Você está na página 1de 12

Transmission Line Protection

Transmission Line Protection Applications 144


Transmission line protection reliability issues and how GE Multilin products provide enhanced reliability
through special techniques and methods are described in this section. Different transmission line protection
applications and how GE Multilin products fit into each are provided at the end of the section.

Selector Guide Complete transmission line protection product comparison 154


A reference table highlighing the feature set for each protection system

L90 Phase segregated line current differential protection 155


The L90 provides high-speed current differential protection suitable for transmission lines and cables of
various voltage levels. The L90 supports dual breaker applications suitable for single and three-pole tripping
applications. The L90 uses synchronized sampling at each relay to limit the impact of communications
channel issues. The differential element employs an adaptive restraint to balance sensitivity for internal
faults and security during external faults. The L90 supports inter-relay protection communications via direct
fiber as well as different interfaces including RS422, G.703 and C37.94. The L90 also provides Synchrophasor
measurement over Ethernet as per IEEE C37.118.

L60 Sub-cycle phase comparison protection 163


The L60 provides fast and secure sub-cycle phase comparison protection, for both two-terminal and three-
terminal lines, lines with series compensation and for single-pole and three-pole tripping applications. The L60
can operate using existing Power Line Carrier or fiber optic communications, and compensates for channel
asymmetry and charging currents. The L60 can provide complete support of dual-breaker line terminals by
using multiple current inputs. Supports both dual and single phase comparison, and can be configured for
tripping or blocking applications.

D90Plus Sub-cycle line distance protection & advanced automation controller 171
The D90Plus is a sub-cycle line distance protection system and bay controller suitable for protecting transmission
lines and cables including lines equipped with series compensation. The D90Plus supports dual-breaker
applications and can be used for single or three-pole tripping. The D90Plus supports different teleprotection
schemes, including DCB, DCU, POTT, Hybrid POTT, and PUTT. The D90 Plus also provides Synchrophasor
measurement over Ethernet per IEEE C37.118. The automation controller, dedicated programmable logic
separate from programmable logic for protection applications, color annunciator and HMI panels make
D90Plus a stand-alone substation controller.

181
D60 Transmission line protection with three/single pole tripping
The D60 is suitable for protecting transmission lines and cables including lines equipped with series
compensation. The D60 supports dual-breaker applications and can be applied in single-pole or three-pole
tripping applications. The D60 is applicable to different teleprotection schemes, including DCB, DCU, POTT,
Hybrid POTT, and PUTT, and includes inter-relay protection communications via direct fiber as well as different
interfaces including RS422, G.703 and C37.94. The D60 also provides Synchrophasor measurement over
Ethernet per IEEE C37.118.

D30 Cost-effective, three pole, primary and backup distance protection 189
The D30 is a cost-effective distance protection system suitable for primary protection of sub-transmission lines
and as a backup protection for HV, EHV lines, reactors and generators. The D30 provides three zones of phase
and ground distance protection along with complete overcurrent and voltage protection functions intended
for three-pole tripping applications. The D30 comes with versatile automation features using which custom
pilot schemes can be built. The D30 also includes inter-relay protection communications via direct fiber as well
as different interfaces including RS422, G.703 and C37.94.

g Multilin
143
TRANSMISSION lINE Protection Applications

Introduction
Transmission lines are a vital part of the electrical distribution system,
as they provide the path to transfer power between generation and
load. Transmission lines operate at voltage levels from 69kV to
765kV, and are ideally tightly interconnected for reliable operation.
Factors like de-regulated market environment, economics, right-
of-way clearance and environmental requirements have pushed
utilities to operate transmission lines close to their operating limits.
Any fault, if not detected and isolated quickly will cascade into a
system wide disturbance causing widespread outages for a tightly
interconnected system operating close to its limits.
Transmission protection systems are designed to identify the
location of faults and isolate only the faulted section . The key
challenge to the transmission line protection lies in reliably detecting
and isolating faults compromising the security of the system.

