Product GEMINI™

38AKS028-044
Data 38AH024-034
With 40RM016-034
Commercial Air-Cooled
Split Systems
50 Hz
63 to 127 kW (18 to 35.8 Nominal Tons)

These dependable split systems


match Carrier’s indoor-air handlers
with outdoor condensing units for a
wide selection of commercial cooling
solutions.

Features/Benefits
Building owners will appreciate the
high unit EERs (Energy Efficiency
Ratios) offered by the 38AKS and
38AH units. These units provide
greater efficiency than similar units in
the marketplace, which translates into
year-round operating savings. Latest
safety standards for 38AKS and 38AH
units are assured through UL and UL,
38AKS,38AH Canada approvals.
Constructed for long life
The 38AKS and 38AH units are
designed and built to last. Cabinets are
constructed of pre-painted galvanized
steel, delivering unparalleled protection
against the environment. Inside and
outside surfaces are protected to
ensure long life, good looks and reli-
able performance. The copper tube-
aluminum fin outdoor coil construc-
tion provides long term reliability and
improved heat transfer. Where condi-
tions require them, copper fin coils are
available. For corrosive or coastal
environments an epoxy barrier is avail-
able to provide superior coil durability.
Reliability
The 38AKS and 38AH condensing
units offer the building owner compo-
nents and operating controls designed
for performance dependability. These
40RM016-034 condensing units feature the time
proven highly reliable 06D and 06E
compressors. Unloading capability for

Copyright 2004 Carrier Corporation Form 38A-C11PD


superior part load performance is a features, and easy installation. Its ver- High efficiency, precision-balanced
standard feature of these compressors. satility and state-of-the-art features fans minimize air turbulence, surging,
The compressor mounting system help to ensure that your split system and unbalanced operation, cutting
has vibration isolation to provide quiet provides economical performance operating expenses.
operation and reduce component now and in the future. The economizer accessory precisely
stress. Indoor-air quality (IAQ) controls the blend of outdoor air and
Each compressor is equipped with a features room air to achieve comfort levels.
crankcase heater to eliminate the oc- When the outside air enthalpy is
The unique combination of IAQ fea-
currence of liquid slugging at start-up. suitable, outside air dampers can fully
tures in the 40RM Series air handlers
The compressors also include an oil open to provide “free” cooling.
helps to make sure that only clean,
level sight glass for maintenance ease. fresh, conditioned air is delivered to Rugged dependability
The following safety features are the occupied space. 40RM units are made to last. The
included in each unit: Direct-expansion (DX) cooling coils die-formed galvanized steel panels
• Anti short cycling control prevent the build-up of humidity in the ensure structural integrity under all
• Low oil pressure safety room, even during part-load condi- operating conditions. Galvanized steel
• Low refrigerant pressure safety tions. The 40RM016-034 sizes feature fan housings are securely mounted to
• High refrigerant pressure safety dual-circuit coils. a die-formed galvanized steel deck.
• Calibrated circuit breakers Standard 2-in. (50.3 mm) disposable Mechanically bonded coil fins provide
filters remove dust and airborne parti- improved heat transfer. Rugged pillow-
38AH series block bearings are securely fastened to
cles from the occupied space.
38AH condensing units feature 2 com- the solid steel fan shaft with split collets
pressors and 2 refrigeration circuits. The pitched PVC drain pan can be
and clamp locking devices.
These units can be matched with a adjusted for a right-hand or left-hand
single air handler or two separate air connection to provide positive Coil flexibility
handlers. drainage and to prevent standing Model 40RM direct-expansion coils
condensate. have galvanized steel casings; inlet and
Standard units are designed for
constant volume control. A variable air The 40RM accessory economizer outlet connections are on the same
volume (VAV) control is available as a can provide ventilation air to improve end. The coils are designed for use
factory-installed option. The VAV units indoor-air quality. When used with with Refrigerant 22 and have 3/8-in.
feature electrically controlled compres- CO2 sensors, the economizer admits diameter copper tubes mechanically
sor unloading to precisely match unit fresh outdoor air to replace stale, recir- bonded to aluminum sine-wave fins.
capacity to building loads. The VAV culated indoor air. The coils include matched, factory-
equipped unit has a simple control installed TXVs with matching distribu-
Economy tor nozzles. Accessory hot water and
interface for connection to a VAV
The 40RM Series packaged air han- steam coils and electric heaters are
discharge air control system.
dlers have low initial costs, and they also available.
Ease of installation and service continue to save money by providing
These units are equipped with hinged reduced installation expense and Easier installation and service
control box access panels, control energy-efficient performance. The multipoise design and component
interface terminal boards, liquid line Quick installation is ensured by the layout help you to get the unit installed
shut off valves and compressor service multipoise design. Units can be in- and running quickly. The DX coils have
valves. stalled in either the horizontal or factory-installed TXVs with matching
vertical configuration without modifica- distributor nozzles. Units can be con-
Innovative Carrier 40RM tions. All units have drain-pan connec- verted from horizontal to vertical oper-
air-handling units — ideal tions on both sides, and pans can be ation by simply repositioning the unit.
matches for 38AKS and pitched for right-hand or left-hand Drain pan connections are duplicated
38AH condensing units operation with a simple adjustment. on both sides of the unit. The filters,
The 40RM Series has excellent fan Fan motors and contactors are motor drive, TXVs, and coil connec-
performance, efficient direct- prewired and thermostatic expansion tions are all easily accessed by remov-
expansion (DX) coils, a unique valves (TXVs) are factory-installed on ing a single side panel.
combination of indoor air quality all 40RM models.

2
Table of contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1,2
Model Number Nomenclature — 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Nomenclature — 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . 5
Model Number Nomenclature — 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . 6
Capacity Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical Data — 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8,9
Physical Data — 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10,11
Physical Data — 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12,13
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-16
Dimensions — 38AKS028, 034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Dimensions — 38AKS044 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Dimensions — 38AH024-034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Dimensions — 40RM016-024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Dimensions — 40RM028, 034 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22,23
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24-50
38AKS Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24,25
38AKS/40RM Combination Ratings . . . . . . . . . . . . . . . . . . . . . . . . .26-31
38AH Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32-35
38AH/40RM Combination Ratings . . . . . . . . . . . . . . . . . . . . . . . . . .36-43
40RM Unit Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44-50
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51-54
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55-58
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59-61
Typical Control Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . .62-65
Application Data — 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66,67
Application Data — 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68-70
Application Data — 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .71-73
Guide Specifications — 38AKS Units. . . . . . . . . . . . . . . . . . . . . . . . . . .74-76
Guide Specifications — 38AH Units . . . . . . . . . . . . . . . . . . . . . . . . . . .77-79
Guide Specifications — 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . .80-82

3
Model number nomenclature — 38AKS units
38AKS 028 –– – 9 0 3 ––

38AKS – Commercial Air-Cooled Not Used


Condensing Units (Semi-Hermetic)

Packaging
1 – Std. Domestic Packaging
Nominal Capacity – kW* (Tons†) 3 – Export Packaging - Top
028 – 82.8 (23.4) and Bottom Skid
034 – 94.5 (26.5)
044 – 127.0 (35.8)

Not Used Revision Number


0 – Original

Condenser Coil Fin Material


– – Aluminum (Standard)
C – Copper (Optional) Voltage Designation
K – Pre-Coated Aluminum (Optional) 3 – 346-3-50
E – E-Coated Al Fin/Cu Tubes (Optional) 8 – 230-3-50
F – E-Coated Cu Fin/Cu Tubes (Optional) 9 – 400-3-50

LEGEND
Al — Aluminum
Cu — Copper
*Gross capacity based on 36 C air temperature entering condenser and 8 C saturated suction temperature.
†Gross capacity based on 95 F air temperature entering condenser and 45 F saturated suction temperature.

Quality Assurance
Certified to ISO 9001:2000

4
Model number nomenclature — 38AH units
38AH 024 –– – 9 1 3 A A

38AH – Commercial Air-Cooled Compressors


Condensing Unit A – Standard Compressors – One Suction
Pressure-Actuated Unloader on Lead
Compressor
Nominal Capacity – kW (Tons) C – Variable Air Volume (VAV) Option –
024 – 63 (18) Includes 2 Electric Unloaders on Lead
028 – 73 (21) Compressor and Control Box
034 – 87 (25) Modifications

Not Used Fan Motors and Labels


A – Standard Condenser Fan Motors
and Labels
Condenser Coil Fin Material
– – Aluminum (Standard)
C – Copper (Optional) Packaging
K – Pre-Coated Aluminum (Optional) 1 – Standard Domestic Packaging –
E – E-Coated Al Fin/Cu Tubes (Optional) Bottom Skid
F – E-Coated Cu Fin/Cu Tubes (Optional) 3 – Export Packaging – Top and Bottom
Skid
Voltage Designation
3 – 346-3-50
8 – 230-3-50 Revision Number
9 – 400-3-50 1 – Current Revision

LEGEND
Al — Aluminum
Cu — Copper

Quality Assurance
Certified to ISO 9001:2000

5
Model number nomenclature — 40RM units
40RM – 016 –– B 9 0 3 GC

40RM – Commercial Packaged Factory-Installed Options


Air Handler GC – Unpainted, Standard Motor, and
Standard Drive
Cooling Coil HC – Unpainted, Standard Motor, and
– – Direct Expansion Medium-Static Drive (Not available
to sizes 016-028)
Nominal Capacity – kW (Tons) TC – Unpainted, Alternate Motor, and
016 – 52 (15) Medium-Static Drive (sizes 016-028)
024 – 70 (20) YC – Unpainted, Alternate Motor, and
028 – 87 (25) High-Static Drive*
034 – 105 (30) ED – Painted, Standard Motor, and
Standard Drive
Not Used FD – Painted, Standard Motor, and
Medium-Static Drive
Expansion Device (Not available for sizes 016-028)
B – Thermostatic Expansion Valve RD – Painted, Alternate Motor, and
H – High Capacity 4-Row Coil Medium-Static Drive
(sizes 016-028)
WD – Painted, Alternate Motor, and
Voltage Designation (V-Ph-Hz) High-Static Drive*
8 – 230-3-50
9 – 400-3-50

Revision Number Packaging


0 – Original Model 3 – Export Packaging

*YC and WD option codes for all 034 size units designate standard motor and high-static drive.

Quality Assurance
Certified to ISO 9001:2000

6
Capacity summary
AIR- AIR-HANDLING SYSTEM GROSS CAPACITY SYSTEM GROSS CAPACITY CONDENSING UNIT
CONDENSING HANDLING UNIT AIRFLOW (Standard 3-Row Coil) (High-Capacity 4-Row Coil) ONLY GROSS CAPACITY
UNIT
UNIT 40RM L/s Cfm kW* Btuh† kW* Btuh† kW** Btuh††
024 3800 8,000 75.6 256,000 83.8 285,800
028 028 4700 10,000 80.4 273,000 84.3 287,700 82.8 281,000
034 5650 12,000 84.6 288,000 88.7 302,800
38AKS
028 4700 10,000 88.2 298,000 89.9 306,800
034 94.5 320,000
034 5650 12,000 93.1 316,000 94.8 323,500
044 034 5650 12,000 113.8 385,000 111.8 381,600 127.0 429,000
016 2800 6,000 57.3 195,000 60.2 205,300
024 024 3800 8,000 62.5 214,000 64.7 220,600 63.0 216,000
028 4700 10,000 66.3 227,000 68.6 234,000
024 3800 8,000 68.9 236,000 72.1 246,100
38AH
028 028 4700 10,000 73.5 251,000 76.7 261,600 73.0 250,000
034 5650 12,000 77.6 265,000 80.5 274,500
028 4700 10,000 82.6 283,000 86.0 293,600
034 87.0 297,000
034 5650 12,000 87.7 300,000 90.9 310,000

LEGEND †System gross capacities are rated according to indoor unit airflow,
db — Dry Bulb 95 F air temperature entering condenser, and 67 F wb air tempera-
wb — Wet Bulb ture entering evaporator.
SST — Saturated Suction Temperature **Condensing unit gross capacity based on 36 C air temperature enter-
ing condenser and 8 C SST.
*System gross capacities are rated according to indoor unit airflow, ††Condensing unit gross capacity based on 95 F air temperature enter-
35 C air temperature entering condenser, and 20 C wb air tempera- ing condenser and 45 F SST.
ture entering evaporator.

ESTIMATED SOUND POWER LEVELS


50 Hz UNITS
ESTIMATED RADIATED SOUND POWER LEVELS, dB — 38AH024-034 AND 38AKS028-034

OCTAVE BAND CENTER FREQUENCY, Hz


UNIT dB(A)
63 125 250 500 1000 2000 4000 8000
38AH024 97.7 93.6 91.0 88.5 87.6 85.7 78.8 74.4 92.5
38AH028 97.7 93.6 91.1 88.6 87.9 85.6 78.5 74.5 92.6
38AH034 98.5 94.2 91.9 89.5 88.7 86.1 76.0 74.9 93.2
38AKS028 97.7 93.3 91.0 88.7 88.4 84.5 77.8 74.0 92.4
38AKS034 98.5 94.1 91.8 89.5 89.2 85.3 78.6 74.8 93.2
38AKS044 101.5 97.3 94.4 92.1 91.3 87.5 81.5 78.1 95.6
NOTES: 2. Since this data is estimated, the sound power levels should not be
1. Estimated sound power levels, dB re 1 Picowatt guaranteed or certified as being the actual sound power levels.
This data is based upon a limited amount of actual testing with the The acoustic center of the unit is located at the geometric center of
estimated sound power data being generated from this data in the unit.
accordance with ARI (Air Conditioning and Refrigeration Institute,
U.S.A. Standard) standard 370 for large outdoor refrigerating and
air conditioning equipment.

ESTIMATED SOUND POWER LEVELS (Lw) — 40RM016-034

OCTAVE BAND CENTER FREQUENCY, Hz


UNIT
Cfm dB(A) 63 125 250 500 1000 2000 4000
40RM016 6,000 92.7 98.9 94.9 90.9 91.9 85.9 83.9 79.9
40RM024 8,000 96.4 102.6 98.6 94.6 95.6 89.6 87.6 83.6
40RM028 10,000 96.2 102.5 98.5 94.5 95.5 89.5 87.5 83.5
40RM034 12,000 98.5 104.7 100.7 96.7 97.7 91.7 89.7 85.7
NOTE: Since this data is calculated, these sound power levels may be different than the actual sound power levels.
The acoustic center of the unit is located at the geometric center of the unit.

7
Physical data — 38AKS units
38AKS028-044 UNITS — SI
UNIT 38AKS 028 034 044
NOMINAL CAPACITY (kW)* 82.8 94.5 127.0
OPERATING WEIGHTS (kg)
With Aluminum-Fin Coils (Standard) 748 818 1106
With Copper-Fin Coils (Optional) 818 911 1246
REFRIGERANT R-22
Operating Charge, Typical (kg)† 13.8 19.7 29.5
COMPRESSOR Reciprocating, Semi-Hermetic
Qty...Model 1...06E9265 1...06E9275 1...06E9299
No. Cylinders (ea) 6 6 6
Speed (r/s) 24.2
Oil Charge (L) 9 9 9.5
Capacity Steps 100%, 66%, 33%
Unloader Settings (kPag)
No. 1 Load 524
Unload 400
No. 2 Load 538
Unload 414
Crankcase Heater Watts 180
CONDENSER FANS Propeller Type — Direct Drive
Qty...r/s 2...16 3...16
Diameter (mm) 762
Nominal kW 0.75
Nominal Airflow (L/s total) 7400 11,180
Watts (Total) 1490 1750 1520
CONDENSER COIL Enhanced Copper Tubes, Lanced Aluminum Fins
Rows...Fins/m 2...748 3...670 3...670
Face Area (sq m) 3.6 3.6 5.4
Storage Capacity (kg)** 17 26 38
CONTROLS
Pressurestat (kPag)
High-Pressure Switch
Cutout 2940 ± 50
Cut-in 2200 ± 40
Low-Pressure Switch
Cutout 185 ± 20
Cut-in 300 ± 35
Oil Pressure Switch
Cutout 43
Cut-in 62
FAN CYCLING CONTROLS
Operating Pressure (kPag)
No. 2 Fan, Close 1760 ± 70
Open 1100 ± 70
PRESSURE RELIEF Fusible Plug
Location Liquid and Suction Line
Temperature (C) 100
PIPING CONNECTIONS (in. ODM)
Suction 15 / 8 21 / 8 21 / 8
Liquid 7/
8
Hot Gas Stub 5/
8

*Based on operation at 8 C saturated suction temperature and 36 C outdoor ambient temperature.


†Typical operating charge with 7.6 m of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at 51.7 C.

8
38AKS028-044 UNITS — ENGLISH
UNIT 38AKS 028 034 044
NOMINAL CAPACITY (tons)* 23.4 26.5 35.8
OPERATING WEIGHTS (lb)
With Aluminum-Fin Coils (Standard) 1650 1803 2437
With Copper-Fin Coils (Optional) 1804 2009 2745
REFRIGERANT R-22
Operating Charge, Typical (lb)† 30.5 43.5 65.0
COMPRESSOR Reciprocating, Semi-Hermetic
Qty...Model 1...06E9265 1...06E9275 1...06E9299
No. Cylinders (ea) 6 6 6
Speed (rpm) 1450
Oil Charge (pt) 20.0 20.0 19.0
Capacity Steps 100%, 66%, 33%
Unloader Setting (psig)
No. 1 Load 76
Unload 58
No. 2 Load 78
Unload 60
Crankcase Heater Watts 180
CONDENSER FANS Propeller Type — Direct Drive
Qty...Speed (Rpm) 2...950 3...950
Diameter (in.) 30
Nominal Hp 1.0
Nominal Airflow (cfm total) 15,700 23,700
Watts (Total) 1490 1750 1520
CONDENSER COIL Enhanced Copper Tubes, Lanced Aluminum Fins
Rows...Fins/in. 2...19 3...17 3...17
Face Area (sq ft) 39.2 39.2 58.4
Storage Capacity (lb)** 37.7 56.6 84.4
CONTROLS
Pressurestat (psig)
High-Pressure Switch
Cutout 426 ± 7
Cut-in 320 ± 20
Low-Pressure Switch
Cutout 27 ± 3
Cut-in 44 ± 5
Oil Pressure Switch
Cutout 6.2
Cut-in 9.0
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close 255 ± 10
Open 160 ± 10
PRESSURE RELIEF Fusible Plug
Location Liquid and Suction Line
Temperature (F) 210
PIPING CONNECTIONS (in. ODM)
Suction 15 / 8 21 / 8 21 / 8
Liquid 7/8
Hot Gas Stub 5/
8

*Based on operation at 45 F saturated suction temperature and 95 F outdoor ambient.


