SINAMICS

Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Guide to updating firmware from versions V4.3.x through V4. 6.x


to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Contents
1 Hardware requirements ........................................................................................................................................................... 3

2 Guide to updating firmware via Starter and CompactFlash card ............................................................................................. 5

2.1 Preconditions .................................................................................................................................................................. 5

2.2 Starting situation ............................................................................................................................................................. 5

2.3 Firmware update procedure ........................................................................................................................................... 5

2.3.1 Back up your data ....................................................................................................................................................... 5

2.3.2 Connect the PC/PG to the drive .................................................................................................................................. 5

2.3.3 Back up the existing project........................................................................................................................................ 5

2.3.4 Switch off the electronic power supply ...................................................................................................................... 7

2.3.5 Insert the CF card in the reader for the PC / PG ......................................................................................................... 7

2.3.6 Back up licenses .......................................................................................................................................................... 7

2.3.7 Delete the entire contents of the CF card .................................................................................................................. 7

2.3.8 Copy new firmware to the CF card ............................................................................................................................. 7

2.3.9 Install the backed-up licenses ..................................................................................................................................... 7

2.3.10 Install the backed-up project ................................................................................................................................. 7

2.3.11 Insert the CF card into the Control Unit ................................................................................................................. 9

2.3.12 Switch on the electronic power supply .................................................................................................................. 9

2.3.13 Perform automatic firmware update in the drive .................................................................................................. 9

2.3.14 Restart following completion of firmware update ............................................................................................... 10

3 Guide to updating via the web server .................................................................................................................................... 11

3.1 Preconditions ................................................................................................................................................................ 11

3.2 Starting situation ........................................................................................................................................................... 11

3.3 Firmware update procedure ......................................................................................................................................... 11

3.3.1 Establish the network connection (hardware) ......................................................................................................... 11

Page 1 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

3.3.2 Configure the network connection (software) ......................................................................................................... 11

3.3.3 Check the network connection ................................................................................................................................. 13

3.3.4 Start the web server ................................................................................................................................................. 14

3.3.5 Log in to the web server ........................................................................................................................................... 16

3.3.6 Update the firmware in the web server ................................................................................................................... 19

3.3.7 Complete the firmware update ................................................................................................................................ 21

3.3.8 Restore the original PC/PG settings .......................................................................................................................... 21

Page 2 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

1 HARDWARE REQUIREMENTS

The hardware release of the Control Units determines which firmware versions can be installed.

The CU310-2DP (order number 6SL3040-1LA00-0AA0) and CU310-2PN (order number 6SL3040-1LA01-0AA0) are not supported
by firmware versions lower than V4.4.

Any hardware release of the CU320-2DP with order number 6SL3040-1MA00-0AA0 can be upgraded to device version V4.6 /
V4.7.

The CU320-2 PN with order number 6SL3040-1MA01-0AA0 is supported by firmware version V4.4 and higher.

The hardware version of your Control Unit is specified on the type plate:

Type plate with order number and


hardware version

Type plate with order number and


hardware version

Fig. 1-1: CU320-2DP with type plate

Page 3 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Short type plate with order


number and hardware version

Fig. 1-2: CU310-2 type plate with version data


1
Firmware versions of V4.3.x or higher can only be installed on 1GB or 2GB CompactFlash cards. 1GB cards are supplied with
firmware version V4.3.x or higher and 2GB cards with firmware version V4.6 or higher.

1
The 2GB CompactFlash cards are an essential requirement for use of the feature Powerfail-proof firmware update via web
server.

Page 4 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

2 Guide to updating firmware via Starter and CompactFlash card

2.1 Preconditions

 Reader for CompactFlash cards for connection to a PC/PG

 PC/PG with STARTER


2
o Version >= 4.3.x incl. appropriate SSP for new firmware version

o With communication interface to the Control Unit

2.2 Starting situation

The starting situation involves a SINAMICS S120 converter on which the installed firmware version is to be changed.

2.3 Firmware update procedure

2.3.1 BACK UP YOUR DATA


To back up your parameter settings, perform the following steps.

2.3.2 CONNECT THE PC/PG TO THE DRIVE


Connect the PC/PG to the drive using, for example, the PROFIBUS or PROFINET interface. For a detailed description of this
process, refer to the Starter Help.

2.3.3 BACK UP THE EXISTING PROJECT


If a project is already stored on the CF card, use STARTER to download it to the PC/PG and make a backup copy if necessary.

If the firmware has a new device version number (e.g. if you are updating versions V4.3.x through 4.6.x to V4.7.x), you must
also select the relevant drive unit in the STARTER project tree and then select the required device version by clicking on menu
options Target device  Device version with the right mouse button:

2
SSP: SINAMICS Support Package:
The appropriate SSP for the firmware is stored in subdirectory ADDON\SINAMICS\ES_TOOL\SSP in the zip file containing the
new firmware

Page 5 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 2-1: STARTER menu selection "Device version"

Fig. 2-2: STARTER menu "Device version" with new update version selected

Page 6 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

NOTICE

All project data and parameters on the CompactFlash card are deleted by the upgrade process described below!

