What is Digital Technology?

• Electronic technology that generates, stores


and process data in terms of high and low
state or True & False state
 Two states: High (1) and Low (0)
 Each of these state digits is referred to as a bit
 String of Bits addressed as a Byte (1 byte = 8
bits or 16 bits or 32 bits data)

1
4/26/2016

What is Digital Technology?

Why Digital Substation in Electrical


System?

Objectives.....
• Reduced Complex wiring
• Reduced Maintenance cost
• Interoperability between vendors
• Pre and Post information about equipment
health and substation occurrences, provides
the information about reliability and
availability of electrical system
• Faster remedial actions based on data
received

2
4/26/2016

What are the Digital Equipments


used in Electrical System?
• Digital relays (MicroP
(MicroP relays)
• Digital meters
• Ethernet switches / Modem
• Communication cable
• Data concentrators and I/Os
• GPS clock / receiver antenna
• Phasor measurement unit
• HVDC controller
• Generator controller
• Fiber optic CT/VT
• Merging unit

What are the Physical media available for


Digital data transmission in Electrical System?

• RS232 communication cable


 Point to point network connection
• RS485 communication cable
 Multidrop network connection
• Ethernet RJ45 communication cable
 Unicast, Multicast and Broadcast through
ethernet
• Fiber optic communication cable
 Unicast, Multicast and Broadcast through
ethernet

3
4/26/2016

What are the Physical media available for


Digital data transmission in Electrical System?

• Data transmission is through Satellite


 GPS time synchronization

What are the Communication Protocols for Digital


data transmission used in Electrical System?

• Modbus
 Introduced by Modicon
 Mainly use for SCADA and metering at local/remote
end

• DNP
• ETHERNET (TCP/IP)
 Use for networking (LAN < 5km)
• IEC60870-
IEC60870-5-103/104
 Open protocol for protection
• IEC61850
 Open protocol for substation automation
 Beyond protocol (application for substation
engineering)

4
4/26/2016

What are the Communication Protocols for Digital


data transmission used in Electrical System?

• IEC61850 Protocol
 Open protocol for substation automation
 Interoperability: Exchange information between
IED’s from different vendors
 Use this information for own function (CB status
received by IED1 can send GOOSE message to
IED2)
 Flexible configuration

Where to apply Digital technology in


Electrical System?

• Digital Applications in Electrical System


 Power Generation
 Wind and Solar Generation
 Thermal and Hydro Generation
 Power Transmission
 Power Distribution

5
4/26/2016

Where to apply Digital technology in


Electrical System?
• Operations Optimizations
 Power plant/Process Industries Operation
 Remote control of generator
 Synchronization
 Transmission system Operation, monitoring &
control
 SCADA, Load dispatch control, Unmanned
control/remote operation of substation
 Distribution system Operation
 Reactive power control through capacitor bank ON/OFF
 Load shedding
• Asset Performance
 On line monitoring of equipment

What are the Applications of Digital technology in


Electrical System?
 General Purpose:
 Monitoring Functions
 Online monitoring power system/relaying parameters
(i.e. Voltages/Currents/Power/Status of Digital Inputs &
Outputs, Status of protection function operated/not
operated, Circuit breaker status ON/OFF, Power
transformer operating parameters monitoring etc.)
 Control Functions
 Circuit breaker / Isolator Operations from remote
location
 Load shedding in Auto/Manual mode, Capacitor bank
control, static VAR compensator control
 Recording and Analysis
 Sequence of Event with time stamping
 Disturbance storing and analysis

6
4/26/2016

What are the Applications of Digital technology in


Electrical System?
 General Purpose:
 Power system and Substation details available at one
point location / remote location
 Unmanned Substation / Remote operation

Digital technology used in Electrical


System
• Electrical SCADA system / PMS system
 Substation Automation
 Power management, Grid Islanding and Load
shedding system
 Monitoring of active and reactive power details
at remote end
• Synchrophasor system
 Wide area monitoring, protection and control
• Numerical Protection & Control
 Line differential application
 Disturbance and Event recording
 Metering
 Transfer trip of distance protection scheme

7
4/26/2016

What Is Conventional S/S?

