Escolar Documentos
Profissional Documentos
Cultura Documentos
SB-210+
V-200/V-300 Series
Additional text information
to be placed
TK 50982-1-MM (Rev.here
5, 09/14)
TK 5XXXX-X-PL
Ingersoll Rand’s Climate Solutions sector delivers energy-efficient HVACR solutions for
customers globally. Its world class brands include Thermo King, the leader in transport
temperature control and Trane, a provider of energy efficient heating, ventilating and air
conditioning systems, building and contracting services, parts support and advanced controls
for commercial buildings and homes.
Distributed by:
TK 50982-1-MM
2
Revision History
Rev. 5 – TK 50982-1-MM (Rev. 5, 09/14) Add DSR units, update Compressor Maintenance,
and other general updates.
This manual is published for informational purposes only and the information so provided should
not be considered as all-inclusive or covering all contingencies. If further information is required,
Thermo King Corporation should be consulted.
Sale of product shown in this manual is subject to Thermo King’s terms and conditions
including, but not limited to, the Thermo King Limited Express Warranty. Such terms and
conditions are available upon request. Thermo King’s warranty will not apply to any
equipment which has been “so repaired or altered outside the manufacturer’s plants as,
in the manufacturer’s judgment, to effect its stability.”
3
Recover Refrigerant
At Thermo King, we recognize the need to preserve the environment
and limit the potential harm to the ozone layer that can result from
allowing refrigerant to escape into the atmosphere.
R-134a/R-404A
WARNING: Use only Polyol Ester-based refrigeration compressor oil in
R-134a/R-404A units. See Thermo King Parts Manual for part number.
Do not mix Polyol Ester and standard synthetic compressor oils. Keep Polyol
Ester compressor oil in tightly sealed containers. If Polyol Ester oil becomes
contaminated with moisture or standard oils, dispose of properly–DO NOT USE.
When servicing Thermo King R-134a or R-404A units, use only those service
tools certified for and dedicated to R134a/R-404A refrigerant and Polyol Ester
compressor oils. Residual non-HFC refrigerants or oils will contaminate R-134a
and R-404A systems.
4
CHANGES, COMMENTS and SUGGESTIONS
You are invited to comment on this manual so it can be updated and improved to better meet you
needs. Any corrections, comments or suggestions are welcome. Please complete the following
information:
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
Return to:
5
About This Manual
Purpose
The purpose of this manual is to provide general maintenance information necessary to maintain the
climate control unit at peak operating standards. This includes system and bill of material numbers, safety
information, general unit information, maintenance procedures and related information (such as wiring
and schematic diagrams), and some diagnostic and troubleshooting information.
NOTE: This manual may cover more than one unit. Therefore, it may contain information not
applicable to your unit.
Contents
This manual is organized into the following chapters:
Chapter Purpose
Safety Precautions Provides detailed safety information. You should be familiar with the
safety precautions before working on any unit.
Model Systems (Systems This table lists the bills of material and kit options that apply to the
Designations) Table Thermo King units covered in this manual. Use this information to:
1. Determine if you have the right manual for your unit: the bill of material
(B/M) number on your unit serial plate should match one of the bill of
material numbers listed in this section. If you cannot find your unit in the
table, call TK Service for more information.)
2. Communicate with TK Service Department: If you need to call TK
Service, you must know your model number so that the service
representative can help you.
Specifications Lists unit specifications.
Unit Description Gives an overview description of the unit including standard and optional
features, general information, and unit photographs or illustrations.
Operating Instructions Provides unit operating instructions.
Maintenance Inspection Schedule Table of routine maintenance procedures.
Maintenance Chapters Provides detailed maintenance procedures required for your unit.
(Electrical, Refrigeration, Compressor, Clutch, Structural)
Diagnosis Chapters Provides troubleshooting information for diagnosing problems.
Diagrams Includes diagrams such as refrigeration, schematic, and wiring diagrams
applicable to units covered in this manual.
Blank Pages
This manual may contain blank pages at the end of chapters. This is normal. There is no information
missing from the manual.
6
About This Manual
Roadside/Curbside Terminology
Roadside/Curbside terminology: These terms can be confusing because of differences between North
America and Europe. Please note:
Curbside: The side to the driver’s right when the driver is in his seat and facing forward.
Roadside: The side to the driver’s left when the driver is in his seat and facing forward.
7
Table of Contents
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Before you Call Thermo King Service! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Blank Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Roadside/Curbside Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using the Model Tables in “About this Unit” . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Practices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Auto Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Refrigeration Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical Hazards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Microprocessor Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Welding of Units or Truck Bodies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
High Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Low Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Battery Installation and Cable Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Model Systems (System Designations) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Electric Standby Compressor Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Optional Electric Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Solder Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Condenser . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Evaporator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
DSR Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Oil Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Liquid Injection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Evaporator Drain Tube Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Units with DSR Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Protection Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Control Box in Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
P.C. Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Common Relays in Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Standby Relays in Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Multi-Temp Relays in Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Defrost Timer in Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Clutch Timer in Units with In-Cab Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
8
Table of Contents
9
Table of Contents
Electrical Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Maintenance Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Selecting the Temperature Scale for In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Setpoint Differential Adjustment for In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Trouble Shooting In-Cab Controller M13 and M16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Defrost System for Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Defrost Timer Settings for Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Defrost Relay for Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Defrost Solenoid Valve for Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Testing the Defrost System for Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . 52
Defrost Timer Test for Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Defrost System for Units with DSR Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Defrost Termination Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Condenser Fan Pressure Switch (CFPS) R-134a Units Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Testing CFPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Liquid Injection System (R-404A Units Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Testing Liquid Injection Solenoid Valve and Metering Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Condenser Fan Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Condenser Fan Motor Removal and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Evaporator Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Evaporator Fan Motor Removal and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Electric Standby Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Units with In-Cab Controller (M13, M16, M17) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Units with DSR Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Refrigeration Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Maintenance Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evacuating and Charging the Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Solenoid Valve Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Evacuation and Charging Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Checking the Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Testing the Refrigerant Charge with an Empty Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Testing the Refrigerant Charge with a Loaded Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Checking Compressor Oil Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Refrigeration System Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Cleanup Procedure for Small Truck Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Refrigeration Service Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Condenser Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Filter-Drier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
High Pressure Cutout Switch (HPCO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
High Pressure Cutout Switch Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
High Pressure Cutout and Condenser Fan Pressure Switch Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 65
High Pressure Transducer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Defrost Solenoid Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Liquid Injection Solenoid Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Heat Pilot Solenoid Test (Model 30 and 50 Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Liquid Solenoid Test (Multi-Temp Units Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Solenoid Valve Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Oil Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Liquid Injection Metering Orifice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Discharge Check Valve (Model 20 and 50 Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Testing the Discharge Check Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Double Discharge Check Valve Assembly Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Double Discharge Check Valve Assembly Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Discharge Check Valve Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Evaporator Coil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Expansion Valve Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
10
Table of Contents
11
Table of Contents
12
Safety Precautions
13
Safety Precautions
14
Safety Precautions
15
Safety Precautions
16
Model Systems (System Designations)
17
Model Systems (System Designations)
NOTE: When calling the dealer or factory for information or parts please have the Bill of Material
number for your particular unit handy.
18
Specifications
Electrical System
Fuses
See Unit Description chapter for detailed fuse lists and PC board illustrations.
Condenser Fan Motors
Voltage Full Load rpm Full Load Current
12 Vdc 2800 8.0 to 9.5 amps @ 13Vdc
24 Vdc 2800 3.9 to 4.1 amps @ 26Vdc
Evaporator Fan Motors
Voltage Full Load rpm Full Load Current
12 Vdc 2800 6.1 to 6.2 amps @ 13Vdc
24 Vdc 2800 3.5 to 3.9 amps @ 26Vdc
Coils for Hot Gas Solenoids, Condenser Solenoids, and Liquid Line Solenoids
Voltage Current Resistance
12 Vdc 2.3 amps 5.2 ohms
24 Vdc 1.3 amps 20 ohms
Liquid Injection Solenoid Coils
Voltage Current Resistance
12 Vdc 0.7 amps 17 ohms
24 Vdc 0.2 amps 67 ohms
Refrigerant System
R-134A REFRIGERATION SYSTEM (V-200/V-300)
Refrigerant Charge: V-200 10/20 3.0 lbs. (1.36 Kg)
V-300 10/20 3.85 lbs. (1.75 Kg)
Defrost Termination Switch: Opens 48.0 ± 5.4 F (8.9 ± 3.0 C)
Closes 36.0 ± 5.4 F (2.2 ± 3.0 C)
High Pressure Cutout Switch (if used): Opens 300 ± 10 psig (2068 ± 69 kPa)
Closes 200 ± 20 psig (1378 ± 69 kPa)
Low Pressure Cutout: Opens 5 to 11 in. Hg vacuum (-17 to -34 kPa)
Closes 4 to 7 psig (28 to 48 kPa)
Condenser Fan Pressure Switch (if used): Opens 130 ± 10 psig (896 ± 69 kPa)
Closes 180 ± 10 psig (1241 ± 69 kPa)
19
Specifications
Compressor
Model: V-200 /V-200 MAX 8 cu. in. (131 cc), Swash Plate, 6 Cylinder
V-300 /V-300 MAX 9 cu. in. (147 cc), Swash Plate, 6 Cylinder
Compressor Oil Charge: 1 Compressor systems 8 oz. (236.5 ml)
2 Compressor systems 14 oz. (414.0 ml)
Compressor Oil Type Polyol Ester P/N 203-515
Defrost Method Hot gas
Defrost Timer: Initiation Interval Adjustable, 1 hour to 10 hours
Termination Interval Termination is not timed.
Defrost is terminated by Klixon switch.
CAUTION: Do not mix compressor oil types. Failure to use correct Thermo King recommended oil
will invalidate your warranty.
20
Specifications
Belt Tension
Field Reset
Engine Driven Compressor Belt Check vehicle manufacturer specifications
Electric Standby Compressor Belt 58 (use Tool P/N 204-427)
Solder Applications
Components Used for: Details
Copper to copper or copper to General refrigeration Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
brass tubing connections Use: Solder Type 15% Silver TK No. 203-364 Use: Flux
Type TK No. 203-365
Copper to stainless steel or Refrigeration tubing Joint Clearances: 0.003 to 0.005 in. (0.076 to 0.127 mm)
brass to stainless steel connections of Use: Solder Type 35% Silver TK No. 203-366 Use: Flux
dissimilar metals Type TK No. 203-365
NOTE: Some units may be equipped with an evaporator pressure regulating valve (EPR). To reduce the
chance of overheating the EPR valve, 95-5 solder or equivalent may be used.
Use 95-5 TK No. 204-167
Use Flux TK No. 204-417
21
Unit Description
22
Unit Description
23
Unit Description
Low Battery Voltage Alarm: Disconnects the unit Liquid Injection System
when the battery voltage falls below 10.5 Vdc in
12 Vdc systems or below 21 Vdc in 24 Vdc MAX units use R-404A and have a liquid
systems. injection system to limit discharge temperature of
the engine driven compressor. If the discharge gas
Buzzer: It is energized when the vehicle battery leaving the compressor reaches a temperature of
and the electric power supply are connected at the 230 ± 5 F (110 ± 3 C) the liquid injection switch
same time. It is also energized if the doors are closes, providing voltage to the liquid injection
opened while the refrigeration unit is running. solenoid. The solenoid opens a valve, allowing
Unit Control without In-Cab Control Box: The unit liquid refrigerant to flow from the liquid line near
can also be operated by the Electronic Control the drier inlet to the metering orifice. The
System without the In-Cab Control Box, under metering orifice is attached to the suction line
conditions selected by the In-Cab Control Box fitting on the engine driven compressor on earlier
before it is disconnected. units, or to the suction tube assembly in the
Manual or Automatic Defrost: It is possible to condenser in later units. As the refrigerant passes
choose between manual or automatic defrost. through the metering orifice it expands and
evaporates, cooling the suction gas entering the
Maintenance Warning: On-screen warning of the compressor. This cooling effect is transferred to
need to carry out maintenance on the unit. the discharge gas leaving the compressor from the
Return Air Temperature Sensor: On-screen adjacent cavity in the compressor head. When the
reading of the temperature in the load discharge gas is cooled to 200 ± 5 F (93 ± 3 C),
compartment. the liquid injection switch opens, the liquid
Setpoint Temperature Reading: On-screen injection solenoid closes and refrigerant no longer
setpoint temperature reading. flows through the liquid injection system.
Electric Power Warning: On-screen warning that
the unit is connected to an electric power supply. Evaporator Drain Tube Heaters
Evaporator heaters are used in R-404A units to
Oil Separator avoid drain tube blockage because of ice
accumulation inside the evaporator. Two
An oil separator is a standard feature on all these harnesses are located inside the drain tube.
units. The oil separator separates compressor oil Heaters are on while the power relays energize to
from refrigerant vapor and returns the oil to the keep ice from forming in drain tubes.
compressor through the suction line. The oil
separator helps provide positive oil return at high
compressor speeds and low operating Electric Standby Operation
temperatures. This feature enhances compressor
lubrication and extends compressor life. Units with In-Cab Controller
During electric standby operation, the thermostat
Refrigerant controls the operation of the unit by energizing
and de-energizing the power relay, the electric
• V-200/V-300 and V-200/V-300 DSR units use relays, and the heat contactor. The thermostat
R-134a refrigerant. places the unit in cool by energizing the power
• V-200/V-300 MAX, V-200/V-300 MAX DSR, relay and the electric relays.
V-200/V-300 MAX TC, V-200/V-300 MAX The thermostat places the unit in null by
TC DSR, V-200/V-300 MAX TCI DSR, and de-energizing all the relays and contactors. The
V-200/V-300 MAX SPECTRUM DSR units thermostat places the unit in heat by energizing
use R-404A refrigerant. the heat contactor.
24
Unit Description
When the power relay and the electric relays are • Jet Lube™ Compressor Lubrication
energized, they close contacts that energize the (Standard)
fan relay, the motor contactor, and the electric
• Jet Cool™ Compressor injection cooling
standby compressor clutch.
(Standard with MAX units)
When the heat contactor is energized, it energizes
• Heat, Truck Engine (Optional - Model 10)
the electric evaporator heaters and the fan relay.
• Heat, Truck Engine and Electric Standby
Units with DSR Control System Heater Strips (Optional - Model 20)
When the unit is connected to an electric power • Hot Gas Heat (Model 30 and 50 Units Only)
source, the switch relay and the standby relay are
energized and provide rectified power from the Protection Features
transformer to the electronic control system.