†Typical operating charge with 25 ft of interconnecting piping.
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at 125 F.

9
Physical data — 38AH units
38AH024-034 UNITS — SI
024 028 034
UNIT 38AH
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2
NOMINAL CAPACITY (kW) 63 73 87
OPERATING WEIGHT (kg)
With Aluminum-Fin Coil (Standard) 798.3 825.6 853.0
With Copper-Fin Coil (Optional) 872.3 899.0 951.2
REFRIGERANT R-22
Operating Charge, Typical (kg)** 9.10 9.10 9.10 9.10 11.40 11.40
Shipping Charge (kg) 1.36 1.36 1.36 1.36 1.36 1.36
COMPRESSOR Reciprocating Semi-Hermetic
Qty...Model 1...06DH824 1...06DA824 1...06DH328 1...06DA328 1...06DH328 1...06DA537
No. Cylinders 6 6 6 6 6 6
Speed (r/s) 24.3 24.3 24.3 24.3 24.3 24.3
Oil Charge per Circuit (L) 4.73
Capacity Steps (%)
(FIOP or Acy) 100 100 100 100 100 100
Standard 67* — 67* — 67* —
VAV FIOP 33† — 33† — 33† —
Unloader Setting (kPa) Factory Installed
Load 524 — 524 — 524 —
Unload 400 — 400 — 400 —
CONDENSER FANS Propeller Type — Direct Driven
Qty...Speed (r/s) 2...16
Diameter (mm) 762 762 762
Nominal Hp 1.0 1.0 1.0
Nominal Airflow (L/s) 7870 7870 7400
Watts (total) 3100
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins/m 2...748 2...748 3...670
Total Face Area (sq m) 3.64 3.64 3.64
Storage Capacity (kg)†† 17.4 17.4 26.0
CONTROLS
Pressurestat (kPa)
High Pressure
Cutout 2940 ± 50
Cut-in 2200 ± 140
Low Pressure
Cutout 185 ± 20
Cut-in 300 ± 35
Oil Pressure Manual Reset
Cutout 42
Cut-in 62
FAN CYCLING CONTROLS
Temperature (C)
No. 2 Fan, Close 21.1 ± 1.6
Open 15.6 ± 1.6
PRESSURE RELIEF Fusible Plug
Location Liquid Line, Suction Line, Compressor
Temperature (C) 100
CONNECTIONS (in. ODM)
Suction 13/8
Liquid 5/ 8

LEGEND *Standard unit — single pressure-actuated suction unloader on com-


FIOP — Factory-Installed Option pressor no. 1.
VAV — Variable Air Volume †VAV FIOP — double electrically actuated unloaders on compressor
no. 1.
**Typical operating charge with 7.6 m of interconnecting piping.
††Storage capacity of condenser coil with coil 80% full of liquid R-22 at
48.8 C.

10
38AH024-034 UNITS — ENGLISH
024 028 034
UNIT 38AH
Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2
NOMINAL CAPACITY (Tons) 18 21 25
OPERATING WEIGHT (lb)
With Aluminum-Fin Coil (Standard) 1760 1820 1880
With Copper-Fin Coil (Optional) 1923 1982 2097
REFRIGERANT R-22
Operating Charge, Typical (lb)** 20 20 20 20 25 25
Shipping Charge (lb) 3 3 3 3 3 3
COMPRESSOR Reciprocating Semi-Hermetic
Qty...Model 1...06DH824 1...06DA824 1...06DH328 1...06DA328 1...06DH328 1...06DA537
No. Cylinders 6 6 6 6 6 6
Speed (rpm) 1450 1450 1450 1450 1450 1450
Oil Charge per Circuit (Pt) 10
Capacity Steps (%)
(FIOP or Acy) 100 100 100 100 100 100
Standard Unit 67* — 67* — 67* —
VAV FIOP 33† — 33† — 33† —
Unloader Setting (psig) Factory Installed
Load 76 — 76 — 76 —
Unload 58 — 58 — 58 —
CONDENSER FANS Propeller Type — Direct Driven
Qty...Speed (rpm) 2...950
Diameter (in.) 30 30 30
Nominal Hp 1.0 1.0 1.0
Nominal Airflow (cfm) 16,700 16,700 15,700
Watts (total) 3100
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fin
Rows...Fins/in. 2...19 2...19 3...17
Face Area (sq ft) 39.20 39.20 39.20
Storage Capacity (lb)†† 37.7 37.7 56.6
CONTROLS
Pressurestat (psig)
High Pressure
Cutout 426 ± 7
Cut-in 320 ± 20
Low Pressure
Cutout 27 ± 3
Cut-in 44 ± 5
Oil Pressure Manual Reset
Cutout 6.0
Cut-in 8.8
FAN CYCLING CONTROLS
Temperature (F)
No. 2 Fan, Close 70 ± 3
Open 60 ± 3
PRESSURE RELIEF Fusible Plug
Location Liquid Line, Suction Line, Compressor
Temperature (F) 210
CONNECTIONS (in. ODM)
Suction 13/8
Liquid 5/ 8

LEGEND *Standard unit — single pressure-actuated suction unloader on com-


FIOP — Factory-Installed Option pressor no. 1.
VAV — Variable Air Volume †VAV FIOP — double electrically actuated unloaders on compressor
no. 1.
**Typical operating charge with 25 ft of interconnecting piping.
††Storage capacity of condenser coil with coil 80% full of liquid R-22 at
120 F.

11
Physical data — 40RM units
40RM UNITS — SI
UNIT 40RM 016 024 028 034
NOMINAL CAPACITY (kW) 52 70 87 105
OPERATING WEIGHT (kg)
Base Unit with TXV (3 Row/4 Row) 311/323 313/331 463/470 467/482
Plenum 102 102 148 148
FANS
Qty...Diam. (mm) 2...381 2...381 2...457 2...457
Nominal Airflow (L/s) 2831 3775 4719 5663
Airflow Range (L/s) 2124-3539 2831-4719 3539-5899 4247-7079
Nominal Motor kW (Standard Motor)*
230-3-50, 400-3-50 2.16 3.73 5.59 7.46
Motor Speed (r/s)
230-3-50, 400-3-50 23.8 23.8 23.8 23.8
REFRIGERANT R-22
Operating charge (kg)
(approx per circuit)† 1.13/1.13 1.59/1.59 2.04/2.04 2.27/2.27
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (kPag) 2999
Face Area (sq m) 1.64 1.85 2.30 2.77
No. of Splits 2 2 2 2
No. of Circuits per Split (3 Row/4 Row) 12/16 13/18 15/20 18/24
Split Type...Percentage Face...50/50
Fins/m 591 670 591 591
STEAM COIL
Max Working Pressure (kPag at 204.4 C) 1207
Total Face Area (sq m) 1.24 1.24 1.39 1.39
Rows...Fins/m 1...394 1...394 1...394 1...394
HOT WATER COIL
Max Working Pressure (kPag) 1034
Total Face Area (sq m) 1.24 1.24 1.39 1.39
Rows...Fins/m 2...335 2...335 2...493 2...493
Water Volume
(L) 52.6 54.1
(m3) 0.052 0.054
PIPING CONNECTIONS,
Qty...Size (in.)
DX Coil — Suction (ODF) 2...11/8 2...11/8 2...13/8 2...13/8
DX Coil — Liquid Refrigerant (ODF) 2...5/8
Steam Coil, In (MPT) 1...21/2
Steam Coil, Out (MPT) 1...11/2
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1...11/4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
Qty...Size 4...406 × 508 × 51 4...508 x 610 x 51
4...406 × 610 × 51 4...508 x 635 x 51
Access Location Right or Left Side
LEGEND *Refer to Alternate Fan Motor Data table on page 71 for alternate motor
DX — Direct Expansion data.
TXV — Thermostatic Expansion Valve †Units are shipped without refrigerant charge.

12
40RM UNITS — ENGLISH
UNIT 40RM 016 024 028 034
NOMINAL CAPACITY (Tons) 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit with TXV (3 Row/4 Row) 685/713 690/730 1020/1050 1030/1062
Plenum 225 225 325 325
FANS
Qty...Diam. (in.) 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 6000 8000 10,000 12,000
Airflow Range (cfm) 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nominal Motor kW (Standard Motor)*
230-3-50, 400-3-50 2.9 5.0 7.5 10.0
Motor Speed (rpm)
230-3-50, 400-3-50 1425
REFRIGERANT R-22
Operating Charge (lb)
(approx per circuit)† 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 17.67 19.88 24.86 29.83
No. of Splits 2 2 2 2
Split Type...Percentage Face...50/50
No. of Circuits per Split (3 Row/4 Row) 12/16 13/18 15/20 18/24
Fins/in. 15 17 15 15
STEAM COIL
Max Working Pressure (psig at 400 F) 175
Total Face Area (sq ft) 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...12.5 2...12.5
Water Volume
(gal) 13.9 14.3
(ft3) 1.85 1.90
PIPING CONNECTIONS,
Qty...Size (in.)
DX Coil — Suction (ODF) 2...11/8 2...11/8 2...13/8 2...13/8
DX Coil — Liquid Refrigerant (ODF) 2...5/8
Steam Coil, In (MPT) 1...21/2
Steam Coil, Out (MPT) 1...11/2
Hot Water Coil, In (MPT) 1...2
Hot Water Coil, Out (MPT) 1...2
Condensate (PVC) 1
1...1 /4 ODM/1 IDF
FILTERS Throwaway — Factory Supplied
4...16 × 20 × 2 4...20 × 24 × 2
Qty...Size (in.) 4...16 × 24 × 2 4...20 × 25 × 2
Access Location Right or Left Side
LEGEND *Refer to Alternate Fan Motor Data table on page 71 for alternate motor
DX — Direct Expansion data.
TXV — Thermostatic Expansion Valve †Units are shipped without refrigerant charge.

13
Options and accessories
38AKS, 38AH factory-installed options Gage panel package provides a suction and a discharge
Enviro-Shield™ condenser options are available to pressure gage for the refrigerant circuit.
match coil protection to site conditions for optimum dura- ModuPanel™ control box allows systems to operate as
bility. See table below and refer to the Application Data for VAV (variable air volume) systems. Includes microproces-
selection guidance. Consult your Carrier representative for sor, satellite sequencer, 4 status lights, 5-hour bypass timer,
further information. and locked enclosure.
VAV option (38AH only) provides unit with 2 electric Hot-gas bypass kit (38AKS only) prevents the indoor
unloaders and control box modifications necessary to con- coil from freezing up during low airflow or low return-air
nect to a field-installed VAV controller. temperature applications by maintaining minimum suction
pressure.
38AKS, 38AH field-installed accessories
Carrier’s line of thermostats provide both programma-
Electric unloader package includes hardware and
ble and non-programmable capability with the new
solenoid valve to convert a pressure-operated unloader to Debonair® line of commercial programmable thermostats,
electric unloading.
the Commercial Electronic thermostats provide 7-day
Pressure-operated unloading (38AH only) allows programmable capability for economical applications.
compressor to be unloaded in response to compressor suc-
PremierLink™ controller is a field retrofit split system
tion pressure. control compatible with the Carrier Comfort Network
–20 F (–29 C) low-ambient temperature kit (Motor- (CCN) and other building automation systems (BAS). This
master®) controls outdoor-fan motor operation to main- control is designed to allow users the access and ability to
tain the correct head pressure at low outdoor ambient change factory-defined settings thus expanding the func-
temperatures. Only one low ambient temperature kit is tion of the standard unit.
required per unit.

CONDENSER COIL OPTIONS

COPPER-TUBE COILS ENVIRONMENT


WITH ENVIRO-SHIELD Mild Moderate Severe Combined
OPTION* Standard Industrial
Coastal Coastal Coastal Industrial/Coastal
Al Fins (Standard Coils) X
Cu Fins X
Al Fins, E-Coating X
Cu Fins, E-Coating X X
Al Fins, Pre-coated X
LEGEND *See “Selection Guide: Environmental Corrosion Protection” Catalog
Al — Aluminum No. 811-287 for more information.
Cu — Copper
Enviro-Shield — Family of Coil Protection Options
E-Coated — Epoxy coating Applied to Entire Coil Assembly
Pre-Coated — Epoxy coating Applied to Fin Stock Material

14
40RM factory-installed options Return-air grille provides a protective barrier over the
Prepainted steel units are available from the factory for return-air opening and gives a finished appearance to units
applications that require painted units. Units are con- installed in the occupied space. Accessory is available
structed of pre-painted steel panels in American Sterling unpainted or painted.
Gray color. Subbase provides a stable, raised platform and room for
High-capacity 4-row coils are available to provide condensate drain connection for floor-mounted units.
increased latent/sensible capacities and efficiencies. Accessory is available unpainted or painted.
Alternate fan motors and drives are available to pro- Overhead suspension package includes necessary
vide the widest possible range of performance. brackets to support units in horizontal ceiling installations.
CO2 sensors can be used in conjunction with the econo-
40RM field-installed accessories mizer accessory to help meet indoor air quality require-
Discharge plenum directs the air discharge directly into ments. The sensor signals the economizer to open when
the occupied space; integral horizontal and vertical louvers the CO2 level in the space exceeds the set point. A Carrier
enable redirection of airflow. Accessory is available Comfort System programmable thermostat can also be
unpainted or painted. used to override the sensor if the outside air temperature is
Two-row hot water coils have 5/8-in. (15.875 mm) too high or too low.
diameter copper tubes mechanically bonded to aluminum Condensate drain trap includes an overflow shutoff
plate fins. Coils have non-ferrous headers. switch that can be wired to turn off the unit if the trap
One-row steam coil has 1-in. (25.44 mm) OD copper becomes plugged. The kit also includes a wire harness that
tube and aluminum fins. The Inner Distributing Tube (IDT) can be connected to an alarm if desired. The transparent
design provides uniform temperatures across the coil face. trap is designed for easy service and maintenance.
The steam coil has a broad operating pressure range; up to UV-C germicidal lamps kill mold and fungus, which may
20 psig at 260 F (138 kpag at 126 C). The IDT steam coils grow on evaporator coil and condensate pan surfaces. The
are especially suited to applications where sub-freezing air use of UV-C germicidal lamps eliminates the foul odors
enters the unit. that result from this growth of mold and fungus. It also pro-
Electric resistance heat coils have an open-wire design vides a self-cleaning function for the evaporator coil and
and are mounted in a rigid frame. Safety cutouts for high drain pan.
temperature conditions are standard.
Economizer (enthalpy controlled) provides ventilation
air and “free” cooling if outside ambient temperature and
humidity are suitable. It can also be used with CO2 sensors
to help meet indoor air quality requirements.

15
Options and accessories (cont)
40RM WITH DISCHARGE PLENUM, 40RM WITH HOT WATER OR STEAM COIL
RETURN GRILLE, AND SUBBASE
HOT WATER OR
STEAM COIL

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE
FAN
COIL
UNIT
FAN COIL
UNIT

40RM WITH ECONOMIZER 40RM WITH CONDENSATE DRAIN TRAP


AND UV-C GERMICIDAL LAMPS

ECONOMIZER

UV-C GERMICIDAL LAMPS

16
Dimensions — 38AKS028,034

NOTES:
1. There must be 4 ft [1220 mm] for service and for unre-
stricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT WEIGHT WEIGHT
38AKS (lb) (kg)
028 1650 748
028C 1804 818
034 1803 818
034C 2009 911
NOTE: A “C” in model number indicates unit has optional
factory-installed copper-fin coil.
4. Dimensions in [ ] are millimeters.
APPROXIMATE OPERATING WEIGHT*
AT SUPPORT POINTS — LB (KG)*
UNIT
1 2 3 4 TOTAL
38AKS
028 418 626 242 364 1650
(189.6) (284.0) (109.8) (165.1) (748.4)
459 673 272 399 1803
034 (208.2) (305.3) (123.4) (181.0) (817.8)
*Standard copper tube aluminum-fin coil.

17
Dimensions — 38AKS044

NOTES:
1. There must be 4 ft [1220 mm] for service and for unre-
stricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space
above unit.
3. The approximate operating weight of the unit is:
UNIT WEIGHT WEIGHT
38AKS (lb) (kg)
044 2437 1106
044C 2745 1246
NOTE: A “C” in model number indicates unit has
optional factory-installed copper-fin coil.

APPROXIMATE OPERATING WEIGHT*


AT LIFTING HOLES — LB (KG)*
UNIT
1 2 3 4 TOTAL
38AKS
720 900 455 362 2437
044
(327) (409) (207) (165) (1106)
*Standard copper tube aluminum-fin coil.

18
Dimensions — 38AH024-034

NOTES:
1. There must be 4 ft [1220 mm] for service and for unrestricted airflow on all
sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air space above unit.
3. ‘‘C’’ in the package number indicates copper coils.
4. Dimensions in [ ] are in millimeters.
5. The approximate operating weight of the unit is shown below.
6. Certified dimensional drawing is available on request.