Factors influencing line protection


The high level factors influencing line protection include the simplicity and security for single pole tripping, dependability for
criticality of the line (in terms of load transfer and system stability), protection communications between line terminals, security for
fault clearing time requirements for system stability, line length, the dual-breaker line terminals, and simplicity and dependability of
system feeding the line, the configuration of the line (the number redundant protection schemes.
of terminals, the physical construction of the line, the presence
of parallel lines), the line loading, the types of communications Single -pole tripping
available, and failure modes of various protection equipment. Single pole tripping using distance protection is a challenging
The more detailed factors for transmission line protection directly application. A distance relay must correctly identify a single-phase
address dependability and security for a specific application. The fault, and trip only the circuit breaker pole for the faulted phase. The
protection system selected should provide redundancy to limit relay also must initiate the recloser and breaker failure elements
the impact of device failure, and backup protection to ensure correctly on the fault event. The distance elements protecting the
dependability. Reclosing may be applied to keep the line in service unfaulted phases must maintain security during the open-pole
for temporary faults, such as lightning strikes. The maximum load condition and any reclosing attempts.
current level will impact the sensitivity of protection functions, and The D90Plus Line Protection System and D60 Line Distance Relay use
may require adjustment to protection functions settings during simple, dedicated control logic for single pole tripping applications.
certain operating circumstances. Single-pole tripping applications This control logic uses a Phase Selector, Trip Output and Open
impact the performance requirements of distance elements, Pole Detector in conjunction with other elements as shown in the
differential elements, and communications schemes. simplified block diagram.
The physical construction of the transmission line is also a factor The Trip Output is the central logic of single pole tripping. The Trip
in protection system application. The type of conductor, the size of Output combines information from the Open Pole Detector, Phase
conductor, and spacing of conductors determines the impedance of Selector, and protection elements to issue a single pole or three pole
the line, and the physical response to short circuit conditions, as well trip, and also to initiate automatic reclosing and breaker failure. The
as line charging current. In addition, the number of line terminals Phase Selector is the key element for maintaining the security of
determines load and fault current flow, which must be accounted single pole tripping applications, quickly and accurately identifying
for by the protection system. Parallel lines also impact relaying,
as mutual coupling influences the ground current measured by
Reset Open Pole
protective relays. The presence of tapped transformers on a line, or
V, I Open Pole(s)
reactive compensation devices such as series capacitor banks or Phase Selector Trip Output
shunt reactors, also influences the choice of protection system, and
the actual protection device settings. 21P Init BF

AR

GE Multilin Application Advantages 21G

Before considering using a GE Multilin relay for a specific transmission Dir. Supv.

line protection application, it is important to understand how the


Open Pole
relay meets some more general application requirements for Detector
simplicity, security, and dependability. GE Multilin relays provide
Single pole trip logic

144 www.GEMultilin.com
TRANSMISSION lINE Protection Applications

the faulted phase or phases based on measured currents and or dual-channel, to support point-to-point communications, dual
voltages, by looking at the phase angles between the positive point-to-point communications, or ring communications between
sequence, negative-sequence, and zero-sequence components. up to 16 relays.
The Open Pole Detector ensures the relay operates correctly during Line Current Differential: Communications is an integral piece of
a single pole trip, placing the relay in an open pole condition when a line differential relay, as the currents from one line terminal must
a single pole trip command is issued, or one pole of the circuit be sent to relays at other line terminals to perform the differential
breaker is open. The Open Pole Detector asserts on a single pole calculation. This requires the use of a digital communications
trip command, before the circuit breaker pole actually opens, to channel, which is commonly a multiplexed channel where channel
block protection elements that may misoperate under an open switching may occur. The analog information must be precisely time
pole condition, such as negative sequence elements, undervoltage synchronized between the line ends for the differential calculation
protection, and phase distance elements associated with the to be correct. Synchronization errors show up as phase angle offset,
faulted phase (for example, AB and CA elements for an AG fault). where identical currents produce phasors with different phase
The Open Pole Detector also resets and blocks the Phase Selector angles, and transient errors, where changes in current are seen at
so the other distance elements may operate for evolving faults. The different times at different measurement points. For example, on a
Open Pole Detector also accounts for line charging current and for 60 Hz system, every 1ms of time shift between terminals introduces
weak infeed conditions. a 21.6° phase shift into the measured currents.
Once the Open Pole Detector operates, a further trip will cause There are two methods to account for the phase shift between line
the Trip Output to declare a three pole fault, indicating either an terminals due to the communications channel delay. One method is
evolving fault condition or a reclose onto a permanent phase-to- to measure the round-trip channel delay, and shift the local current
ground fault. This total logic simplifies the setting of the D60 for phase by an angle equal to ½ of the round-trip delay time. This
single pole tripping, and ensures dependable and secure operation method is simple to implement, but creates a transient error when
when faced with single line-to-ground faults. the communications channel is switched. In addition, the differential
The L90 Line Differential Relay and the L60 Line Phase Comparison element will be temporarily blocked when the communications
Relay are both phase-segregated, current only relays. Single pole channel switches, or noise in the communications channel causes
tripping on these relays does not present any unusual challenges, communications packet loss.
as each phase of the protection element operates independently of The L90 Line Differential Relay employs a different method, using
the other unfaulted phases. synchronous sampling by internally synchronizing the clocks on
each L90. This method achieves high reliability, as the round-trip
Communications channel delay is not vitally important. The differential element
Often transmission lines are protected by using schemes that successfully operates during channel switching or after packet loss,
require communications with relays located at other line terminals. because the communications packets are precisely synchronized.
The reliability of the communications obviously impacts the In the L90, synchronization is accomplished by synchronizing the
reliability of the protection system. GE Multilin relays include clocks to each other rather than to a master clock. Each relay
features that maintain reliable operation of the protection compares the phase of its clock to the phase of the other clocks and
communications during power line faults, communications channel compares the frequency of its clock to the power system frequency
delays, communications channel switching, and communications and makes appropriate adjustments. The frequency and phase
channel dropout. tracking algorithm keeps the measurements at all relays within a
Pilot protection: Pilot protection schemes, such as directional plus or minus 25 microsecond error during normal conditions for
comparison blocking and permissive over-reaching transfer trip, a 2 or 3 terminal system. In all cases, an estimate of phase error
use simple on/off communications between relays. There are many is computed and used to automatically adapt the restraint region
methods to send this signal. The most common method is to use of the differential element. The time synchronization algorithm
contact closure to an external communication circuit, such as power can also use a GPS satellite clock to compensate for channel
line carrier, microwave, radio, or fiber optic communications. GE asymmetry. The use of a GPS clock is not normally required, except
Multilin relays simplify fiber optic communications method by using in applications such as a SONET ring where the communications
internal fiber optic communications via Direct I/O, eliminating the channel delay may be asymmetric.
need for external communications devices. Direct I/O is a reliable This method produces synchronization accurate to within 125
mechanism that is simple to configure, securely transmits digital microseconds between the relays on each end of the protected
status points such as tripping or blocking commands between line. By using internally synchronized sampling, the L90 can
relays via directly-connected or multiplexed fiber optic channels. accommodate 4 consecutive cycles of communications channel
Direct I/O operates within 2ms for high speed communications to loss before needing to block the differential element . If the
the remote line end. communications channel is restored within 5 seconds of channel
Direct I/O is available in any of the transmission line relays by loss, the L90 differential element will restart on the first received
adding an internal communications card. The output of the card packet, without any time synchronization delay, due to the inertia
can be IEEE C37.94, RS422 or G.703 communications to interface of the internal clocks of the relays.
with fiber optic multiplexers, or may be a direct fiber connection Line Phase Comparison: As with line differential, communications
to other relays. The communications card can be single-channel