• High Pressure Cutout Switch (Units with
During electric standby operation, the electronic In-Cab Controller) - The High Pressure Cutout
control system controls the operation of the unit Switch is a pressure sensitive switch. It is
by energizing and de-energizing the compressor located in the discharge line near the oil
contactor. separator on Model 10 units. It is located in
The electronic control system places the unit in the discharge check valve on Model 20 units.
cool, heat or defrost by energizing the compressor If the discharge pressure rises above the
contactor. switch’s opening pressure, the switch opens
The electronic control system places the unit in the circuit to the PR Relay to stop the unit.
null by de-energizing the compressor contactor. The opening pressure for R-134a units is
300 psig (2068 kPa). The opening pressure for
R-404A units is 450 psig (3100 kPa).
Unit Features
When the discharge pressure falls below the
• Condenser
switch’s closing pressure, the switch closes to
• ES200 Max Evaporator (V-200) restart the unit. The closing pressure for
R-134a units is 200 psig (1379 kPa). The
• ES300 Max Evaporator (V-300)
closing pressure for R-404A units is 375 psig
• Slim ES100 Max Evaporator for TC Units (2585 kPa).
(V-200)
• High Pressure Transducer (Units with DSR
• Slim ES150 Max Evaporator for TC Units Control System) - The high pressure
(V-300) transducer is a pressure sensitive device. It is
located in the discharge line near the oil
• In-Cab Controls with Digital LED or LCD
separator outlet.
Thermometer (Standard)
If the discharge pressure rises above a certain
• Electronic Thermostat (Standard)
pressure, the ECM opens the circuit to the
• Defrost Timer (Standard) compressor clutch to stop unit operation.
• Automatic Hot Gas Defrost (Standard) For units with R-134a, the ECM opens the
compressor clutch circuit at 300 psig (2068
• Manual Defrost Switch (Standard)
kPa) and shuts down the unit. The ECM closes
• Condenser Fan Pressure Switch (Standard in the compressor clutch circuit when the
some R-134a units) pressure drops to 200 psig (1379 kPa).
• Suction Pressure Regulator (Standard with
MAX units)
• Evaporator Drain Heaters (Standard with
MAX units)
25
Unit Description
P.C. Board
All Printed Circuit Boards manufactured for
Thermo King can be easily identified by the Part
Number stamped on them.
Even though that all P.C. Boards have a similar
layout, there are some differences from one to
another depending on the unit model and which
functions they carry out.
Connectors AJA1774 1 2 3
All connector codes (C-1, C-2, etc.) are stamped 1. Fuse 1 4. Fuse 4
on the P.C. Board. Pins on the connectors are 2. Fuse 2 5. Fuse 5 (TC units only)
numbered counter-clockwise. 3. Fuse 3 6. Fuse 6(TC units only)
Figure 4: P.C. Board Fuses (In-Cab Controller)
26
Unit Description
27
Unit Description
The Defrost Relay is energized when the In-Cab Pilot Solenoid Relay 2 (PS2)
Controller Defrost Switch or by the Defrost Timer
When the Remote Fan Relay 2 is energized,
completes the circuit through the Defrost
battery voltage energizes the liquid line solenoid
Termination Switch to ground.
for the front evaporator. It is controlled by the first
The Defrost Relay will remain energized until the compartment thermostat.
defrost cycle is terminated by the Defrost
Termination Switch or the In-Cab Controller Pilot Solenoid Relay 3 (PS3)
ON/OFF Switch is pressed.
When the Remote Fan Relay 3 is energized,
battery voltage energizes the liquid line solenoid
Standby Relays in Units with In-Cab for the remote evaporator. It is controlled by the
Controller second compartment thermostat.
The standby relays CR1, CR2 and ER are located
on the P.C. Board in Model 20. Defrost Timer in Units with In-Cab
Controller
Commutation Relays (CR1 and CR2)
The Defrost Timer automatically initiates the
When the Commutation Relays are energized the Defrost Cycle at the preset time intervals. The
electric power for the unit changes from Battery time interval can be set with the Red Round
Supply to Power Cord Supply. Selector and the A and B Switches. See Defrost
Timer Setings in the Electrical Maintenance
Electric Standby Relay (ER) section.
When the Electric Standby Relay is energized it The Defrost Timer is powered directly by truck
turns on the AC Motor of the electric standby battery, this means that the Defrost Timer is
compressor and de-energized engine driven always counting (while the Defrost Termination
compressor clutch. Switch is closed) even when the unit is turned off.
28
Unit Description
F7
F9
F10
F1
F11
F5 F6 F3 F4 F2
F1. Fuse 1 (5 amps) Power Supply Circuit to PCB1 F6. Fuse 6 (2 amps) Defrost Drain Heaters (HT1
and HT2)
F2. Fuse 2 (15/10 amps) Condenser Fan Motor (CFM) F7. Fuse 7 (15/10 amps) Not Used
F3. Fuse 3 (15/10 amps) Evaporator Fan Motor (EFM1) F8. Fuse 8 (20 amps) Remote Liquid Solenoid
Valve (PS2), Host Liquid Solenoid Valve
F4. Fuse 4 (15/10 amps) Evaporator Fan Motor (EFM2)
(PS3), Remote Hot Gas Defrost Solenoid
Valve (PS4), Suction Bypass Solenoid (PS11)
F5. Fuse 5 (20/10 amps) Compressor Clutch 1 (CCL1), F9. Fuse 9 (15/10 amps) Evaporator Fan Motor
Compressor Clutch 2 (CCL2), Liquid Injection Switch (EFM3)
(LIS), Liquid Injection Valve (LIV), Host Hot Gas F10. Fuse 10 (15 amps) Not Used
Defrost Solenoid Valve (PS1), Compressor Motor
Contactor (CMC), 26A Circuit to Heat Option F11. Fuse 11 (2 amps) Defrost Drain Heaters (HT3
and HT4)
Figure 6: ECM Platform 2 with Covers Removed Showing Fuses on PCB1 and PCB2
29
Unit Description
30
Unit Description
31
Unit Description
the pump and water valve. Voltage is also applied If power is shut off, the unit comes back in Null
from the 26A circuit through diode D6 to pin two mode when the unit is restarted. There is a
of a three pin header on the PC board. This momentary delay at auto start-up for circuit
voltage turns on two transistors on the board that protection.
energize the fan relay and also turns on the
NOTE: The compressor will “bump start” five
evaporator fans. The compressor and condenser
times while coming out of Null when the unit is
fans do not operate during the heating mode.
restarted after being turned off. This does not
The heat option for V-200 and V-300 20 (electric happen if the unit went into Null because it
standby) models consists of the above reached setpoint. In a “bump start” the
components, a heater contactor and an electric compressor is turned on for about one second
heating element. This heating element is attached and then goes off for about four seconds.
to the water coil described above. If the unit is not
Decrease in
plugged into electric standby power the water heat Temperature
COOL
works the same as described above, with one X C/F above the setpoint
difference. Current from the 2C circuit flows
through a normally closed set of contacts in the
Temperature Setpoint NULL
heater contactor before going to the heat relay. MODE
32
Unit Description
Cool Defrost
When cooling is required (when there is a Defrost can be initiated any time the evaporator
requirement to lower the evaporator return air coil temperature is below 36 F (2.2 C), causing
temperature in the load compartment), the the defrost termination switch to close. Defrost is
controller energizes the compressor clutch (or initiated automatically by the defrost timer, or
compressor contactor in model 20 units) and manually using the In-Cab Control Box.
evaporator fans. The controller monitors the
Defrost will continue until the evaporator coil
discharge pressure through the high pressure
temperature rises 48 F (8.9 C), causing the defrost
transducer (THPCO). The condenser fans are
termination switch to open ending the defrost
energized if necessary and turn on and off as
cycle. Defrost cycle can be also terminated by
determined by the controller.
pressing the On/Off Key to turn the unit off, and
The unit operates in Cool mode until the setpoint then pressing it again to turn the unit back on.
temperature is reached. The unit then enters Null
When defrost is required, the controller energizes
mode. When the temperature rises to a
the defrost solenoid so most of the high pressure
pre-determined number of degrees, the unit
refrigerant vapor leaves the compressor and flows
restarts in Cool mode.
through the defrost line, defrost solenoid, and
drain pan heater to the evaporator. There, the
Null
refrigerant heats the evaporator and returns to the
The unit operates in Null mode when the setpoint compressor through the suction lines. Some of the
temperature is reached and cooling (or heating) is refrigerant flows through the condenser and liquid
not required. All outputs are de-energized. If the lines to force any liquid refrigerant out through
temperature rises a pre-determined number of the drier and expansion valve to the evaporator.
degrees, the unit restarts in Cool mode. If the From which it returns to the compressor through
temperature falls a pre-determined number of the suction lines.
degrees, and a heat option is present, the unit
restarts in Heat mode. Serial Number Locations
In addition, the evaporator fans (parameter EFc) CONDENSER: Nameplate located on the front
might operate during Null mode. inside edge of condenser frame.
EVAPORATOR: Nameplate located on the outside
Heat
edge of the evaporator cover.
If a Heat option is present, the unit enters Heat ENGINE DRIVEN COMPRESSOR: Nameplate
mode when the temperature falls a pre-determined located on compressor body. The engine driven
number of degrees below the setpoint compressor is located in the truck engine
temperature. When heat is required, the outputs of compartment.
the microprocessor energize the evaporator fans.
STANDBY COMPRESSOR: Nameplate located on
(For units with Electric Standby, the Compressor
Motor Contactor are energized when the standby compressor body. The Standby compressor is
input is high). located inside the Condenser assembly.
33
Unit Description
AMA533
Figure 9: Condenser
ARA050
AMA516
1
2
3
4
34
Unit Description
AMA521
8 9 7 2 8 4
3
10 5
AMA522
35
Operating Instructions for Units with In-Cab
Controller (M13, M16, M17)
Introduction Description
Unit operation is controlled with a In-Cab 1. ON-OFF KEY (M13, and M16 only)
Controller, which is mounted in the truck cab. It It is used to start/stop the unit. The internal
includes an on-off switch, manual defrost switch, return air temperature will be automatically
thermometer, thermostat, thermostat adjustment, displayed.
and indicator lights. The in-cab controller comes
2. ON LED Indicator (M13, and M16 only)
in several model numbers as follow:
When on, it indicates that the unit has been
• V-200/V-300 =Model M13 Control Box started by pressing the on-off key.
• V-200/V-300 Max=Model M13 Control
Box 1
AJA1771
36
Operating Instructions for Units with In-Cab Controller (M13, M16, M17)
6. Setpoint Adjust Dial (M13, M16, M17) 11. Defrost LED Indicator (M13, and M16 only)
It is used to adjust the setpoint temperature. When on, it indicates the unit is working on
defrost mode.
7. Setpoint Key (M13, M16, M17)
It is used to display the setpoint temperature. 12. Manual Defrost Key (M13 and M16 only)
It is used to initiate the defrost cycle manually.
11
7
AJA1804
12
Figure 17: Setpoint Key & Dial
AJA1806
9. AC Overload LED (M13, and M16 only) Selecting the Temperature Scale
When on, it indicates the unit has been
stopped by the AC overload relay. Temperature readings can be displayed in the
Celsius scale or Fahrenheit scale. Dip switch 3,
10. Unit Operation LED (M13, M16, M17) located inside the In-Cab Controller, is used to
When on, it indicates the unit is cooling. select which scale is displayed. See the Electrical
When the unit is Stopped by the Thermostat, Maintenance chapter for complete instructions.
HPCO or LPCO, the Unit Operation LED
must be “OFF” and the ON LED Indicator
must remain “ON”.
8 11
AJA1805
10
37
Operating Instructions for Units with In-Cab Controller (M13, M16, M17)
38
Operating Instructions for Units with In-Cab Controller (M13, M16, M17)
2. Press the On-Off switch on the In-Cab 2. Spot check and record load temperature while
Controller, the ON/OFF LED must go ON. loading. Especially note any off-temperature
product.
3. Adjust the thermostat setting. Adjust the
thermostat setting in the second In-Cab 3. Load product so that there is adequate space
Controller on TC units. for air circulation completely around the load.
DO NOT block the evaporator inlet or outlet.
Electric Standby Operation 4. Products should be pre-cooled before loading.
1. Connect the external power supply to the Thermo King units are designed to maintain
power receptacle. Make sure that the power loads at the temperature at which they were
supply voltage is correct for the unit. The loaded. Transport refrigeration units are not
Power Cord LED should go ON. designed to pull hot loads down to
temperature.
39
Operating Instructions for Units with In-Cab Controller (M13, M16, M17)
40
Operating Instructions for Units with DSR
Control System
In truck-driven units, temperature control is based Unit Controls
on two values: The setting (Setpoint) of the WARNING: Never operate the unit unless you
electronic thermostat and the evaporator return completely understand the controls; otherwise
temperature. The difference between these two serious injury may occur.
temperatures will determine the mode of
operation: cool, heat, or null.
Cool: When the temperature in the load
compartment is higher than the setpoint, the unit
runs in cool mode to reduce the evaporator return
temperature.
Heat (If So Equipped): When the temperature in
the load compartment is lower than the setpoint,
the unit changes to heat mode to raise the
Figure 24: In-Cab Control Box
evaporator return temperature. Display, Keys and Symbols
Null: Once the Setpoint Temperature has been
reached, and while the temperature remains 1. Display It is always active and backlit except
between X F/C above or below the setpoint, there when the unit is disconnected (no
is no demand for transfer of heat or cold, and the power) or when the unit is connected
unit runs in null mode. but has been manually switched off
from the In-Cab Control Box. It
Defrost: After a scheduled period of time in cool normally displays the return air
mode, between 1 and 8 hours, the unit runs in this temperature.
fourth mode of operation to eliminate ice that has 2. On/Off This key is used to start/stop the unit.
accumulated in the evaporator coil. Defrost can be Key It is always lit except when the unit is
initiated automatically or manually. disconnected (no power), and thus
acts as an indicator of the presence of
power in the unit.
Decrease in
Temperature
COOL 3. Select Selects prompt screens and
X C/F above the setpoint
Key information screens.
4. Up Key Is used to increase the setpoint
temperature.
Temperature Setpoint NULL
MODE 5. Down Key Is used to reduce the setpoint
temperature.