CENTER OF
CORNER WEIGHT — lb [kg] GRAVITY
UNIT TOTAL
38AH UNIT WT
A Dim. B Dim. lb [kg]
‘‘1’’ ‘‘2’’ ‘‘3’’ ‘‘4’’ in. in.
[mm] [mm]
024 631.6 577.6 263.1 287.7 40.00 1760
[286.5] [262.0] [119.3] [130.5] [1016] [798.3]
024C 666.5 609.5 309.0 337.9 43.00 1923
[302.3] [276.5] [140.2] [153.3] [1092] [872.3]
028 658.7 602.4 267.0 291.9 39.25 1820
[298.8] [273.3] [121.1] [132.4] [997] 32.75 [825.6]
693.0 633.8 313.0 342.2 42.25 [832] 1982
028C
[314.3] [287.5] [142.0] [155.2] [1073] [899.0]
034 667.0 610.0 288.0 315.0 41.00 1880
[302.5] [276.7] [130.7] [142.9] [1041] [853.0]
034C 718.3 656.8 344.8 377.0 44.00 2097
[325.8] [297.9] [156.4] [171.0] [1117] [951.2]

19
Dimensions — 40RM016-024

TXV — Thermostatic Expansion Valve


NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 76 mm (3 in.)
• Front: 762 mm (2 ft, 6 in.)
• Right side: 762 mm (2 ft, 6 in.)
• Left side: 762 mm (2 ft, 6 in.)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT WEIGHT
UNIT 40RM
lb (kg)
3-Row 016 685 (311)
Coil 024 690 (313)
4-Row 016 713 (323)
Coil 024 730 (331)

20
Dimensions — 40RM028,034

CONTROL BOX

CONTROL BOX
TXV — Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
• Rear: 76 mm (3 in.)
• Front: 762 mm (2 ft, 6 in.)
• Right side: 762 mm (2 ft, 6 in.)
• Left side: 762 mm (2 ft, 6 in.)
• Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT WEIGHT
UNIT 40RM
lb (kg)
3-Row 028 1020 (463)
Coil 034 1030 (467)
4-Row 028 1050 (470)
Coil 034 1062 (482)

21
Selection procedure
38AH024-034/40RM — SI III Determine sizes of liquid and suction lines.
NOTE: This book contains combination ratings for Enter the Refrigerant Pipe Sizes table. The sizes
38AH024-034 units and matching 40RM air handlers. If shown are based on an equivalent length of pipe.
the 38AH units are matched with 39 Series air handlers, This equivalent length is equal to the linear length of
use the Carrier AHU (Air-Handling Unit) selection program pipe indicated at the top of each sizing column, plus
software package for combination ratings. If Totaline® a 50% allowance for fitting losses. (For a more accu-
P702 water coolers are used, determine the performance rate determination of actual equivalent length in
by cross-plotting the condensing unit performance found place of using the estimated 50% value, refer to
in this book against the P702 performance in the P702 Carrier System Design Manual.) For this example,
product data book. If the 38AH condensing units are note in the linear length column that the proper
matched with 2 independent 40RM units, cross-plot for pipe size is 5/8 in. for the liquid lines and 13/8 in.
performance ratings or contact Carrier Application Engi- for the suction lines.
neering for assistance. IV Determine fan rpm and bhp (brake
I Determine cooling load, evaporator-air tem- horsepower).
perature and quantity. At the Air Handler Fan Performance table, enter
Given: the 40RM024 section at 3800 L/s and move to the
Total Cooling Capacity External Static Pressure (ESP) column. Note that the
Required (TC) . . . . . . . . . . . . . . . . . . . . . . 60 kW conditions require 13.71 r/s at 2.81 kW.
Sensible Heat Capacity V Determine motor and drive.
Required (SHC) . . . . . . . . . . . . . . . . . . . 48 kW Enter the Fan Motor Data tables and find that the
Temperature Air Entering standard motor shaft (kW) for a 40RM024 unit
Condenser (Edb) . . . . . . . . . . . . . . . . . . . 36 C is rated at 3.73. Since the kW required is 2.81, a
Temperature Air Entering standard motor satisfies the requirement and should
Evaporator (db/wb) . . . . . . 26.7 C db, 20 C wb be used.
Evaporator Air Quantity. . . . . . . . . . . . . 3800 L/s
External Static Pressure . . . . . . . . . . . . .150 Pa Next, find the type of drive that satisfies the
13.71 r/s requirement in the Drive Data tables. For a
Length of Interconnecting
40RM024 unit, the Standard Drive table shows an
Refrigerant Piping . . . . . . . . . . . . 18 m (Linear)
r/s range of 11.9 to 14.6. Since the r/s required is
II Select condensing unit air-handler combination. 13.71, the standard drive satisfies the requirement
For this example, select a 38AH024 matched with and should be used. Select the standard motor and
a 40RM024. This 38AH024/40RM024 condens- standard drive combination (option code GC or ED).
ing unit-air handler combination provides 62.5 kW
of total cooling capacity and 49.2 kW of sensible
capacity at the given conditions. If other tempera-
tures or airflow values are required, interpolate the
values from the combination ratings.

22
38AH024-034/40RM — English III Determine sizes of liquid and suction lines.
NOTE: This book contains combination ratings for Enter the Refrigerant Pipe Sizes table. The sizes
38AH024-034 units and matching 40RM air handlers. If shown are based on an equivalent length of pipe.
the 38AH units are matched with 39 Series air handlers, This equivalent length is equal to the linear length of
use the Carrier AHU (Air-Handling Unit) selection program pipe indicated at the top of each sizing column, plus
software package for combination ratings. If Totaline® a 50% allowance for fitting losses. (For a more accu-
P702 water coolers are used, determine the performance rate determination of actual equivalent length in
by cross-plotting the condensing unit performance found place of using the estimated 50% value, refer to
in this book against the P702 performance in the P702 Carrier System Design Manual.) For this example,
product data book. If the 38AH condensing units are note in the linear length column that the proper
matched with 2 independent 40RM units, cross-plot for pipe size is 5/8 in. for the liquid lines and 13/8 in.
performance ratings or contact Carrier Application Engi- for the suction lines.
neering for assistance. IV Determine fan rpm and bhp (brake
I Determine cooling load, evaporator-air tem- horsepower).
perature and quantity. At the Air Handler Fan Performance table, enter
Given: the 40RM024 section at 8000 cfm and move to the
Total Cooling Capacity External Static Pressure (ESP) column. Note that the
Required (TC) . . . . . . . . . . . . . . . . 210,000 Btuh conditions require 930 rpm at 4.7 bhp.
Sensible Heat Capacity V Determine motor and drive.
Required (SHC) . . . . . . . . . . . . . .175,000 Btuh Enter the Fan Motor Data tables and find that the
Temperature Air Entering alternate motor hp for a 40RM024 unit is rated at
Condenser (Edb) . . . . . . . . . . . . . . . . . . . .95 F 7.5 hp. Since the bhp required is 4.7, an alternate
Temperature Air Entering motor satisfies the requirement and should be used.
Evaporator (db/wb) . . . . . . . . 80 F db, 67 F wb
Next, find the type of drive that satisfies the 930 rpm
Evaporator Air Quantity. . . . . . . . . . . . . 8000 cfm
External Static Pressure . . . . . . . . . . . 1.0 in wg requirement in the Drive Data tables. For a
40RM024 unit, the Medium-Static Drive table shows
Length of Interconnecting
an rpm range of 814 to 1018. Since the rpm
Refrigerant Piping . . . . . . . . . . . . .30 ft (Linear)
required is 930, the medium-static drive satisfies the
II Select condensing unit air-handler combination. requirement and should be used. Select the alternate
For this example, select a 38AH024 matched with a motor and medium-static drive combination (option
40RM024. This 38AH024/40RM024 condensing code TC or RD).
unit-air handler combination provides 214,500 Btuh
of total cooling capacity and 179,000 Btuh of sensible
capacity at the given conditions. If other temperatures
or airflow values are required, interpolate the values
from the combination ratings.

23
Performance data
38AKS CONDENSING UNIT RATINGS — SI

38AKS028 38AKS044
SST Air Temperature Entering Condenser (C) SST Air Temperature Entering Condenser (C)
(C) 28 32 36 40 44 48 52 (C) 28 32 36 40 44 48 52
TC 55.3 52.4 49.5 46.6 43.8 41.0 38.3 TC 82.8 78.8 74.8 70.9 67.1 63.3 59.5
–6 kW 17.4 18.0 18.6 19.1 19.6 20.0 20.4 –6 kW 27.3 28.1 29.0 29.7 30.4 31.0 31.5
SDT 41.2 44.8 48.5 52.1 55.8 59.6 63.3 SDT 41.4 45.3 49.3 53.3 57.3 61.3 65.3
TC 60.4 57.3 54.2 51.1 48.1 45.2 42.3 TC 90.9 86.5 82.3 78.0 73.9 69.8 65.7
–4 kW 18.2 18.9 19.5 20.1 20.6 21.1 21.5 –4 kW 28.3 29.3 30.3 31.1 31.9 32.6 33.2
SDT 42.1 45.7 49.3 52.9 56.5 60.2 63.8 SDT 41.3 45.3 49.3 53.3 57.3 61.3 65.3
TC 64.4 61.1 57.8 54.7 51.5 48.5 45.4 TC 97.3 92.7 88.2 83.7 79.4 75.0 70.7
–2 kW 18.8 19.5 20.3 20.9 21.5 22.0 22.4 –2 kW 29.0 30.1 31.2 32.2 33.0 33.8 34.5
SDT 42.9 46.4 50.0 53.6 57.1 60.7 64.4 SDT 41.4 45.3 49.3 53.3 57.3 61.3 65.3
TC 69.9 66.4 62.9 59.6 56.3 53.0 49.7 TC 106.0 101.0 96.5 91.7 87.1 82.4 77.8
0 kW 19.6 20.4 21.2 21.9 22.6 23.1 23.7 0 kW 30.0 31.2 32.4 33.5 34.5 35.4 36.2
SDT 43.9 47.4 50.9 54.5 58.0 61.6 65.1 SDT 41.8 45.6 49.4 53.4 57.3 61.3 65.3
TC 75.6 71.9 68.3 64.7 61.2 57.7 54.3 TC 115.0 110.0 105.0 99.9 95.1 90.2 85.3
2 kW 20.5 21.3 22.2 23.0 23.7 24.3 24.9 2 kW 31.2 32.5 33.7 34.9 36.0 37.0 37.9
SDT 45.0 48.5 52.0 55.4 59.0 62.5 66.0 SDT 42.5 46.2 50.0 53.7 57.5 61.4 65.4
TC 80.2 76.3 72.5 68.7 65.0 61.4 57.8 TC 121.0 116.0 111.0 106.0 101.0 96.1 91.1
4 kW 21.1 22.0 22.9 23.8 24.5 25.2 25.9 4 kW 32.1 33.5 34.8 36.0 37.2 38.2 39.2
SDT 45.9 49.3 52.8 56.2 59.7 63.2 66.7 SDT 43.2 46.9 50.5 54.2 58.0 61.7 65.5
TC 86.4 82.3 78.3 74.3 70.3 66.5 62.7 TC 130.0 125.0 120.0 114.0 109.0 104.0 98.8
6 kW 22.0 23.0 23.9 24.8 25.7 26.5 27.2 6 kW 33.3 34.8 36.2 37.6 38.8 40.0 41.1
SDT 47.1 50.5 53.9 57.3 60.8 64.2 67.7 SDT 44.2 47.8 51.5 55.1 58.7 62.4 66.1
TC 91.2 87.0 82.8 78.6 74.5 70.5 66.5 TC 138.0 132.0 127.0 121.0 116.0 110.0 105.0
8 kW 22.6 23.7 24.7 25.7 26.6 27.4 28.2 8 kW 34.2 35.8 37.3 38.8 40.1 41.3 42.5
SDT 48.0 51.4 54.8 58.2 61.6 65.0 68.4 SDT 45.0 48.6 52.2 55.8 59.4 63.0 66.7
TC 97.9 93.5 89.0 84.6 80.3 76.0 71.7 TC 148.0 142.0 136.0 130.0 124.0 118.0 113.0
10 kW 23.5 24.6 25.7 26.8 27.8 28.7 29.5 10 kW 35.5 37.2 38.8 40.4 41.8 43.2 44.4
SDT 49.3 52.7 56.0 59.4 62.8 66.1 69.5 SDT 46.1 49.7 53.2 56.8 60.4 64.0 67.6
LEGEND
38AKS034 — — Out of Range
SST Air Temperature Entering Condenser (C) kW — Compressor Power
(C) 28 32 36 40 44 48 52 SDT — Saturated Discharge Temperature at Compressor (C)
SST — Saturated Suction Temperature (C)
TC 62.4 58.9 55.3 51.7 48.1 44.5 40.8 TC — Gross Cooling Capacity (kW)
–6 kW 20.0 20.6 21.2 21.6 21.9 22.2 22.2
SDT 42.1 46.0 50.0 54.1 58.0 62.0 66.1
TC 68.7 65.0 61.3 57.6 53.7 49.9 46.1
–4 kW 20.7 21.4 22.2 22.7 23.2 23.5 23.7
SDT 42.2 46.1 50.1 54.1 58.1 62.1 66.1
TC 73.3 69.7 66.0 62.1 58.2 54.3 50.3
–2 kW 21.3 22.1 22.9 23.5 24.1 24.5 24.8
SDT 42.7 46.4 50.2 54.1 58.1 62.0 66.1
TC 79.5 75.8 72.1 68.3 64.3 60.3 56.1
0 kW 22.1 23.0 23.9 24.6 25.2 25.8 26.2
SDT 43.6 47.2 50.8 54.5 58.3 62.1 66.1
TC 85.9 82.1 78.2 74.3 70.3 66.3 62.1
2 kW 23.0 24.0 24.9 25.7 26.4 27.1 27.6
SDT 44.6 48.1 51.7 55.2 58.9 62.5 66.2
TC 90.9 87.0 83.0 79.0 74.9 70.8 66.6
4 kW 23.7 24.7 25.7 26.6 27.4 28.1 28.7
SDT 45.4 48.9 52.5 56.0 59.5 63.1 66.6
TC 97.8 93.6 89.5 85.3 81.0 76.8 72.4
6 kW 24.6 25.7 26.8 27.8 28.6 29.4 30.1
SDT 46.6 50.1 53.5 57.0 60.5 64.0 67.5
TC 103.0 98.8 94.5 90.2 85.8 81.4 76.9
8 kW 25.2 26.4 27.6 28.6 29.6 30.5 31.2
SDT 47.5 50.9 54.4 57.8 61.3 64.7 68.2
TC 110.0 106.0 101.0 96.9 92.3 87.7 83.0
10 kW 26.2 27.4 28.7 29.8 30.9 31.9 32.7
SDT 48.8 52.2 55.6 59.0 62.4 65.8 69.2

24
38AKS CONDENSING UNIT RATINGS — ENGLISH

38AKS028 38AKS044
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 85 95 100 105 115 120 125 (F) 85 95 100 105 115 120 125
TC 181.0 167.0 161.0 154.0 141.0 134.0 128.0 TC 271.0 252.0 243.0 234.0 216.0 208.0 199.0
20 kW 17.4 18.3 18.6 19.0 19.6 19.8 20.0 20 kW 27.3 28.5 29.0 29.5 30.3 30.7 31.0
SDT 108.0 117.0 122.0 126.0 136.0 141.0 145.0 SDT 109.0 119.0 124.0 129.0 139.0 144.0 149.0
TC 202.0 187.0 180.0 173.0 159.0 152.0 145.0 TC 305.0 284.0 274.0 264.0 245.0 235.0 225.0
25 kW 18.5 19.4 19.8 20.2 20.9 21.2 21.5 25 kW 28.6 30.0 30.7 31.3 32.3 32.8 33.2
SDT 110.0 119.0 124.0 128.0 137.0 142.0 146.0 SDT 109.0 119.0 124.0 129.0 139.0 144.0 149.0
TC 225.0 209.0 201.0 193.0 178.0 171.0 163.0 TC 341.0 319.0 308.0 297.0 275.0 265.0 254.0
30 kW 19.5 20.6 21.0 21.5 22.3 22.7 23.0 30 kW 29.9 31.5 32.3 33.0 34.2 34.8 35.3
SDT 112.0 121.0 126.0 130.0 139.0 143.0 148.0 SDT 109.0 119.0 124.0 129.0 139.0 144.0 149.0
TC 249.0 231.0 223.0 215.0 198.0 190.0 182.0 TC 377.0 355.0 343.0 332.0 309.0 297.0 286.0
35 kW 20.6 21.7 22.3 22.8 23.7 24.2 24.6 35 kW 31.3 33.1 33.9 34.7 36.1 36.8 37.4
SDT 115.0 123.0 128.0 132.0 141.0 145.0 150.0 SDT 111.0 120.0 125.0 129.0 139.0 144.0 149.0
TC 274.0 256.0 246.0 237.0 220.0 211.0 202.0 TC 415.0 391.0 379.0 367.0 343.0 331.0 319.0
40 kW 21.6 23.0 23.6 24.1 25.2 25.7 26.2 40 kW 32.9 34.8 35.7 36.6 38.2 38.9 39.6
SDT 117.0 126.0 130.0 135.0 143.0 148.0 152.0 SDT 113.0 122.0 126.0 131.0 140.0 145.0 150.0
TC 301.0 281.0 271.0 261.0 242.0 233.0 224.0 TC 455.0 429.0 416.0 403.0 377.0 365.0 352.0
45 kW 22.8 24.2 24.9 25.5 26.7 27.3 27.8 45 kW 34.5 36.6 37.6 38.6 40.3 41.1 41.9
SDT 120.0 129.0 133.0 137.0 146.0 150.0 154.0 SDT 115.0 124.0 128.0 133.0 142.0 147.0 151.0
TC 329.0 307.0 297.0 287.0 266.0 256.0 246.0 TC 497.0 468.0 455.0 441.0 413.0 400.0 386.0
50 kW 23.9 25.5 26.2 26.9 28.3 28.9 29.5 50 kW 36.1 38.4 39.5 40.6 42.5 43.5 44.3
SDT 123.0 131.0 136.0 140.0 148.0 152.0 157.0 SDT 117.0 126.0 131.0 135.0 144.0 149.0 153.0
LEGEND
38AKS034 — — Out of Range
SST Air Temperature Entering Condenser (F) kW — Compressor Power
(F) 85 95 100 105 115 120 125 SDT — Saturated Discharge Temperature at Compressor (F)
SST — Saturated Suction Temperature (F)
TC 203.0 187.0 178.0 170.0 153.0 145.0 136.0 TC — Gross Cooling Capacity (1000 Btuh)
20 kW 20.0 20.8 21.1 21.4 21.8 21.8 21.8
SDT 110.0 120.0 125.0 130.0 140.0 145.0 150.0
TC 230.0 212.0 204.0 195.0 176.0 167.0 158.0
25 kW 21.0 22.0 22.4 22.8 23.4 23.6 23.7
SDT 110.0 120.0 125.0 130.0 140.0 145.0 150.0
TC 256.0 239.0 230.0 221.0 202.0 192.0 182.0
30 kW 22.0 23.2 23.7 24.1 24.9 25.3 25.5
SDT 112.0 121.0 126.0 130.0 140.0 145.0 150.0
TC 283.0 265.0 256.0 247.0 228.0 218.0 208.0
35 kW 23.1 24.4 25.0 25.5 26.5 26.9 27.2
SDT 114.0 123.0 127.0 132.0 141.0 146.0 150.0
TC 311.0 292.0 282.0 273.0 253.0 243.0 233.0
40 kW 24.3 25.7 26.4 27.0 28.1 28.6 29.0
SDT 117.0 125.0 130.0 134.0 143.0 147.0 152.0
TC 340.0 320.0 310.0 300.0 279.0 269.0 259.0
45 kW 25.4 27.0 27.8 28.5 29.7 30.3 30.8
SDT 119.0 128.0 132.0 136.0 145.0 149.0 154.0
TC 371.0 350.0 339.0 328.0 307.0 296.0 285.0
50 kW 26.6 28.4 29.2 30.0 31.4 32.1 32.7
SDT 122.0 130.0 135.0 139.0 148.0 152.0 156.0

