1
4/26/2016
Objectives.....
• Reduced Complex wiring
• Reduced Maintenance cost
• Interoperability between vendors
• Pre and Post information about equipment
health and substation occurrences, provides
the information about reliability and
availability of electrical system
• Faster remedial actions based on data
received
2
4/26/2016
3
4/26/2016
• Modbus
Introduced by Modicon
Mainly use for SCADA and metering at local/remote
end
• DNP
• ETHERNET (TCP/IP)
Use for networking (LAN < 5km)
• IEC60870-
IEC60870-5-103/104
Open protocol for protection
• IEC61850
Open protocol for substation automation
Beyond protocol (application for substation
engineering)
4
4/26/2016
• IEC61850 Protocol
Open protocol for substation automation
Interoperability: Exchange information between
IED’s from different vendors
Use this information for own function (CB status
received by IED1 can send GOOSE message to
IED2)
Flexible configuration
5
4/26/2016
6
4/26/2016
7
4/26/2016
Digital
•Digital
Substation
8
4/26/2016
• Part 1 to 10
• Part 6 for SCL
• Part 8-
8-1 for IEC GOOSE/GSE (Generic object
oriented substation event) message
Also known as Virtual inputs and outputs
Data type Boolean (0 / 1 states)
Station bus application (Interlocks, alarms, trip logic)
• Part 9-
9-2 for Process bus Implementation
Sampled value
Analogue values to be converted in to Digital values
Digital values applied to Protection relays
9
4/26/2016
SCADA Station
HMI
Substation Substation
HMI Computer
Router WAN
CT CT
MU IOU IOU MU
PT PT
XCBR
10
4/26/2016
Digital
CT/VT IEDs
C
Intelligent A
Breaker
Power System B
The “Digital Substation”: both power system data and control over the LAN.
11
4/26/2016
12
4/26/2016
13
4/26/2016
80 samples/cycle
Part 9-2:
Where do We need Time Synchronization???
14
4/26/2016
15
4/26/2016
Manufacturer 1 Manufacturer 2
16
4/26/2016
17
4/26/2016
18
4/26/2016
Control Engineering
HMI
Center
Router
Station
10 MBit/s Switch Controller
RS485-
Ethernet
SCADA HMI
RS232
Station Controller
RS485/RS422/RS232, IEC60870
19
4/26/2016
Q1A IO module
RS485/RS422/RS232, IEC60870
CB 52
Q2
RS232
Relays Meters
Hardwired
20
4/26/2016
SCADA HMI
RJ45, IEC60870-
IEC60870-5-104
Station Controller
RJ45-
RJ45-Copper or FO, IEC61850
IEC61850 S/S
• Communication
Network Architectures
21
4/26/2016
IED IED IED IED IED IED IED IED IED IED
IED IED IED IED IED
IED IED IED IED IED
22
4/26/2016
Communication
through LAN-
LAN-B Failed
PATH 1 PATH 2
Fault
IED IED IED IED IED IED IED IED IED IED
IED IED IED IED IED
IED IED IED IED IED
23
4/26/2016
Duplicate ring
24
4/26/2016
25
4/26/2016
Easy to configure
High availability
Better visualization
26
4/26/2016
IEC61850
IEEE C37.92 Low energy analogue
IEC 61869-
61869-9 Digital Interface for CT/VT
IEC 61869-
61869-13 Standardization of MU
IEC 60044-
60044-7 Electronic VT
IEC 60044-
60044-8 Electronic CT
PC 37.235 Rogowski Coil Guide
PSRC WG I8 Optical CT/PT Guide
IEC TC38WG37L. Kojovic (US), F. Rahmatian (CA)
C37.1 SCADA
C37.111 COMTRADE
C37.118-
C37.118-1/2 Synchrophasor system