X C/F below the setpoint
6. Enter Key Is used to enter a new command such
Increase in
HEAT
temperature as manual defrost, etc.
7. Buzzer It is energized when the vehicle
Figure 23: Thermostat Algorithm battery and the electric power supply
are connected simultaneously. It is
Factory setting for X is 5 F (3 C). During unit also energized if the doors are
installation, this value can be adjusted by between opened while the refrigeration unit is
2 and 9 F (1 and 5 C) in increments of 1 F/C. running.
Units with R-134a refrigerant: Temperatures can 8. Cool (Thermometer with an arrow pointing
Symbol downward). The unit is cooling.
be controlled from -8 F to +71 F (-22 C to +22 C).
9. Heat (Thermometer with an arrow pointing
Units with R-404A refrigerant: Temperatures can Symbol upward). The unit is heating.
be controlled from -26 F to +71 F (-32 C to +22 10. C/ F Indicates whether the on-screen
C). Symbol temperature reading is in degrees
Celsius (C) or degrees Fahrenheit
(F).
41
Operating Instructions for Units with DSR Control System
11. Alarm Indicates that there is an alarm in the Should there be an alarm, the alarm symbol will
Symbol system. also appear on screen.
12. Warns of the need to carry out
Maintenance maintenance to the unit. Single-Temperature Units
Symbol
13. Defrost Indicates the unit is in Defrost Mode.
Symbol
14. Electrical Indicates that the unit is in Electric
Symbol Standby.
Standard Display
This is the display that appears when the On/Off
key is pressed and the unit started. It normally
displays the return air temperature (of both load Figure 27: Single-Temperature Units
compartments in multi-temperature units) and the
current operating mode with the appropriate 1. Press and release the Select key twice, and the
symbol. current Setpoint Temperature and the letters
SP will appear on screen.
42
Operating Instructions for Units with DSR Control System
2. Press the Up or Down arrow keys to select the 4. Remote Compartment: The present Setpoint
desired Setpoint Temperature. Each time Temperature in the remote compartment and
either of these buttons is pressed and released, the letters SP2 will appear on screen.
the Setpoint Temperature will change 1
degree.
3. Press and release the Select key, and the
Standard Display will reappear on screen.
IMPORTANT: If the SELECT key is not pressed
within 20 seconds to select the new Setpoint
Temperature, the unit will continue to run at the Figure 29: Remote Compartment Setpoint
original Setpoint Temperature.
5. Press the Up or Down arrow keys to select the
desired Setpoint Temperature. Each time
In Multi-Temperature Units
either of these buttons is pressed and released,
1. Main (Host) Compartment: Press and the Setpoint Temperature will change 1
release the Select key twice, and the current degree.
Setpoint Temperature in the main
compartment and the letters SP will appear on 6. Press and release the Select key, and the
screen. Standard Display will reappear on screen.
IMPORTANT: If the SELECT key is not pressed
within 20 seconds to select the new Setpoint
Temperature, the unit will continue to run at the
original Setpoint Temperature.
43
Operating Instructions for Units with DSR Control System
2. To activate manual defrost, press the Enter Press and release the Select key to display the
key and then the Up or Down key and the current alarm code on screen. If there is more than
defrost condition will change to On. one active alarm, all the alarm codes on the unit
can be viewed in sequence by pressing and
releasing the Select key.
Auto Start
The alarm stops the unit, the Alarm symbol
appears on screen and the unit starts up
automatically once the alarm condition has been
Figure 31: Defrost Condition On
rectified.
3. Press the Select key twice to return to the
Standard Display (three times in
multi-temperature units), where the Defrost
symbol will appear when the defrost cycle
begins (the defrost termination switch must
be closed).
Alarms
When the unit is not operating properly, the
microprocessor records the alarm code, alerts the
operator by displaying the Alarm symbol and,
Figure 35: P1E Alarm
depending on the type of alarm, shuts the unit
down. In multi-temperature units, should a P2E (return
air temperature read error in the remote
There are three alarm categories:
compartment alarm code), --- will also appear on
screen together with the alarm symbol, instead of
Manual Start the remote compartment return air temperature
The alarm stops the unit, and only the ALARM reading.
symbol appears on screen.
44
Operating Instructions for Units with DSR Control System
Press and release the Select key to display the Alarm Description
current alarm code on screen. If there is more than P1E Main or Single Cargo Box Return Air
one active alarm, all the alarm codes on the unit Temperature Reading Error (open circuit or
can be viewed in sequence by pressing and short-circuit). Contact your Service Dealer.
releasing the Select key. P2E Remote Cargo Box Return Air
Temperature Reading Error (open circuit or
Buzzers short-circuit). Contact your Service Dealer.
C Communications Failure. Contact your
They are energized when the vehicle battery and Service Dealer.
the electrical supply are connected simultaneously
(the unit continues running in standby mode).
They are also energized if the doors open, if this Clearing Alarm Codes
option is selected. The alarm condition in the unit must first be
corrected. After clearing the alarm condition,
Alarm Code Descriptions press and release the Select key to remove
existing Alarm codes. The standard display will
Alarm Description appear once the Alarm codes have been cleared.
Manual Start
OL Electric Motor Overload. Unit protection Viewing Information Screens
system during electric standby operation. If
the problem persists when the unit is
restarted, contact your Service Dealer.
Main Menu
bAt Low Battery Voltage. Unit and battery From the Standard Display use the Select key to
protection system. display:
Auto Start
1. Alarms (if any active)
HP High Pressure Alarm. Indicates that the
refrigeration system will shut down in the 2. Manual Defrost
event of excessively high pressure in the
refrigerant circuit. If the problem persists 3. Temperature Setpoint
when the unit is restarted, contact your
Service Dealer. Hourmeter Menu
LP Low Pressure Alarm. Indicates that the From the Standard Display press the Select key
refrigeration system will shut down in the
event of excessively low pressure in the
for 3 seconds to open the Hourmeter Menu, then
refrigerant circuit. If the problem persists use the SELECT key to display:
when the unit is restarted, contact your
1. HC: Hours remaining to maintenance notice.
Service Dealer.
PSE High Pressure Sensor Failure. The high 2. tH: The total amount of time the unit has been
pressure sensor has become faulty or switched on protecting the load.
disconnected. Contact your Service
Dealer. 3. CC: Engine-driven compressor operating
tEP Electric Motor Thermal Protection Alarm. If hours.
the problem persists when the unit is 4. EC: Electric standby compressor operating
restarted, contact your Service Dealer
hours.
dr1, dr2 Doors Open. This option must be
activated. 5. Return to Main Menu.
tCO Control Module Overheating. If the
(Hot) problem persists when the unit is restarted,
contact your Service Dealer.
SOF Software failure. Contact your Service
Dealer.
45
Operating Instructions for Units with DSR Control System
After Start Inspection 4. Half an hour after loading the truck, initiate a
defrost cycle with the In-Cab Control Box. If
Thermostat: Adjust the thermostat setting to
the coil temperature is below 36 F (2.2 C), the
above and below the compartment temperature to
unit will defrost. The defrost cycle should stop
check thermostat operation (see Operating
automatically.
Modes).
Pre-cooling: With the thermostat set at the desired
temperature, run the unit for half-an-hour to one
Weekly Pretrip Inspection
hour (or longer if possible) before loading the The following Weekly Pretrip Inspection should
truck. Pre-cooling eliminates residual heat and be completed before loading the truck. While the
acts as a good test of the refrigeration system. weekly inspection in not a substitute for regularly
Defrost: When the unit has finished pre-cooling scheduled maintenance inspections, it is important
the truck interior - the evaporator temperature part of the preventive maintenance program
should have dropped below 36 F (2.2 C) - initiate designed to head off operating problems before
a defrost cycle with the In-Cab Control Box. The they happen.
defrost cycle should stop automatically. 1. LEAKS. Inspect for refrigerant leaks and
worn refrigerant lines.
Loading Procedure 2. BELTS. Inspect for cracks, wear and proper
1. To minimize frost accumulation in the belt tension.
evaporator coil and a heat increase inside the 3. MOUNTING BOLTS. Inspect bolts are
load compartment, ensure that the unit is OFF properly tightened.
before opening the doors. (The unit may
continue to run when the truck is being loaded 4. ELECTRICAL. Electrical connections should
in a warehouse with the doors closed.) be securely fastened. Wires and terminals
should be free of corrosion, cracks or
2. Carefully check and record the load moisture.
temperature when loading the truck. Note
whether any products are out of temperature 5. DEFROST DRAINS. Check the defrost drain
range. hose and fittings to be sure that they are open
so condensate can run out during defrosting.
3. Load the product in such a way that there is Check the bottom end of drain hose to be sure
sufficient space for the air to circulate that is not plugged or crushed.
throughout the load. DO NOT block the
evaporator inlet or outlet. 6. STRUCTURAL. Visually check for physical
damage.
4. Product should be pre-cooled before loading.
Thermo King units are designed to maintain 7. REFRIGERANT CHARGE. Check for proper
the load at the temperature at which it is refrigerant charge level.
loaded. Transport refrigeration units are not
designed to reduce the load temperature. Weekly Post Trip Checks
1. Wash the unit.
Procedure after loading
2. Check for leaks.
1. Ensure that all doors are closed and locked.
3. Check for loose or missing hardware.
2. Adjust the thermostat to the desired
temperature setpoint. 4. Check for physical damage to unit.
3. Start the unit.
46
Maintenance Inspection Schedule
NOTE: Thermo King reserves the right to deny NOTE: See the appropriate chapter in this
warranty coverage on claims due to lack of maintenance manual for instructions on how to
maintenance or neglect. Claims in question must correctly perform required maintenance.
be supported by maintenance records.
Electrical
Semi-
Weekly Monthly Annual Annually Check condition of or service the following:
• • Check defrost initiation and termination.
• • Check thermostat cycle sequence.
• • Check operation of protection shutdown circuits.
• Check thermostat and thermometer calibration in 32 F (0 C)
ice-water bath.
• Inspect wire harness for damaged wires or connections.
• Inspect DC fan motors.
Refrigeration/Heating
Semi-
Weekly Monthly Annual Annually Check condition of or service the following:
• • Check refrigerant level.
• Replace dehydrator.
• Check compressor pressure regulator and suction pressure
regulator settings if applicable.
Structural
Semi-
Weekly Monthly Annual Annually Check condition of or service the following:
• • • • Visually inspect unit and refrigerant hoses for fluid leaks.
• • • • Visually inspect unit for damaged, loose or broken parts.
• • • • Clean defrost drains.
• • • Inspect belts for condition and proper tension (belt tension tool
P/N 204-427).
• • • Clean entire unit including evaporator coil and condenser coil.
• • Check all unit mounting bolts, brackets, lines, hoses, etc.
47
Electrical Maintenance
1. Dip Switches
48
Electrical Maintenance
Setpoint Differential
Adjustment for In-Cab
Controller (M13, M16, M17)
Adjust the thermostat setpoint differential to 4 F
(2 C).
1. Remove the In-Cab Controller from its
bracket.
2. Remove the cover from the back of the In-Cab
Controller.
3. Turn the adjusting potentiometer to the 12
o’clock position.
4. Replace the cover and place the In-Cab
Controller back in its bracket.
NOTE: Do not run a R-134a unit to -26 F (-32
C). R-404A units may be operated at -26 F (-32
C).
1. 1 Amp Fuse
2. 12/24 Volt Jumper
3. Main Harness Plug
4. Dip Switches
5. Sensor Plug
6. Setpoint Differential Potentiometer Set to 12 o’clock position
49
Electrical Maintenance
AJA1775
SYMPTOMS REMEDY
Blank display when the On/Off Switch is pressed. 1st. Check voltage on Pin 3 C-9 (Pin 2 when is unit
working in electric mode).
2nd. Check Fuse 4/1 located inside the In-Cab
Controller.
3rd. Replace In-Cab Controller.
Unit is not cooling when the Box Temperature is 1st. Check voltage on Pin 6 C-9.
higher than the Setpoint Temperature. 2nd. Replace In-Cab Controller.
Unit Operation LED is OFF when the unit is cooling. 1st. Check voltage on Pin 7 C-9.
2nd. Replace In-Cab Controller.
Defrost cycle is not initiated when the Manual 1st. Box temperature must be higher than Setpoint
Defrost Switch is pressed. temperature; unit must be in cool mode.
2nd. Evaporator coil temperature must be lower than
36.0 ± 5.4 F (2.2 ± 3.0 C) (defrost termination switch
closed).
3rd. While keeping the Manual Defrost Switch pressed,
check voltage on Pin 8 C-9.
4th. Replace In-Cab Controller.
Defrost LED is OFF when the unit is in Defrost 1st. Check for open circuit on Wire Y, between Pin 4
Mode. C-9 and Pin 2 C-3.
2nd. Check voltage on Pin 8 C-9.
3rd. Replace In-Cab Controller.
Temperature displayed is out of range. 1st. Check that the In-Cab Controller 12/24V selector is
in the correct position.
2nd. Check the thermostat sensor.
50
Electrical Maintenance
SYMPTOMS REMEDY
Unit is not working in Electric Mode. 1st. Check the AC Overload Relay (AC Overload Led
must be OFF).
2nd. Check the fuses on the P.C. Board.
3rd. Check voltage on Pin 2 C-9.
4th. Check voltage on Pin 1 C-9.
5th. Replace In-Cab Controller.
Unit is stopped by the AC OL Relay, but the AC 1st. Check voltage on Pin 5 C-9.
Overload LED is OFF. 2nd. Replace In-Cab Controller.
Defrost System for Units with Defrost Timer Settings for Units with
In-Cab Controller (M13, M16, In-Cab Controller (M13, M16, M17)
M17) NOTE: The defrost timer is directly connected to
the battery. This means that the defrost timer is
A defrost cycle can be started by pressing the
always timing, even if the unit is turned off.
manual defrost switch, or automatically by the
defrost timer, when the defrost termination switch The defrost timer has two selector switches (A
is closed and the unit is in cool mode. and B) and a round red selector that are used to set
The defrost cycle operates by energizing the the timer interval.
defrost relay. The defrost relay energizes the The factory setting for the defrost timer is four
defrost solenoid valve (and the condenser hours. Use the following information to change
solenoid valve on units equipped with the heat the setting of the defrost timer.
option). The defrost relay also interrupts power to
1 2
the evaporator and condenser fans, which stops
the evaporator and condenser fans.