Digital
•Digital
Substation

8
4/26/2016

IEC61850 Digital S/S: Standards

• Part 1 to 10
• Part 6 for SCL
• Part 8-
8-1 for IEC GOOSE/GSE (Generic object
oriented substation event) message
 Also known as Virtual inputs and outputs
 Data type Boolean (0 / 1 states)
 Station bus application (Interlocks, alarms, trip logic)
• Part 9-
9-2 for Process bus Implementation
 Sampled value
 Analogue values to be converted in to Digital values
 Digital values applied to Protection relays

IEC61850 Digital S/S: Standards

Part 9-2: Sampled values for Process bus


Implementation
 80 Samples/Cycle for Protection
Function (4kHz sampling rate)
4000packets
4000packets / seconds
 256 Samples/Cycle for Metering
Function (12.
12.8kHz sampling rate)
12800packets
12800packets / seconds
 Reduce Field wiring cost

9
4/26/2016

What is IEC61850 Digital Substation?

SCADA Station
HMI

Station Bus Fiber


Communications Optic
IEC61850-7-2/3/4
Gateway cable
IEC61850-8-1

IED1 IED2 IED3


Fiber
Optic
cable
Process Bus
CT IEC61850-9-2 VT

IEC61850 Digital Substation: Typical


Basic Structure

Substation Substation
HMI Computer

Router WAN

Ethernet Substation Bus


Switch
SCADA Master
IED IED IED IED

Ethernet Switch Process Bus

CT CT
MU IOU IOU MU
PT PT
XCBR

10
4/26/2016

IEC61850 Digital Substation: Typical


Basic Structure

“Station Bus” LAN


IEC 61850-8-1

“Process Bus” LAN


IEC 61850-9-2
IEDs

Digital
CT/VT IEDs

C
Intelligent A
Breaker
Power System B

The “Digital Substation”: both power system data and control over the LAN.

IEC61850 Digital Substation: Typical


Basic Structure

11
4/26/2016

IEC61850 Digital Substation: Typical


Basic Structure

IEC61850 Digital Substation: Typical


Basic Structure

12
4/26/2016

IEC61850 Digital Substation: Typical


Basic Structure

IEC61850 Digital Substation: Merging


unit

13
4/26/2016

IEC61850 Digital Substation: Merging


unit

80 samples/cycle

IEC61850 Digital Substation: Merging


unit

Part 9-2:
Where do We need Time Synchronization???

 <1 ms (General Applications)


 Sequence of Events
 DFR, Oscillography
 <10 microseconds (High Precision)
 Sampled Value (IEC61850
(IEC61850-
61850-9-2)
 SynchrophasorW (C37
(C37.
37.118)
118)

14
4/26/2016

IEC61850 Digital Substation: Basic


Structure by using Optical CT/VT

IEC61850 Digital Substation: CFE


project (USA)

15
4/26/2016

IEC61850 Digital Substation: Optical CT

Manufacturer 1 Manufacturer 2

IEC61850 Digital S/S: Optical CT

• Smaller size and Lighter weight


(approximately 20%) compare to
conventional CT
• Easy to install at site
• No CT saturation
• No maintenance
• Require less burden because the high level
output (1A/5A) not require to drive
• Composite insulator (no gas/oil inside)

16
4/26/2016

IEC61850 Digital S/S: Optical CT

Digital Substation: Instrument


Transformer

17
4/26/2016

Digital Substation: Ethernet connector

10Base-T 100Base-T 1000Base-T


IEEE Standard IEEE 802-3i IEEE 802-3u IEEE 802-3ab
Suitable Cable Category 3, 5 Category 5 Category 5e
Transmission 10M bps 100M bps 1000M bps
Speed

