TEMPERATURE RISE

General
An isolation transformer’s main as lightbulbs. Lightbulbs have a increased, the amount of energy
purpose is to transfer electrical certain amount of resistance and converted to heat also increases.
energy from the primary coil to the when a voltage is developed This is where efficiency, maximum
secondary coil (input to output). In across the lightbulb some of the temperature rise, and insulation
doing this, the transformer converts energy is converted into heat. system temperatures are important
some of the electrical energy into Transformers also have a in regards to isolation transformers.
heat energy. Transformers resistance and when the power
develop heat in the same manner supplied from the transformer is

Efficiency
Equipment is desired to operate at outer portion of the conductors What these losses add up to is
a high efficiency. The efficiency of (see Harmonics Application Note heat. A transformer with a low
a transformer is determined by its UK#12). As the harmonic content efficiency has more losses,
output power and its losses. increases, the losses due to skin generating more heat than a
Fortunately, losses in transformers effect also increases. K-rated transformer with a high efficiency.
are relatively small. The losses in transformers are ideal in these This additional heat is dangerous.
a transformer come from the coils, applications. The core loss is The lifetime of electrical devices
skin effect, and excitation of the typically constant from no load to decreases rapidly when the
core. The loss due to the coils is full load. The actual losses depend temperature limit is exceeded. To
equal to the square of the current on the type of steel used and the keep low efficient transformers cool
times the resistance of the way it is manufactured. A high manufacturers use fans, water
conductor (I2 x R). This value grade silicon steel assembled in an cooling systems, and air
varies upon changes in the load. interwoven pattern produces low conditioners. These cooling
Skin effect is caused by high excitation losses. devices bring additional cost and
frequency currents traveling on the maintenance.

Temperature Limits
Transformers are designed to a temperature that the insulation can transformer runs the chance of
maximum temperature rise value. reach without degrading. Once being destroyed by the excess
This value is usually 80° C, 115° C, this temperature is exceeded, the heat.
or 150° C. These values are life expectancy of a transformer will
usually based on a maximum be cut in half for every 10°C to a A desirable indoor dry type
ambient temperature of 40° C, thus point where the insulation transformer is convection (self)
a transformer with a 115° C degrades, destroying the cooled and has a maximum
maximum temperature rise will not transformer and usually anything temperature rise of 115° C with an
reach a temperature above 155° C connected to it. insulation temperature of 200° C.
(the total temperature is equal to Beware of the 80° C rise
the temperature rise plus the Transformers with a low efficiency transformers. They are often a
ambient temperature). emit a lot of heat and need cooling 115° C rise transformer that has
devices to get rid of the excess been de-rated, providing a costly
The insulation of the conductors heat. These devices are costly approach.
also have a maximum temperature and usually need constant
value. This value is usually 200° C maintenance. Also, if one of these
or 220° C. This is the maximum cooling methods fail, the

Page 1 of 2
Ultra-K
The Ultra-K manufactured by system. The Ultra-K doesn’t harmonics. The Ultra-K has
Controlled Power Company is a K- require any fans for cooling double or triple shielding for
rated shielded isolation because it is 98% efficient optimal noise attenuation and
transformer, manufactured with providing in excess of 200,000 comes with the option of a high
high grade M-6 silicon steel and hours MTBF. It is offered in K- frequency filter and TVSS for surge
has a maximum temperature rise factors of K-4, K-7, K-13, and K-20 suppression.
of 115° C with a 200° C insulation to handle the heat generated by

Summary
Transformers with efficiencies less respectable transformer is one device. Controlled Power
than 96% produce an excessive which has a maximum temperature Company manufactures the Ultra-K
amount of heat and usually have rise of 115° C and a 200° C to exceed these specifications.
an unsatisfactory temperature rise insulation system that doesn’t
and insulation system. A require fans or any other cooling