2.3.4 SWITCH OFF THE ELECTRONIC POWER SUPPLY


Disconnect the power supply from the Control Unit (including the 24 V DC supply)

2.3.5 INSERT THE CF CARD IN THE READER FOR THE PC / PG


 Remove the CompactFlash card from the Control Unit

 Insert this CompactFlash card into the reader connected to/in the PC/PG

2.3.6 BACK UP LICENSES


If the CompactFlash card contains a KEYS folder, back it up using the Windows Explorer on the PC/PG. This folder contains
possible license keys for software options under license.

2.3.7 DELETE THE ENTIRE CONTENTS OF THE CF CARD


Delete all files and folders from the CompactFlash card using Windows Explorer on the PC.

2.3.8 COPY NEW FIRMWARE TO THE CF CARD


 Extract the new firmware from the zip file using an unzip application, e.g. WINZIP, to any temporary directory of your
choice on the PC/PG.

 Use Windows Explorer to move the contents of the temporary directory to the CompactFlash card.

2.3.9 INSTALL THE BACKED-UP LICENSES


Use Windows Explorer to move the KEYS folder (if applicable, see step 2.3.6), from the PC/PG to the main directory on the
CompactFlash card.

2.3.10 INSTALL THE BACKED-UP PROJECT


 Navigate to the backed-up project in STARTER (see step 2.3.3)

Page 7 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

 Select the drive unit in the STARTER project navigator

 Execute the command Load to File System in the context menu (right mouse button) (see Fig. 2-3)

 In the dialog which now appears (see Fig. 2-4), select the drive / main directory of the CompactFlash card under Select
target and then start the project export to the CompactFlash card.

The project will now be transferred with all drive parameter settings including DCC libraries (if applicable) to the CompactFlash
card.

Fig. 2-3: STARTER menu selection "Load to File System"

Page 8 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 2-4: STARTER menu "Load to File System"

Alternatively, you can copy the project to the CompactFlash card at a later time (when you are connected online to the drive
unit) using command Download followed by "Copy RAM to ROM".

2.3.11 INSERT THE CF CARD INTO THE CONTROL UNIT


 Remove the CompactFlash card safely (using Remove hardware) from the reader

 Insert the CompactFlash card into the CU310-2/CU320-2 Control Unit

2.3.12 SWITCH ON THE ELECTRONIC POWER SUPPLY


Reconnect the power supply to the Control Unit (including the 24 V DC supply)

2.3.13 PERFORM AUTOMATIC FIRMWARE UPDATE IN THE DRIVE


With firmware version V4.3.x and later, the firmware of the integrated components is updated automatically.

During this process, the RDY (READY) LED on the Control Unit flashes orange at a frequency of 0.5 Hz.

Fig. 2-5: STARTER alarm display while updating of component firmware is in progress

Page 9 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

When the firmware update process is complete, the LED flashes faster at 2 Hz.

Warning 1007 is active for the upgraded components and is displayed in the STARTER alarm window:

Fig. 2-6: STARTER alarm display following updating of component firmware

2.3.14 RESTART FOLLOWING COMPLETION OF FIRMWARE UPDATE


When the update process is complete, restart the Control Unit by switching the power supply off and then on again.

Done. The drive unit is now functional again.

The current firmware versions of the modules are displayed in the STARTER version overview:

Fig. 2-7: STARTER version overview

Page 10 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

3 GUIDE TO UPDATING VIA THE WEB SERVER

3.1 Preconditions

 PC/PG with Ethernet card

 Physical network connection (Ethernet) between the Control Unit and the PC/PG

3.2 Starting situation


3
The starting situation involves a SINAMICS S120 converter on which firmware version V4.6 or higher is already installed and
needs to be changed to a different firmware version.

3.3 Firmware update procedure

The following guide explains the steps you need to take in order to update firmware via the SINAMICS web server on a
Windows PC.

3.3.1 ESTABLISH THE NETWORK CONNECTION (HARDWARE)


The PC/PG and the Control Unit can be networked via the PROFINET interface or via the commissioning interface on the
Control Unit.

The process of creating a network connection using the commissioning interface is described by way of an example below:

Ethernet
connection

Fig. 3-1: Hardware setup

3.3.2 CONFIGURE THE NETWORK CONNECTION (SOFTWARE)


 Open the window Network connections by selecting
Start  Settings Network Connections on the Windows PC:

3
The firmware update process can be used, for example, to import hotfixes or service packs of version V4.6

Page 11 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 3-2: Network connections

 Select the LAN interface which is connected to the Control Unit

 Open the properties box for this network connection by clicking on the relevant command in the context menu (right
mouse button)

Fig. 3-3: Properties of the network connection

 Select Internet Protocol (TCP/IP) in the properties box

Page 12 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

 Click on the Properties button

 Make a note of the existing settings so that you can restore them later!