www.GEMultilin.com 145
TRANSMISSION lINE Protection Applications

is an integral part of phase comparison relaying. Simple binary Distance: Distance relays applied at dual-breaker line terminals are
communications, such as power line carrier or microwave, is used vulnerable to mis-operation on external faults. During a close-in
to send a pulse to the remote end when the phase angle of the reverse external fault, the voltage is depressed to a very low level,
measured current is positive. Coordination between the pulses from and the security of the relay is maintained by directional supervision.
the remote end, and the phase angle measured at the local end, If one of the line CTs saturates, the current measured by the relay
must be maintained. may increase in magnitude, and be in the opposite direction of the
actual fault current, leading to an incorrect operation of the forward
The L60 Line Phase Comparison Relay directly solves two common
distance element for an external fault.
challenges with the carrier signal. The first issue is channel delay.
The channel delay is measured during commissioning and is The D90Plus Line Protection System and the D60 Line Distance Relay
entered as a setting in the phase comparison element. The remote handles the challenge of dual-breaker line terminals by supporting
phase angle measurements are buffered and delayed by this value two three-phase current inputs to support breaker failure, overcurrent
to match the incoming pulses from the remote relays. The L60 has protection, and metering for each circuit breaker. The relays then
two communications channels, and two independent channel time mathematically add these currents together to form the total line
delays, to support three-terminal lines. current used for distance and directional overcurrent relaying.
The other common issue is pulse asymmetry of the carrier signal. Directly measuring the currents from both circuit breakers allows
Carrier sets may extend, either the mark (on) or space (off) signals the use of supervisory logic to prevent the distance element and
at the receiving end compared with the originally sent signal. This directional overcurrent elements from operating incorrectly for
difference is measured during commissioning by using oscillography reverse faults due to CT error. This supervisory logic does not impact
data, and simply entered as a setting in the phase comparison the speed or sensitivity of the protection elements, operates during
element. all load conditions, and correctly allows tripping during an evolving
In addition, the L60 supports some other methods to improve external-to-internal fault condition.
the reliability of protection communications. For short lines with The dual-breaker line terminal supervisory logic essentially
negligible charging current, the channel delay measurement can determines if the current flow through each breaker is either forward
be automated by running a loop-back test during normal system or reverse. Both currents should be forward for an internal fault, and
conditions and measuring the difference between the sent and one current should be forward and one reverse for an external line
received pulses. The L60 also supports automated check-back of fault. The supervisory logic uses, on a per-phase basis, a high-set
the carrier system. Under normal conditions, the relay can initiate fault detector (FDH), typically set at 2-3 times the nominal rating
transmission of and modulate the analog signal to exchange small of the CT, and a directional element for each CT input to declare a
amounts of information. This automatic loop-back can replace forward fault, for each breaker. The logic also uses, on a per-phase
the carrier guard signal, and more importantly, verifies the entire basis, a low-set fault detector (FDL), typically set at 1.5-2 times the
communications path, including the relays on both ends. nominal rating of the CT, and a directional element to declare a
reverse fault, for each breaker.
Security for dual-breaker terminals
Dual-breaker terminal line terminals, such as breaker-and-a-half Relay 1 Relay 2
f f
and ring bus terminals, are a common design for transmission System
+ Frequency +
lines. The standard practice is to sum the currents from each circuit
breaker externally by paralleling the CTs, and using this external Compute - - Compute
Frequency Frequency
sum as the line current for protection relays. This practice works f - f1 Deviation f1 f2 Deviation f - f2
well during actual line faults. However, for some external fault
events, poor CT performance may lead to improper operation of
Phase Frequency Phase Frequency
line protection relays. Loop Filter Loop Filter