25
Performance data (cont)
38AKS/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — SI

38AKS028/40RM024 WITH STANDARD 3-ROW COIL 38AKS028/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s Evaporator Air — L/s
Temp (C) Temp (C)
Air Entering 2900 3800 4700 Air Entering 4250 5650 7050
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) (Edb)
22 20 16 22 20 16 22 20 16 22 20 16 22 20 16 22 20 16
TC 86.6 81.7 73.9 90.6 84.8 77.6 93.1 87.7 80.5 TC 99.5 92.5 85.7 102.5 95.8 90.0 104.3 98.7 93.5
20 SHC 44.0 51.5 73.9 48.9 59.2 77.6 53.4 65.8 80.5 24 SHC 54.0 65.4 85.7 61.7 75.3 90.0 68.7 84.4 93.5
kW 19.70 19.31 18.70 20.01 19.55 18.99 20.20 19.78 19.22 kW 20.71 20.16 19.62 20.94 20.42 19.96 21.09 20.54 20.24
TC 81.9 77.1 70.0 85.6 80.0 73.6 87.8 82.7 76.4 TC 93.9 86.8 80.8 96.4 90.0 85.0 98.0 92.7 88.4
28 SHC 42.2 49.6 70.0 47.1 57.1 73.6 51.6 63.5 76.4 28 SHC 51.9 63.0 80.8 59.6 72.7 85.0 66.6 81.7 88.4
kW 21.44 20.84 19.95 21.90 21.20 20.39 22.18 21.54 20.75 kW 22.94 22.05 21.30 23.25 22.45 21.82 23.45 22.78 22.25
TC 79.4 74.6 67.8 82.9 77.5 71.3 85.0 80.0 74.1 TC 91.0 83.8 78.2 93.3 86.9 82.3 94.8 89.5 85.7
32 SHC 41.2 48.6 67.8 46.1 55.9 71.3 50.6 62.2 74.1 32 SHC 50.8 61.8 78.2 58.5 71.4 82.3 65.5 80.3 85.7
kW 22.57 21.85 20.84 23.09 22.28 21.36 23.41 22.66 21.78 kW 24.29 23.22 22.38 24.64 23.68 23.00 24.86 24.08 23.51
TC 77.0 72.2 65.8 80.2 74.9 69.2 82.2 77.4 71.9 TC 87.9 80.8 75.6 90.0 83.8 79.6 91.4 86.3 83.0
36 SHC 40.2 47.6 65.8 45.2 54.8 69.2 49.6 61.0 71.9 36 SHC 49.6 60.5 75.6 57.3 70.0 79.6 64.4 78.9 83.0
kW 23.66 22.81 21.67 24.23 23.30 22.28 24.59 23.74 22.76 kW 25.61 24.34 23.42 25.98 24.87 24.14 26.22 25.32 24.73
TC 74.4 69.7 63.7 77.4 72.4 67.0 79.3 74.7 69.6 TC 84.8 77.7 73.0 86.6 80.6 76.9 87.9 83.0 80.1
40 SHC 39.2 46.6 63.7 44.2 53.6 67.0 48.6 59.8 69.6 40 SHC 48.4 59.2 73.0 56.1 68.6 76.9 63.2 77.4 80.1
kW 24.82 23.84 22.58 25.45 24.39 23.27 25.84 24.87 23.82 kW 27.00 25.50 24.52 27.38 26.11 25.34 27.64 26.62 26.02
TC 71.8 67.1 61.4 74.6 69.7 64.6 76.4 71.9 67.2 TC 81.8 74.6 70.2 — 77.4 74.1 — 79.8 77.3
44 SHC 38.2 45.5 61.4 43.2 52.4 64.6 47.6 58.5 67.2 44 SHC 47.3 57.9 70.2 — 67.2 74.1 — 76.0 77.3
kW 26.02 25.01 23.79 26.63 25.57 24.49 27.01 26.04 25.04 kW 28.17 26.62 25.68 — 27.23 26.52 — 27.74 27.20
TC 69.7 64.3 58.1 72.8 67.2 61.8 74.8 69.6 64.7 TC — 72.5 67.8 — — 72.2 — — —
48 SHC 37.3 44.4 58.1 42.5 51.3 61.8 47.0 21.9 64.7 48 SHC — 57.1 67.8 — — 72.2 — — —
kW 27.31 25.93 24.73 28.10 26.68 25.30 28.61 27.30 26.04 kW — 28.03 26.82 — — 27.96 — — —
TC — 61.9 56.1 — 64.8 59.7 — — 62.5 TC — — 65.3 — — — — — —
52 SHC — 43.4 56.1 — 50.2 59.7 — — 62.5 52 SHC — — 65.3 — — — — — —
kW — 26.99 25.46 — 27.74 26.40 — — 27.15 kW — — 27.88 — — — — — —

38AKS028/40RM028 WITH STANDARD 3-ROW COIL 38AKS034/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s Evaporator Air — L/s
Temp (C) Temp (C)
Air Entering 3500 4700 5900 Air Entering 3500 4700 5900
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) (Edb)
22 20 16 22 20 16 22 20 16 22 20 16 22 20 16 22 20 16
TC 93.2 89.7 80.1 96.9 90.7 83.9 99.0 93.5 87.1 TC 100.5 98.5 86.7 104.9 98.6 90.5 107.4 101.6 93.8
20 SHC 49.1 57.0 80.1 55.3 67.5 83.9 61.2 75.4 87.1 24 SHC 51.9 59.4 86.7 58.1 71.0 90.5 64.0 78.9 93.8
kW 20.21 19.94 19.18 20.50 20.02 19.48 20.67 20.24 19.74 kW 22.37 22.22 21.34 22.69 22.23 21.63 22.88 22.45 21.87
TC 88.2 83.8 75.7 91.4 85.4 79.4 93.2 88.0 82.6 TC 95.4 92.3 82.0 99.2 93.0 85.8 101.5 95.9 89.1
28 SHC 47.3 55.3 75.7 53.4 65.2 79.4 59.2 72.9 82.6 28 SHC 49.9 57.7 82.0 56.1 68.6 85.8 62.0 76.4 89.1
kW 22.22 21.68 20.65 22.62 21.87 21.13 22.85 22.20 21.52 kW 24.32 23.96 22.78 24.77 24.05 23.22 25.02 24.38 23.59
TC 85.5 80.7 73.3 88.5 82.5 77.0 90.2 85.1 80.1 TC 92.8 89.1 79.5 96.4 90.2 83.4 98.6 93.0 86.6
32 SHC 46.3 54.4 73.3 52.4 64.0 77.0 58.2 71.6 80.1 32 SHC 49.0 55.8 79.5 55.2 67.3 83.4 61.0 75.1 86.6
kW 23.48 22.76 21.66 23.92 23.03 22.21 24.18 23.42 22.68 kW 25.59 25.09 23.80 26.08 25.24 24.32 26.37 25.62 24.76
TC 82.8 77.6 71.0 85.5 79.7 74.6 87.1 82.2 77.7 TC 90.2 86.1 77.3 93.6 87.5 81.1 95.6 90.2 84.3
36 SHC 45.3 53.6 71.0 51.3 62.8 74.6 57.1 70.3 77.7 36 SHC 48.0 56.0 77.3 54.2 66.1 81.1 60.0 73.9 84.3
kW 24.70 23.77 22.60 25.18 24.14 23.25 25.46 24.59 23.79 kW 26.91 25.25 24.85 27.45 26.57 25.46 27.77 26.91 25.97
TC 80.0 74.5 68.6 82.4 76.7 72.2 83.9 79.2 75.2 TC 87.5 82.9 74.9 90.7 84.6 78.7 92.5 87.3 81.9
40 SHC 44.2 52.7 68.6 50.2 61.5 72.2 56.1 69.0 75.2 40 SHC 47.0 55.1 74.9 53.1 64.9 78.7 59.0 72.6 81.9
kW 26.00 24.83 23.61 26.50 25.31 24.36 26.81 25.82 24.98 kW 28.16 27.41 26.10 26.68 27.68 26.72 28.98 28.12 27.24
TC 77.3 71.3 66.1 79.4 73.8 69.7 80.8 76.2 72.6 TC 84.7 79.6 72.4 87.7 81.6 76.1 89.4 84.2 79.3
44 SHC 43.2 51.8 66.1 49.2 60.3 69.7 55.0 67.7 72.6 44 SHC 46.0 54.2 72.4 52.1 63.6 76.1 57.9 71.2 79.3
kW 27.19 25.91 24.80 27.66 26.45 25.56 27.95 26.96 26.20 kW 29.38 28.32 26.80 29.99 28.72 27.59 30.35 29.28 28.25
TC — 68.5 63.3 — 71.7 67.3 — — 70.7 TC 82.8 76.3 68.8 86.0 79.0 73.1 88.0 82.0 76.8
48 SHC — 51.0 63.3 — 59.4 67.3 — — 70.7 48 SHC 45.3 53.2 68.8 51.5 62.5 73.1 57.5 70.3 76.8
kW — 27.02 25.68 — 27.83 26.71 — — 27.56 kW 30.70 29.30 27.66 31.40 29.87 28.60 31.83 30.53 29.39
TC — 65.6 61.0 — — 65.0 — — — TC 80.1 73.1 66.4 83.0 76.0 70.7 84.9 79.0 74.3
52 SHC — 50.2 61.0 — — 65.0 — — — 52 SHC 44.3 52.3 66.4 50.5 61.2 70.7 56.4 68.9 74.3
kW — 27.96 26.75 — — 27.81 — — — kW 31.95 30.27 28.65 32.65 30.98 29.69 33.11 31.70 30.56

LEGEND 3. Formulas:
— — Out of Range SHCkW x 1000
Edb — Entering Dry Bulb Ldb C = Edb C –
1.23 x L/s
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
Ldb — Leaving Dry Bulb coil (hlwb)
Lwb — Leaving Wet Bulb TCkW x 1000
SHC — Sensible Heat Capacity (kW) Gross Ldb C: hlwb = hewb –
TC — Total Capacity (kW) Gross 1.20 x L/s

NOTES: where hewb = enthalpy of air entering evaporator coil (kj/kg).


1. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
2. SHC is based on 26.7 C db air entering indoor coil. piping sized to the outdoor unit field connections. (Equivalent length is equal
to the actual length plus a 50% allowance for fitting losses.) For other equiv-
alent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

26
38AKS/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — SI (cont)

38AKS034/40RM034 WITH STANDARD 3-ROW COIL 38AKS044/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — L/s Evaporator Air — L/s
Temp (C) Temp (C)
Air Entering 4250 5650 7050 Air Entering 4250 5650 7050
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) (Edb)
22 20 16 22 20 16 22 20 16 22 20 16 22 20 16 22 20 16
TC 107.5 100.9 92.9 111.2 104.4 97.3 113.4 107.4 100.9 TC 125.9 118.7 105.4 132.8 123.7 111.1 136.7 128.1 115.8
24 SHC 57.1 68.9 92.9 64.7 79.0 97.3 71.7 88.3 100.9 24 SHC 64.2 76.3 105.4 72.2 87.5 111.1 79.4 97.5 115.8
kW 22.89 22.40 21.81 23.16 22.66 22.13 23.33 22.88 22.40 kW 29.60 29.04 28.01 30.14 29.43 28.45 30.44 29.77 28.82
TC 101.9 95.0 87.8 105.1 98.4 92.1 107.0 101.3 95.7 TC 121.1 114.0 102.1 127.1 118.6 107.5 130.6 122.6 112.0
28 SHC 55.0 66.4 87.8 62.6 76.4 92.1 69.6 85.5 95.7 28 SHC 62.4 74.3 102.1 70.3 85.2 107.5 77.4 95.1 112.0
kW 25.07 24.27 23.44 25.44 24.66 23.94 25.66 25.00 24.36 kW 32.30 31.50 30.16 32.98 32.02 30.77 33.36 32.47 31.27
TC 99.1 92.0 85.1 102.1 95.3 89.5 104.0 98.2 93.0 TC 118.8 112.0 101.3 124.2 116.3 106.3 127.2 119.9 110.4
32 SHC 53.9 65.2 85.1 61.5 75.1 89.5 68.6 84.2 93.0 32 SHC 61.5 73.5 101.3 69.2 84.2 106.3 76.2 93.9 110.4
kW 26.44 25.48 24.56 26.85 25.94 25.14 27.10 26.32 25.62 kW 33.92 32.94 31.41 34.68 33.55 32.13 35.12 34.08 32.72
TC 96.2 89.0 82.7 98.9 92.3 86.9 100.7 95.1 90.4 TC 115.9 108.8 98.4 120.9 113.0 103.5 123.9 116.7 107.7
36 SHC 52.8 64.0 82.7 60.4 73.8 86.9 67.5 82.8 90.4 36 SHC 60.3 72.1 98.4 68.1 82.8 103.5 75.2 92.4 107.7
kW 27.87 26.73 25.71 28.31 27.25 26.39 28.59 27.70 26.95 kW 35.55 34.43 32.81 36.35 35.10 33.61 36.81 35.68 34.26
TC 93.3 86.0 80.0 95.8 89.2 84.2 97.4 92.0 87.7 TC 112.3 104.9 95.0 117.1 109.1 100.1 119.9 112.7 104.3
40 SHC 51.7 62.7 80.0 59.3 72.4 84.2 66.4 81.4 87.7 40 SHC 59.0 70.5 95.0 66.8 81.1 100.1 73.8 90.6 104.3
kW 29.10 27.91 26.94 29.51 28.44 27.63 29.78 28.89 28.19 kW 37.31 36.03 34.35 38.13 36.75 35.22 38.61 37.38 35.94
TC 90.2 82.8 77.3 92.5 86.0 81.5 94.0 88.7 84.9 TC 109.3 101.6 92.2 113.9 105.8 97.3 116.6 109.4 101.5
44 SHC 50.5 61.4 77.3 58.2 71.0 81.5 65.3 79.9 84.9 44 SHC 57.8 69.2 92.2 65.7 79.6 97.3 72.7 89.2 101.5
kW 30.52 28.98 27.82 31.00 29.64 28.70 31.31 30.20 29.41 kW 38.86 37.43 35.68 39.71 38.21 36.63 40.21 38.88 37.41
TC 89.0 80.3 74.1 91.6 84.0 79.0 93.4 87.1 83.0 TC 106.5 97.9 88.3 111.2 102.4 93.9 114.0 106.3 98.4
48 SHC 50.0 60.3 74.1 57.9 70.1 79.0 65.0 79.2 83.0 48 SHC 56.8 67.6 88.3 64.7 78.2 93.9 71.9 87.8 98.4
kW 32.05 30.15 28.82 32.61 30.96 29.88 32.99 32.64 30.74 kW 40.58 38.61 36.43 41.64 39.64 37.69 42.28 40.53 38.72
TC — 77.2 71.5 — 80.8 76.3 — 83.8 80.2 TC 103.5 94.7 85.7 107.9 99.2 91.2 110.5 103.0 95.7
52 SHC — 59.0 71.5 — 68.7 76.3 — 77.7 80.2 52 SHC 55.6 66.3 85.7 63.6 76.7 91.2 70.7 86.3 95.7
kW — 31.25 29.88 — 32.12 31.04 — 32.85 31.98 kW 42.27 40.10 37.87 43.34 41.19 39.22 43.99 42.13 40.33

LEGEND 3. Formulas:
— — Out of Range SHCkW x 1000
Edb — Entering Dry Bulb Ldb C = Edb C –
1.23 x L/s
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
Ldb — Leaving Dry Bulb coil (hlwb)
Lwb — Leaving Wet Bulb TCkW x 1000
SHC — Sensible Heat Capacity (kW) Gross Ldb C: hlwb = hewb –
TC — Total Capacity (kW) Gross 1.20 x L/s

NOTES: where hewb = enthalpy of air entering evaporator coil (kj/kg).


1. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
2. SHC is based on 26.7 C db air entering indoor coil. piping sized to the outdoor unit field connections. (Equivalent length is equal
to the actual length plus a 50% allowance for fitting losses.) For other equiv-
alent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

27
Performance data (cont)
38AKS/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — ENGLISH

38AKS028/40RM024 WITH STANDARD 3-ROW COIL 38AKS028/40RM034 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm Evaporator Air — Cfm
Temp (F) Temp (F)
Air Entering 6,000 8,000 10,000 Air Entering 9,000 12,000 15,000
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 276.7 254.2 231.0 289.4 267.4 245.0 297.0 276.2 256.3 TC 317.8 291.3 271.9 328.5 302.8 289.0 334.2 312.9 302.9
85 SHC 139.7 174.3 221.2 156.4 201.3 245.0 171.3 226.0 256.3 85 SHC 172.3 224.7 268.2 199.4 261.6 289.0 221.4 295.1 302.9
kW 21.72 20.72 19.69 22.28 21.30 20.31 22.62 21.70 20.81 kW 23.55 22.37 21.51 24.02 22.88 22.27 24.28 23.33 22.88
TC 265.3 244.1 222.8 276.9 256.1 236.3 283.6 264.4 247.1 TC 302.9 277.5 260.7 312.6 288.1 277.0 317.6 297.8 290.3
95 SHC 135.3 170.1 214.1 151.9 196.6 236.3 166.5 220.6 247.1 95 SHC 166.7 219.2 258.0 194.0 255.7 277.0 215.9 288.5 290.3
kW 23.45 22.43 21.41 24.00 23.00 22.05 24.32 23.41 22.57 kW 25.25 24.03 23.22 25.72 24.54 24.01 25.95 25.01 24.64
TC 259.0 238.0 217.3 270.4 249.7 230.7 276.7 258.0 241.6 TC 295.9 270.3 254.3 305.4 280.8 270.7 310.1 290.5 284.0
100 SHC 132.9 167.6 209.2 149.5 193.8 230.7 164.1 217.6 241.6 100 SHC 164.0 216.4 252.3 191.5 252.8 270.7 213.4 285.3 284.0
kW 24.28 23.18 22.11 24.87 23.79 22.81 25.20 24.22 23.37 kW 26.20 24.86 24.03 26.69 25.41 24.89 26.93 25.92 25.58
TC 253.0 232.6 212.8 263.8 243.7 226.0 269.7 251.7 236.6 TC 288.2 263.1 248.3 297.1 273.2 264.4 301.5 282.6 277.3
105 SHC 130.6 165.4 205.4 147.1 191.3 226.0 161.6 214.8 236.6 105 SHC 161.1 213.5 246.8 188.7 249.7 264.4 210.5 281.8 277.3
kW 25.03 23.85 22.69 25.66 24.49 23.46 26.01 24.96 24.08 kW 27.08 25.62 24.76 27.61 26.21 25.70 27.86 26.76 26.45
TC 240.9 222.0 204.1 250.7 231.9 216.6 255.6 239.4 226.7 TC — 248.9 236.5 — 258.1 251.7 — — 263.9
115 SHC 126.0 161.1 197.7 142.4 186.3 216.6 156.7 209.2 226.7 115 SHC — 207.9 236.1 — 243.6 251.7 — — 263.9
kW 26.63 25.34 24.11 27.29 26.01 24.97 27.63 26.52 25.65 kW — 27.17 26.32 — 27.80 27.36 — — 28.20
TC — 210.5 193.6 — 219.8 206.1 — — 216.1 TC — — 224.6 — — — — — —
125 SHC — 156.4 188.6 — 181.2 206.1 — — 216.1 125 SHC — — 224.5 — — — — — —
kW — 26.82 25.59 — 27.50 26.50 — — 27.23 kW — — 27.84 — — — — — —

38AKS028/40RM028 WITH STANDARD 3-ROW COIL 38AKS034/40RM028 WITH STANDARD 3-ROW COIL
Evaporator Air — Cfm Evaporator Air — Cfm
Temp (F) Temp (F)
Air Entering 7,500 10,000 12,500 Air Entering 7,500 10,000 12,500
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 298.5 274.6 252.4 310.3 286.1 267.8 316.9 295.7 280.8 TC 322.9 298.4 272.1 336.1 311.1 287.8 344.0 321.0 301.3
85 SHC 157.1 200.0 247.5 177.6 232.2 267.8 197.3 261.4 280.8 85 SHC 166.0 209.6 265.5 186.7 242.5 287.8 206.3 272.4 301.3
kW 22.69 21.63 20.64 23.21 22.14 21.32 23.51 22.56 21.90 kW 24.75 23.82 22.82 25.25 24.30 23.42 25.55 24.68 23.93
TC 285.4 262.5 242.8 296.2 273.1 257.5 302.0 282.2 270.0 TC 310.6 286.4 262.1 323.0 298.4 277.7 330.3 308.1 291.0
95 SHC 152.2 195.1 238.6 172.6 226.9 257.5 192.3 255.5 270.0 95 SHC 161.5 204.7 256.4 182.1 237.3 277.6 201.8 266.8 291.0
kW 24.41 23.31 22.36 24.93 23.82 23.07 25.21 24.26 23.67 kW 26.56 25.44 24.31 27.14 26.00 25.03 27.48 26.45 25.65
TC 278.8 255.7 236.9 289.3 266.2 251.7 294.9 275.3 264.2 TC 304.2 279.9 256.5 316.5 291.8 272.1 323.5 301.5 285.4
100 SHC 149.8 192.4 233.2 170.2 224.0 251.7 190.0 252.5 264.2 100 SHC 159.1 202.1 251.2 179.8 234.5 272.1 199.5 263.9 285.4
kW 25.31 24.10 23.13 25.85 24.65 23.90 26.14 25.13 24.55 kW 27.51 26.29 25.12 28.12 26.89 25.90 28.47 27.38 26.57
TC 271.9 249.3 231.7 281.9 259.3 246.2 287.1 268.2 258.4 TC 297.9 274.0 251.9 309.6 285.5 267.2 316.2 295.0 280.3
105 SHC 147.3 189.8 228.5 167.6 221.2 246.2 187.4 249.4 258.4 105 SHC 156.8 199.7 247.0 177.4 231.9 267.2 197.1 261.1 280.3
kW 26.13 24.82 23.79 26.72 25.40 24.64 27.02 25.92 25.35 kW 28.38 27.06 25.83 29.03 27.69 26.68 29.40 28.22 27.40
TC 258.1 236.6 221.4 267.2 245.8 235.3 271.6 254.2 246.9 TC 284.2 260.6 204.7 295.2 271.5 255.9 301.2 280.9 268.6
115 SHC 142.2 184.7 219.0 162.4 215.6 235.3 182.2 243.3 246.9 115 SHC 151.8 194.4 236.7 172.3 226.2 255.9 192.1 254.9 268.6
kW 27.80 26.33 25.30 28.41 26.96 26.24 28.72 27.53 27.03 kW 30.02 28.57 27.34 30.70 29.34 28.28 31.06 29.82 29.06
TC — 224.0 210.2 — — 224.3 — — — TC 271.2 247.3 229.1 281.7 257.8 244.4 287.2 267.3 257.2
125 SHC — 179.5 208.8 — — 224.3 — — — 125 SHC 147.0 189.0 226.1 167.6 220.6 244.4 187.4 249.0 257.2
kW — 27.80 26.80 — — 27.82 — — — kW 31.64 29.99 28.73 32.37 30.72 29.79 32.75 31.37 30.67

LEGEND 3. Formulas:
— — Out of Range SHCBtuh
Edb — Entering Dry Bulb Ldb F = Edb F –
1.10 x cfm
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
Ldb — Leaving Dry Bulb coil (hlwb)
Lwb — Leaving Wet Bulb TCBtuh
SHC — Sensible Heat Capacity (kW) Gross Ldb F: hlwb = hewb –
TC — Total Capacity (kW) Gross 4.5 x cfm

NOTES: where hewb = enthalpy of air entering evaporator coil (Btuh/lb).


1. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting pip-
2. SHC is based on 80 F db air entering indoor coil. ing sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equiva-
lent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

28
38AKS/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — ENGLISH (cont)
LEGEND
38AKS034/40RM034 WITH STANDARD 3-ROW COIL — — Out of Range
Edb — Entering Dry Bulb
Evaporator Air — Cfm Ewb — Entering Wet Bulb
Temp (F)
Air Entering 9,000 12,000 15,000 kW — Compressor Motor Power Input
Condenser Evaporator Air — Ewb (F) Ldb — Leaving Dry Bulb
(Edb) Lwb — Leaving Wet Bulb
72 67 62 72 67 62 72 67 62 SHC — Sensible Heat Capacity (kW) Gross
TC 344.6 317.4 294.0 256.9 330.1 311.5 363.8 340.6 326.0 TC — Total Capacity (kW) Gross
85 SHC 182.5 235.1 288.2 209.0 272.7 311.5 231.3 307.3 326.0
kW 25.57 24.55 23.65 26.04 25.02 24.32 26.30 25.42 24.87 NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
TC 331.0 304.2 282.8 342.5 316.2 300.1 348.8 326.6 314.3 2. SHC is based on 80 F db air entering indoor coil.
95 SHC 177.3 229.8 278.1 204.1 267.1 300.1 226.3 301.1 314.3 3. Formulas:
kW 27.51 26.27 25.27 28.05 26.82 26.08 28.34 27.31 26.74
SHCBtuh
TC 324.3 297.3 276.8 335.5 309.2 294.1 341.6 319.6 308.3 Ldb F = Edb F –
100 SHC 174.8 227.1 272.6 201.7 264.2 294.1 223.9 298.0 308.3 1.10 x cfm
kW 28.51 27.16 26.14 29.08 27.76 27.00 29.38 28.28 27.72 Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
TC 317.1 290.6 271.3 327.8 302.1 288.4 333.5 312.2 302.3 coil (hlwb)
105 SHC 172.0 224.4 267.7 199.1 261.4 288.4 221.2 294.8 302.3 TCBtuh
kW 29.45 27.98 26.91 30.05 28.62 27.85 30.36 29.18 28.63 Ldb F: hlwb = hewb –
4.5 x cfm
TC 302.2 276.0 258.9 312.1 286.9 275.7 317.2 296.8 289.3
115 SHC 166.4 218.6 256.4 193.8 255.2 275.6 215.7 288.0 289.3 where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
kW 31.12 29.51 28.46 31.74 30.19 29.49 32.05 30.80 30.33 4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting pip-
TC 288.3 261.8 246.5 — 272.5 263.3 — 282.5 276.9 ing sized to the outdoor unit field connections. (Equivalent length is equal to
125 SHC 161.1 213.0 245.1 — 249.4 263.3 — 281.7 276.9 the actual length plus a 50% allowance for fitting losses.) For other equiva-
kW 32.83 30.99 29.93 — 31.73 31.10 — 32.43 32.04 lent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

38AKS044/40RM034 WITH STANDARD 3-ROW COIL


Evaporator Air — Cfm
Temp (F)
Air Entering 9,000 12,000 15,000
Condenser Evaporator Air — Ewb (F)
(Edb)
72 67 62 72 67 62 72 67 62
TC 413.7 382.6 344.5 432.1 399.8 364.9 443.5 412.4 382.2
85 SHC 208.7 260.9 334.0 234.4 300.7 364.9 257.8 338.8 382.2
kW 32.85 31.60 30.08 33.58 32.29 30.89 34.04 32.80 31.59
TC 399.2 368.7 333.6 416.4 384.9 353.6 426.9 397.2 370.5
95 SHC 203.2 255.4 324.2 229.1 294.7 353.6 252.3 332.2 370.5
kW 35.19 33.74 32.08 36.00 34.51 33.03 36.50 35.10 33.83
TC 391.8 361.5 328.0 408.3 377.3 347.7 418.3 389.4 364.4
100 SHC 200.4 252.5 319.0 226.4 291.7 347.7 249.4 328.7 364.4
kW 36.36 34.80 33.08 37.21 35.61 34.09 37.72 36.24 34.95
TC 384.2 354.1 322.2 400.1 369.5 341.7 409.6 381.5 358.2
105 SHC 197.5 249.6 313.8 223.6 288.5 341.7 246.5 325.2 358.2
kW 37.55 35.88 34.11 38.44 36.74 35.20 38.97 37.41 36.11
TC 368.5 339.0 310.2 383.1 353.5 329.2 391.7 365.1 345.2
115 SHC 191.5 243.6 302.9 217.8 282.1 329.2 240.6 318.1 345.2
kW 39.77 37.95 36.17 40.68 38.85 37.35 41.21 39.57 38.33
TC 352.6 323.3 297.2 366.4 337.2 316.0 374.3 348.7 331.7
125 SHC 185.5 237.4 291.1 212.2 275.5 316.0 234.8 310.8 331.7
kW 41.94 39.90 38.08 42.91 40.87 39.39 43.45 41.67 40.48

29
Performance data (cont)
38AKS/40RM COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — SI

38AKS028/40RM024 WITH 4-ROW HIGH-CAPACITY COILS 38AKS034/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s Evaporator Air — L/s
Temp (C) Temp (C)
Air Entering 2830 3780 4720 Air Entering 3540 4720 5900
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) (Edb)
17 19 22 17 19 22 17 19 22 17 19 22 17 19 22 17 19 22
TC 75.4 82.6 90.3 80.3 87.6 95.4 83.4 90.9 98.8 TC 82.0 89.5 97.4 86.3 93.9 101.8 89.9 96.9 104.8
29 SHC 60.2 48.3 36.1 71.3 56.2 40.6 80.6 63.7 45.0 29 SHC 69.0 54.8 40.1 81.1 63.7 45.3 89.9 72.3 50.4
kW 21.83 22.91 24.02 22.58 23.64 24.76 23.05 24.14 25.26 kW 23.75 24.89 26.04 24.40 25.54 26.70 24.96 25.98 27.15
TC 72.0 79.0 86.4 76.6 83.7 91.1 79.6 86.6 94.1 TC 78.5 85.7 93.3 82.7 89.8 97.4 86.5 92.6 100.2
35 SHC 58.9 47.0 34.9 69.8 55.0 39.5 79.6 62.5 44.0 35 SHC 67.6 53.5 39.0 79.6 62.5 44.2 86.5 71.1 49.3
kW 23.31 24.51 25.75 24.13 25.32 26.55 24.63 25.80 27.05 kW 25.19 26.45 27.75 25.93 27.17 28.43 26.59 27.65 28.90
TC 70.3 77.2 84.4 74.6 81.7 89.0 77.7 84.4 91.8 TC 76.7 83.8 91.1 80.8 87.8 95.2 84.8 90.4 97.8
38 SHC 58.2 46.4 34.4 69.0 54.4 39.0 77.7 61.9 43.4 38 SHC 66.9 52.9 38.4 78.7 62.0 43.7 84.8 70.5 48.8
kW 24.04 25.28 26.58 24.85 26.12 27.40 25.39 26.60 27.92 kW 25.88 27.20 28.55 26.67 27.94 29.27 27.39 28.43 29.76
TC 68.6 75.3 82.4 72.8 79.6 86.8 76.2 82.2 89.5 TC 74.9 81.8 88.9 78.7 85.6 92.9 83.0 88.1 95.4
41 SHC 57.6 45.8 33.8 68.4 53.8 38.4 76.2 61.2 42.9 41 SHC 66.3 52.3 37.8 78.7 61.4 43.1 83.0 69.8 48.3
kW 24.80 26.11 27.46 25.62 26.96 28.31 26.27 27.46 28.81 kW 26.61 27.98 29.38 27.39 28.74 30.13 28.22 29.23 30.63
TC 65.2 71.6 78.3 69.1 75.4 82.2 72.8 77.8 84.7 TC 71.2 77.7 84.5 75.0 81.2 88.2 79.4 83.4 90.4
46 SHC 56.3 44.7 32.6 66.8 52.6 37.3 72.8 60.0 41.7 46 SHC 64.9 51.0 36.7 75.0 60.1 42.1 79.4 68.5 47.1
kW 26.26 27.68 29.15 27.11 28.52 29.99 27.95 29.06 30.52 kW 27.99 29.48 31.00 28.88 30.27 31.81 29.86 30.76 32.29

38AKS028/40RM028 WITH 4-ROW HIGH-CAPACITY COILS 38AKS034/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s Evaporator Air — L/s
Temp (C) Temp (C)
Air Entering 3540 4720 5900 Air Entering 4250 5660 7080
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) (Edb)
17 19 22 17 19 22 17 19 22 17 19 22 17 19 22 17 19 22
TC 77.1 84.3 91.7 81.3 88.3 95.8 85.2 91.0 98.6 TC 87.2 95.0 103.1 91.6 99.2 107.4 96.6 101.8 110.0
29 SHC 67.1 53.1 38.5 78.8 62.1 43.8 85.2 70.6 48.9 29 SHC 78.5 61.7 44.4 91.6 72.5 50.8 96.6 82.6 56.8
kW 22.01 23.07 24.15 22.65 23.67 24.75 23.20 24.06 25.15 kW 24.55 25.70 26.90 25.21 26.34 27.53 25.95 26.72 27.91
TC 73.7 80.4 87.6 77.5 84.2 91.4 81.8 86.6 93.8 TC 83.4 90.9 98.7 88.1 94.7 102.6 93.0 97.2 105.1
35 SHC 65.8 51.8 37.4 77.5 60.9 42.8 81.8 69.4 47.9 35 SHC 76.9 60.5 43.3 88.1 71.3 49.7 93.0 81.2 55.7
kW 23.52 24.68 25.87 24.18 25.34 26.51 24.90 25.71 26.92 kW 26.07 27.35 28.66 26.87 27.99 29.32 27.72 28.39 29.73
TC 71.9 78.6 85.5 75.7 82.1 89.2 80.1 84.4 91.4 TC 81.5 88.9 96.5 86.4 92.5 100.2 91.1 94.8 102.6
38 SHC 65.1 51.3 36.9 75.7 60.3 42.3 80.1 68.7 47.4 38 SHC 76.2 59.9 42.7 86.4 70.6 49.1 91.1 80.6 55.2
kW 24.25 25.47 26.71 24.94 26.12 27.39 25.75 26.52 27.77 kW 26.88 28.15 29.51 27.69 28.80 30.17 28.56 29.21 30.58
TC 70.2 76.6 83.4 74.1 80.0 86.8 78.3 82.1 89.0 TC 79.6 86.7 94.2 84.6 90.1 97.7 89.1 92.4 100.0
41 SHC 64.4 50.7 36.3 74.1 59.7 41.7 78.3 68.1 46.8 41 SHC 75.4 59.3 42.1 84.6 70.0 48.6 89.1 79.9 54.6
kW 25.01 26.27 27.57 25.76 26.93 28.24 26.61 27.34 28.65 kW 27.57 28.97 30.40 28.55 29.63 31.06 29.42 30.06 31.49
TC 66.5 72.7 79.1 70.8 75.7 82.2 74.7 77.7 84.2 TC 75.5 82.2 89.5 81.0 85.4 92.6 85.1 87.6 94.8
46 SHC 63.0 49.5 35.3 70.8 58.5 40.7 74.7 66.8 45.7 46 SHC 73.5 58.0 41.0 81.0 68.7 47.4 85.1 78.4 53.5
kW 26.45 27.84 29.26 27.41 28.49 29.92 28.27 28.94 30.35 kW 28.99 30.49 32.08 30.21 31.18 32.75 31.11 31.66 33.21

