transformers
Advanced GIS substations with
IEC 61850-9-2 LE process bus
Content
Towards the digital GIS substations 2 Non-conventional instrument transformers (NCITs) and
IEC 61850-9-2 LE process bus for GIS substations
Optimized substation design 3 Transmission substations with NCITs and process bus for
sampled analog values
NCIT for gas-insulated switchgears 5 ABB’s ELK-CP14 and ELK-CP3 non-conventional instrument
transformers
Protection and control portfolio 7 Relion ® 670 series feeder protection and control devices
with IEC 61850-9-2LE
8 REB500 busbar and breaker failure protection system
Protection and control concepts 9 Enhanced substation automation, protection and control sys-
tems with IEC 61850-9-2 LE
Technical data 11 The most important technical data of ELK-CP14 and ELK-CP3
and the CP-MU merging units
2 Non-conventional instrument transformers | Advanced GIS substations with IEC 61850-9-2LE process bus
On the way to digital GIS substations
Non-conventional instrument transformers (NCITs) and
IEC 61850-9-2 LE process bus for gas-insulated switchgear
substations
By providing complete solutions with IEC 61850-9-2 LE1 As defined by IEC 61850-9-2, sampled analog values are
process integration, as part of substations with non-conven- transmitted by so-called merging units (MUs). The MU time
tional instrument transformers (NCIT), ABB proves its market correlates and merges analog data from individual phases or
and technology leading position in high-voltage substations measuring points in the substation before transmitting them
and substation automation systems. via the Ethernet network, where the data can be accessed by
protection and control devices. In the case of ABB’s gas-
With more than ten years of in-service experience with NCITs insulated switchgear (GIS) installations, the merging units
for transmission level applications and the largest installed receive their data through optical connections from the NCITs.
base of IEC 61850 substation automation systems, ABB Because this connection is optical, the location of the MU is
combines the two technologies in its offerings with NCIT virtually independent of the cable length.
and process bus for sampled analog values.
One of ABB’s NCIT and IEC 61850-9-2 LE process bus pilot installations
1
IEC 61850-9-2 LE is used to denote the implementation guideline for the digital interface to instrument transformers using IEC 61850-9-2, published
by UCA International Users Group. The guideline describes an application profile of IEC 61850-9-2, facilitating implementation and interoperability.
The UCA International Users Group is a non-profit corporation focused on assisting users and vendors in the deployment of standards for real-time
applications for industries sharing common requirements.
Advanced GIS substations with IEC 61850-9-2LE process bus | Non-conventional instrument transformers 3
Optimized substation design
Transmission level substations with NCITs and process bus for
sampled analog values
To optimize the performance of transmission substations One example is the connecting of NCITs to protection and
ABB has introduced new NCITs and process bus control devices via fiber optic cables. This isolates the devices
solutions. The ELK-CP series of NCITs, for GIS from the process and therefore no secondary CT and VT
substations, and process bus solutions, for sampled circuits need to be handled.
analog values according to IEC 61850-9-2 LE, bring the
benefits of the most economic and modern technologies.
IEC 61850-9-2 LE is fully integrated in ABB‘s REB500 and Reduced life-cycle costs and increased availability
Relion® series protection and control devices. Permanent real-time system-wide supervision of all electro-
nic components in the complete measuring chain lowers
The fully redundant, combined current and voltage NCITs routine maintenance requirements and enables fast and exact
and process bus bring multiple benefits, as demonstrated fault finding accross the entire station automation, protection
in numerous installations around the world. and control system. Information on system health can be
transferred to remote control and maintenance centers, supporting
efficient management and maintenance of resources.
4 Non-conventional instrument transformers | Advanced GIS substations with IEC 61850-9-2LE process bus
The primary sensor’s lifetime and availability goes far Space-saving design
beyond those of conventional equipment, especially of Installing NCITs in place of conventional equipment reduces
voltage transformers. ABB’s well-designed and redundant the total weight of equipment and minimizes space require-
sensor electronics (secondary converter) allow replacement ments of the switchgear.
without the need to interrupt power, re-configure or re-calibrate,
helping to reduce outage time and increase system availability. Reduced copper cabling
The optical connections between NCITs and merging units
The ability to adjust nominal values of the NCIT using soft- and the fiber optic Ethernet network of the process bus,
ware, dramatically reduces the efforts and costs associated eliminate parallel copper wiring for current and voltage
with rating changes. measurement. This reduces not only the number of copper
cables in the substation, it also allows the use of narrower
Highest accuracy for protection and metering cable trenches.
With linear characteristics across the complete measurment
range of voltages and currents, ABB’s NCITs combine the Additional environmental benefits
wide dynamic range required for protection with the high Thanks to the compact design of ABB’s NCITs, the required
accuracy for metering applications in a single device. volume of SF 6 gas is considerably reduced. On-site gas
handling can also be reduced, because the NCIT can be
The transmission of sampled values according to installed in the factory and it does not need to be dissembled
IEC 61850-9-2 LE, through a fiber optic network, guarantees for HV testing.
permanently supervised communication that is immune to
electro-magnetic disturbances and virtually independent of Compared to conventional current and voltage transformers,
the cable length. the NCITs and merging unit suffer lower the power losses in
substations and therefore safe energy during their entire life
time.