When current flows through a dual-breaker line terminal, the line 1 2


current measured by a relay using external summation matches
( 2 - 1)/2 Ping-Pong time stamps Ping-Pong ( 2 - 1)/2
the actual line current only if the two CTs are accurate. The most Phase Phase
Deviation Deviation
significant relaying problem is CT saturation in either CT. The current
measured by the relay may contain a large error current, which
can result in the relay operating due to an incorrect magnitude or ( 2 - 1)/2 GPS time stamps GPS ( 2 - 1)/2
Phase Phase
direction decision. This incorrect operation may also occur if the Deviation Deviation

linear error current of the CTs due to accuracy class is close to the
through current level. These errors appear in the measured phase GPS GPS
Clock Clock
currents. As a result, relays that calculate the negative sequence
and zero sequence currents from the measured phase currents may
also see errors. Clock synchronization block diagram for a two terminal system using L90 current
differential system

146 www.GEMultilin.com
TRANSMISSION lINE Protection Applications

Tripping is permitted during all forward faults, even with weak infeed The starting point for the restraint is the locally measured current
at the dual-breaker terminal. Tripping is blocked for all reverse with the largest magnitude. This ensures the restraint is based on one
faults when one breaker sees forward current and one breaker of the measured currents for all fault events, and increases the level
sees reverse current. During an evolving external-to-internal fault, of restraint as the fault magnitude increases. ILOC_REST_TRAD is this
tripping is initially blocked, but when the second fault appears in the maximum current magnitude applied against the actual differential
forward direction, the block is lifted to permit tripping. characteristic settings. ILOC_ADA is the sum of the squares estimate
of the measurement error in the current, and is used to increase the
Line Differential: Line differential protection is prone to tripping
restraint as the uncertainty of actual measurement increases, such
due to poor CT performance on dual-breaker terminals, as the error
as during high magnitude fault events and CT saturation. MULT is an
current from the CTs is directly translated into a differential current.
additional factor that increases the error adjustment of the restraint
The only possible solution for traditional line differential relays is to
current based on the severity of the fault event and the likelihood the
decrease the sensitivity of the differential element, which limits the
fault is an external fault, when CT saturation is most likely to cause
ability of the differential element to detect low magnitude faults,
an incorrect operation.
such as highly resistive faults.
The values of ILOC and ILOC_RESTRAINT are transmitted to the L90
The L90 Line Differential Relay supports up to four three-phase current
relays located at the other line ends. The differential and restraint
inputs for breaker failure, overcurrent protection, and metering for
values used in the actual tripping decision combine both the local
each circuit breaker. The relay then uses these individual currents
differential and restraint current, and the differential and restraint
to form the differential and restraint currents for the differential
currents from the remote line ends. These calculations are performed
protection element.
individually on each phase.
The L90 differential element design explicitly accounts for the
performance of the CTs for dual-breaker line terminals. Each L90 I DIFF = I LOC + I REMOTE 1 + I REMOTE 2
protecting a transmission line calculates differential and restraint
quantities based on local information directly measured by the relay,
(I REST ) 2 = (I LOC _ RESTRAINT ) 2+ (I REM 1 _ RESTRAINT ) 2+ (I REM 2 _ RESTRAINT ) 2
and information received from relays located at the remote line ends.
Considering the worst case external fault with CT saturation, the
Tripping decisions are made locally be each relay.
differential current IDIFF will increase due to the CT error that
The information sent by one L90 to the other L90s on the line is the appears in ILOC. However, the restraint current IREST will increase
local differential and restraint currents. The local differential current more significantly, as the ILOC_RESTRAINT uses the maximum of the
is the sum of all the local currents on a per-phase basis. One L90 can local currents, that is increased based on the estimation of CT errors
accept up to 4 current measurements, but only 2 currents are used and presence of CT saturation. The end result is a correct restraining
for a dual-breaker application. of the differential element.
I LOC = I 1 + I 2 + I 3 + I 4 Phase Comparison: The L60 Line Phase Comparison Relay supports
two three-phase current inputs for breaker failure, overcurrent
The local restraint current is defined by the following equation for protection, and metering for each circuit breaker. The relay then uses
each phase. these individual currents to form the local phase angle information

I LOC _ RESTRAINT = (I LOC _ REST _ TRAD ) + MULT • (I


2
LOC _ ADA ) 2 for use in the phase comparison scheme.

CT 1 saturates
i2 is reduced 10 - 15 pu
i2 i
IF + ILine IF + ILine
2 >0.1 pu error with
> 0.1 pu error
CT 1 CT 1 iLine shows incorret
magnitude, direction
52 iLine 52 iLine Id > 0.2 pu
52 >0.2 pu error 52
Ir = 10 - 15 pu
Relay Relay Relay L90 NO TRIP
ILine ILine