Digital Substation: Ethernet connector

1Gbps Ethernet link speed is highly recommended for Process bus


in switch network

18
4/26/2016

Digital Substation: IEC60870


IEC60870--5-103

Control Engineering
HMI
Center

Router

Station
10 MBit/s Switch Controller
RS485-
Ethernet

Bay Relay A Relay B Bay Relay A Relay B


Controller Controller

Conventional Conventional Conventional Conventional


Switchgear CT / VT's Switchgear CT / VT's

Digital Substation: IEC60870


IEC60870--5-103

SCADA HMI

RS232

Station Controller

RS485/RS422/RS232, IEC60870

SWB1 SWB2 SWB3 SWB4

19
4/26/2016

Digital Substation: IEC60870


IEC60870--5-103

Q1A IO module

RS485/RS422/RS232, IEC60870
CB 52

Q2
RS232

Relays Meters

IEC61850 Station Bus Implementation

Ethernet Switch Ethernet Switch

Hardwired

20
4/26/2016

IEC61850 Station Bus Implementation

SCADA HMI

RJ45, IEC60870-
IEC60870-5-104
Station Controller

RJ45-
RJ45-Copper or FO, IEC61850

Bay Switch 1 Bay Switch 2

SWB1 SWB2 SWB3 SWB4

IEC61850 S/S

• Communication
Network Architectures

21
4/26/2016

IEC61850 S/S: Network Topology


(Digital Substation)
Cascading Bus
Architecture
1 2 3 4 N

IED IED IED IED IED IED IED IED IED IED
IED IED IED IED IED
IED IED IED IED IED

• Cost-effective bus architecture – messages cascade from


switch to switch.

IEC61850 S/S: Network Topology


(Digital Substation)
Star Connected Bus Architecture
Station
level
Switches
Bay level
Switches
Communication
of IEDs failed Failed

• Simple Connections & Configurations


• Not Protected against single point failure

22
4/26/2016

IEC61850 S/S: Network Topology


(Digital Substation)
Redundant Star Connected Bus Architecture

Communication
through LAN-
LAN-B Failed

IEDn1 IEDn2 IEDn3 IEDn4 IEDn5 IEDn6

• Entire network is duplicated


• Increase complexity & cost of substation
• Each devices have two IP addresses & two application
instances

IEC61850 S/S: Network Topology


(Digital Substation)

Ring Connected Bus Architecture

PATH 1 PATH 2
Fault

IED IED IED IED IED IED IED IED IED IED
IED IED IED IED IED
IED IED IED IED IED

• N+1 Fault Tolerant Ring Architecture

23
4/26/2016

IEC61850 S/S: Network Topology


(Digital Substation)

Double Ring Connected Bus Architecture

Duplicate ring

IED3 IED4 IED5


IED1 IED2

IEC61850 Standard Contents……:


Part 4/5

Performance Class P1: Total Transmission Time shall be


around 10ms

Performance Class P2/3: Total Transmission Time shall be


around 3ms

24
4/26/2016

IEC61850 Standard Contents……:


Part 4/5

Transmission Time of Point to Point = GOOSE encoding at


sender + Network delay + GOOSE decoding at receiver

• Network delay is 100microS at 100Mbps link speed &


10microS at 1Gbps speed

Digital S/S: Conventional S/S

• Complex wiring of Conventional S/S


• Less Reliability of Conventional S/S
• Required Periodic maintenance for
Conventional S/S
• Required More space and money for
installation of Conventional S/S
• More Commissioning Time for Conventional
S/S
• More Troubleshooting Time for Conventional
S/S
• Require more Manpower for Operations of
Conventional S/S
• Operators & Experienced Technicians can
able to operate Conventional S/S

25
4/26/2016

Digital S/S: Conventional S/S


• Instrument transformer maintenance not
require in case of Fiber optic CT/VT used
• Avoided Current transformer saturation
due to DC offset in case of Fiber optic CT
used

Digital S/S: Key Points

• Digital S/S have following;


 Easy to use

 Easy to configure

 Good cyber security

 High availability

 Better visualization

 Flexible Alarm system

 Easy to use report generation

 Availability of Historical data

 Accurate time synchronization for process bus

 Ensure the availability of time sychronization

 Merging unit performance shall not be affect by external


ethernet trafic

 Merging unit shall have good performance under EMI/EMC


conditions and shall have self diagnostics feature of failure

26
4/26/2016

Digital S/S: Key Standards

IEC61850
IEEE C37.92 Low energy analogue
IEC 61869-
61869-9 Digital Interface for CT/VT
IEC 61869-
61869-13 Standardization of MU
IEC 60044-
60044-7 Electronic VT
IEC 60044-
60044-8 Electronic CT
PC 37.235 Rogowski Coil Guide
PSRC WG I8 Optical CT/PT Guide
IEC TC38WG37L. Kojovic (US), F. Rahmatian (CA)
C37.1 SCADA
C37.111 COMTRADE
C37.118-
C37.118-1/2 Synchrophasor system