39 Refined steel, 1.4571

Baffles CuZn37 Refined steel, 1.4571

Shell St35.8I

Connection/guide chamber GG 25

Clamp-type feet S235JRG2

Coat of paint Zinc phosphate primer pickled and passivized Grey/green

MEDIA ROUTING MAX. OPERATING TEST OVERPRESSURE MAX. OPERATING


OVERPRESSURE TEMPERATURE

Shell side 20 bar According to DGRL 110 C

Tube side 10 bar According to DGRL 80 C

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
WRA 200
Specially developed for heat recovery from the exhaust gases of stationary compustion
engines in block-type thermal power stations.

EXHAUST GAS HEAT EXCHANGER

The principle of media routing here is:


"Exhaust gas through the tubes."
Tube side one pass, more tube dimensions.
The heat exchanger has straight internal
tubes and fixed non-removable tube bundle
whose shell tube is welded to the tubesheet
so that the joint is tightly sealed. Termal
shield protects the tube/tubesheet
connections against overheating and heat
accumulation.
Axial compensator in the casing tube can be
installed. Gas side chambers are equipped
with inspection covers.

In accordance with all pertinent national and


international certification bodies, regulations
and construction regulations such as
Pressure Eguipment Directive, AD 2000,
WRA 200
Detail thermal sheet ASME- VIII, U-Stamp, TEMA standard,
CHINA-SQL. Customer specifications is no
problem either.

COMPONENT MATERIAL OPTIONAL REMARKS

Internal tubes Refined steel, 1.4571 St35.8I

Tubesheets Refined steel, 1.4571

Baffles Refined steel, 1.4571

Shell St35.8I

Connection/guide chamber St35.8I / P 265 GH


gas inlet

Connection/guide chamber Refined steel, 1.4571


gas outlet

Coat of paint Silicon aluminium colour Refined steel, pickled and


passivized

MEDIA ROUTING MAX. OPERATING TEST OVERPRESSURE MAX. OPERATING


OVERPRESSURE TEMPERATURE

Shell side 10 bar 150 C

Tube side 0,5 bar 550 C

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
References

High performance pumps Lubricant cooling

Lubricant cooling Hydrogen cooling

Compressed air cooling Ship engine cooling

Other commonly used areas:


Process gas cooling, sulphuric acid, methanol cooling and oil supply systems.

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi
Optional materials for the model series BCF/P, CCF/P, SSCF/P
COMPONENT BCF/BCP CCF/CCP SSCF/SSCP

Internal tubes CuZn20Al F34, CuNi30Fe F37, 1.4571, CuNi30Fe, CuZn20Al F34
SF-Cu F22 (F25), 1.4571

Tubesheets CuZn39Pb3 P265GH as a fixed tubesheet as 1.4571 in the case of the P


well as version
1.4571 as a floating tubesheet for
the P version

Baffles

Shell Flange connections, shell side, Flange connections screwed in Flange connections, shell side,
screwed in on screwed in
the shell side

Connection chambers, Plastic coating, G-CuSn 10 Plastic coating, G-CuSn10 Stand only made of of
Stand Stand not made of G-CuSn 10 Stand not made of G-CuSn 10 EN-GJL-200

Seals PTFE, Viton PTFE, Viton PTFE, Viton

Coat of paint Other RAL colours, priming coat Other RAL colours, priming coat

Angular feet Clamp feet made of S235JRG2 Clamp feet made of S235JRG2 Clamp feet made of 1.4571

Insulation Only in combination with angular Only in combination with angular Only in combination with angular
feet feet feet

Quality
Quality means safety. Each unit is construction and pressure tested before leaving the factory.
ViFlow Finland helps the customer with the maintenance and spare parts of all the products that we
sell. Our service does not end with the delivery of the product.

ViFlow Finland Oy is part of ViFlow Group, one of the leading suppliers of heat exchangers and pressure vessels in the
Nordic Region.
Beside of the shell and tube heat exchangers introduced in this leaflet we also manufacture own shell and tube heat
exchangers. The product range is completed with gasketed plate heat exchangers, brazed plate heat exchangers, totally
laserwelded plate and shell heat exchangers, tanks, reactors and other production equipment.
Contact us for more information.

ViFlow Finland Oy Kauppakartanontie 7 A 1 00930 Helsinki puh. +358 40 178 0920 fax +358 9 4789 2800
viflow@viflow.fi www.viflow.fi