10 - 15 pu 10 - 15 pu
Id > 0.2 pu
IF IF
52 52 Ir > 0.2 pu
52 503 TRIP 52 503
10 - 15 pu
CT 2 CT 2 with
> 0.1 pu error
i1 i1
>0.1 pu error
Impact of CT saturation on two-breaker line applications.
(a) Accurate CTs preserve the reverse line current direction under weak remote Sensitivity of Line Differential system for Dual-Breaker applications
feed.
(b) Saturation of the CT carries the reverse current may invert the line current
as measured from the externally summated CTs

www.GEMultilin.com 147
TRANSMISSION lINE Protection Applications

A phase comparison relay operates by comparing the relative phase the same protection scheme. The other method is to use multiple sets
angles of the current from each end of the transmission line. When of protection using different protection principles. Depending on the
the measured current exceeds the level of a fault detector, and the voltage class, either method of redundancy may involve using 2 or 3
phase angles from each end of the line are in phase, the phase sets of protection. In both cases, the goal is to increase dependability,
comparison relay operates. For a dual-breaker application using an by ensuring the protection operates for a fault event. Security may
external sum, the saturation of one CT may cause the relay current be improved through the use of so-called voting schemes (e.g. 2-out-
to increase high enough to operate the fault detector. Because the of-3), potentially at the expense of dependability.
current from the unsaturated CT predominates in this waveform, the Multiple sets of protection using the same protection scheme involves
phase angle of the relay current may change. If the phase angle of using multiple relays and communications channels. This is a method
the relay current is in phase with the relay current at the remote end to overcome individual element failure. The simplest method is to
of the line, the relay will trip. use two protection relays of the same type, using the same scheme
The L60 in dual-breaker applications selects the appropriate phase and communications channel. This only protects against the failure
angle, based on the information measured from the current flow of one relay. In some instances, relays of different manufacturers are
through both circuit breakers. The relay uses fault detectors on each used, to protect against common mode failures. It is also common to
current input, and develops the phase angle for each current input, use redundant communications channels, in case of failure on one
and then special dual breaker logic consolidates the fault detector communications channel. Often, the communications channels use
flags and the phase angle pulses for the line terminal. different methods, such as power line carrier and fiber optic. This is
The fault detector flag is set for a line terminal if either fault especially true due to the concerns of power line carrier operation
detector from the two breakers is picked up. The type of phase during internal fault events.
comparison protection scheme, tripping or blocking, controls the An alternative way to increase reliability through redundancy is to
pulse combination logic. For a tripping scheme, a positive polarity use multiple protection methods on the same line such as phase
is declared for the terminal if one breaker displays positive polarity comparison and permissive over-reaching transfer trip, using
with its respective fault detector picked up, while the other breaker different communications channels. This method protects against
either does not show negative polarity or its fault detector is not individual element failure of both relays and communications
picked up. channels. More importantly, it protects against the failure of one of
the protection methods. For example, a VT circuit fuse failure blocks
Redundancy Considerations to Enhance Reliability a distance relay from operating, while a line differential system or
The reliability of transmission system protection is dependent on phase comparison system will continue to operate. For this reason,
the reliability of the protection scheme used and the individual often at least one current-only scheme, such as phase comparison
components of the protection scheme. Transmission protection or line differential, and then one pilot protection scheme based on
systems typically use redundancy to increase the dependability distance relays are employed.
of the system. There are two general methods of implementing
redundancy. One method is to use multiple sets of protection using

CT 1 CT 1

52 52

52 52

CT 2 CT 2

Multilplexed Fiber Optic


D90Plus Distance - D90Plus Distance -
POTT Scheme POTT Scheme

Multilplexed Fiber Optic


D60 Distance - D60 Distance -
POTT Scheme POTT Scheme

Multilplexed Fiber Optic (different channel)


L90 Line L90 Line
Differential Differential

Power Line Carrier


L60 Phase L60 Phase
Comparison Comparison

Redundancy Requirements - Alternate Main Protection Possibilities from GE Multilin

148 www.GEMultilin.com
TRANSMISSION lINE Protection Applications

A second advantage of using multiple protection methods to protect systems are full-featured distance relays. These relays are on a
one line is the ability to increase the security of the line. It is possible common hardware and software platform, simplifying engineering,
to implement a “voting” scheme, where at least 2 protection methods design, installation, and operations issues. All of these relays support
must operate before the line can be actually tripped. Such a voting multiple communications options, including power line carrier,
scheme may be applied permanently on lines where security is an microwave, and fiber optic communications. The relays are also
issue, such as major inter-tie lines. A voting scheme may also be designed to communicate with each other, to implement voting
applied only when the system is at risk, such as during wide-area schemes, reclosing control, and other applications.
disturbances, either automatically based on system conditions, or
by command from system operators. Typical Applications
GE Multilin simplifies solutions when multiple protection schemes This section highlights some typical application of GE Multilin line
are used by providing both protective relays that only use current protection relays. This section is not intended as a comprehensive
and protective relays that use both current and voltage. The L60 list of possible applications. For questions about the correct relay for
Line Phase Comparison Relay and the L90 Line Differential Relay a specific application, please review the individual catalog sheet for
are both current-only protection relays with different operating a specific relay model, or contact GE Multilin.
principles. The D90 Plus, D60 and D30 Line distance protection