Energizing the defrost solenoid valve diverts hot
gas into the evaporator coil, melting ice. A defrost
termination switch de-energizes the defrost relay
when evaporator temperature rises above 48 F
(8.9 C).
To check the defrost cycle, run the unit on Cool to
drop the evaporator coil to a temperature below
36 F (2.2 C).
Press the manual defrost switch. The unit should
AGA1225
shift from Cool to Defrost Mode. If the unit
continues to Cool, double check the evaporator Figure 40: Defrost Timer
coil temperature, and refer to “Testing the Defrost
1. Refer the following timing table. A similar
System.”
table is located on the printed circuit board.
On TC units defrost is performed on both
evaporators at the same time. Defrost termination TIMING Switch SCALE
TABLE
is controlled by the defrost termination switch on A B
the main evaporator. 0.25 - 2.5 Down Up From 0.25 to 2.5
minutes
1 - 10 Up Down From 1 to 10 minutes
8 - 80 Up Up From 8 to 80 minutes
64 - 640 Down Down From 1 to 10 hours
51
Electrical Maintenance
2. Choose the range in the timing table in which Testing the Defrost System for Units
your timing needs are included and set with In-Cab Controller (M13, M16,
switches A and B to the desired position. M17)
Example: Setting selector switches A and B to To test the defrost system, run the unit on cool
positions A: down and B: down chooses the until the evaporator coil temperature is below
time range of approximately 1 to 10 hours (64 36.0 ± 5.4 F (2.2 ± 3.0 C) and press the manual
to 640 minutes). defrost switch.
3. Set the round red selector to the desired value. If the unit doesn’t shift to defrost cycle go to
The round red selector multiplies the step 1.
minimum value of the chosen range by the
1. Check the evaporator temperature.
value it is pointing at.
Be sure the evaporator temperature is actually
Example: If the selector points to position 2,
below 36.0 ± 5.4 F (2.2 ± 3.0 C), otherwise
approximately 2 hours (2 x 64 = 128 minutes)
the unit will not defrost. Use a test
Example: If the selector points to position 4, thermometer to check the evaporator
approximately 4 hours (4 x 64 = 256 minutes). temperature.
2. Check the defrost termination switch.
Defrost Relay for Units with In-Cab
Controller (M13, M16, M17) If the unit fails to defrost, place a jumper wire
between the 12 and CH wires at the defrost
The defrost relay controls operation of the defrost
termination switch. Press the manual defrost
cycle. When the defrost timer or the manual
switch.
defrost switch completes the circuit through the
defrost termination switch to ground, the defrost If the unit shifts to defrost, the defrost
relay is energized. This energizes the defrost termination switch is defective.
solenoid valve (wire 26) and de-energizes the fan
If the unit does not shift to defrost, check for
relay.
an open circuit in the 12 wire back to Pin 2
The defrost relay stays energized until the defrost C-3. If the 12 wire is not open go to step 3.
cycle is terminated by the defrost termination
3. Check voltage on Pin 1 C-3.
switch, or the On/Off Key is pressed.
If voltage is present on Pin 1 C-3, replace the
Defrost Solenoid Valve for Units defrost relay.
with In-Cab Controller (M13, M16, If voltage is not present, go to step 4.
M17)
4. Check for open circuit on wire GR that goes to
The defrost solenoid valve is an electrical valve
the In-Cab Controller (Pin 8 C-9).
that controls the flow of refrigerant through the
refrigeration system. If the wire GR is not open, go to step 5.
The defrost solenoid valve is energized by the 26 5. Press and hold manual defrost switch, check
wire (Pin 1 C-1). When the defrost solenoid valve the voltage on Pin 8 C-9.
is energized it routes hot refrigerant gas to the
If voltage is present on Pin 8 C-9 and the rest
evaporator.
of the above mentioned points are correct,
replace the printed circuit board.
If voltage is not present on Pin 8 C-9, check
the In-Cab Controller.
52
Electrical Maintenance
Defrost Timer Test for Units with Defrost initiation and termination settings are
In-Cab Controller (M13, M16, M17) accessed through the Guarded Access Menu.
Refer to the Direct Smart Reefer Microprocessor
The defrost timer initiates the defrost cycle.
Control System Diagnostic Manual TK 52573 for
1. Verify that the evaporator coil temperature is instructions on the use of Guarded Access Menu
lower than 36.0 ± 5.4 F (2.2 ± 3.0 C). If not, features.
place a jumper wire between the 12 and CH
The Defrost Initiation Timer offers programming
wires at the defrost termination switch.
choices of 30 to 480 minutes, increments of 30
2. Set the defrost timer to approximately 1 minutes. The factory setting is 240 minutes. This
minute (selector switches A:↓, B:↓ and round parameter allows maintenance personnel to set the
red selector in position 4). Defrost Initiation Timer. When it times-out, it
switches the unit from Cool mode to Defrost
3. After approximately one minute, defrost
mode. The timer counts all the time that the unit is
should be initiated. The Defrost LED, defrost
in Cool mode. The count resets when Defrost
relay, and defrost solenoid valve must be
mode starts. If the timer is set at 0 (zero), this is a
activated.
test position. Defrost mode starts in 15 seconds.
Defrost System for Units with The Defrost Termination Timer offers
programming choices of 5 to 50 minutes, in
DSR Control System increments of 5 minutes. The factory setting is 45
Defrost is initiated automatically by the minutes. This parameter allows maintenance
programmable defrost timer, or manually by personnel to set the Defrost Termination Timer,
means of the In-Cab Control Box. If demand which begins counting from the initiation of a
defrost is enabled, a demand defrost cycle occurs, Defrost mode. When the timer times-out, the unit
based on the Defrost Initiation Timer (DIT) and is switched from Defrost mode to Null mode. The
the Defrost Termination Switch (DTS1 or DTS2) timer resets at the end of a Defrost mode, or after
being closed. The evaporator coil temperature the Defrost Termination Timer has timed-out. If
must be below 36 F (2.2 C) to allow defrost. the timer is set at 0 (zero), this is a test position.
Defrost mode stops in 15 seconds.
When defrost is required, the microprocessor
output energizes the defrost solenoid to supply hot
refrigerant to the evaporator coil. The Defrost Defrost Termination Switch
Initiation Timer (DIT) has counted-down its The switch is mounted in the evaporator coil and
required time-setting, and the Defrost Termination controls the defrost cycle in response to the
Switch (DTS1 or DTS2) is closed. evaporator coil temperature. The switch is closed
The unit remains in Defrost mode until the when the evaporator coil temperature is below
Defrost Termination Switch setpoint is reached 36 F (2.2 C). completing the defrost circuit to
(that is, when the evaporator coil temperature ground and preparing the electrical system for the
rises to 48.0 F (8.9 C), or until the Defrost defrost cycle.
Termination Timer (DTT) count is completed). If When the unit does shift into a defrost cycle, the
the evaporator coil temperature does not rise evaporator fan stops, and heat from the hot
above 48.0 F (8.9 C) within the defrost duration refrigerant gas melts the frost from the evaporator
time limit, the microprocessor terminates the coil. The switch opens and terminates the defrost
defrost operation. cycle when the evaporator coil temperature rises
The startup of the evaporator fans is delayed for above 48 F (8.9 C).
several seconds after Defrost mode ends to
prevent water from the melting ice from being
sprayed on the load.
On multi temp units defrost is performed on all
evaporators at the same time.
53
Electrical Maintenance
3. Run the unit on Cool. When the condenser 6. With the jumper wire in place the suction
head pressure is higher than 180 ± 10 psig pressure should rise.
(1241 ± 69 kPa) the condenser fan motor must 7. Remove the jumper. The suction pressure
be running and the voltmeter should indicate should return to the stabilized pressure in
approximately 0 volts. step 4.
4. Run the unit on Cool. When the condenser 8. If the suction pressure does not change, check
head pressure is lower than 130 ± 10 psig (896 the CLU wire for voltage, the LIS and LIS1
± 69 kPa) the condenser fan motor must be wires for continuity, the liquid injection
stopped and the voltmeter should indicate solenoid valve, and the metering orifice.
approximately truck battery voltage.
9. Shut off the unit and the truck, remove the
gauge manifold set, and reconnect the LIS and
CLU wires to the liquid injection switch.
54
Electrical Maintenance
Condenser Fan Motor Removal and Evaporator Fan Motor Removal and
Installation Installation
Removal Removal
1. Turn the unit off. 1. Turn the unit off.
2. Remove the condenser if necessary. 2. Remove the fan motor mounting bolts (4).
3. Remove the fan motor/fan guard mounting 3. Disconnect the motor power plug.
bolts (4).
4. Remove the fan motor and disconnect the
4. Remove the fan guard if used. motor power plug.
5. Lift the fan motor and disconnect the motor Installation
power plug.
1. Connect the fan motor power plug.
6. Remove the fan motor from the condenser.
2. Attach the fan motor to the evaporator and
Installation tighten the fan motor mounting bolts (4).
1. Connect the fan motor power plug. 3. Start the unit and verify correct fan motor
operation.
2. Place the fan motor (and fan guard if used) in
the condenser. Install and tighten the fan guard
and fan motor mounting bolts (4).
3. Install the condenser cover if removed before.
4. Start the unit and verify correct fan motor
operation.
55
Electrical Maintenance
56
Electrical Maintenance
7. Check the voltage on both ends of the 2RB 13. Check the voltage on the CMC wire at the
wire at the standby relay (STDR). If voltage is compressor contactor. If voltage is not present,
not present, the 2RB wire is open. If the check the continuity of the CMC circuit to Pin
voltage on both ends of the 2RB wire is 10 in Connector 2 on PCB1 in the ECM, or to
acceptable, go to step 8. Pin B1 in Connector 1 on PCB1 in the ECM,
and Fuse 5 on the ECM. If the CMC wire has
8. Check the voltage on the 2RB1 wire at the
good continuity and Fuse 5 is good, the ECM
switch relay (C1R). If voltage is not present,
may be defective. If the voltage on the CMC
check the continuity of the 2RB1 wire from
wire is acceptable, go to step 14.
the standby relay (STDR). If the voltage on
the 2RB1 wire at the switch relay (C1R) is 14. Check for continuity to ground on the CHE
acceptable, go to step 9. wire at the compressor motor contactor
(CMC). If there is good continuity to ground
9. Check for continuity to ground on the SWS
on the CHE wire at the compressor motor
wire at the switch relay (C1R). If continuity to
contactor (CMC), the compressor contactor is
ground is not present, check for continuity to
probably defective. If continuity to ground on
ground on the CH4 wire at the switch relay
the CHE wire at the compressor contactor is
(C1R). If the CH4 wire has good continuity to
not present, go to step 15.
ground, the switch relay (C1R) is probably
defective. If there is good continuity to ground 15. Check the continuity of the CHE wire from
on the SWS wire at the switch relay (C1R), go the compressor motor contactor (CMC) to the
to step 10. chassis ground.
10. Check for continuity to ground on the SWS
wire at the standby relay (STDR). If
continuity to ground is not present, check the
continuity of the SWS wire from the switch
relay (C1R). If there is good continuity to
ground on the SWS wire at the standby relay
(STDR), go to step 11.
11. Check the voltage on the 2RA wire at the
standby relay (STDR). If voltage is not
present, the standby power relay is probably
defective. If the voltage on the 2RA wire at
the standby power relay is acceptable, go to
step 12.
12. Check the voltage on the PC1 wire at Pin 2 in
the PSC Connector on PCB1 in the ECM, or
the PC wire at Pin 10 in Connector 2 on PCB1
in the ECM. If voltage is not present, check
the continuity of the PC1 or PC circuit to the
terminal board (TB) the 2RA circuit to the
standby relay (STDR). If the voltage on the
PC1 or PC wire is acceptable, go to step 13.
57
Refrigeration Maintenance
NOTE: The following procedures involve 4. After completing the evacuation procedure,
servicing the refrigeration system. Some of these remove the magnet tools and replace the
service procedures are regulated by Federal, and solenoid coil assembly on the solenoid valve
in some cases, by State and Local laws. and hand tighten the coil retaining nut.
All regulated refrigeration service procedures
must be performed by an EPA certified Evacuation and Charging Procedure
technician, using approved equipment and The liquid line sight glass helps the operator to
complying with all Federal, State and Local determine the amount of charge under established
laws. operating conditions. These units can be damaged
by an overcharge of refrigerant. The amount of
Evacuating and Charging the refrigerant the system can hold depends on circuit
volume which is affected by hose length.
Refrigeration System
The most satisfactory method of evacuating and
Procedures charging the system is as follows:
IMPORTANT: Thermo King Evacuation Station 1. Connect a gauge manifold set to the suction
P/N 204-725 and Evacuation Station Operation and discharge service ports on the engine
and Field Application Instructions (TK-40612) is driven compressor.
required.
2. Connect the center hose of the gauge manifold
NOTE: The oil in the evacuation station vacuum to the manifold of an evacuation station. The
pump should be changed after each use. use of Thermo King Evacuation Station
P/N 204-725 is recommended.
Solenoid Valve Positions 3. Connect the hose from a drum of refrigerant to
The liquid injection valve and the defrost solenoid the manifold of the evacuation station. Make
must be in the open position during evacuation sure the valve on the refrigerant drum is
procedures. These valves must be held open closed.
manually using special magnet tools (P/N
4. Open the valves on the gauge manifold and
204-1074) designed for this purpose.
the valves on the evacuation station.
NOTE: The heat pilot solenoid (PS5 if used) is
5. Start the vacuum pump and evacuate the
normally open so it does not need to be held open
system to 500 microns. After the system
with a magnet tool.
reaches 500 microns, evacuate the system for
1. Unscrew the solenoid coil retaining nut and an additional hour.
remove the coil assembly.
NOTE: If the system will not come down to
2. Place a magnet tool on the solenoid valve 500 microns, there is probably a leak in the
stem. system or in the evacuation and charging
equipment hoses. Find and repair the leak.
3. Carry out the evacuation procedure.
58
Refrigeration Maintenance
1
11. Start the unit on engine operation and run the
truck engine at approximately 1000 rpm.
2
12. Set the thermostat at 32 F (0 C), and run the
unit in cool until the box temperature
approaches 32 F (0 C).