38AKS028/40RM034 WITH 4-ROW HIGH-CAPACITY COILS 38AKS044/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — L/s Evaporator Air — L/s
Temp (C) Temp (C)
Air Entering 4250 5660 7080 Air Entering 4250 5660 7080
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) (Edb)
17 19 22 17 19 22 17 19 22 17 19 22 17 19 22 17 19 22
TC 81.9 89.4 97.2 86.8 93.1 101.0 91.6 95.6 103.4 TC 101.8 110.9 120.4 107.5 116.6 126.2 111.3 120.2 129.9
29 SHC 76.0 60.0 42.9 86.8 70.8 49.3 91.6 80.7 55.3 29 SHC 84.1 66.8 49.1 99.1 77.7 55.4 111.3 87.8 61.4
kW 22.84 23.92 25.03 23.51 24.46 25.57 24.21 24.82 25.92 kW 33.03 34.90 36.81 34.20 36.06 38.02 34.97 36.77 38.73
TC 78.2 85.3 92.8 83.4 88.7 96.2 87.8 91.0 98.5 TC 97.8 106.5 115.7 102.9 111.7 120.9 107.1 115.1 124.3
35 SHC 74.8 58.8 41.8 83.4 69.5 48.1 87.8 79.4 54.3 35 SHC 82.6 65.4 47.8 97.1 76.2 54.1 107.1 86.4 60.1
kW 24.40 25.59 26.84 25.26 26.15 27.39 25.98 26.54 27.76 kW 34.80 36.76 38.83 35.94 37.95 40.03 36.90 38.70 40.79
TC 76.2 83.1 90.6 81.7 86.4 93.8 85.9 88.7 96.0 TC 95.8 104.3 113.2 100.7 109.3 118.2 105.2 112.5 121.4
38 SHC 73.8 58.2 41.3 81.7 68.9 47.6 85.9 78.7 53.7 38 SHC 81.8 64.7 47.2 96.2 75.5 53.4 105.2 85.7 59.5
kW 25.14 26.38 27.70 26.10 26.97 28.27 26.84 27.38 28.66 kW 35.71 37.74 39.87 36.87 38.91 41.05 37.96 39.69 41.83
TC 74.3 81.0 88.2 79.9 84.2 91.4 84.0 86.3 93.5 TC 93.7 102.1 110.8 98.6 106.8 115.5 103.1 109.9 118.6
41 SHC 72.7 57.6 40.7 79.9 68.3 47.1 84.0 77.9 53.2 41 SHC 81.0 64.0 46.5 95.2 74.8 52.8 103.1 85.0 58.8
kW 25.92 27.22 28.58 26.99 27.83 29.18 27.77 28.24 29.59 kW 36.56 38.69 40.89 37.78 39.85 42.05 38.93 40.65 42.84
TC 70.6 76.7 83.6 76.2 79.7 86.5 80.1 81.5 88.4 TC 89.4 97.3 105.6 93.8 101.7 109.9 98.8 104.6 112.8
46 SHC 70.6 56.3 39.6 76.2 67.0 46.0 80.1 76.4 52.1 46 SHC 79.4 62.5 45.1 93.8 73.3 51.4 98.8 83.5 57.5
kW 27.44 28.82 30.28 28.68 29.46 30.91 29.54 29.85 31.32 kW 38.19 40.43 42.74 39.46 41.63 43.95 40.85 42.46 44.79
LEGEND 3. Formulas:
— — Out of Range SHCkW x 1000
Edb — Entering Dry Bulb Ldb C = Edb C –
1.23 x L/s
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
Ldb — Leaving Dry Bulb coil (hlwb)
Lwb — Leaving Wet Bulb TCkW x 1000
SHC — Sensible Heat Capacity (kW) Gross Ldb C: hlwb = hewb –
TC — Total Capacity (kW) Gross 1.20 x L/s

NOTES: where hewb = enthalpy of air entering evaporator coil (kj/kg).


1. Direct interpolation is permissible. Do not extrapolate. 4. Capacities are based on 7.6 actual m (12.2 equivalent m) of interconnecting
2. SHC is based on 26.7 C db air entering indoor coil. piping sized to the outdoor unit field connections. (Equivalent length is equal
to the actual length plus a 50% allowance for fitting losses.) For other equiv-
alent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

30
38AKS/40RM COMBINATION RATINGS — 4-ROW HIGH-CAPACITY COILS — ENGLISH

38AKS028/40RM024 WITH 4-ROW HIGH-CAPACITY COILS 38AKS034/40RM028 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm Evaporator Air — Cfm
Temp (F) Temp (F)
Air Entering 6,000 8,000 10,000 Air Entering 7,500 10,000 12,500
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 257.4 282.2 308.4 274.1 299.2 325.8 284.9 310.4 337.3 TC 280.1 305.6 332.5 294.8 320.8 347.7 307.1 331.0 357.9
85 SHC 205.5 164.8 123.1 243.4 191.9 138.8 275.4 217.4 153.8 85 SHC 235.6 187.1 137.0 276.9 217.7 154.8 307.1 246.9 172.1
kW 21.83 22.91 24.02 22.58 23.64 24.76 23.05 24.14 25.26 kW 23.75 24.89 26.04 24.40 25.54 26.70 24.96 25.98 27.15
TC 245.9 269.7 295.2 261.5 285.8 311.3 272.0 295.7 321.5 TC 267.9 292.7 318.7 282.5 306.8 332.7 295.4 316.4 342.2
95 SHC 201.1 160.7 119.4 238.5 188.0 135.0 272.0 213.4 150.2 95 SHC 230.9 182.8 133.3 271.9 213.6 151.0 295.4 242.9 168.4
kW 23.31 24.51 25.75 24.13 25.32 26.55 24.63 25.80 27.05 kW 25.19 26.45 27.75 25.93 27.17 28.43 26.59 27.65 28.90
TC 240.1 263.5 288.4 254.7 278.9 303.9 265.3 288.3 313.7 TC 261.8 286.0 311.1 276.0 299.7 325.0 289.5 308.7 334.2
100 SHC 198.8 158.6 117.4 235.6 185.9 133.2 265.3 211.4 148.3 100 SHC 228.6 180.6 131.1 268.8 211.6 149.2 289.5 240.7 166.7
kW 24.04 25.28 26.58 24.85 26.12 27.40 25.39 26.60 27.92 kW 25.88 27.20 28.55 26.67 27.94 29.27 27.39 28.43 29.76
TC 234.4 257.2 281.4 248.5 271.8 296.3 260.1 280.8 305.5 TC 255.7 279.2 303.7 268.8 292.5 317.1 283.4 300.9 325.8
105 SHC 196.7 156.6 115.5 233.7 183.9 131.2 260.1 209.2 146.4 105 SHC 226.3 178.5 129.1 268.8 209.5 147.4 283.4 238.5 164.8
kW 24.80 26.11 27.46 25.62 26.96 28.31 26.27 27.46 28.81 kW 26.61 27.98 29.38 27.39 28.74 30.13 28.22 29.23 30.63
TC 222.7 244.6 267.5 235.9 257.4 280.9 248.8 265.9 289.4 TC 243.0 265.3 288.7 256.2 277.4 301.1 271.0 285.0 308.7
115 SHC 192.3 152.5 111.5 228.2 179.7 127.5 248.8 204.9 142.6 115 SHC 221.5 174.2 125.2 256.2 205.3 143.6 271.0 234.0 160.8
kW 26.26 27.68 29.15 27.11 28.52 29.99 27.95 29.06 30.52 kW 27.99 29.48 31.00 28.88 30.27 31.81 29.86 30.76 32.29

38AKS028/40RM028 WITH 4-ROW HIGH-CAPACITY COILS 38AKS034/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm Evaporator Air — Cfm
Temp (F) Temp (F)
Air Entering 7,500 10,000 12,500 Air Entering 9,000 12,000 15,000
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 263.5 287.8 313.2 277.6 301.7 327.2 290.9 310.7 336.6 TC 297.9 324.3 352.1 312.9 338.8 366.7 330.1 347.7 375.8
85 SHC 229.3 181.2 131.6 269.1 212.1 149.7 290.9 241.2 167.2 85 SHC 267.9 210.7 151.5 312.9 247.8 173.3 330.1 282.1 194.1
kW 22.01 23.07 24.15 22.65 23.67 24.75 23.20 24.06 25.15 kW 24.55 25.70 26.90 25.21 26.34 27.53 25.95 26.72 27.91
TC 251.6 274.7 299.0 264.8 287.7 312.1 279.3 295.6 320.4 TC 284.9 310.5 337.1 300.9 323.5 350.5 317.7 331.8 358.8
95 SHC 224.7 177.1 127.8 264.8 208.0 146.1 279.3 236.9 163.5 95 SHC 262.5 206.5 147.7 300.9 243.5 169.7 317.7 277.4 190.2
kW 23.52 24.68 25.87 24.18 25.34 26.51 24.90 25.71 26.92 kW 26.07 27.35 28.66 26.87 27.99 29.32 27.72 28.39 29.73
TC 245.7 268.3 292.0 258.5 280.4 304.7 273.5 288.1 312.3 TC 278.3 303.5 329.5 295.0 315.7 342.2 311.0 323.8 350.3
100 SHC 222.5 175.1 126.0 258.5 206.1 144.4 273.5 234.7 161.7 100 SHC 260.2 204.5 145.9 295.0 241.3 167.8 311.0 275.1 188.5
kW 24.25 25.47 26.71 24.94 26.12 27.39 25.75 26.52 27.77 kW 26.81 28.15 29.51 27.69 28.80 30.17 28.56 29.21 30.58
TC 239.6 261.6 284.7 253.0 273.0 296.6 267.5 280.4 304.1 TC 271.7 296.2 321.7 289.0 307.8 333.7 304.3 315.7 341.5
105 SHC 220.0 173.1 124.1 253.0 204.1 142.6 267.5 232.5 159.7 105 SHC 257.6 202.4 143.9 289.0 239.1 165.8 304.3 272.9 186.6
kW 25.01 26.27 27.57 25.76 26.93 28.24 26.61 27.34 28.65 kW 27.57 28.97 30.40 28.55 29.63 31.06 29.42 30.06 31.49
TC 227.1 248.2 270.3 241.9 258.4 280.7 255.1 265.3 287.7 TC 257.9 280.9 305.5 276.5 291.8 316.4 290.6 299.1 323.6
115 SHC 215.1 169.0 120.5 241.9 199.8 138.9 255.1 228.1 156.2 115 SHC 251.0 198.0 139.9 276.5 234.5 161.9 290.6 267.7 182.7
kW 26.45 27.84 29.26 27.41 28.49 29.92 28.27 28.94 30.35 kW 28.99 30.49 32.08 30.21 31.18 32.75 31.11 31.66 33.21

38AKS028/40RM034 WITH 4-ROW HIGH-CAPACITY COILS 38AKS044/40RM034 WITH 4-ROW HIGH-CAPACITY COILS
Evaporator Air — Cfm Evaporator Air — Cfm
Temp (F) Temp (F)
Air Entering 9,000 12,000 15,000 Air Entering 9,000 12,000 15,000
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) (Edb)
62 67 72 62 67 72 62 67 72 62 67 72 62 67 72 62 67 72
TC 279.7 305.5 332.1 296.4 318.0 345.0 312.8 326.3 353.3 TC 347.6 378.8 411.3 367.0 398.3 431.0 380.2 410.6 443.5
85 SHC 259.7 204.9 146.4 296.4 241.8 168.3 312.8 275.6 189.0 85 SHC 287.1 228.1 167.7 338.3 265.2 189.3 380.2 300.0 209.8
kW 22.84 23.92 25.03 23.51 24.46 25.57 24.21 24.82 25.92 kW 33.03 34.90 36.81 34.20 36.06 38.02 34.97 36.77 38.73
TC 267.2 291.2 317.0 284.9 302.8 328.6 299.8 310.6 336.3 TC 334.0 363.8 395.1 351.4 381.6 412.9 365.8 393.1 424.4
95 SHC 255.4 200.8 142.6 284.9 237.5 164.4 299.8 271.3 185.4 95 SHC 282.2 223.4 163.4 331.7 260.3 184.7 365.8 295.2 205.3
kW 24.40 25.59 26.84 25.26 26.15 27.39 25.98 26.54 27.76 kW 34.80 36.76 38.83 35.94 37.95 40.03 36.90 38.70 40.79
TC 260.4 284.0 309.4 278.9 295.1 320.4 293.4 302.8 327.9 TC 327.2 356.3 386.8 344.0 373.1 403.6 359.2 384.3 414.8
100 SHC 252.0 198.9 140.9 278.9 235.3 162.6 293.4 268.8 183.6 100 SHC 279.4 221.0 161.2 328.7 257.8 182.5 359.2 292.8 203.2
kW 25.14 26.38 27.70 26.10 26.97 28.27 26.84 27.38 28.66 kW 35.71 37.74 39.87 36.87 38.91 41.05 37.96 39.69 41.83
TC 253.7 276.7 301.3 272.8 287.5 312.1 286.8 294.6 319.3 TC 319.9 348.7 378.4 336.6 364.6 394.3 352.0 375.4 405.0
105 SHC 248.4 196.7 139.0 272.8 233.2 160.9 286.8 266.0 181.8 105 SHC 276.5 218.5 159.0 325.2 255.4 180.2 352.0 290.3 201.0
kW 25.92 27.22 28.58 26.99 27.83 29.18 27.77 28.24 29.59 kW 36.56 38.69 40.89 37.78 39.85 42.05 38.93 40.65 42.84
TC 241.1 262.0 285.5 260.3 272.1 295.5 273.6 278.4 301.9 TC 305.3 332.4 360.5 320.5 347.2 375.3 337.6 357.2 385.3
115 SHC 241.1 192.4 135.2 260.3 228.8 157.2 273.6 260.8 177.9 115 SHC 271.1 213.5 153.9 320.5 250.4 175.6 337.6 285.1 196.5
kW 27.44 28.82 30.28 28.68 29.46 30.91 29.54 29.85 31.32 kW 38.19 40.43 42.74 39.46 41.63 43.95 40.85 42.46 44.79

LEGEND 3. Formulas:
— — Out of Range SHCBtuh
Edb — Entering Dry Bulb Ldb F = Edb F –
1.10 x cfm
Ewb — Entering Wet Bulb
kW — Compressor Motor Power Input Lwb = wet-bulb temperature corresponding to enthalpy air leaving indoor
Ldb — Leaving Dry Bulb coil (hlwb)
Lwb — Leaving Wet Bulb TCBtuh
SHC — Sensible Heat Capacity (kW) Gross Ldb F: hlwb = hewb –
TC — Total Capacity (kW) Gross 4.5 x cfm

1. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil (Btuh/lb).
2. SHC is based on 80 F db air entering indoor coil. 4. Capacities are based on 25 actual ft (40 equivalent ft) of interconnecting pip-
ing sized to the outdoor unit field connections. (Equivalent length is equal to
the actual length plus a 50% allowance for fitting losses.) For other equiva-
lent lengths, refer to the Carrier System Design Manual, Part 3, for line
losses.