Directional Overcurrent

Typical Functions Additional Functions


67P Phase directional overcurrent 25 Synchrocheck
3Y
67N Neutral directional 79 Reclosing
52 overcurrent V, S Voltage and Power metering
3Y
or Functions Typical Product Order Code
2D
Typical Functions F60-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX

Alternative D30-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX

+ Additional functions Included in typical


Alternative Included in typical
67P 67N 25 79 Alternative Included in typical

V S

Directional Overcurrent – Dual Breaker

Typical Functions Additional Functions


67P Phase directional overcurrent 25 Synchrocheck
3Y
67N Neutral directional 79 Reclosing
overcurrent V, S Voltage and Power metering
52
Functions Typical Product Order Code
Typical Functions D60-N02-HCH-F8L-H6P-M8L-PXX-UXX-WXX

+ Additional functions Included in typical

3Y External electrical sum of


breaker currents (traditional F60-N00-HCH-F8L-H6P-M8L-PXX-UXX-WXX
or
2D method)
Only 1 synchrocheck function in F60
D30-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
and D30
D60-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
52

3Y 67P 67N 25 79
2
V S

www.GEMultilin.com 149
TRANSMISSION lINE Protection Applications

Stepped-Distance Protection Typical Functions Additional Functions


21P Phase distance 67P Phase directional overcurrent
21G Ground distance 67N Neutral directional
overcurrent
50BF Breaker Failure
3Y 25 Synchrocheck
52 Synchrophasors 79 Reclosing
Phasor Measurement Unit V, S Voltage and Power metering
3Y

Functions Typical Product Order Code


Typical Functions D30-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX

Alternative D60-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
21P 21G 67P 67N 50BF D90P-A-E-S-S-01-S-S-S-X-H-X-A-X-A-X-X-01-X
3 3 + Additional functions Included in typical
V S 25 79 No 50BF in D30

+ Synchrophasors D60-N06-HCH-F8L-H6P-MXX-PXX-UXX-WXX
D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X

Stepped-Distance Protection – Dual Breaker


Typical Functions Additional Functions
21P Phase distance 67P Phase directional overcurrent
1 21G Ground distance 67N Neutral directional
overcurrent
50BF Breaker Failure
25 Synchrocheck
79 Reclosing
3Y
V, S Voltage and Power metering

Synchrophasors
52
Phasor Measurement Unit

Functions Typical Product Order Code


Typical Functions D90P-A-E-S-S-01-S-S-S-X-H-X-A-X-A-X-X-01-X
D60-N02-HCH-F8L-H6P-M8L-PXX-UXX-WXX
3Y
+ Additional functions Included in typical

External electrical sum of


breaker currents (traditional D60-N00-HCH-F8L-H6P- MXX-PXX-UXX-WXX
52 method)
Only 1 synchrocheck function D30-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
In D30

3Y 21P 21G 67P 67N 50BF + Synchrophasors D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X


3 3 2
D60-N08-HCH-F8L-H6P-M8L-PXX-UXX-WXX
V S 25 79
2

150 www.GEMultilin.com
TRANSMISSION lINE Protection Applications

Pilot Protection Schemes


Typical Functions Additional Functions
21P Phase distance 67P Phase directional overcurrent
21G Ground distance 67N Neutral directional
overcurrent
85 Power line carrier / micro-
wave transmitter & receiver / 50BF Breaker Failure
fiber or digital channel Synchrocheck
25
79 Reclosing
3Y V, S Voltage and Power metering
52
Other Communications Options Synchrophasors
3Y 85
85 Inter-Relay Communications Phasor Measurement Unit
85 Sonet Multiplexer

Functions Typical Product Order Code


21P 21G 67P 67N 50BF
Typical Functions D90P-A-E-S-S-01-S-S-S-X-H-X-A-X-A-X-X-01-X
3 3
85 by others D60-N00-HCH-F8L-H6P-MXX-PXX-UXX-WXX
V S 25 79 85
+ Additional functions Included in typical

+ Synchrophasors D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X
D60-N06-HCH-F8L-H6P-MXX-PXX-UXX-WXX

Other Communications Options

Direct I/O, 1300nm Singlemode D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7K


Laser, 64km

RS422 interface D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7W

G.703 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7S

C37.94 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W77

SONET Multiplexer JungleMux with 86448 and 86441 units

Pilot Protection Schemes – Dual Breaker


Typical Functions Additional Functions
21P Phase distance 67P Phase directional overcurrent
1 21G Ground distance 67N Neutral directional
overcurrent
85 Power line carrier / micro-
wave transmitter & receiver 50BF Breaker Failure
25 Synchrocheck
79 Reclosing
3Y
V, S Voltage and Power metering