13. Make sure that the unit is running in cool, the
compressor is running at approximately 1000
rpm, the suction pressure is 2 to 8 psig (14 to
55 kPa), and the head pressure is at least
3
4 180 psig (1241 kPa) for R-134a systems or
275 psig (1896 kPa) for R-404A systems. If
necessary, raise the head pressure by covering
the condenser.
ARA053
14. With these conditions established, open the
1. Gauge Manifold Set valve on the refrigerant drum to deliver liquid.
2. Engine Driven Compressor 15. Observe the suction pressure and slowly open
3. Evacuation Station
the low side gauge manifold valve to allow
liquid refrigerant to flow into the compressor
4. Refrigerant Drum suction service valve.
Figure 42: Evacuating and
Charging Refrigeration System
16. Control the liquid flow so the suction pressure
increases approximately 20 psig (138 kPa).
6. After the additional hour of evacuation, close 17. Observe the liquid line sight glass. Close the
the valve at the evacuation pump, stop the valve on the refrigerant drum when the
vacuum pump, and observe the reading on the bubbles disappear from the sight glass.
vacuum gauge for 5 minutes. The pressure
should not exceed 2000 microns. 18. Close the low side valve on the gauge
manifold and operate the unit for 15 minutes.
NOTE: If the pressure exceeds 2000 microns
within 5 minutes, look for a leak in the 19. Model 20 and 50 only.
system or in the evacuation and charging a. Turn the unit Off and shut off the truck
equipment hoses. Find and repair the engine.
leak.Then repeat steps 5 and 6.
b. Connect the electric power receptacle to
7. Open the vacuum valve at the vacuum pump, an appropriate electric power supply. Start
start the vacuum pump, and evacuate the and run the unit in cool on electric
system to 500 microns. operation for a minimum of 15 minutes.
8. When the system reaches 500 microns, close c. Turn the unit Off and disconnect the
the vacuum valve at the evacuation station electric power supply. Start the truck and
manifold. The system is now ready to charge. run the unit in cool on engine operation for
9. Close the low side valve on the gauge a minimum of 15 minutes.
manifold, leave the high side valve on the 20. Check the liquid line sight glass for bubbles.
gauge manifold open, and open the valve on Repeat steps 13 through 20 if bubbles are
the refrigerant drum to deliver liquid. visible.
10. Allow 2.60 lb (1.20 kg) of R-134a or 2.75 lb 21. Stop the unit, shut off the truck engine and
(1.25 kg) of R- 404A refrigerant to enter the remove the gauge manifold set.
system. Then close the valve on the refrigerant
drum and the high side valve on the gauge
manifold.
59
Refrigeration Maintenance
22. The above conditions MUST be established 2. Run the unit in cool on engine driven
each time the refrigerant level is checked, or if compressor operation.
refrigerant needs to be added for any reason.
3. Cover the condenser to drive any excess
NOTE: To prevent oil migration from one refrigerant from the condenser into the
compressor to another, and for proper oil receiver tank.
return when a compressor is operating,
4. As the head pressure rises, check the liquid
operate a compressor for a minimum of 15
line sight glass. There should be no bubbles in
minutes. Do not operate a compressor for
the flow of refrigerant through the liquid line
shorter intervals.
sight glass. Bubbles in the refrigerant indicate
the unit is low on refrigerant. Refer to
Checking the Refrigerant “Evacuating and Charging the Refrigeration
Charge System” on page 58 for information about
adding refrigerant.
If the unit has an insufficient charge of refrigerant,
the evaporator will be “starved” and the box NOTE: If no bubbles are present, there is
temperature will rise even though the unit is sufficient refrigerant in the unit for that load
operating. Also, an insufficient charge does not at that particular box temperature. This test
circulate enough oil to properly lubricate the does not determine if the unit contains a full
compressor. The charge can be determined by charge of refrigerant.
inspection of the refrigerant through the sight
glass with the following conditions established: Checking Compressor Oil
Testing the Refrigerant Charge with
Charge
an Empty Box The compressors are furnished with the amount of
oil shown in the Specifications chapter. The oil
1. Place a test box over the evaporator.
level in the compressor will change after the
2. Install gauge manifold set. compressor is initially run, making any level
measurements inaccurate.
3. Run the unit in cool on engine driven
compressor operation until the thermometer To ensure an adequate oil supply, the following
reads 32 F (0 C). procedure must be followed whenever the
refrigerant charge is lost or removed from a unit:
4. Establish head pressure of 180 psig (1241
kPa) for R-134a systems or 275 psig (1896 1. Install a compressor on the system having a
kPa) for R-404A systems. It may be necessary residual oil supply and self-lubricating system
to partially cover the condenser grille on the such as a TK 214 model. Connect an oil
front of the unit to create the desired head separator on the discharge or suction line to
pressure. collect and drain out circulated oil.
5. Look at the liquid line sight glass. Under these NOTE: A suction line oil separator can be
conditions there should be no bubbles in the improvised by installing a suction filter
flow of refrigerant through the liquid line sight upside down in the suction line near the
glass. Bubbles in the refrigerant indicate the compressor. Cap off both access ports, and
unit is low on refrigerant. Refer to “Charging use the lower one to drain off the
the Refrigeration System” for information accumulated oil.
about adding refrigerant.
2. Place a normal amount of oil in the cleanup
compressor before operating.
Testing the Refrigerant Charge with
a Loaded Box 3. Charge with 6.0 to 7.0 lb (2.7 to 3.2 kg) of
refrigerant.
1. Install a gauge manifold.
60
Refrigeration Maintenance
4. Operate at a low speed (600 to 800 rpm) for 2 2. Make sure that the oil trap is correctly
hours, or until the compressor oil level reaches installed.
a minimum allowable level, whichever occurs
3. Recover the contaminated refrigerant from the
first. Drain the collected oil from the oil
system.
separator as it fills, taking care to not allow
any collected oil to recirculate. 4. Remove the lines from the compressors
(engine driven and standby).
5. Prepare the original compressor that was
removed from the unit (or a replacement) by 5. Flush each compressor using the flushing
draining out any existing oil and replacing the compressor and an HFC refrigerant. (Always
oil with the amount of oil shown in the recover the refrigerant before disconnecting
Specifications chapter. the flushing compressor.)
6. Install the original compressor (or its
replacement), and proceed with the manual
evacuation and refrigerant charging
procedure.
61
Refrigeration Maintenance
8. Remove the internal parts from the expansion 10. If no leaks are found, evacuate the system. A
valve. leak-free and dry system will maintain a 1000
micron vacuum for five minutes or longer.
9. Open any the suction pressure regulator valves
to their highest setting. 11. Charge the system with proper amount of the
correct refrigerant.
10. Install a temporary suction line filter (P/N
204-498 and P/N 66-2988) in the suction line. 12. Operate the unit and check for proper
operation. (Adjust any suction pressure
11. Install a connecting pipe in place of the
regulators.)
standby compressor.
13. After two weeks of operation, change the
12. Connect the flushing compressor system to the
drier.
engine driven compressor discharge and
suction lines (see illustration).
13. Evacuate the system and check for leaks.
Continue to evacuate to remove moisture and
air.
14. Install HFC refrigerant and run the flushing
compressor to flush the system. Energize
(open) the defrost solenoid during 30% to
40% of the clean-up. Solid contaminants will
collect in the suction line filter. Oil from the
system and from the flushing compressor will
drain out of the suction line filter. (Add
compressor oil as required.) Refrigerant oil in
the flushing compressor will absorb acids
from the system.
15. Test the recovered compressor oil for acid
contamination.
16. Continue flushing until the compressor oil is
clean.
62
Refrigeration Service Operations
NOTE: It is generally good practice to replace Compressor
the filter drier whenever the high side is opened
or when the low side is opened for an extended Removal
period of time.
1. Recover the refrigerant charge from the
WARNING: Disconnect the power supply system.
before servicing the unit to prevent
2. For the electric standby compressor, remove
personal injury.
the condenser cover to access the compressor.
3. Loosen and remove the compressor drive belt.
AMA521
8 9 7 2 8 4
3
10 5
AMA522
63
Refrigeration Service Operations
64
Refrigeration Service Operations
High Pressure Cutout Switch 300 psig (2068 kPa) on R-134a units, or
(HPCO) 450 psig (3102 kPa) on R-404A units, the
High Pressure Cutout will stop the
The high pressure cutout switch is located on a compressor.
discharge line inside the condenser unit. If the
discharge pressure rises above 300 psig NOTE: The discharge pressure should never
(2068 kPa) on R-134a units or 450 psig (3102 be allowed to exceed a pressure of 450 psig
kPa) on R-404A units, the switch opens the 7A (3102 kPa).
circuit de-energizing the power relay. 4. Failure of the high pressure cutout system to
stop compressor operation should be
High Pressure Cutout Switch Test investigated first by checking the control
To test the switch, rework a gauge manifold per circuit operation and second by high pressure
Figure 45. cutout switch replacement.
Installation
1. Apply a refrigerant loctite to the threads of the
switch.
2. Install and tighten the switch and reconnect
the wires.
3. Pressurize the system and test for leaks.
4. Evacuate the system.
5. Reinstall the condenser cover.
1. Relief Valve (66-7392)
6. Recharge the unit with the proper refrigerant.
2. O-Ring (33-1015)
3. Adapter Tee Weather Head (No. 552X3) High Pressure Transducer
Figure 45: High Pressure Cutout Manifold
Removal
1. Connect the gauge manifold to the compressor
1. Recover the refrigerant charge.
discharge service port.
2. Remove the condenser grille if necessary.
NOTE: Service manifold hoses must have
Schrader valve (tube valve) depressors. 3. Disconnect the wires and remove the
transducer.
2. Set the thermostat well below the box
temperature so that the unit will be in cool.
Installation
3. Raise the discharge pressure of the
1. Install and tighten the switch and reconnect
compressor by blocking the condenser coil air
the wires.
flow. When the discharge pressure reaches
65
Refrigeration Service Operations
2. Pressurize the system and test for leaks. Liquid Injection Solenoid Test
3. Reinstall the condenser grille (if removed). See “Testing Liquid Injection Solenoid Valve and
4. Evacuate and recharge the system. Metering Orifice” on page 54.
66
Refrigeration Service Operations
4. Check the temperatures of the refrigeration 3. Place the valve in position with the flow arrow
lines on both sides of the liquid solenoid by pointing in the direction noted when removed.
hand. Both sides should be warm. If not, the 4. Solder or connect the inlet and outlet
liquid solenoid might be stuck closed. connections. After the valve cools, assemble
5. Set the thermostat for the compartment being the valve and install the coil.
tested to the highest setting to make that
compartment shift to Null. CAUTION: Use a heat sink to prevent
damaging the valve when soldering.
6. The suction pressure should fall because the
liquid solenoid closes when the compartment 5. Pressurize the refrigeration system and test for
shifts to Null. leaks.
7. Check the temperatures of the refrigeration 6. Evacuate the system.
lines on both sides of the liquid solenoid by
hand. A temperature difference between the 7. Reinstall the cover.
two sides of the liquid solenoid indicates it is 8. Recharge the unit with the proper refrigerant.
leaking.
8. Remove the gauge manifold set when finished Oil Separator
with the test.
Removal
Solenoid Valve Replacement 1. Recover the refrigerant charge.
NOTE: Valves that have nylon seats must be 2. Remove the condenser cover.
disassembled before soldering.
3. Disconnect the ORS nuts at the end of the oil
Removal separator.
1. Recover the refrigerant charge. 4. Loosen the mounting hardware and remove
the oil separator.
2. Remove the condenser cover, evaporator
cover, or Multi-Temp/Heat kit cover to access Installation
the solenoid valve.
1. Coat the new O-rings with refrigerant oil
3. Remove the coil and disassemble the valve if (same type that is used in the system) and
unsoldering the valve. place the new O-rings in the ORS fittings on
the ends of the oil separator.
67
Refrigeration Service Operations
68
Refrigeration Service Operations
AMA518
Figure 47: Double Discharge Check Valve Assembly Used on Early Units
7. Observe the gauge manifold readings of the 12. Observe the gauge manifold readings of the
electric standby compressor. The high side electric standby compressor. The head
pressure should remain the same as the pressure should increase and the suction
pressure in step 3 after the high and low sides pressure should decrease.
were equalized. If the high side pressure is
13. Observe the gauge manifold readings of the
increasing or has increased noticeably, the
engine driven compressor. The high side
discharge check valve to the standby
pressure should remain the same as the
compressor is leaking internally.
pressure in step 9 after the high and low sides
8. Turn the unit off and shut off the truck engine. were equalized. If the high side pressure is
Connect the remote control box to an increasing or has increased noticeably, the
appropriate electric power source. discharge check valve to the engine driven
compressor is leaking internally. Stop the unit.
9. Observe the gauge manifold reading of the
engine driven compressor. If the high side and 14. Remove the gauge manifold sets and the
low side readings are not the same, open the electric standby power source. Connect the
gauge manifold valves and equalize the wires to the liquid injection solenoid valve.
pressures. Close the gauge manifold valves.
If the double discharge check valve assembly
10. Adjust the thermostat so the unit will run in is leaking internally, refer to the repair
cool. procedures.
11. Start and run the unit on electric standby.
69
Refrigeration Service Operations
70
Refrigeration Service Operations
3. Remove the feeler bulb from the suction line 6. If no leaks are found, evacuate the system.
clamps. Note the position of the feeler bulb on 7. Connect the evaporator fan motor wires.
the suction line. Install the evaporator cover.
71
Refrigeration Service Operations
8. Recharge the unit with the proper refrigerant. 2. Install and tighten the switch and reconnect
the wires.
Low Pressure Cutout Switch 3. Pressurize the refrigeration system and test for
(LPCO) leaks.
The low pressure cutout switch is located on the 4. If no leaks are found, evacuate the system.
suction line in the evaporator. If the suction
5. Connect the evaporator fan motor wires if
pressure drops below 5 to 11 in. Hg of vacuum
disconnected. Install the evaporator cover or
(-17 to -37 kPa), it opens the circuit to the power
the Multi-Temp Kit cover.
relay to stop the unit. To check the low pressure
cutout: 6. Recharge the unit with the proper refrigerant.
72
Refrigeration Service Operations
Test for SPR on Accumulator in 7. Remove the gauge manifold set from the
Multi-Temp Units electric standby compressor and place it on the
engine driven compressor.
