Você está na página 1de 2

120-VOLT WIRE SIZING TABLE

BASED ON MAXIMUM OF 3% VOLTAGE DROP

LOAD DISTANCE IN FEET


(VA) 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300
500 12 12 12 12 12 12 12 12 12 12 10 10 10 10 10
600 12 12 12 12 12 12 12 12 10 10 10 10 10 10 8
700 12 12 12 12 12 12 12 10 10 10 10 10 8 8 8
800 12 12 12 12 12 12 10 10 10 10 10 8 8 8 8
900 12 12 12 12 12 10 10 10 10 8 8 8 8 8 8
1000 12 12 12 12 12 10 10 10 8 8 8 8 8 6 6
1100 12 12 12 12 10 10 10 10 8 8 8 8 6 6 6
1200 12 12 12 12 10 10 10 8 8 8 8 6 6 6 6
1300 12 12 12 12 10 10 8 8 8 8 6 6 6 6 6
1400 12 12 12 10 10 10 8 8 8 6 6 6 6 6 6
1500 12 12 12 10 10 8 8 8 8 6 6 6 6 6 4
1600 12 12 12 10 10 8 8 8 6 6 6 6 6 4 4
1700 12 12 12 10 10 8 8 8 6 6 6 6 4 4 4
1800 12 12 10 10 8 8 8 6 6 6 6 6 4 4 4
1900 12 12 10 8 8 8 8 6 6 6 6 4 4 4 4
2000 12 12 10 8 8 8 6 6 6 6 6 4 4 4 4
2100 12 12 10 8 8 8 6 6 6 6 4 4 4 4 4
2200 12 12 10 8 8 8 6 6 6 6 4 4 4 4 4
2300 12 12 10 8 8 8 6 6 6 4 4 4 4 4 4
2400 12 12 10 8 8 6 6 6 6 4 4 4 4 4 3
2500 12 12 10 8 8 6 6 6 4 4 4 4 4 3 3
2600 12 12 10 8 8 6 6 6 4 4 4 4 4 3 3
2700 12 10 10 8 8 6 6 6 4 4 4 4 3 3 3
2800 12 10 10 8 6 6 6 4 4 4 4 4 3 3 3
2900 12 10 10 8 6 6 6 4 4 4 4 3 3 3 2
3000 12 10 8 8 6 6 6 4 4 4 4 3 3 3 2
BY JONAS MCBRIDE 11.16.99