Advanced GIS substations with IEC 61850-9-2LE process bus | Non-conventional instrument transformers 5
NCITs for gas-insulated switchgears
ABB’s ELK-CP14 and ELK-CP3 non-conventional instrument
transformers
a b
GIS feeder showing two alternative arrangements of the ELK-CP NCIT: (a) after the circuit breaker, and (b) in the cable termination.
The features of the ELK-CP14 and ELK-CP3 NCITs are Highest accuracy
proof of ABB’s extensive expertise in the field of high- ABB’s ELK-CP14 and ELK-CP3 combined current and voltage
voltage technology and non-conventional instrument sensors feature the highest accuracy and linearity throughout
transformers. the entire measuring range, supporting protection as well as
revenue metering applications.
6 Non-conventional instrument transformers | Advanced GIS substations with IEC 61850-9-2LE process bus
PPL1 IEC 61850-9-2LE
CP-MU
The CP-MU merging unit connects up to three 3-phase measuring points IEC 61850-9-2 LE compliance certificate
Vast experience
Over 300 of ABB’s ELK-CP NCITs have been in continuous pendent three-phase voltage and current measuring points,
service for more than a decade. This installed base is an in- allowing for optimal system design with a minimum of com-
valuable source of experience in the field of non-conventional ponents in 1½-breaker- as well as double-busbar-switchgear
instrument transformers. arrangements.
The CP-MU follows the IEC 61850-9-2 implementation acco- Further more, the merging unit is capable of calculating sum-
ring to the UCA International Users Group’s implementation mated currents from any NCIT inputs and dispatch them via its
guideline, also refered to as IEC 61850-9-2 LE Ethernet ports to protection and control devices.
One merging unit for ELK-CP14 and ELK-CP3 Fit for retrofit
The CP-MU merging unit is designed for ABB’s ELK-CP14 Applying non-conventional instrument transformers in sub-
and ELK-CP3 NCITs. It can interface with up to three inde- station retrofits simplifies the process and therefore reduces
outage times, by avoiding the need to change ratios.
1
PPL: Point-to-point link, the optical connection between NCIT and merging unit.
2
1PPS: One pulse per second, used to synchronized sampling by different devices
Advanced GIS substations with IEC 61850-9-2LE process bus | Non-conventional instrument transformers 7
Protection and control portfolio
Feeder protection and control with IEC 61850-9-2 LE process bus
RET670
Group 1 protection
Transformer differential protection
Overcurrent protection
Thermal overload protection
Disturbance recording
CP-MU
ELK-CP MU 2
RET670
redundant U/I Group 2 protection
NCIT
Overcurrent protection
Overvoltage protection
Overexitation protection
Disturbance recording
REB500
Busbar protection
Busbar differential protection
Breaker failure protection
End-fault protection
Disturbance recording
ABB’s portfolio of IEC 61850-9-2 LE compliant protection and The following Relion® 670 series protection and control IEDs
control IEDs includes the Relion®670 series of advanced fully support IEC 61850-9-2LE:
protection and control IEDs, as well as the decentralized
REB500 busbar protection system. With these products Bay control IED REC670
and systems ABB comprehensively covers all protection Line distance protection IED REL670
and control applications using IEC61850-9-2LE. Line differential protection IED RED670
Transformer protection IED RET670
Relion ® 670 series protection and control IEDs
The Relion® 670 series of protection and control IEDs provides For synchronized sampling all IEDs feature a one-pulse-per-
versatile functionality, and maximum flexibility and performance second (1PPS) input.
to meet the highest requirements in generation and transmis-
sion protection systems. Relion® 670 series IEDs are: All devices support mixed configuration with IEC 61850-9-2 LE
and conventional CT and VT interfaces. This is used, for
− − Equipped with functionality specifically required in trans- example, in transformer differential protection applications with
mission applications, eg, series compensation and 1- and NCITs on the high-voltage side and conventional CTs and VTs
3-phase tripping, voltage control, extended disturbance on the low-voltage side, as shown in the diagram above.
recording, as well as binary and analog data transfer
between IEDs Line differential protection runs with both conventional
−− Capacity for GOOSE1 messaging for horizontal communication as well as IEC 61850-9-2 LE-based remote-end substations.
− − Equipped with powerful and flexible hardware.
1
GOOSE: Generic object oriented substation event, for the fast exchange of information between IEC 61850 servers.
8 Non-conventional instrument transformers | Advanced GIS substations with IEC 61850-9-2LE process bus
Busbar and breaker failure protection with IEC 61850-9-2 LE
process bus
Function examples
REB500 busbar protection system with IEC 61850-9-2 LE process bus, combined with conventional CTS and VTs
REB500 decentralized busbar protection system In addition to low-impedance busbar differential protection,
REB500 IEDs provide reliable and proven busbar protection REB500 integrates comprehensive backup protection
for different switchgear configurations. functionality, including both breaker failure and end-fault
protection, reducing both wiring and cabling.