Use this test for suction pressure regulators
located on the accumulator tank in the 8. Start the unit and run it in Defrost on the
Multi-Temp Kit. engine driven compressor at 1800 to 2000
RPM until the suction pressure stabilizes.
1. Install a gauge manifold set on the engine
driven compressor. 9. The suction pressure should be 26 psig (180
kPa) or less. If the setting is above 26 psig
2. Place a jumper wire between the 12 and CHB
(180 kPa), remove the protective cap and
wires at the defrost termination switch to
adjust the suction pressure regulator valve to
ensure the unit will run in Defrost.
the correct setting.
3. Start the unit and run it in Defrost on the
10. Remove the gauge manifold set and the
engine driven compressor at 1800 to 2000
jumper wire when finished with the test.
RPM until the suction pressure stabilizes.
4. The suction pressure should be 26 psig (180 Test for SPR in Evaporator on Model
kPa). If the setting is incorrect, remove the 30 and 50 SPECTRUM Units
protective cap and try to adjust the suction
Use this test for suction pressure regulators
pressure regulator valve to the correct setting
located in the evaporators on Model 30 and 50
before assuming it is faulty.
SPECTRUM units.
5. Remove the gauge manifold set and the
1. Install a gauge manifold set on the engine
jumper wire when finished with the test.
driven compressor.
Test for SPR in Evaporator on 2. Set the thermostat for the fresh (Remote)
Single Temperature Model 20 Units compartment to just below the compartment
temperature so it will be in Null. Set the
Use this test for suction pressure regulators
thermostat for the frozen (Host) compartment
located in the evaporator on single temperature
the highest setting so it will run in Heat.
units.
3. Start the unit and run it on the engine driven
1. Install a gauge manifold set on the electric
compressor at 1800 to 2000 RPM until the
standby compressor.
suction pressure stabilizes.
2. Connect the unit power receptacle to an
4. The suction pressure should be 26 psig (180
appropriate electric power source.
kPa). If the setting is incorrect, remove the
3. Place a jumper wire between the 12 and CHB protective cap and try to adjust the suction
wires at the defrost termination switch to pressure regulator valve to the correct setting
ensure the unit will run in Defrost. before assuming it is faulty.
4. Start the unit and run it in Defrost on the 5. Set the thermostat for the frozen (Host)
electric standby compressor until the suction compartment to just below the compartment
pressure stabilizes. temperature so it will be in Null. Set the
thermostat for the fresh (Remote)
5. The suction pressure should be 26 psig (180
compartment the highest setting so it will run
kPa). If the setting is incorrect, remove the
in Heat.
protective cap and try to adjust the suction
pressure regulator valve to the correct setting 6. Start the unit and run it on the engine driven
before assuming it is faulty. compressor at 1800 to 2000 RPM until the
suction pressure stabilizes.
6. Stop the unit and disconnect it from the
electric power source.
73
Refrigeration Service Operations
7. The suction pressure should be 26 psig (180 8. On units equipped with a suction bypass
kPa). If the setting is incorrect, remove the solenoid, remove magnet and reinstall the coil
protective cap and try to adjust the suction on the solenoid.
pressure regulator valve to the correct setting
9. Start the unit with both compartments set to
before assuming it is faulty.
the desired setpoints and let the unit pull
8. Remove the gauge manifold set when finished down.
with the test.
NOTE: It is normal for the frozen
compartment to pull down faster than the
Test for SPR in Multi-Temp Kit on fresh compartment on first start up.
Multi-Temp Units
Use this test for suction pressure regulators Suction Pressure Regulator Valve
located in the Multi-Temp Kit but not on the Replacement
accumulator tank in multi-temp units.
Removal
This suction pressure regulator valve is sometimes
called the suction bypass CPR valve. It balances 1. Recover the refrigerant charge.
the suction pressure between the fresh and frozen
2. Remove the condenser, evaporator, or
evaporators to allow both evaporators to have
Multi-Temp Kit cover.
equal capacity to control the two zones. This
system gives priority to the frozen section. It also 3. Unsolder the suction pressure regulator valve
keeps refrigerant from migrating into the frozen from the suction tubes.
evaporator when it is not running.
Installation
1. Install a gauge manifold set on the engine
driven compressor. 1. Clean the tubes for soldering.
2. Set the thermostat for the fresh (Remote) 2. Place the valve in position and solder the
compartment to just below the compartment connections.
temperature so it will be in Null. Set the
3. Pressurize the refrigeration system and test for
thermostat for the frozen (Host) compartment
leaks.
the lowest setting so it will run in Cool.
4. If no leaks are found, evacuate the system.
3. Start the unit and run it on the engine driven
compressor at 1800 to 2000 RPM. 5. Install the cover that was removed.
4. Bring the frozen compartment to 5 to 7 F (3 to 6. Recharge the unit with the proper refrigerant.
4 C) above setpoint. Record the suction
pressure and then shut the unit off. In-Line Check Valves
5. On units equipped with a suction bypass (Multi-Temp Units Only)
solenoid, remove the coil and install a magnet
Multi-Temp units use in-line check valves in the
(P/N 204-1074) to close valve.
hot gas and/or liquid lines. These check valves are
6. Raise the frozen (Host) compartment setpoint located in the Multi-Temp/Heat kit. An in-line
to just below the compartment temperature so check valve is not repairable and must be replaced
it will be in Null, and lower the fresh if it fails. A heat sink must be used on the in-line
(Remote) compartment setpoint to 35 F (2 C) check valve when it is being soldered in place to
and start the unit. prevent damage to the neoprene seal.
7. With the unit running, set the suction pressure
Removal
to the recorded value from step 4 by adjusting
the suction bypass CPR valve. Once the 1. Recover the refrigerant charge.
suction pressure has been set, turn the unit off.
2. Remove the Multi-Temp/Heat kit cover.
74
Refrigeration Service Operations
Installation
NOTE: A heat sink must be used on the in-line
check valve when it is being soldered in place to Figure 50: Cutting the Hose
prevent damage to the neoprene seal.
2. Fit two clips of the appropriate diameter over
1. Clean the tubes for soldering. the hose. Use only one clip for hose #4.
2. Place the check valve in position. The arrow
on the valve body indicates the direction of
refrigerant flow through the valve.
3. Place a heat sink on the check valve. ASA127
4. Solder the inlet and outlet connections. Figure 51: Fitting the Clips
5. Install the mounting hardware for the check 3. Lubricate the cylinder of the fitting that will
valve, if used. be inserted into the hose using refrigerant oil.
6. Pressurize the refrigeration system and test for
leaks.
7. If no leaks are found, evacuate the system.
8. Install the Multi-Temp/Heat kit cover.
9. Recharge the unit with the proper refrigerant. ASA128
75
Refrigeration Service Operations
76
Compressor Maintenance
77
Compressor Maintenance
ABA382
78
Compressor Maintenance
79
Compressor Maintenance
Suction
• Short term 6 psig minimum
• Long term 14 psig minimum
Temperature
• Non operational: above -40 F and below 250 F
• Operating mode between 32 F and 200 F
Recommended Pressure
Charts Figure 65: Recommended Pressures for R-134a
80
Compressor Maintenance
81
Compressor Maintenance
82
Compressor Maintenance
Compressor Oil Type • After the initial charge has been added
the system must be topped off by
Compressor oil P/N 203-515 is required in all metering liquid refrigerant slowly
direct drive (vehicle powered) units. through the suction side of the
compressor while the unit is running.
Charging the Refrigeration Make sure that the high side valve on
System the gauge manifold is closed to block the
passage of refrigerant to or from the
IMPORTANT: When charging the refrigeration discharge side of the system. Control
system on initial installation and anytime that the liquid flow so the suction pressure
the system is completely evacuated make sure of increases by approximately 20 psig (138
the following recommendations. kPa).
• The refrigeration system must be evacuated • Refer to the Refrigeration Maintenance
to the recommended micron value chapter of this manual for specific
(VACCUM) of 500 microns. After the information about the unit.
system reaches 500 microns, evacuate the
system for an additional hour. Then close
the valve at the evacuation pump, stop the Initial Installation Pressure
vacuum pump, and observe the reading on Regulator Setting
the vacuum gauge for 5 minutes. The During initial installation and when the pressure
pressure should not exceed 2000 microns. regulator is replaced, the pressure regulator must
• An initial charge of liquid refrigerant must be adjusted in order to make sure that the unit
be added through the discharge hose at the roadside and standby refrigeration capacity is
roadside compressor while the unit is off. correct. Please follow the procedures in the
The average amount of charge that the unit Refrigeration Service Operations chapter of this
will take is around 3/4 to 7/8 of the total manual to properly adjust these valves.
recommended charge. This amount varies
due to the ambient condition that would
affect the pressure inside the refrigerant
supply bottle. This allows the unit to have
an initial refrigerant charge in the system
and protects the compressor from excessive
liquid intake.
83
Compressor Maintenance
Torque Requirements
Fastener Ft-Lb N•m Kgf-cm
Armature Retaining Nut 13.0 ± 2.0 17.7 ± 2.9 180 ± 30
Oil Fill Plug 14.5 ± 3.6 19.6 ± 4.4 200 ± 50
Hose Fitting 1”- 14 26.7 ± 2.9 36.3 ± 3.9 370 ± 40
Hose Fitting 3/4” Tube-O 17.3 ± 2.5 23.5 ± 3.4 240 ± 35
Hose Fitting 7/8” Tube-O 23.9 ± 2.9 32.4 ± 3.9 330 ± 40
Hose Fitting 1- 1/16” Tube-O 30 ± 3 40.0 ± 4.0 414 ± 41
Pad Bolt M10 28.9 ± 2.9 39.2 ± 3.9 440 ± 40
Pad Bolt M8 26.3 ± 2.9 34.0 ± 3.9 350 ± 40
Pressure Release Valve (PRV) 7.1 ± 1.4 9.8 ± 2.0 100 ± 20
Mounting
Rotation
TK 7 and TK 5 series compressors can be rotated
90° either direction from an upright position.
NOTE: Oil plug is at 12:00 o-clock when
compressor is upright.
Ear Deflection
Total combined ear deflection or bending must not
exceed 0.016 in. (0.4 mm). Engine brackets which
allow mounting ears to exceed 0.016 in. (0.4 mm)
deflection can cause cracked or broken ears.
Deflection of the ear can also result in refrigerant
Figure 70: 90 Degree Rotation
leakage.
TK 08, TK 13, TK 15, TK 16, and TK 21 series
compressors can be rotated 45° either direction
from an upright position.
NOTE: Oil plug is at 7:00 O-clock when
compressor is upright.
84
Compressor Maintenance
2
1
8
10
9 12
11
Clutch Removal
Armature Nut Removal – Wobble
Compressor
1. If armature dust cover is present, remove the 3
or 6 bolts holding it in place and remove
cover.
2. Insert pins of armature plate spanner into
threaded holes of armature assembly.
3. Hold armature assembly stationary while
removing retaining nut with 3/4 in., 19 mm, or
14 mm socket wrench.
85
Compressor Maintenance
86
Compressor Maintenance
Clutch Replacement
Field Coil Installation
1. Place field coil over nose of compressor.
Insert the projection on underside of field coil
ring into the hole in front housing face to set
alignment.
2. Secure field coil with snap ring.
Pulley Installation
1. Set pulley bearing perpendicular over
compressor nose.
2. Place the pulley/bearing installer into the
bearing bore. Ensure that the edge rests only
on the inner race of the bearing, not on the
seal, pulley or outer bearing race.
Figure 80: Loosen Lead Wire Clamp Screw
87
Compressor Maintenance
88
Compressor Maintenance
89
Compressor Maintenance
90
Compressor Maintenance
Step 1
Identify what unit model has been Unit Model Standard Recommended Compressor
selected for the vehicle.
V-200 (MAX) TK 13
Consult the Thermo King Unit Selection V-300 (MAX) TK 15
Guide to ensure correct choice of unit.
V-520 (MAX) TK 16
Choose initial compressor from “Standard
V-520 RT (MAX) TK 16
Recommended Compressor” column.
Standard Recommended Compressor (circle one): TK13 TK15 TK16
Step 2
Consult the Compressor Mounting Kit Instructions to determine whether a Tab Mount or Direct Mount is
necessary.
Figure 92: Tab Mount Assembly Figure 93: Direct Mount Assembly
91
Compressor Maintenance
Step 3
Identify the Clutch Pulley Assembly that will be used with the unit.
Figure 94: Double A Groove Figure 95: Poly V Groove Figure 96: Variable Groove
Clutch Pulley Diameter: Clutch Pulley Diameter: Clutch Pulley Diameter:
5.31 in. (135 mm) 4.69 in. (119 mm) 6.26 in. (159 mm)
Clutch Pulley Assembly (circle one): Double A (5.31") Poly V (4.69") Variable (6.26")
Step 4
Complete the following equation to calculate the Sustained Compressor Speed (RPM):
Sustained Compressor Speed (circle one): Less than 3,000 RPM More than 3,000 RPM
If more than 3,000 RPM...
Alternate Recommended Compressor (circle one): TK 08 TK 13 TK 15
92
Compressor Maintenance
Step 5
Check compressor dimensions from the V-Series Compressor Chart below; verify the fit of the
compressor in the vehicle.
Figure 97: Tab Mount Assembly Figure 98: Direct Mount Assembly
Step 6
Find the compressor product number by using the chart that corresponds with your selected Mount Kit
and your compressor, as determined above.