31
Performance data (cont)
38AH CONDENSING UNIT RATINGS — SI

38AH024 38AH034
SST Air Temperature Entering Condenser (C) SST Air Temperature Entering Condenser (C)
(C) 24 28 32 36 40 44 48 52 (C) 24 28 32 36 40 44 48 52
TC 42.9 40.6 38.0 35.6 33.0 30.6 28.2 25.7 TC 59.8 57.1 54.0 51.1 48.1 45.3 42.4 39.5
–6 kW 11.3 11.6 12.1 12.6 13.0 13.4 13.7 14.2 –6 kW 16.6 17.3 18.1 18.9 19.7 20.4 21.0 21.8
SDT 35.2 39.2 43.2 47.1 51.1 55.2 59.2 63.2 SDT 35.9 40.0 43.9 47.9 51.9 55.9 59.9 63.8
TC 47.0 44.6 41.8 39.2 36.6 34.0 31.4 28.8 TC 65.5 62.2 59.2 56.0 52.9 49.8 46.8 43.5
–4 kW 11.5 11.9 12.5 13.0 13.5 13.9 14.3 14.9 –4 kW 17.0 17.7 18.6 19.5 20.3 21.0 21.8 22.7
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2 63.2 SDT 36.1 40.1 44.0 48.0 51.9 55.9 59.9 63.8
TC 51.4 48.6 45.8 43.0 40.2 37.4 34.8 31.8 TC 70.8 67.5 64.2 60.8 57.5 54.3 51.0 47.7
–2 kW 11.7 12.1 12.8 13.4 14.0 14.5 15.0 15.6 –2 kW 17.3 18.1 19.1 20.0 21.0 21.7 22.6 23.5
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2 63.2 SDT 36.2 40.3 44.1 48.1 52.0 56.0 59.9 63.9
TC 55.5 52.8 49.8 47.0 44.0 41.2 38.4 35.5 TC 76.4 73.0 69.5 66.0 62.5 59.1 55.7 52.2
0 kW 11.9 12.4 13.1 13.8 14.5 15.0 15.6 16.3 0 kW 17.6 18.6 19.5 20.6 21.6 22.5 23.4 24.5
SDT 35.6 39.6 43.5 47.4 51.3 55.3 59.2 63.2 SDT 36.8 40.7 44.5 48.4 52.2 56.1 60.1 63.8
TC 59.9 57.0 54.0 51.0 48.2 45.2 42.2 39.3 TC 82.2 78.7 75.0 71.4 67.7 64.2 60.6 57.0
2 kW 12.1 12.7 13.5 14.2 14.9 15.5 16.1 16.9 2 kW 18.0 19.0 20.1 21.2 22.2 23.2 24.1 25.3
SDT 36.2 40.1 43.9 47.8 51.6 55.5 59.3 63.2 SDT 37.5 41.3 45.1 48.8 52.7 56.4 60.3 64.0
TC 64.3 61.4 58.2 55.2 52.2 49.0 46.0 42.9 TC 88.0 84.3 80.5 76.8 72.9 69.2 65.5 61.7
4 kW 12.3 13.0 13.8 14.6 15.4 16.0 16.7 17.5 4 kW 18.4 19.5 20.7 21.8 22.9 24.0 24.9 26.2
SDT 36.9 40.7 44.4 48.1 51.9 55.6 59.4 63.1 SDT 38.2 42.0 45.6 49.3 53.0 56.8 60.5 64.2
TC 69.2 66.0 62.8 59.6 56.4 53.2 50.0 46.8 TC 94.4 90.4 86.5 82.4 78.5 74.6 70.6 66.7
6 kW 12.5 13.3 14.1 15.0 15.8 16.5 17.3 18.1 6 kW 18.9 20.0 21.2 22.5 23.6 24.7 25.8 27.1
SDT 37.7 41.4 45.1 48.8 52.4 56.2 59.9 63.6 SDT 39.0 42.8 46.4 50.0 53.7 57.4 61.1 64.8
TC 74.1 70.8 67.4 64.0 60.8 57.4 54.0 50.7 TC 100.8 96.7 92.5 88.2 84.1 80.0 75.8 71.7
8 kW 12.8 13.6 14.5 15.4 16.3 17.1 17.8 18.8 8 kW 19.4 20.5 21.8 23.1 24.3 25.5 26.6 28.0
SDT 38.5 42.1 45.8 49.4 53.1 56.8 60.4 64.1 SDT 39.9 43.7 47.2 50.8 54.5 58.1 61.7 65.4
TC 78.9 75.6 72.0 68.6 65.2 61.6 58.2 54.7 TC 107.3 102.9 98.6 94.1 89.7 85.5 81.1 76.8
10 kW 13.0 13.8 14.8 15.8 16.7 17.6 18.4 19.4 10 kW 19.6 20.9 22.3 23.7 25.1 26.3 27.5 29.0
SDT 39.2 42.9 46.5 50.1 53.8 57.4 61.0 64.7 SDT 40.9 44.5 48.1 51.7 55.3 58.9 62.4 66.0
LEGEND
38AH028 kW — Compressor Power
Air Temperature Entering Condenser (C) SDT — Saturated Discharge Temperature at Compressor (C)
SST SST — Saturated Suction Temperature
(C) 24 28 32 36 40 44 48 52 TC — Gross Cooling Capacity (kW)
TC 51.1 48.6 46.0 43.4 40.8 38.4 36.0 33.3
–6 kW 13.4 14.0 14.7 15.3 15.9 16.5 17.1 17.7 NOTES:
SDT 35.4 39.3 43.3 47.3 51.2 55.2 59.1 63.1 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
2. Ratings include suction line losses due to an accumulator.
TC 55.2 52.8 50.0 47.4 44.8 42.2 39.6 37.0
–4 kW 13.8 14.3 15.1 15.8 16.5 17.1 17.7 18.4
SDT 36.0 39.8 43.7 47.6 51.4 55.3 59.2 63.0
TC 59.7 57.0 54.2 51.4 48.6 46.0 43.2 40.5
–2 kW 14.1 14.7 15.5 16.3 17.0 17.7 18.3 19.1
SDT 36.5 40.3 44.1 47.8 51.6 55.5 59.3 63.1
TC 64.5 61.6 58.6 55.6 52.8 49.8 47.0 43.9
0 kW 14.4 15.1 15.9 16.8 17.5 18.3 19.0 19.8
SDT 37.1 40.9 44.6 48.4 52.1 55.9 59.6 63.4
TC 69.3 66.2 63.2 60.0 57.0 54.0 51.0 47.9
2 kW 14.7 15.5 16.4 17.3 18.1 18.9 19.7 20.6
SDT 37.8 41.7 45.3 49.0 52.7 56.5 60.2 64.0
TC 74.0 71.0 67.6 64.4 61.2 58.0 54.8 51.6
4 kW 15.0 15.9 16.8 17.8 18.7 19.5 20.4 21.3
SDT 38.8 42.4 46.1 49.7 53.4 57.1 60.7 64.4
TC 79.4 76.2 72.6 69.2 65.8 62.4 59.2 55.6
6 kW 15.3 16.3 17.3 18.3 19.2 20.2 21.0 22.2
SDT 39.6 43.3 46.9 50.5 54.1 57.8 61.4 65.1
TC 85.0 81.6 77.8 74.2 70.6 67.0 63.4 59.8
8 kW 15.7 16.6 17.7 18.8 19.8 20.8 21.8 22.9
SDT 40.5 44.1 47.7 51.3 54.9 58.5 62.2 65.7
TC 90.6 86.8 83.0 79.0 75.2 71.6 67.8 64.0
10 kW 16.0 17.0 18.2 19.3 20.4 21.4 22.4 23.6
SDT 41.5 45.0 48.6 52.1 55.7 59.3 62.9 66.4

32
38AH CONDENSING UNIT CIRCUIT RATINGS — SI

38AH024 CIRCUIT NO. 1 OR 2 38AH034 CIRCUIT NO. 1


SST Air Temperature Entering Condenser (C) SST Air Temperature Entering Condenser (C)
(C) 24 28 32 36 40 44 48 52 (C) 24 28 32 36 40 44 48 52
TC 21.5 20.3 19.0 17.8 16.5 15.3 14.1 12.8 TC 25.0 23.7 22.3 21.0 19.6 18.3 17.0 15.6
–6 kW 5.6 5.8 6.1 6.3 6.5 6.7 6.9 7.1 –6 kW 6.7 7.0 7.3 7.7 8.0 8.3 8.5 8.9
SDT 35.2 39.2 43.2 47.1 51.1 55.2 59.2 63.2 SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.3 63.2
TC 23.5 22.3 20.9 19.6 18.3 17.0 15.7 14.4 TC 27.5 26.0 24.6 23.1 21.7 20.3 18.9 17.4
–4 kW 5.7 5.9 6.2 6.5 6.8 7.0 7.2 7.5 –4 kW 6.8 7.1 7.5 7.9 8.2 8.5 8.9 9.2
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2 63.2 SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.3 63.2
TC 25.7 24.3 22.9 21.5 20.1 18.7 17.4 15.9 TC 29.9 28.4 26.8 25.2 23.7 22.2 20.7 19.1
–2 kW 5.8 6.1 6.4 6.7 7.0 7.3 7.5 7.8 –2 kW 6.9 7.2 7.7 8.1 8.5 8.8 9.2 9.6
SDT 35.2 39.2 43.2 47.2 51.2 55.2 59.2 63.2 SDT 35.1 39.2 43.2 47.3 51.3 55.3 59.3 63.4
TC 27.8 26.4 24.9 23.5 22.0 20.6 19.2 17.7 TC 32.4 30.8 29.2 27.6 25.9 24.4 22.8 21.2
0 kW 5.9 6.2 6.6 6.9 7.2 7.5 7.8 8.2 0 kW 7.0 7.4 7.8 8.3 8.7 9.1 9.5 9.9
SDT 35.6 39.6 43.5 47.4 51.3 55.3 59.2 63.2 SDT 35.5 39.5 43.4 47.4 51.3 55.3 59.3 63.2
TC 29.9 28.5 27.0 25.5 24.1 22.6 21.1 19.7 TC 35.0 33.4 31.7 30.0 28.3 26.7 25.0 23.4
2 kW 6.1 6.4 6.7 7.1 7.5 7.8 8.1 8.5 2 kW 7.1 7.5 8.0 8.5 8.9 9.3 9.7 10.2
SDT 36.2 40.1 43.9 47.8 51.6 55.5 59.3 63.2 SDT 36.1 39.9 43.8 47.6 51.5 55.3 59.2 63.0
TC 32.2 30.7 29.1 27.6 26.1 24.5 23.0 21.4 TC 37.7 35.9 34.2 32.5 30.7 29.0 27.3 25.5
4 kW 6.2 6.5 6.9 7.3 7.7 8.0 8.4 8.8 4 kW 7.2 7.7 8.2 8.7 9.1 9.6 10.0 10.5
SDT 36.9 40.7 44.4 48.1 51.9 55.6 59.4 63.1 SDT 36.6 40.4 44.1 47.8 51.6 55.4 59.2 62.9
TC 34.6 33.0 31.4 29.8 28.2 26.6 25.0 23.4 TC 40.6 38.7 36.9 35.0 33.2 31.4 29.6 27.7
6 kW 6.3 6.6 7.1 7.5 7.9 8.3 8.6 9.1 6 kW 7.3 7.8 8.3 8.9 9.4 9.8 10.3 10.9
SDT 37.7 41.4 45.1 48.8 52.4 56.2 59.9 63.6 SDT 37.2 41.1 44.7 48.4 52.1 55.9 59.6 63.4
TC 37.0 35.4 33.7 32.0 30.4 28.7 27.0 25.4 TC 43.5 41.5 39.6 37.6 35.7 33.8 31.9 29.9
8 kW 6.4 6.8 7.2 7.7 8.1 8.5 8.9 9.4 8 kW 7.5 8.0 8.5 9.1 9.6 10.1 10.6 11.2
SDT 38.5 42.1 45.8 49.4 53.1 56.8 60.4 64.1 SDT 38.2 41.9 45.5 49.1 52.8 56.5 60.1 63.8
TC 39.5 37.8 36.0 34.3 32.6 30.8 29.1 27.3 TC 46.3 44.3 42.3 40.2 38.2 36.3 34.3 32.3
10 kW 6.5 6.9 7.4 7.9 8.4 8.8 9.2 9.7 10 kW 7.6 8.1 8.7 9.3 9.9 10.4 10.9 11.5
SDT 39.2 42.9 46.5 50.1 53.8 57.4 61.0 64.7 SDT 39.1 42.7 46.3 49.9 53.5 57.1 60.7 64.3

38AH028 CIRCUIT NO. 1 OR 2 38AH034 CIRCUIT NO. 2


SST Air Temperature Entering Condenser (C) SST Air Temperature Entering Condenser (C)
(C) 24 28 32 36 40 44 48 52 (C) 24 28 32 36 40 44 48 52
TC 25.5 24.3 23.0 21.7 20.4 19.2 18.0 16.7 TC 34.8 33.4 31.7 30.1 28.5 27.0 25.4 23.9
–6 kW 6.7 7.0 7.3 7.7 8.0 8.3 8.5 8.9 –6 kW 9.9 10.3 10.8 11.2 11.7 12.1 12.5 13.0
SDT 35.4 39.3 43.3 47.3 51.2 55.2 59.1 63.1 SDT 36.7 40.7 44.6 48.6 52.6 56.5 60.5 64.4
TC 27.6 26.4 25.0 23.7 22.4 21.1 19.8 18.5 TC 38.0 36.2 34.6 32.9 31.2 29.5 27.9 26.1
–4 kW 6.9 7.2 7.5 7.9 8.2 8.5 8.9 9.2 –4 kW 10.2 10.6 11.1 11.6 12.1 12.5 12.9 13.4
SDT 36.0 39.8 43.7 47.6 51.4 55.3 59.2 63.0 SDT 36.9 41.0 44.8 48.7 52.6 56.6 60.5 64.5
TC 29.8 28.5 27.1 25.7 24.3 23.0 21.6 20.3 TC 40.9 39.1 37.4 35.6 33.8 32.1 30.3 28.6
–2 kW 7.0 7.4 7.8 8.1 8.5 8.8 9.2 9.5 –2 kW 10.4 10.9 11.4 11.9 12.5 12.9 13.4 13.9
SDT 36.5 40.3 44.1 47.8 51.6 55.5 59.3 63.1 SDT 37.3 41.3 45.0 48.8 52.7 56.6 60.5 64.3
TC 32.2 30.8 29.3 27.8 26.4 24.9 23.5 22.0 TC 44.0 42.2 40.3 38.4 36.6 34.7 32.9 31.0
0 kW 7.2 7.6 8.0 8.4 8.8 9.1 9.5 9.9 0 kW 10.6 11.2 11.7 12.3 12.9 13.4 13.9 14.5
SDT 37.1 40.9 44.6 48.4 52.1 55.9 59.6 63.4 SDT 38.1 41.8 45.6 49.3 53.1 56.9 60.8 64.4
TC 34.7 33.1 31.6 30.0 28.5 27.0 25.5 23.9 TC 47.2 45.3 43.3 41.4 39.4 37.5 35.6 33.6
2 kW 7.4 7.8 8.2 8.6 9.1 9.5 9.8 10.3 2 kW 10.9 11.5 12.1 12.7 13.3 13.9 14.4 15.1
SDT 37.8 41.7 45.3 49.0 52.7 56.5 60.2 64.0 SDT 38.8 42.7 46.3 50.0 53.8 57.5 61.3 65.0
TC 37.0 35.5 33.8 32.2 30.6 29.0 27.4 25.8 TC 50.4 48.4 46.3 44.3 42.2 40.2 38.2 36.1
4 kW 7.5 7.9 8.4 8.9 9.3 9.8 10.2 10.7 4 kW 11.2 11.8 12.5 13.1 13.8 14.4 14.9 15.7
SDT 38.8 42.4 46.1 49.7 53.4 57.1 60.7 64.4 SDT 39.8 43.5 47.1 50.8 54.4 58.1 61.8 65.4
TC 39.7 38.1 36.3 34.6 32.9 31.2 29.6 27.8 TC 53.9 51.7 49.6 47.4 45.3 43.2 41.0 38.9
6 kW 7.7 8.1 8.6 9.2 9.6 10.1 10.5 11.1 6 kW 11.6 12.2 12.9 13.6 14.2 14.9 15.5 16.2
SDT 39.6 43.3 46.9 50.5 54.1 57.8 61.4 65.1 SDT 40.7 44.4 48.0 51.6 55.2 58.9 62.5 66.2
TC 42.5 40.8 38.9 37.1 35.3 33.5 31.7 29.9 TC 57.4 55.2 52.9 50.6 48.4 46.2 43.9 41.7
8 kW 7.8 8.3 8.9 9.4 9.9 10.4 10.9 11.4 8 kW 11.9 12.5 13.3 14.0 14.7 15.4 16.0 16.8
SDT 40.5 44.1 47.7 51.3 54.9 58.5 62.2 65.7 SDT 41.7 45.4 48.9 52.5 56.1 59.7 63.3 66.9
TC 45.3 43.4 41.5 39.5 37.6 35.8 33.9 32.0 TC 61.0 58.6 56.3 53.9 51.5 49.2 46.8 44.5
10 kW 8.0 8.5 9.1 9.7 10.2 10.7 11.2 11.8 10 kW 12.1 12.8 13.6 14.4 15.2 15.9 16.6 17.4
SDT 41.5 45.0 48.6 52.1 55.7 59.3 62.9 66.4 SDT 42.8 46.3 49.9 53.4 57.0 60.6 64.1 67.7
LEGEND NOTES:
kW — Compressor Power 1. Ratings are based on 8.3 C superheat and use of R-22 refrigerant.
SDT — Saturated Discharge Temperature at Compressor (C) 2. Ratings include suction line losses due to an accumulator.
SST — Saturated Suction Temperature
TC — Gross Cooling Capacity (kW)

33
Performance data (cont)
38AH CONDENSING UNIT RATINGS — ENGLISH

38AH024 38AH034
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 75 85 95 100 105 115 125 (F) 75 85 95 100 105 115 125
TC 141.8 130.6 119.0 113.2 107.4 96.2 84.8 TC 198.0 185.5 171.2 164.4 157.6 144.4 131.0
20 kW 11.4 11.7 12.4 12.7 12.9 13.3 13.8 20 kW 16.6 17.4 18.5 19.0 19.5 20.4 21.4
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 97.0 107.0 117.0 122.0 127.0 137.0 147.0
TC 161.6 149.4 136.8 130.6 124.4 112.0 99.6 TC 223.5 209.4 194.4 187.0 179.6 165.3 150.8
25 kW 11.7 12.1 12.9 13.3 13.6 14.2 14.8 25 kW 17.1 18.1 19.3 19.8 20.5 21.5 22.6
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 97.0 107.0 117.0 122.0 127.0 137.0 147.0
TC 181.6 168.2 154.8 148.0 141.4 128.0 114.6 TC 249.4 234.3 217.7 210.0 202.3 186.0 170.2
30 kW 11.9 12.5 13.5 13.9 14.3 15.0 15.8 30 kW 17.6 18.7 20.1 20.7 21.3 22.5 23.8
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 97.0 107.0 117.0 122.0 127.0 137.0 147.0
TC 202.4 188.4 174.4 167.4 160.4 146.4 132.4 TC 276.2 260.0 243.0 235.5 226.5 209.8 193.2
35 kW 12.2 12.9 14.0 14.5 14.9 15.8 16.6 35 kW 18.0 19.4 20.8 21.5 22.2 23.6 25.0
SDT 97.0 107.0 116.0 121.0 126.0 135.0 145.0 SDT 99.0 109.0 118.0 123.0 128.0 137.0 147.0
TC 223.0 208.0 194.0 186.8 179.6 165.0 150.5 TC 304.5 287.0 269.0 260.0 251.0 233.5 215.8
40 kW 12.5 13.4 14.5 15.0 15.6 16.5 17.5 40 kW 18.7 20.0 21.7 22.4 23.2 24.7 26.2
SDT 98.0 108.0 117.0 122.0 126.0 136.0 146.0 SDT 101.0 110.0 119.0 124.0 129.0 138.0 147.0
TC 247.6 232.0 216.0 208.0 200.0 184.4 168.6 TC 335.0 316.0 297.0 287.0 278.0 259.0 240.0
45 kW 12.8 13.8 15.0 15.6 16.2 17.3 18.4 45 kW 19.3 20.7 22.6 23.3 24.2 25.8 27.4
SDT 101.0 110.0 119.0 123.0 128.0 137.0 146.0 SDT 103.0 112.0 121.0 126.0 130.0 140.0 149.0
TC 268.0 254.0 236.0 228.0 220.0 204.0 188.0 TC 367.0 346.0 325.0 314.0 305.0 283.0 262.0
50 kW 13.1 14.2 15.6 16.2 16.8 18.0 19.3 50 kW 19.7 21.4 23.4 24.3 25.2 27.0 28.8
SDT 103.0 112.0 121.0 125.0 130.0 139.0 148.0 SDT 106.0 115.0 124.0 128.0 133.0 141.0 150.0
LEGEND
38AH028 kW — Compressor Power
SST Air Temperature Entering Condenser (F) SDT — Saturated Discharge Temperature at Compressor (F)
(F) 75 85 95 100 105 115 125 SST — Saturated Suction Temperature
TC — Gross Cooling Capacity (1000 Btuh)
TC 168.4 157.6 145.6 139.8 134.0 122.8 111.4
20 kW 13.5 14.1 15.0 15.4 15.8 16.6 17.4 NOTES:
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
TC 189.0 177.4 164.6 158.4 152.2 140.2 128.0 2. Ratings include suction line losses due to an accumulator.
25 kW 13.9 14.6 15.7 16.1 16.6 17.4 18.3
SDT 97.0 106.0 116.0 121.0 126.0 135.0 145.0
TC 210.2 197.4 183.8 177.2 170.6 157.4 144.2
30 kW 14.3 15.2 16.3 16.8 17.3 18.3 19.3
SDT 98.0 107.0 117.0 121.0 126.0 136.0 146.0
TC 231.6 220.0 204.0 197.6 190.4 176.4 162.6
35 kW 14.8 15.7 17.0 17.6 18.1 19.2 20.3
SDT 99.0 109.0 118.0 123.0 128.0 137.0 147.0
TC 256.8 242.0 226.0 218.0 210.0 195.2 179.8
40 kW 15.1 16.3 17.7 18.3 18.9 20.2 21.5
SDT 102.0 111.0 120.0 125.0 129.0 138.0 147.0
TC 284.0 266.0 250.0 242.0 232.0 216.0 199.0
45 kW 15.7 16.9 18.3 19.0 19.7 21.0 22.3
SDT 104.0 113.0 122.0 127.0 131.0 140.0 149.0
TC 306.0 292.0 272.0 264.0 256.0 238.0 221.0
50 kW 16.0 17.4 19.0 19.8 20.6 22.0 23.5
SDT 106.0 115.0 124.0 129.0 133.0 142.0 151.0