The IEC 61850 enabled REB500 IED is designed to support
different protection philosophies. Distributed protection REB500 busbar protection system is fully compliant with
solutions with bay units assigned to dedicated bay cubicles IEC 61850-9-2 LE.
are supported, as are integrated solutions where all necessary
functionality is contained within a single cubicle. The seamless combination of bay units with IEC 61850-9-2 LE
and conventional bay units in a single system allows the flexible
The versatile hardware and distributed functionality of REB500 extensions of conventional substations.
IEDs enables its application in all types of switchgear configu-
rations, including single-, double- and triple-busbar plus
transfer bus-, quadruple-busbar arrangements and 1½-brea-
ker schemes.
Advanced GIS substations with IEC 61850-9-2LE process bus | Non-conventional instrument transformers 9
Protection and control concepts
Enhanced substation automation, protection and control
systems with IEC 61850-9-2 LE
Maintenance Remote
Station computer / HMI center control center
SYS 600C
Gateway
Station LAN
Decentralized ring
Station bus
IEC61850-8-1
Process bus
Substation automation, protection and control system with IEC 61850 station bus and IEC 61850-9-2 LE process bus
Extensive experience in high-voltage substations, Protection and control concepts, meeting your needs
combined with in-depth expertise in IEC 61850 technology ABB provides safe, reliable and efficient solutions to meet
make ABB a leading supplier of substation automation, your performance needs and your regulatory requirements.
control and protection systems. Building on this sound ABB can design protection and control solutions for any
base, ABB offers complete NCIT and IEC 61850-9-2 LE voltage level, accommodating a broad range of operational
solutions for transmission level GIS substations. philosophies and different environmental conditions.
Worldwide experience substation automation with Enhancing automation, protection and control systems
IEC 61850 with IEC 61850-9-2 LE process bus
More than a thousand IEC 61850 compliant substation automa- Building on our long experience in substation automation,
tion systems delivered for new installations and retrofit control and protection, ABB builds complete system solutions
projects worldwide make ABB the leading provider of with NCITs, IEC 61850-9-2 LE process bus and leading-edge
enhanced automation, control and protection solutions for protection and control devices.
substations of all voltage levels.
10 Non-conventional instrument transformers | Advanced GIS substations with IEC 61850-9-2LE process bus
System 1 System 2
PPL PPL
Full redundancy across the complete metering, Safe access to all analog values increases operational
control and protection chain safety
The fully redundancy of ABB’s combined current and voltage IEC 61850-9-2 LE makes all analog values available on an
NCIT is the basis for designing completely independent systems Ethernet network. For analysis purposes, PC-based tools
for main 1 and main 2 protection functions. This maximizes can simply be connected to the network, eg, to one of the ABB
system availability by avoiding interdependency between the merging unit’s numerous Ethernet ports. Once connected, the
redundant devices. current and voltage values of all phases are available at once,
without touching any CT or VT circuits.
Permanent supervision of the entire system minimizes
maintenance requirements Safe process isolation, minimizing outage requirements
All-embracing supervision of all intelligent components of the The distribution of analog values through the process bus
complete measuring and automation, protection and control Ethernet network allows simple isolation of individual pieces of
systems allows periodic maintenance activities to be reduced equipment without disturbing the transmission of current and
to a minimum. voltage values to other parts of the substation. This enables
more accurate maintenance of individual system components
Efficient system design with minimum components without disruption of service.
Thanks to the number of communication ports available on
the merging unit, on both the NCIT and the IEC61850-9-2LE By replacing of copper cables with optical fibers for the
side, efficient solutions can be designed with a minimum of transmission of current and voltage measurements, the
external Ethernet switches in the process bus network. This secondary equipment can be fully isolated from the primary
enables the number of components to be limited and process, rendering manipulation of CT terminals obsolete.
availability is optimized.
Advanced GIS substations with IEC 61850-9-2LE process bus | Non-conventional instrument transformers 11
Technical data
Non-conventional instrument transformers and merging units
Non-conventional instrument transformer ELK-CP3 ELK-CP14
General
Highest voltage for equipment (Um) kV 550 300
Rated lightning impulse withstand voltage (peak) kV 1,550 1,050
Rated switching impulse withstand voltage (peak) kV 1,250 850
Rated frequency (fr) Hz 50/60 50/60
© ABB Switzerland Ltd, May 2012. The right to modifications or deviations due to technical progress is reserved.
Measurement bandwidth (-3dB) Hz 1,000 1,000
Rated continuous thermal current (metering) A 4,000 3150
Rated continuous thermal current (protection/control) A 6,300 4,000
Rated short-time thermal current (Ith, RMS) kA 63 63
Rated dynamic current (Idyn, peak) kA 170 170
Ambient temperature range °C -40…+40 -30…+40
Weight kg 250 100
Protection class of housing IP65 IP65
Current measurement (IEC 60044-8)
Protection data link
Rated primary current Ipr (configurable) A (with metering) 100…4,000 100…4,000
A (without metering) 100…6,300 100…4,000
Accuracy class 5P TPE 5TPE