DOUBLE A GROOVE
Manufacturing Aftermarket
Model Dimensions
Product Number Product Number
TK 13 A: 3.28 in. (83.3 mm) 702827 102-1016
Tab Mount B: 4.41 in. (112 mm)
Displacement: 8.0 cid (131 cc) C: 9.06 in. (230.2 mm)
D: 4.72 in. (120 mm)
TK 15 A: 3.28 in. (83.3 mm) 702826 102-1014
Tab Mount B: 4.41 in. (112 mm)
Displacement: 9.0 cid (146.7 cc) C: 9.25 in. (235 mm)
D: 4.72 in. (120 mm)
TK 16 A: 3.28 in. (83.3 mm) 702825 102-1012
Tab Mount B: 4.41 in. (112 mm)
Displacement: 10.0 cid (162.9 cc) C: 9.63 in. (244.7 mm)
D: 4.72 in. (120 mm)
TK 16 A: 3.62 in. (92.0 mm) 702927 102-1024
Direct Mount B: 3.43 in. (87 mm)
Displacement: 10.0 cid (162.9 cc) C: 9.65 in. (245 mm)
D: 5.31 in. (135 mm)
93
Compressor Maintenance
POLY V GROOVE
Manufacturing Aftermarket
Model Dimensions
Product Number Product Number
TK 13 A: 3.28 in. (83.3 mm) 702828 102-1017
Tab Mount B: 4.41 in. (112 mm)
Displacement: 8.0 cid (131 cc) C: 9.14 in. (232.2 mm)
D: 4.72 in. (120 mm)
TK 15 A: 3.28 in. (83.3 mm) 702829 102-1018
Tab Mount B: 4.41 in. (112 mm)
Displacement: 9.0 cid (146.7 cc) C: 9.33 in. (237 mm)
D: 4.72 in. (120 mm)
TK 16 A: 3.28 in. (83.3 mm) 702823 102-1011
Tab Mount B: 4.41 in. (112 mm)
Displacement: 10.0 cid (162.9 cc) C: 9.71 in. (246.7 mm)
D: 4.84 in. (123 mm)
TK 16 A: 3.62 in. (92.0 mm) 702824 102-1022
Direct Mount B: 3.43 in. (87 mm)
Displacement: 10.0 cid (162.9 cc) C: 9.65 in. (245 mm)
D: 4.69 in. (119 mm)
VARIABLE GROOVE
Manufacturing Aftermarket
Model Dimensions
Product Number Product Number
TK 15 A: 3.28 in. (83.3 mm) 702832 102-1020
Tab Mount B: 4.41 in. (112 mm)
Displacement: 9.0 cid (146.7 cc) C: 9.25 in. (235 mm)
D: 4.72 in. (120 mm)
TK 16 A: 3.28 in. (83.3 mm) 1A/1B: 702830 1A/1B: 102-1019
Tab Mount B: 4.41 in. (112 mm)
Displacement: 10.0 cid (162.9 cc) C: 9.65 in. (245.1 mm)
D: 6.26 in. (159 mm)
94
Compressor Maintenance
Belt Tensions
Engine Driven Compressor Belt and
Pulleys
Correct pulley alignment and proper belt tension
are very important factors in compressor
installation. The compressor clutch must be
perfectly aligned with the engine pulley and any
auxiliary idler or belt adjustment pulley
components. When installing the clutch, be sure
the shaft drive key is in place and the shaft bolt is
properly tightened. Check the pulley alignment by
holding a 24 to 35 in. (60 to 90 cm) long rod, 0.5
in.(13 mm) in diameter firmly into the V-groove
of the clutch pulley and make sure the rod aligns
squarely with the engine drive pulley groove.
Double check by making sure the belt goes from
pulley to pulley in perfect alignment with no
indication of a sideward bend.
Adjust the belt tension to vehicle manufacturer
specifications. Check the belt tension again after
36 to 48 hours of initial operation of the unit
because the belt may stretch slightly during the
first hours of use. Remember, good alignment and
proper belt tension ensure long belt life.
95
Structural Maintenance
Evaporator Coil
Clean the coils during scheduled maintenance
inspections. Remove any debris (e.g., leaves or
plastic wrap) that reduces the air flow. Clean dirty
coils with compressed air or a pressure washer. Be
careful not to bend the fins when cleaning a coil.
If possible, blow the air or water through the coil
in the direction opposite the normal air flow.
Repair bent fins and any other noticeable damage.
Condenser Coil
Clean the coils during scheduled maintenance
inspections. Remove any debris (e.g., leaves or
plastic wrap) that reduces the air flow. Clean dirty
coils with compressed air or a pressure washer. Be
careful not to bend the fins when cleaning a coil.
If possible, blow the air or water through the coil
in the direction opposite the normal air flow.
Repair bent fins and any other noticeable damage. Figure 100: Evaporator
96
Over-the-Road Mechanical Diagnosis
If desired box temperature cannot be obtained Air In System: Air is not condensable. Its presence
during engine driven compressor operation, any in the system increases head pressure. When the
of the following may be indicated: compressor is stopped, air will gather at the high
point of the high side. Reclaim the refrigerant,
Excessive Heat Load: An excessive heat load on
evacuate the system to 500 microns and recharge
the system will be caused by too many, or
with the proper amount of refrigerant.
excessively long, stops with the doors open.
Excessive heat loads will also be caused by loose Temperature Of The Liquid Line: During normal
doors, loose body panels, warm loads and poor operation, the liquid line will be slightly warmer
insulation. than surrounding air. An extremely hot line
indicates either shortage of refrigerant or lack of a
Dirt On Coils: Dirt on the condenser or evaporator
liquid seal at the receiver outlet. A cold line
coil acts as an insulator reducing the capacity of
indicates a restriction, and some flashing takes
the unit.
place in the liquid line sight glass.
Incorrect Belt Tension: If the
drive belt is not
Dirty Or Wet Filter-Drier: If the outlet line of the
correctly tensioned, the compressor will not be
driven at proper speed, and unit efficiency will be filter-drier is colder than the inlet line, the
reduced. By contrast, too much tension will place filter-drier is either saturated with moisture or is
an additional load on the bearings causing rapid dirty and must be replaced.
wear. Dirt In The Expansion Valve Screen: Reclaim the
refrigerant charge, remove the screen and clean.
Shortage Of Refrigerant: Shortage of refrigerant
Moisture is in the system will collect at the
reduces capacity of the unit. Find and remedy the
expansion valve and freeze. This is indicated by
cause of the shortage and recharge the system. DO
abnormally low suction pressure. Replace the
NOT operate the unit if it is low on refrigerant.
drier, dry the system and recharge.
Faulty Expansion Valve Adjustment: High
Ice On The Evaporator Coil: Note operation under
superheat settings will starve the evaporator
causing low suction pressure. Low superheat Defrost Cycle.
settings will flood the coil causing high suction Air Flow: Do not load product directly in front of
pressure. The superheat setting should be adjusted the air return or discharge. Insure that the fan is
ONLY by a trained refrigeration serviceman. correctly positioned in the orifice to achieve
maximum air flow.
Excessive Oil: Too much compressor oil in the
system may result in lower than normal suction Compressor Life: The following will shorten the
pressure as well as lowered capacity. life of the compressor:
Moisture In The System: Symptom: Expansion • Operating a contaminated system
valve freeze-up—will not refrigerate. Usually this
can be checked by warming the expansion valve • No oil trap
with either the hand or hot towels to see if the • Clogged oil separator (JetLube™)
valve opens. Evacuate the system in the same
manner used during installation. Install a new • Clogged liquid injection orifice (JetCool™)
drier. • Defective liquid injection switch (JetCool™)
Expansion Valve Loses Its Charge: If the • Insufficient oil charge
expansion valve loses its charge, the valve will
close causing the system to go into vacuum. • Wrong or mixed oil
Replace the valve. • Lack of compressor lubrication on installation
and startup
• Excessive compressor speed (maximum speed
3,000 rpm)
97
Electric Standby Mechanical Diagnosis
Compressor does not run Improperly wired Check wiring against diagram
Cycling on high discharge pressure Check condenser air flow and fan
Defrost timer set too low for Adjust timer to higher interval.
application.
98
Electric Standby Mechanical Diagnosis
Box temperature too high Refrigerant shortage Repair leak and recharge
99
Electric Standby Mechanical Diagnosis
Head pressure too low Refrigerant shortage Repair leak and recharge
Frosted or sweating suction line Expansion valve set too low, Adjust expansion valve
admitting excess refrigerant
Condenser coil is cool when unit Refrigerant undercharge Repair leak and recharge
is in cool operation
Compressor inefficient Replace compressor
Unit in vacuum. Frost expansion Ice plugging expansion valve orifice Apply hot wet cloth to expansion
valve only valve. Moisture indicated by
increase in suction pressure.
Replace drier
100
Electric Standby Mechanical Diagnosis
101
Refrigeration Diagnosis Chart
Unit Not Heating (Model 30)
SYMPTOM
No suction pressure
High head pressure
POSSIBLE CAUSES
• • Overcharge of refrigerant
• • • • • • • Shortage of refrigerant
• • • • • • • • No refrigerant
• Air through condenser too hot (ambient)
• Air flow through condenser restricted (dirty)
• • Air through condenser too cold (ambient)
• • • Air in refrigerant system
• Condenser fan blades bent or broken
• Air short cycling around evaporator coil
• • • • Air through evaporator restricted
• • • • • • Evaporator needs defrosting
• • Broken compressor belt
• Compressor discharge valves leaking
• • • Too much compressor oil in system
• Loose compressor pulley
• Compressor bearing loose or burned out
• • • • Broken valve plate in compressor
• • • • Expansion valve power element lost its charge
• • • Expansion valve feeler bulb improperly mounted
• • • Expansion valve feeler bulb making poor contact
• • • • Expansion valve open too much
• • Expansion valve closed too much
• • • Expansion valve needle eroded or leaking
• • • • Expansion valve partially closed by ice, dirt or wax
• • Hot gas solenoid stuck open
• • Defrost solenoid stuck closed
• • • • Liquid refrigerant entering compressor
• • • Restricted line on the low side
• • Restricted line on the high side
• • • Restricted dehydrator
• • Reverse fan rotation
• • • • Faulty pilot solenoid
• • Loose or broken electrical connections
• • • • Gauge out of calibration
• Condenser fan motor not operating
• • • • • • Evaporator fan motor not operating
102
Index
A defrost timer
about this manual 6 settings for units with In-Cab Controller (M13, M16,
after start inspection 39, 46 M17) 51
alarm code descriptions 45 test for Units with In-Cab Controller (M13, M16,
alarms 44 M17) 53
Discharge Check Valve
B Testing 68
belt tensions 95 discharge check valve 68
replacement 70
C double discharge check valve assembly
repair 70
Checking Compressor Oil Charge 60
replacement 70
Checking the Refrigerant Charge 60
drier removal and installation 64
Cleanup Procedure for Small Truck Units 61
DSR Control System 23
clearing alarm codes 45
Clutch Timer 28
Common Relays in Units with In-Cab Controller 27 E
Compressor 22 electric standby circuits 56
compressor Electric Standby Operation 24
electric standby compressor belt 95 Evaporator 22
engine driven compressor belt and pulleys 95 Evaporator Coil 71
function test 77 evaporator coil
maintenance 77 maintenance 96
removal and installation 63 removal and installation 71
compressor oil Evaporator Drain Tube Heaters 24
checking charge 60 evaporator fan motors 55
Condenser 22 removal and installation 55
Condenser Coil 96 Expansion Valve Assembly 71
condenser coil expansion valve removal and installation 71
maintenance 96
removal and installation 64 F
condenser fan motor 55 Fuses 26, 30
removal and installation 55
condenser fan pressure switch 54 H
replacement 65 heat pilot solenoid test 66
testing 54 high pressure cutout switch 65
Connectors 26, 28 replacement 65
contents, manual, description of 6 test 65
Control Box in Units with DSR Control System 28 high pressure transducer 65
Control Box in Units with In-Cab Controller 26
Control Circuits 22 I
Control Systems 22 In-Cab Control Box Operating Instructions (M13, M16,
curbside, definition 7 M17) 38
curbside/roadside terminology, explained 7 In-Cab Controller 23
in-cab controller M13 and M16
D trouble shooting 50
defrost relay 52 in-line check valves 74
defrost solenoid test 66
defrost solenoid valve for Units with In-Cab Controller L
(M13, M16, M17) 52 liquid injection metering orifice
defrost system 53 removal and installation 68
testing for Units with In-Cab Controller (M13, M16, liquid injection solenoid valve and metering orifice,
M17) 52 testing 54
defrost system for units with In-Cab Controller (M13, Liquid Injection System 24
M16, M17) 51 liquid injection system 54
defrost termination switch 53 liquid solenoid test 67
Defrost Timer 28 loading procedure 39, 46
103
Index
R W
R 20 weekly post trip checks 40
recover refrigerant 4 weekly pretrip inspection 39, 46
Refrigerant 24
refrigerant
handling instructions 77
refrigerant charge
checking 60
refrigeration diagnosis chart 102
Refrigeration Service Operations 63
refrigeration system
cleanup procedure for small truck units 61
evacuating and charging 58
refrigeration system checks 61
replacing refrigerant hoses 75
roadside, definition 7
roadside/curbside terminology, explained 7
S
Safety Precautions 13
safety precautions
battery installation and cable routing 16
Safety, Auto Start/Stop 13
Safety, Electrical Hazards 14
Safety, High Voltage 15
Safety, Low Voltage 16
Safety, Refrigerant 13
Safety, Refrigeration Oil 14
Safety, Welding 15
Serial Number Locations 33
solenoid valve replacement 67
104
Wiring, Schematic, and Refrigeration
Diagrams Index
105
Wiring, Schematic, and Refrigeration Diagrams Index
106
V-200/V-300 10 Wiring Diagram
107
V-200/V-300 10 Schematic Diagram
108
V-200/V-300 MAX 10 Wiring Diagram
109
V-200/V-300 MAX 10 Schematic Diagram
110
V-200/V-300 20, V-200/V-300 MAX 20 1 Phase Wiring Diagram - Page 1 of 2
111
V-200/V-300 20, V-200/V-300 MAX 20 1 Phase Wiring Diagram - Page 2 of 2
112
D
CH
REV
MC R1
U1
4 T1
CH
L1
1 J1 5
2RI TO LINE 9 COMP
CH
1E32756
470K
1 1 2 MOTOR
CH
OL
1E32755 SHEET 1 OF 1
2 1
1
3 T1
V200/300 20 & 20 MAX
4
X
PS2506
L1(BLK) T1A 3
U1 W2 SR
R2 R3 V1 U2 J P
C1
Thermo King
5 6
Y L2(WHT)
PC2 T2
1K 10K
CM
115/230 1PH
13 14
J1 J1 J1 J1 3
CH T2 W1 V2
C4A
G
1 2 4
CH(GRN) H2 PC4 C5 C6
T1A
2
T1
CHH
REF DWG:
7
SEE 2B
F5 NOTE H2 BATT
C-2 2B F7
3 2
CODE IDENT NO
87a
C-2 02
ESR2
0V 115V 208V 230V 30 87
3. START CAPACITOR C6 VALUE IS 300μF FOR 115V
TITLE
SIZE
1. CONNECT H2 WIRE TO MATCH INPUT VOLTAGE.
TR 02
4
4. RUN CAPACITOR C4 VALUE IS 60μF FOR 115V
2
2
2. F5 FUSE FOR 115V IS 8A, FOR 230V USE 4A.
27-Sep-05
13-Apr-05
18-Apr-07
0V 0V
CAD GENERATED DRAWING,
11,5V 11,5V
DO NOT MANUALLY UPDATE
CH CH
2R
-
X1 X2 X3 X4 2R CHK
Bridge for C1
DATE
Bridge for
WMAXWELL
5 12V
12V only
0V
F3 30 87
6 2R
33000μF
RWS
25A
ENG APPVL
C-2 2RB
APPROVED
-
CHECKED
Bridge for
6 5 2RB
DRAWN
12V only
R1
C-4 C-4
CH 2.2K
THIS DOCUMENT CONTAINS PROPRIETARY
F1 C-1
PRIOR WRITTEN PERMISSION OF THERMO
BR2
FOR WHICH TRANSMITTED WITHOUT THE
87a
ITS CONTENTS MAY NOT BE DISCLOSED
CHD
YOU IN CONFIDENCE AND TRUST, AND
EF1 EFM1
IN WHOLE OR IN PART TO OTHERS OR
3
IS TO BE RETURNED UPON REQUEST.