52 Other Communications Options Synchrophasors


85 Inter-Relay Communications Phasor Measurement Unit
85 Sonet Multiplexer

Functions Typical Product Order Code


3Y 85
Typical Functions D90P-A-E-S-S-01-S-S-S-X-H-X-A-X-A-X-X-01-X
85 by others D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-WXX
52 + Additional functions Included in typical

+ Synchrophasors D90P-A-E-S-S-01-P-S-S-X-H-X-A-X-A-X-X-01-X
3Y 21P 21G 67P 67N 50BF D60-N06-HCH-F8L-H6P-M8L-PXX-UXX-WXX
3 3 2 External electrical sum of D60-N00-HCH-F8L-H6P- MXX-PXX-UXX-WXX
V S 25 79 85 breaker currents (traditional
2 method)

Other Communications Options

Direct I/O, 1300nm Singlemode D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7K


1 Laser, 64km

RS422 interface D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7W

G.703 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W7S

C37.94 D60-N00-HCH-F8L-H6P-M8L-PXX-UXX-W77

SONET Multiplexer JungleMux with 86448 and 86441 units

www.GEMultilin.com 151
TRANSMISSION lINE Protection Applications

Line Differential Protection


Typical Functions Additional Functions
87L Line differential 21P Phase distance
85 Sonet Multiplexer 21G Ground distance
67P Phase directional overcurrent
1 67N Neutral directional
overcurrent
50BF Breaker Failure
25 Synchrocheck
3Y 79 Reclosing
52 V, S Voltage and Power metering

3Y 85 Other Communications Options Synchrophasors


85 Inter-Relay Communications Phasor Measurement Unit

Functions Typical Product Order Code


Typical Functions L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7W
87L 67P 67N 50BF Identical relay
on other line + Additional functions Included in typical
terminals
21P 21G 25 79 85 + Synchrophasors
L90-N06-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7W
3 3
SONET Multiplexer JungleMux with 86448 and 86443 units

Other Communications Options D60-N08-HCH-F8L-H6P-M8L-PXX-UXX-WXX

Direct I/O, 1300nm Singlemode Included in typical


Laser, 64km

+ Synchrophasors L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7K

G.703 L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7S

C37.94 L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W77

Line Differential Protection – Dual Breaker Typical Functions Additional Functions


87L Line differential 21P Phase distance
1
85 Sonet Multiplexer 21G Ground distance
67P Phase directional overcurrent
67N Neutral directional
overcurrent
3Y 50BF Breaker Failure
25 Synchrocheck
79 Reclosing
52 V, S Voltage and Power metering

Other Communications Options Synchrophasors


85 Inter-Relay Communications Phasor Measurement Unit

Functions Typical Product Order Code


Typical Functions L90-N02-HCH-F8L-H6P-L8L-NXX-SXX-UXX-W7W
3Y 85
+ Additional functions Included in typical

+ Synchrophasors
52 L90-N08-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7W

Electrical sum of breaker


currents (traditional method) L90-N00-HCH-F8L-H6P-LXX-NXX-SXX-UXX-W7W
87L 67P 67N 50BF
3Y SONET Multiplexer JungleMux with 86448 and 86443 units
2
21P 21G 25 79 85 Other Communications Options
3 3 2
Direct I/O, 1300nm Singlemode L90-N02-HCH-F8L-H6P-L8L-NXX-SXX-UXX-W7K
Identical relay Laser, 64km
on other line
terminals G.703 L90-N02-HCH-F8L-H6P-L8L-NXX-SXX-UXX-W7S
1
C37.94 L90-N02-HCH-F8L-H6P-L8L-NXX-SXX-UXX-W77

152 www.GEMultilin.com
TRANSMISSION lINE Protection Applications

Phase Comparison Protection Typical Functions Additional Functions


1
87PC Phase Comparison 21P Phase distance
85 Power Line Carrier / 21G Ground distance
Microwave Phase directional overcurrent
67P
3Y 67N Neutral directional
52 overcurrent
50BF Breaker Failure
3Y 85 25 Synchrocheck
79 Reclosing
V, S Voltage and Power metering

Functions Typical Product Order Code


87 Typical Functions L60-N00-HCH-F8P-H6P-L8L-NXX-SXX-UXX-WXX
PC 67P 67N 50BF Identical relay
on other line
terminals
21P 21G 25 79 85
3 3

Phase Comparison Protection – Dual Breakers


1 Typical Functions Additional Functions
87PC Line differential 21P Phase distance
85 Power Line Carrier / 21G Ground distance
Microwave 67P Phase directional overcurrent
3Y
67N Neutral directional
overcurrent
50BF Breaker Failure
52 25 Synchrocheck
79 Reclosing
V, S Voltage and Power metering

