DA Phase-1 300 Substation Point to Point Testing

Zone:
Substations: Substaion To Control Centers - Point To Point Test Results and Signal List
Station:
Test Result
SI. KV Level Bayname B3 Text Element Name Alarm text for DCC Signal Discreption Info Sig IEC Test
Priority DCC Remarks
No (B2) (B3 Name) (LBS Toward) (SND use only) (Element Text) Type Address (SND use only)
SLD GenS
Open
1 LBS Load Break Switch Load Break Switch Status Status DPI 152 LB tc
Close
Open
2 LBS Load Break Switch Load Break Switch Command Control DC 202 LB tc
Close
App
3 EFIBTLW EFI Battery Low EFI Low Battery Alarm AIStat SPI 69 AI AD5-1
Disp
App
4 EFIOPTD EFI Operated EFI Operated Status SPI 68 EFIOP_ts
Disp
Open
5 Iso ETH Earth Switch Status LBS1 ETH STATUS Status DPI 158 IsoE-1-S
Close
Open
6 LBS Load Break Switch Load Break Switch Status Status DPI 153 LB tc
Close
Open
7 LBS Load Break Switch Load Break Switch Command Control DC 203 LB tc
Close
Open
8 Iso ETH Earth Switch Status LBS1 ETH STATUS Status DPI 159 IsoE-1-S
Close
Open
9 CB Circuit Breaker Transformer Switch Status Status DPI 154 CB-2
Close
Open
10 Iso ETH Earth Switch Status Trafo LBS Earth Status Status DPI 156 IsoE-1-S
Close
App
11 TROVLDTR Overload trip Transformer Tripping Alarm AlStat SPI 64 AI-A1-1
Disp
11 T1 LD1
App
12 TRFHITMP High Temperature TRF High Temperature Alarm AlStat SPI 66 AI AD2-1
Disp
App
13 TRMDI100 Transformer MDI 100% Transformer MDI Trip 100% AlStat SPI 71 AI AD2-1
Disp
App
14 TRMDI80 Transformer MDI 80% Transformer MDI Alarm 80% AlStat SPI 73 AI AD2-1
Disp

9/24/2017 1 of 2 Rev-02
App
15 DoorOpen Substation Door Open Door Open/Close AIStat SPI 60 AI-AD6-1 Sensor not available
Disp
local
16 SuperMod RMU Selector Switch Local/Remote Switch AIStat SPI 75 SuperMod
remote
Open
17 Test Point Test Point Dummy Control Control DPI 151 CB-0
Close
Open
18 Test Point Test Point Dummy Status Status DC 206 CB-0
Close
App
19 DSHITemp DA High Temperature Alarm DSA Panel High Temperature AIStat SPI 56 AI-AD2-1
Disp
App
COMMON

COMMON
20 DSACFAIL AC Supply Fail DSA AC Supply Fail AIStat SPI 54 AI AD2-1
Disp
App
11

21 DBatCHAl Battery Charger Alarm DSA Battery Charger Alarm AIStat SPI 55 AI-AD2-1
Disp
App
22 RMUGASL Gas Pressure Low RMU Gas Pressure Low AIStat SPI 59 AI AD2-1
Disp
App
23 RTUMaAL RTU Major Alarm RTU Major Alarm AIStat SPI 52 AI-AD5-1
Disp
App
24 RTUMinAL RTU Minor Alarm RTU Minor Alarm AIStat SPI 53 AI-AD5-1
Disp
App
25 RTU-MCB RTU MCB Trip RTU CTRL MCBTRP AIStat SPI 51 AI-AD5-1
Disp
App
26 EARTTFTA Earth Wire Theft Alarm Earth Theft Alarm AIStat SPI 63 AI AD2-1 Sensor not available
Disp
App
27 PDCablTR PD for Cable Termination Partial Disch Cable Trmintn AIStat SPI 62 AI AD2-1 Sensor not available
Disp
Analog as per below
28 0.4 LVDB 1 LVDB 1 I Balanced Current Transformer Load Current MvMoment 1 mv-l11
(MN) table

Analog as per below


29 0.4 LVDB 2 LVDB 2 I Balanced Current Transformer Load Current MvMoment 2 mv-l11
(MN) table

Analog Value/Current Signal Testing CT Ratio:


Displayed Value in SCADA
Current Injected
TRF - 1 TRF - 2
0.5 A
1A
1.5 A
2A
2.5 A
3A
3.5 A
4A
4.5 A
4.99/5.0 A
Verified By:
Contractor Dewa/DAM Dewa/OTD-TCS Dewa/DO-DFO Dewa/DO-DCC Dewa/OTD-MS

Name: Name: Name: Name: Name: Name:

Signature: Signature: Signature: Signature: Signature: Signature:

Date: Date: Date: Date: Date: Date:

9/24/2017 2 of 2 Rev-02