 Select the settings as they are shown in Fig. 3-4 and confirm by clicking on the OK button:

Fig. 3-4: TCP/IP settings on the PC/PG

Note
In the steps described above, it has been assumed that the network settings for the commissioning interface are still the same
as the factory settings (p8901 – p8904). If this is not the case, an IP address contained in the same subnet as the IP address of
the Control Unit must be entered in the dialog shown in Fig. 3-4 .

3.3.3 CHECK THE NETWORK CONNECTION


Open the DOS Shell (Start -> Run -> cmd -> OK) on the Windows PC and execute a Ping command to the Control Unit (IP
address: 169.254.11.22):

Page 13 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 3-5: Unsuccessful ping to the Control Unit

Fig. 3-6: Successful ping to the Control Unit

Check the network connection and the network settings on the PC/PG and the Control Unit if the ping is unsuccessful (see Fig.
3-5).

3.3.4 START THE WEB SERVER


If step 3.3.3 has been successful, launch the web browser on your PC/PG and enter the IP address of the Control Unit in the
address line:

Page 14 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 3-7: Start the web server

If the Ping worked, but the start page of the web server is not displayed, then the problem is probably attributable to one of
the following:

1. The firmware on the Control Unit is lower than version V4.6

 A web server is not a component of the firmware

2. The proxy server settings of the web browser are not correct

 Check the proxy server settings (see Section 3.3.4.1)

3. The web server is not activated on the Control Unit

 Follow the instructions in step 3.3.5.2

3.3.4.1 Proxy server settings on the PC/PG


Where a direct connection exists between the PC/PG and the Control Unit (see Fig. 3 1), a proxy server should not be set in the
web browser.

The method of changing proxy server settings varies depending on the web browser product and can differ from version to
version of the same web browser product. Consult the Help function of the relevant browser product for instructions.

To enter proxy server settings in Internet Explorer 7, for example, select

Page 15 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Tools  Internet Options  Connections  LAN Settings:

Fig. 3-8: LAN settings / Proxy server configuration

IMPORTANT

Before you make any changes, make a note of the existing settings so that you can restore them after the firmware has been
updated!

3.3.5 LOG IN TO THE WEB SE RVER

3.3.5.1 Control Unit has not yet been parameterized


If the Control Unit is still set to its factory settings and the web page shown in Fig. 3-9 is displayed, then you don't need to log
in, i.e. you do not need to enter either a user name or a password and you can proceed immediately with step 3.3.6.

Page 16 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 3-9: Start page of web server when Control Unit is not parameterized

3.3.5.2 Administrator password is not known


If you do not know the administrator password or a user administrator has not yet been set up for the web server, then you
must now configure the user administrator accordingly in STARTER (at least STARTER V4.3.2; Starter V4.3.1 with appropriate
SSPs is not sufficient):

 Set up a link to the Control Unit in STARTER (see also Chapter 2.3.2)

 Select the relevant drive (not the Control Unit) in the project navigator

 In the context menu (right mouse button), select the command "Web server".

Page 17 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 3-10: STARTER: Configuring the web server settings

 Now activate the web server and the user administrator in the web server dialog:

Fig. 3-11: Activating the web server and web server users in STARTER

 Then execute the command Copy RAM to ROM.

Page 18 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

3.3.5.3 Administrator password is known


Log in to the web server with the user name Administrator and the password that you have already chosen for the Control Unit
in question:

Fig. 3-12: Start page following logon as administrator

3.3.6 UPDATE THE FIRMWARE IN THE WEB SERVER


 Navigate to the page Manage config in the web server

 In the box Send new update data , select the zip file containing the new firmware on your PC/PG:

Page 19 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

Fig. 3-13: Update page of the web server

 Click on button Send update data to start the firmware update process:

Fig. 3-14: Firmware download progress dialog

 Now be patient and follow the status messages / instructions displayed by the web server.

Page 20 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014


SINAMICS
Guide to updating firmware from versions V4.3.x through V4.6.x to V4.7.x for SINAMICS S120 with CU310-2 and CU320-2

3.3.7 COMPLETE THE FIRMWARE UPDATE


 When the update process is complete, it might be necessary to restart the Control Unit manually (see Section 2.3.14 )
depending on the device versions of the components installed in the drive.

 After you have restarted the Control Unit (if necessary), refresh the web page displayed for the drive in the web
browser by pressing key F5 .

 You can now check whether the firmware update was successful / unsuccessful by examining the version data
displayed on the web server start page and by selecting tab Messages and Logs  Diagbuffer (log in using your
administrator ID):

Fig. 3-15: Checking the success of the firmware update in the diag buffer

 Any active messages are displayed on tab Messages and Logs  Alarms Drive where they can also be acknowledged.
Messages which cannot be acknowledged must be processed accordingly.

3.3.8 RESTORE THE ORIGINAL PC/PG SETTINGS


If you have changed the network settings (see Fig. 3-4) and / or the proxy server settings (see Fig. 3-8) on the PC/PG in order to
update the firmware, you must now restore them to their original values.

Page 21 / 21 June 30, 2014 Unrestricted / © Siemens AG 2014