Functions Typical Product Order Code


3Y 85 Typical Functions L60-N00-HCH-F8P-H6P-L8L-NXX-SXX-UXX-WXX

52

87
3Y PC 67P 67N 50BF
Identical relay
2
on other line
21P 21G 25 79 85 terminals
3 3

www.GEMultilin.com 153
TRANSMISSION lINE Protection Applications

Transmission Line Protection


Selector Guide

FEATURES ANSI L90 L60 D90Plus D60 D30


Distance 21 • • • • •
APPLICATIONS

Line Differential - Current Comparison 87L •


Line Differential - Phase Comparison 87PC •
Breaker-and-Half configurations • • • •
Series Compensation • • • • •
Three terminal lines • • • • •
Lines with In-zone transformers • • • • •
Synchrophasors • • •
Typical Operating Time (cycles) <1 <1 <1 <2 <2
Mho Phase & Ground Distance (No. of Zones) 21P/G 3 3 5 5 3
Quad Phase & Ground Distance (No. of Zones) 21P/G 3 3 5 5 3
IOC, Ground/Neutral/Phase/Negative Sequence 50G/N/P/_2 G/N/P/_2 G/N/P/_2 G/N/P/_2 G/N/P/_2 G/N/P/_2
TOC, Ground/Neutral/Phase/Negative Sequence 51G/N/P/_2 G/N/P/_2 G/N/P/_2 G/N/P/_2 G/N/P/_2 G/N/P/_2
Directional overcurrent, Neutral/Phase/Neg. Seq. 67G/N/P/_2 N/P/_2 N/P/_2 N/P/_2 N/P/_2 N/P/_2
Wattmetric Ground Directional • • • •
PROTECTION & CONTROL

Overvoltage Phase/Auxiliary/Neutral 59P/X/N P/X/N P/X/N P/X/N P/X/N P/X/N


Undervoltage Phase/Auxiliary 27P/X P/X P/X P/X P/X P/X
Negative Sequence Overvoltage 59_2 • • • •
Under/Over frequency 81U/O •
Out-of-Step Blocking/Tripping 68B • • • • •
Switch on to Fault (Line Pickup) SOTF • • • • •
Voltage Transformer Fuse Failure VTFF • • • • •
Current Transformer Supervision • • •
Open Pole Detector • • •
Load Encroachment Logic • • • • •
Breaker Failure 50BF • • • •
Breaker Flashover • • • •
Lockout Functionality 86 • • • • •
Synchronism Check or Synchronizing 25 • • • • •
AC Reclosing (No. of Shots) 79 4 4 4 4 4
Trip Modes: Three-Pole/Single-Pole 1&3 1& 3 1&3 1&3 3
Pilot Protection Logic POTT POTT • •
Fault Location • • • • •
Programmable Protection Logic (no of lines) 512 512 512 512 512
Programmable Automation Logic (no of lines) 1024
FlexElements™ • • • • •
User Programmable Self-Test Contact • • • • •
Settings Groups 6 6 6 6 6
Non-volatile latches (up to) 16 16 16 16 16
Contact Inputs Programmable - (up to) 80 80 60 80 80
Contact Outputs Programmable - (up to) 64 64 60 64 64
Virtual Inputs - (up to) 32 32 32 32 32
Virtual Outputs - (up to) 64 64 64 64 64
AUTOMATION

Direct Inputs/Outputs • • • • •
Breaker Control (up to) 2 2 2 2 2
User-Programmable LEDs (up to) 48 48 48 48
User - Programmable Annunciator Alarms (up to) 96
User-Programmable Push Buttons (up to) 12 12 12 12 12
User-Programmable Self Test • • • •
User Definable Displays • • • •
Large HMI •
Timers • • • • •
Selector Switch • • • • •
Digital Counters • • • • •
Digital Elements • • • • •
IRIG-B Input • • • • •
Analog Inputs/Outputs (up to) 24 24 24 24
RTD Inputs (up to) 24 24 24 24
Current, voltage • • • • •
Symmetrical Components • • • • •
Power - Apparent, Real, Reactive • • • • •
MONITORING &

Energy • • • •
METERING

Power Factor • • • • •
Frequency • • • • •
Fault Location • • • • •
Event Recorder - Number of Events 1024 1024 8000 1024 1024
Oscillography - Sampling Rate 64/5 64/5 128/30 64/5 64/5
Disturbance Recorder - Sampling Rate/Duration in seconds 1/300
Breaker Arcing Current • • • • •
Trip/Close Coil Supervision • • • • •
Data Logger • • • •
RS232 Port • • • •
INTERFACES

USB Port •
COMM.

RS485 Port • • • • •
Ethernet Port (Fiber and Copper, up to) 1 1 3 1 1
Direct Fiber Communications (800nm, 1330nm, 1550nm) • • • •
Communication Interface (RS422, G.703, C37.94) • • • •
ModBus (RTU and TCP/IP) • • • • •
DNP3 • • • • •
PROTOCOLS

IEC60870-5-104 • • • • •
UCA2/MMS • • • •
IEC 61850 • • • • •
Simple Network Time Protocol (SNTP) • • • • •
HTTP • • • • •
TFTP • • • • •

* For the most current comparison list, see www.GEMultilin.com/selector/transmission.pdf

0222-v6
154 www.GEMultilin.com

Você também pode gostar