EFR
INFORMATION OF THE THERMO KING
150μF FOR 230V.
6
THERMO KING PROPRIETARY DATA
15A C-4
40μF FOR 230V.
87
D15
7 CHH
THERMO KING CORPORATION
30
D1 D2 C-1
15A
6 EF2 EFM2 CHC
KING CORPORATION
C3 F2
NOTES:
BR1 47μF
2R C-4
85 86 S/S
7
3
EFR 7 CHH
C2 EF
D8
2200μF
Start/Stop
Stop
2RB NC
3A 2B C-3 2
8 F4 HEAT OPTION REVISIONS
C-4 CONN 1 1
CHANGE ORDER REV DATE APPROVED
2 2 508378 A 18-Apr-07 WPM
8 RED 3 3
2RB
BLK
2B
RELEASED
(OPT)
2R1
9 D7A
(MAX 0NLY)
C-21 DTH1 C-21 UPDATED SHORE POWER CABLE
27 A B CHI
TO LINE 1
C-4
3 DTH2
2B
27A
(MAX 0NLY)
A B CHJ LEGEND DESCRIPTION AREA
-------------------------------------
27B
C-22 C-22
D10
BATT BATTERY 3
4
4
5 D6A
BR1 BRIDGE RECTIFIER 6
10 C-A
D4
D11 BR2 BRIDGE RECTIFIER 6
26A
26B
4 87
C-4
30
4 26 CHF CFC CONDENSER FAN CUTIN SW 12
12 4
DR
C-1
(JUMPER FOR MAX CFM CONDENSER FAN MOTOR 12
2RB
87a
UNITS ONLY) CM COMPRESSOR MOTOR 1
4 7 CF CF1 CFM CHG D1 DIODE (OPT) 16
C-3
D6
5
D14 C-4 D4 DIODE (OPT) 10
D5 DIODE 13
13 ST3
C-A 5
86
DR
85
C-3
6 12
DTS
CHB D5A DIODE (OPT) 15
6
C-3 D6A DIODE (OPT) 10
YEL
C-Y
D5 D6 DIODE 12
5A C-Y
7 2D D7A DIODE (OPT) 9
ELEC
GRY
14 HC D9 DIODE 20
26B
L1
H2
21 22
C-Y
5 2RC L3 T3
WP CH D11 DIODE 10
D12 DIODE 16
C-Y L2 T2
D14 DIODE 13
V-200/V-300 20, V-200/V-300 MAX 20 1 Phase Schematic Diagram
87a
TO LINE 2 H2 9 H2
C-Y
L1 T1
(OPT) HR D15 DIODE 6
TO LINE 2 L1 2 L1 (OPT) D2 WV (OPT)
15 86
HR
85
2D
87 30
26A CH
D30
DT
DIODE
DEFROST TIMER
11
10
TO LINE 1
D3
(OPT) DR DEFROST RELAY 12,13
D5A
OVERTEMP
DTH1 DRAIN TUBE HEATER 9
C-Y CH
6
6
SWITCH A1
HC
A2
G/Y 8 TO LINE 10 26A DTH2 DRAIN TUBE HEATER 9
TO LINE 2
F1 FUSE 15A 6
O1
D1 D12
7
C-4 HPCO LPCO C-3
85 86 F2 FUSE 15A 6
C-A
B* 1 7 7A 7B 4 PR F3 FUSE 25A 5
YEL
GRY
F4 FUSE 3A 8
D7
OL
BLU
F7 FUSE 40A 3
G/Y
17
113
F8 FUSE 4A 11
F9 FUSE 5A (OPT) 11
C-9 C-9 C-9 C-9 C-9 C-9 C-9 C-9 F10 FUSE 5A (OPT) 14
EFM1 EVAP FAN MOTOR 1 6
5 2 3 10 8 4 6 P* 7 EFM2 EVAP FAN MOTOR 2 6
EFR EVAP FAN MOTOR RELAY 6,7
K2 C-4 7 CHH ES SELECT EVAP FAN SELECT JUMPER 8
18 FUSE4/1 Relay
12V
ESR1 ELECT STBY RELAY 1 11,21
B 24V PL2R ESR2 ELECT STBY RELAY 2 3,20
C
7
7
K1 PL2R* ESR3 ELECT STBY RELAY 3 5,20
Relay HC HEATER CONTACTOR(OPT)14,16
PL8R
PL1R SETPOINT LED MANUAL C-9 HPCO HIGH PRESSURE CUTOUT SW 16
K2 Defrost HR HEAT RELAY (OPT) 15
19 Reset
K1
Relay
Relay
SETPOINT
adjust
Switch
SETPOINT
S2 PL3R 9 WHT LIS LIQUID INJECTION SW 11
H F LIV LIQUID INJECTION VALVE 11
Select
A TCM -22/+32 C PL6R LPCO LOW PRESSURE CUTOUT SW 16
-32/+32 C D 86 85
ON/OFF PL7R ESR2 MC MOTOR CONTACTOR 1,11
THYRISTOR system DISPLAY C F
M-13 IN-CAB CONTROLLER 18
SYSTEM
AND S4 SETPOINT OL OVERLOAD RELAY 1
DIFFERENTIAL E
20 PL4R
PL5R ON/OFF SETPOINT control
(timer) G adjust M-13 D9 OTS OVER TEMP SW,EVAP (OPT) 16
switch switch S3 PR POWER RELAY 10,16
86 85 PV PILOT VALVE 12
1 C-9 C-10
1 2 C-10
SN
ESR3 R1 RESISTOR 2.2K 5
SN EVAP TEMP SENSOR 21
BRN PNK SR START RELAY 1
S/S EF CONTROL START/STOP
21 ST3 3 C-3
BLK 86
ESR1
85
- EVAP MOTORS 7
ST START TIMER 12
8
8
TR TRANSFORMER 1PH 60HZ 4
ST1 ST1 WP WATER PUMP (OPT) 14
WV WATER VALVE (OPT) 15
A
V-200/V-300 20 3 Phase Wiring Diagram - Page 1 of 2
114
V-200/V-300 20 3 Phase Wiring Diagram - Page 1 of 2
115
V-200/V-300 20 3 Phase Schematic Diagram
116
V-200/V-300 MAX 20 3 Phase Wiring Diagram - Page 1 of 2
117
V-200/V-300 MAX 20 3 Phase Wiring Diagram - Page 2 of 2
118
V-200/V-300 MAX 20 3 Phase Schematic Diagram
119
V-200/V-300 MAX TC 10 Wiring Diagram
120
V-200/V-300 MAX TC 10 Schematic Diagram
121
V-200/V-300 MAX TC 20 1 Phase Wiring Diagram
122
V-200/V-300 MAX TC 20 1 Phase Schematic Diagram
123
V-200/V-300 MAX TC 20 3 Phase 60 Hz Wiring Diagram
124
V-200/V-300 MAX TC 20 3 Phase 60 Hz Schematic Diagram
125
V-200/V-300 MAX TC 20 3 Phase 50 Hz Wiring Diagram
126
V-200/V-300 MAX TC 20 3 Phase 50 Hz Schematic Diagram
127
V-200/V-300 MAX TC 20 SAFEWAY Wiring Diagram
128
V-200/V-300 MAX TC 20 SAFEWAY Schematic Diagram
129
V-200/V-300 10 DSR, V-200/V-300 MAX 10 DSR, V-200 MAX 30 SPECTRUM DSR Wiring Diagram
RELEASED
A 14/Feb/2013
/ / 1
130
V-200/V-300 10 DSR, V-200/V-300 MAX 10 DSR, V-200 MAX 30 SPECTRUM DSR Schematic Diagram
RELEASED
A 14/Feb/2013
/ / 1
131
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Wiring Diagram - Page 1 of 4
RELEASED
A 19/Feb/2014
/ 1
132
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Wiring Diagram - Page 2 of 4
RELEASED
A 19/Feb/2014
/ 1
12V
24V
133
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Wiring Diagram - Page 3 of 4
RELEASED
A 19/Feb/2014
/ 1
12V
24V
134
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Wiring Diagram - Page 4 of 4
RELEASED
A 19/Feb/2014
/ 1
12V
24V
135
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Schematic Diagram - Page 1 of 3
RELEASED 19/Feb/2014
/ /
136
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Schematic Diagram - Page 2 of 3
RELEASED
R E 19/Feb/2014
e
137
V-200/V-300 20 DSR, V-200/V-300 MAX 20 DSR, V-200 MAX 50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Schematic Diagram - Page 1 of 3
RELEASED
R D 19/Feb/2014
b
138
V-200/V-300 MAX TC 10 DSR, V-200/V-300 MAX TCI 10/30 DSR, V-300 MAX 30 SPECTRUM DSR Wiring Diagram
139
V-200/V-300 MAX TC 10 DSR, V-200/V-300 MAX TCI 10/30 DSR, V-300 MAX 30 SPECTRUM DSR Schematic Diagram
140
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Wiring Diagram - Page 1 of 4
RELEASED 12/Sep/2012
/ p/
141
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Wiring Diagram - Page 2 of 4
RELEASED 12/Sep/2012
/ p/
142
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Wiring Diagram - Page 3 of 4
RELEASED 12/Sep/2012
/ p/
143
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Wiring Diagram - Page 4 of 4
/ p/
144
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Schematic Diagram - Page 1 of 3
RELEASED 12/Sep/2012
/ p/
145
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Schematic Diagram - Page 2 of 3
RELEASED 12/Sep/2012
146
V-200 MAX TC 20 DSR, V-200 MAX TCI 20/50 DSR, V-300 MAX 50 SPECTRUM DSR Schematic Diagram - Page 3 of 3
RELEASED 12/Sep/2012
/
147
V-200 MAX 30/50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Wiring Diagram for Remote Evaporators
RELEASED 14/Feb/2013
148
V-200 MAX 30/50 SPECTRUM DSR, V-300 MAX TC 20 DSR, V-300 MAX TCI 20/50 DSR Schematic Diagram for Remote Evaporators
RELEASED 14/Feb/2013
149
V-200 MAX TC 20 DSR, V-200 MAX TCI 10/20/30/50 DSR, V-300 MAX 50 SPECTRUM DSR, V-300 MAX TC 10 DSR, V-300 MAX TCI 10/30 DSR Wiring Diagram for Remote Evaporators
150
V-200 MAX TC 20 DSR, V-200 MAX TCI 10/20/30/50 DSR, V-300 MAX 50 SPECTRUM DSR, V-300 MAX TC 10 DSR, V-300 MAX TCI 10/30 DSR Schematic Diagram for Remote Evaporators
151
V-200 10 Refrigeration Diagram
152
V-200 20 Refrigeration Diagram
153
V-200 MAX 10 Refrigeration Diagram
154
V-200 MAX 20 Refrigeration Diagram
155
V-200 MAX TC 20 Refrigeration Diagram
156
V-300 10 Refrigeration Diagram
157
V-300 20 Refrigeration Diagram
158
V-300 MAX TC 10 Refrigeration Diagram
159
V-300 MAX TC 20 Refrigeration Diagram
160
V-200/V-300 10 DSR Refrigeration Diagram
RELEASED 13/Jun/2013
161
V-200/V-300 MAX 10 DSR Refrigeration Diagram
RELEASED 13/Jun/2013
162
V-200/V-300 20 DSR Refrigeration Diagram
RELEASED 30/Apr/2014 06:30:18 GMT
163
V-200/V-300 MAX 20 DSR Refrigeration Diagram
RELEASED 30/Apr/2014 06:30:18 GMT
164
V-200/V-300 MAX 30 SPECTRUM DSR Refrigeration Diagram
04/Jul/2014
04/
4/Jul/
Jul/2014
/20 07:38:41
07:3
3
388:4
4
41
1 GM
GMT
M DD.0
.0
Y
R
A
N
I
M
I
L
E
R
P
165
V-200/V-300 MAX 50 SPECTRUM DSR Refrigeration Diagram
04/Jul/2014
04/ l/2014 07:38:41
0 38 41 GMT D.0
0
Y
R
A
N
I
M
I
L
E
R
P
166
V-200/V-300 MAX TC 10 DSR Refrigeration Diagram
167
V-200/V-300 MAX TCI 10 DSR Refrigeration Diagram
168
V-200/V-300 MAX TCI 30 DSR Refrigeration Diagram
169
V-200/V-300 MAX TC 20 DSR Refrigeration Diagram
170
V-200/V-300 MAX TCI 20 DSR Refrigeration Diagram
171
V-200/V-300 MAX TCI 50 DSR Refrigeration Diagram
172
Maintenance Manual
SB-210+
V-200/V-300 Series
Additional text information
to be placed
TK 50982-1-MM (Rev.here
5, 09/14)
TK 5XXXX-X-PL
Ingersoll Rand’s Climate Solutions sector delivers energy-efficient HVACR solutions for
customers globally. Its world class brands include Thermo King, the leader in transport
temperature control and Trane, a provider of energy efficient heating, ventilating and air
conditioning systems, building and contracting services, parts support and advanced controls
for commercial buildings and homes.
Distributed by:
TK 50982-1-MM