Você está na página 1de 2

ANLY FLOATLESS RELAY

A61F-G3 / A61F-G4 FLOATLESS CONTROLLER

OPERATIONS & CONNECTIONS :


A61F-G3
Operations Water Supply (AC220V)
The pump stops when the liquid level in the water tank reaches E2 (high) and the pump resumes operation
when the liquid level drops below E3(medium).
When the liquid level in the water tank reaches E1(high), the upper-limit indicator is lit, and alarm is sounded.
When the liquid level in the water tank drops below E4(low), the lower limit indicator
is lit, and alarm is sounded.
Connections
Power supply volatge
AC 110V, connect the power to S0 and S1.
AC 220V, connect the power to S0 and S2.
Water supply - Connect electromagnetic switch coil terminal A to Tb, as shown below.
Water drainage - Connect electromagnetic switch coil terminal A to Ta, as shown below.
RST A61F -G3
Ta Tc Tb B1 B2 LH LC LL
NFB
S0 S1 S2 E1 E2 E3 E4 E5

B PL2 PL1
Be sure to ground terminal E5.
A
PL1: Lower-limit
MC
PL2: Upper-limit
B: Alarm
E1 Water repletion
OL
E2 OFF
To water tank
Water tank E3
ON
E4
Water shortage
M P Water supply source E5

Pr oduc t is s u b j e c t t o c h a n g e w i t h o u t n o t i c e . D04
A61F-G4
Operations Water Supply (AC220V) Connections
The lower-limit indicator lamp for the water supply Power supply volatge
source remains lit while water source level is below E3. AC 110V, connect the power to S0 and S1.
When the water source level rises to E2, the lower-limit AC 220V, connect the power to S0 and S2.
indicator goes out and the pump becomes ready for Install a pushbutton switch between E2 and E8 as
operation. shown by the dotted line on the right.
When the water source level reaches E1, the upper-limit To start the pump or to recover from a power failure,
indicator is lit. if the water source level has not yet reached E2, depress the
The water-shortage indicator for the elevated tank pushbutton switch to start the pump by momentarily
remains lit while the water level in the elevated tank is short-circuiting E2 and E8.
below E7. The indicator lamp goes out when the water When the pump stops during a normal operation subse-
level rises to E7. The pump stops when the water level quent to an alarm issued for a low water source level (water
reaches E5 and the pump starts when the water level level has not reached E3), do not depress the push-
drops below E6. button switch.
If the water source level reaches E4 for any reason, the
tank repletion indicator lamp for the elevated tank is lit.
RST A61F -G4
LL1: Elevated tank water shortage
LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2 E4 E3 E2 E1
NFB LL2: Water supply source lower limit
S0 S1 S2 TC TC2 B TA E8 E7 E6 E5 LH1: Elevated tank repletion
LH2: Water supply source upper limit
BL1: Elevated tank water shortage
BL2: Water supply source lower limit
BH1: Elevated tank repletion
LL1 LL2 LH1 LH2 BL1 BL2 BH1 BH2
MC BH2: Water supply source upper limit
Pushbutton
switch
OL Be sure to ground terminal E8

To water tank

E4
Water repletion
M P Elevated E5
OFF
E1 Water tank E6
Upper limit ON
Water supply E2 E7
ON Water shortage
source E3 E8
OFF
E8
Lower limit

DIMENSIONS : (mm)
A61F-G3 A61F-G4

125 75
186 75

3ӿx4
120
165

146

40

160.5
3ӿx4

90

ANLY ELECTRONICS CO., LTD.


http://www.anly.com.tw
TAIWAN MAIN OFFICE : ANLY ELECTRONICS CO., LTD.
No.19, Lane 202, Fushou St., Shinjuang City, Taipei, Taiwan 242
TEL: +886-2-2996-3202 FAX: +886-2-2996-2017
MALAYSIA BRANCH : JUSTY ELECTRONICS (M) SDN, BHD.
No.1, Jalan 6/89B, Kawasan Perindustrian Trisegi, Batu 3 1/2 Off Jalan Sungei Besi, 57100 Kuala Lumpur, Malaysia
TEL: +60-3-7983-5758 FAX: +60-3-7981-5052
HONG KONG BRANCH : ANLY ELECTRONICS (HK) LTD.
Flat K, 13/F, Edward Mansion, 141 Prince Edward Road W., Kowloon, Hong Kong
TEL: +852-2397-2505 FAX: +852-2397-6080
SHANGHAI BRANCH : ANLY TECHNOLOGY (WUXI) CO., LTD.
Room 13G, No.831, Xinzha Rd., Jingan District, Shanghai, China 200041
TEL: +86-21-6218-3300 FAX: +86-21-6217-5911
NO. A61FG3-G-A