34
38AH CONDENSING UNIT CIRCUIT RATINGS — ENGLISH

38AH024 CIRCUIT NO. 1 OR 2 38AH034 CIRCUIT NO. 1


SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 75 85 95 100 105 115 125 (F) 75 85 95 100 105 115 125
TC 70.9 65.3 59.5 56.6 53.7 48.1 42.4 TC 82.4 76.5 70.2 67.1 64.0 58.0 51.9
20 kW 5.7 5.9 6.2 6.3 6.5 6.7 6.9 20 kW 6.7 7.0 7.5 7.7 7.9 8.3 8.7
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC 80.8 74.7 68.4 65.3 62.2 56.0 49.8 TC 93.8 87.4 80.4 77.0 73.6 67.0 60.3
25 kW 5.8 6.1 6.5 6.7 6.8 7.1 7.4 25 kW 6.9 7.3 7.8 8.0 8.3 8.7 9.2
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC 90.8 84.1 77.4 74.0 70.7 64.0 57.3 TC 105.4 98.3 90.7 87.0 83.3 76.0 68.7
30 kW 6.0 6.3 6.7 7.0 7.2 7.5 7.9 30 kW 7.0 7.5 8.1 8.4 8.6 9.1 9.7
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0
TC 101.2 94.2 87.2 83.7 80.2 73.2 66.2 TC 117.2 110.0 102.0 98.5 94.5 86.8 79.2
35 kW 6.1 6.5 7.0 7.2 7.5 7.9 8.3 35 kW 7.1 7.7 8.3 8.6 8.9 9.5 10.1
SDT 97.0 107.0 116.0 121.0 126.0 135.0 145.0 SDT 97.0 106.0 116.0 121.0 126.0 135.0 145.0
TC 111.5 104.0 97.0 93.4 89.8 82.5 75.3 TC 130.5 122.0 114.0 110.0 106.0 97.5 89.3
40 kW 6.3 6.7 7.3 7.5 7.8 8.3 8.8 40 kW 7.3 7.9 8.6 8.9 9.2 9.9 10.5
SDT 98.0 108.0 117.0 122.0 126.0 136.0 146.0 SDT 97.0 107.0 116.0 121.0 126.0 135.0 145.0
TC 123.8 116.0 108.0 104.0 100.0 92.2 84.3 TC 145.0 135.0 127.0 122.0 118.0 109.0 100.0
45 kW 6.4 6.9 7.5 7.8 8.1 8.6 9.2 45 kW 7.4 8.1 8.9 9.2 9.6 10.3 11.0
SDT 101.0 110.0 119.0 123.0 128.0 137.0 146.0 SDT 99.0 109.0 118.0 123.0 127.0 137.0 147.0
TC 134.0 127.0 118.0 114.0 110.0 102.0 94.0 TC 158.0 149.0 139.0 134.0 130.0 120.0 110.5
50 kW 6.6 7.1 7.8 8.1 8.4 9.0 9.6 50 kW 7.6 8.3 9.2 9.5 9.9 10.7 11.5
SDT 103.0 112.0 121.0 125.0 130.0 139.0 148.0 SDT 102.0 111.0 120.0 125.0 129.0 138.0 147.0

38AH028 CIRCUIT NO. 1 OR 2 38AH034 CIRCUIT NO. 2


SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 75 85 95 100 105 115 125 (F) 75 85 95 100 105 115 125
TC 84.2 78.8 72.8 69.9 67.0 61.4 55.7 TC 115.6 109.0 101.0 97.3 93.6 86.4 79.1
20 kW 6.7 7.0 7.5 7.7 7.9 8.3 8.7 20 kW 9.9 10.4 11.0 11.3 11.6 12.1 12.7
SDT 95.0 105.0 115.0 120.0 125.0 135.0 145.0 SDT 98.0 108.0 118.0 123.0 128.0 138.0 148.0
TC 94.5 88.7 82.3 79.2 76.1 70.1 64.0 TC 129.7 122.0 114.0 110.0 106.0 98.3 90.5
25 kW 6.9 7.3 7.8 8.1 8.3 8.7 9.2 25 kW 10.2 10.8 11.5 11.8 12.2 12.8 13.5
SDT 97.0 106.0 116.0 121.0 126.0 135.0 145.0 SDT 98.0 108.0 118.0 123.0 128.0 138.0 148.0
TC 105.1 98.7 91.9 88.6 85.3 78.7 72.1 TC 144.0 136.0 127.0 123.0 119.0 110.0 101.5
30 kW 7.2 7.6 8.2 8.4 8.7 9.2 9.7 30 kW 10.6 11.2 12.0 12.3 12.7 13.4 14.1
SDT 98.0 107.0 117.0 121.0 126.0 136.0 146.0 SDT 98.0 109.0 118.0 123.0 128.0 138.0 148.0
TC 115.8 110.0 102.0 98.8 95.2 88.2 81.3 TC 159.0 150.0 141.0 137.0 132.0 123.0 114.0
35 kW 7.4 7.9 8.5 8.8 9.1 9.6 10.2 35 kW 10.9 11.7 12.5 12.9 13.3 14.1 14.9
SDT 99.0 109.0 118.0 123.0 128.0 137.0 147.0 SDT 101.0 111.0 120.0 125.0 129.0 139.0 149.0
TC 128.4 121.0 113.0 109.0 105.0 97.6 89.9 TC 174.0 165.0 155.0 150.0 145.0 136.0 126.5
40 kW 7.6 8.2 8.8 9.2 9.5 10.1 10.7 40 kW 11.4 12.1 13.1 13.5 14.0 14.8 15.7
SDT 102.0 111.0 120.0 125.0 129.0 138.0 147.0 SDT 104.0 113.0 122.0 127.0 131.0 140.0 149.0
TC 142.0 133.0 125.0 121.0 116.0 108.0 99.5 TC 190.0 181.0 170.0 165.0 160.0 150.0 140.0
45 kW 7.8 8.4 9.2 9.5 9.9 10.5 11.2 45 kW 11.9 12.6 13.7 14.1 14.6 15.5 16.4
SDT 104.0 113.0 122.0 127.0 131.0 140.0 149.0 SDT 106.0 115.0 124.0 129.0 133.0 142.0 151.0
TC 153.0 146.0 136.0 132.0 128.0 119.0 110.5 TC 209.0 197.0 186.0 180.0 175.0 163.0 151.5
50 kW 8.0 8.7 9.5 9.9 10.3 11.0 11.8 50 kW 12.1 13.1 14.2 14.8 15.3 16.3 17.4
SDT 106.0 115.0 124.0 129.0 133.0 142.0 151.0 SDT 110.0 118.0 127.0 131.0 136.0 144.0 153.0
LEGEND NOTES:
kW — Compressor Power 1. Ratings are based on 15 F superheat and use of R-22 refrigerant.
SDT — Saturated Discharge Temperature at Compressor (F) 2. Ratings include suction line losses due to an accumulator.
SST — Saturated Suction Temperature
TC — Gross Cooling Capacity (1000 Btuh)

35
Performance data (cont)
38AH/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — SI
38AH024 AND 40RM016 WITH STANDARD 3-ROW COIL 38AH024 AND 40RM028 WITH STANDARD 3-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 2100 2800 3500 Air 3500 4700 5900
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 20 16 22 20 16 22 20 16 (Edb) 22 20 16 22 20 16 22 20 16
TC 63.9 59.4 53.2 67.3 62.9 56.9 69.8 64.9 59.2 TC 77.3 70.6 65.0 79.7 73.4 68.9 81.2 76.1 72.2
24 SHC 32.7 37.7 53.2 36.4 43.2 56.9 40.1 48.3 59.2 24 SHC 43.2 51.6 65.0 49.3 60.1 68.9 55.2 67.6 72.2
kW 12.18 11.90 11.52 12.39 12.11 11.75 12.54 12.24 11.89 kW 13.00 12.58 12.24 13.14 12.76 12.48 13.24 12.92 12.68
TC 62.2 57.6 51.7 65.4 61.0 55.3 67.8 63.0 57.6 TC 75.1 68.1 63.1 77.4 71.1 67.0 78.8 73.7 70.2
28 SHC 32.0 36.9 51.7 35.7 42.4 55.3 39.4 47.3 57.6 28 SHC 42.4 50.9 63.1 48.5 59.1 67.0 54.4 66.6 70.2
kW 13.06 12.78 12.40 13.26 12.99 12.63 13.41 13.11 12.77 kW 13.87 13.43 13.12 14.01 13.62 13.36 14.10 13.78 13.56
TC 60.4 56.0 50.3 63.5 59.2 53.7 65.8 61.1 56.0 TC 72.8 65.5 61.1 74.8 68.7 65.0 76.1 71.2 68.1
32 SHC 31.4 36.2 50.3 35.0 41.5 53.7 38.7 46.3 56.0 32 SHC 41.5 50.2 61.1 47.6 58.1 65.0 53.5 65.5 68.1
kW 13.89 13.51 13.01 14.16 13.79 13.31 14.36 13.95 13.51 kW 14.97 14.34 13.96 15.15 14.62 14.29 15.26 14.83 14.56
TC 58.6 54.2 48.8 61.5 57.3 52.1 63.7 59.1 54.4 TC 70.4 62.9 59.1 72.2 66.3 62.9 73.4 68.7 66.0
36 SHC 30.7 35.4 48.8 34.2 40.6 52.1 38.0 45.3 54.4 36 SHC 40.6 49.5 59.1 46.7 57.0 62.9 52.5 64.3 66.0
kW 14.91 14.51 14.02 15.17 14.79 14.32 15.37 14.96 14.52 kW 15.98 15.30 14.96 16.15 15.61 15.30 16.26 15.83 15.58
TC 56.7 52.3 47.0 59.5 55.2 50.3 61.7 57.1 52.5 TC 68.3 60.4 57.1 69.9 64.0 60.9 71.1 66.4 64.0
40 SHC 30.0 34.6 47.0 33.5 39.7 50.3 37.3 44.3 52.5 40 SHC 39.9 48.8 57.1 45.9 56.0 60.9 51.8 63.3 64.0
kW 15.84 15.34 14.74 16.15 15.67 15.10 16.40 15.88 15.36 kW 17.15 16.25 15.88 17.34 16.66 16.31 17.47 16.94 16.66
TC 54.8 50.5 45.5 57.3 53.2 48.6 59.5 55.0 50.8 TC 65.8 57.7 55.0 67.2 61.4 58.7 68.3 63.7 61.7
44 SHC 29.2 33.8 45.5 32.8 38.8 48.6 36.5 43.2 50.8 44 SHC 38.9 48.0 55.0 44.9 54.9 58.7 50.8 62.1 61.7
kW 16.73 16.11 15.40 17.09 16.50 15.84 17.40 16.76 16.16 kW 18.30 17.14 16.76 18.50 17.67 17.28 18.65 18.00 17.72
TC 52.8 48.6 43.8 55.1 51.1 46.8 57.2 52.9 49.0 TC 63.2 55.0 52.8 64.4 58.8 56.4 65.4 61.0 59.4
48 SHC 28.5 32.9 43.8 32.0 37.8 46.8 35.7 42.1 49.0 48 SHC 38.0 47.2 52.8 43.9 53.8 56.4 49.8 60.9 59.4
kW 17.72 17.09 16.38 18.07 17.47 16.82 18.39 17.73 17.15 kW 19.28 18.04 17.72 19.46 18.62 18.26 19.60 18.95 18.71
TC 50.8 46.6 42.1 53.0 49.0 44.9 55.0 50.7 47.1 TC 60.8 52.3 50.7 61.8 56.3 54.2 62.7 58.4 57.1
52 SHC 27.7 32.1 42.1 31.2 36.9 44.9 35.0 41.0 47.1 52 SHC 37.1 46.5 50.7 43.0 52.7 54.2 48.9 58.1 57.1
kW 18.71 18.07 17.37 19.05 18.44 17.81 19.37 18.70 18.14 kW 20.25 18.94 18.69 20.41 19.55 19.24 20.54 19.89 19.69

38AH024 AND 40RM024 WITH STANDARD 3-ROW COIL 38AH028 AND 40RM024 WITH STANDARD 3-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 2900 3800 4700 Air 2900 3800 4700
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 20 16 22 20 16 22 20 16 (Edb) 22 20 16 22 20 16 22 20 16
TC 71.3 66.0 59.9 74.4 68.9 63.5 76.4 71.3 66.3 TC 77.4 71.9 64.7 81.1 75.1 68.6 83.5 77.9 71.6
24 SHC 38.0 45.1 59.9 43.1 52.1 63.5 47.6 58.3 66.3 24 SHC 40.4 47.5 64.7 45.5 54.9 68.6 50.1 61.3 71.6
kW 12.63 12.31 11.93 12.82 12.48 12.15 12.94 12.63 12.32 kW 15.16 14.77 14.25 15.42 14.99 14.53 15.59 15.20 14.75
TC 69.2 64.0 58.1 72.2 66.9 61.7 74.1 69.2 64.5 TC 75.6 70.1 63.2 79.1 73.2 67.0 81.3 75.9 70.0
28 SHC 37.2 44.3 58.1 42.3 51.2 61.7 46.8 57.3 64.5 28 SHC 39.7 46.8 63.2 44.8 54.0 67.0 49.3 60.4 70.0
kW 13.50 13.18 12.81 13.69 13.35 13.03 13.81 13.50 13.20 kW 16.26 15.96 15.58 16.46 16.14 15.79 16.59 16.28 15.96
TC 67.1 62.0 56.4 69.9 64.7 59.9 71.7 66.9 62.6 TC 73.4 68.1 61.6 76.7 71.1 65.3 78.8 73.6 68.2
32 SHC 36.3 43.5 56.4 41.5 50.2 59.9 45.9 56.2 62.6 32 SHC 38.8 45.9 61.6 43.9 53.1 65.3 48.4 59.3 68.2
kW 14.48 14.03 13.55 14.72 14.27 13.84 14.87 14.46 14.08 kW 17.36 16.95 16.44 17.62 17.18 16.72 17.79 17.38 16.95
TC 65.0 59.9 54.7 67.5 62.5 58.0 69.2 64.6 60.7 TC 71.3 66.0 59.8 74.4 68.9 63.4 76.4 71.4 66.3
36 SHC 35.5 42.6 54.7 40.6 49.2 58.0 45.1 55.2 60.7 36 SHC 38.0 45.1 59.8 43.1 52.1 63.4 47.6 58.3 66.3
kW 15.49 15.03 14.55 15.72 15.27 14.86 15.87 15.46 15.10 kW 18.51 17.98 17.36 18.82 18.27 17.72 19.02 18.52 18.01
TC 62.9 57.8 52.7 65.4 60.4 56.1 67.0 62.4 58.7 TC 69.1 63.9 58.0 72.1 66.7 61.5 74.0 69.0 64.3
40 SHC 34.7 41.8 52.7 39.8 48.3 56.1 44.3 54.2 58.7 40 SHC 37.1 44.2 58.0 42.2 51.1 61.5 46.7 57.2 64.3
kW 16.54 15.96 15.38 16.82 16.26 15.76 17.00 16.49 16.06 kW 19.61 18.96 18.23 19.98 19.32 18.67 20.22 19.60 19.02
TC 60.6 55.6 50.9 62.9 58.1 54.1 64.4 60.0 56.7 TC 66.9 61.7 56.2 69.6 64.5 59.6 71.4 66.7 62.4
44 SHC 33.8 40.9 50.9 39.0 47.3 54.1 43.4 53.1 56.7 44 SHC 36.2 43.4 56.2 41.4 50.1 59.6 45.8 56.1 62.4
kW 17.56 16.84 16.17 17.89 17.20 16.63 18.10 17.47 17.00 kW 20.78 20.11 19.39 21.15 20.47 19.84 21.38 20.76 20.19
TC 58.2 53.4 48.9 60.4 55.8 52.1 61.8 57.5 54.6 TC 64.7 59.6 54.4 67.3 62.3 57.8 68.9 64.3 60.4
48 SHC 32.8 40.0 48.9 38.0 46.2 52.1 42.5 21.9 54.6 48 SHC 35.4 42.5 54.4 40.5 49.1 57.8 45.0 21.9 60.4
kW 18.54 17.80 17.14 18.86 18.17 17.61 19.07 18.43 17.99 kW 21.75 21.06 20.35 22.10 21.42 20.80 22.33 21.70 21.17
TC 56.0 51.1 46.9 58.0 53.5 50.0 59.3 55.1 52.5 TC 62.0 57.2 52.4 64.3 59.6 55.6 65.7 61.5 58.1
52 SHC 31.9 39.0 46.9 37.2 45.2 50.0 41.6 50.8 52.5 52 SHC 34.3 41.5 52.4 39.4 47.9 55.6 43.9 53.7 58.1
kW 19.51 18.76 18.12 19.82 19.12 18.60 20.02 19.38 18.97 kW 23.63 22.55 21.49 24.15 23.10 22.20 24.48 23.52 22.76

LEGEND 5. Formulas (cooling)


Edb — Entering Dry Bulb sensible heat capacity (kW)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.23 x 10-3 x (L/s)
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (kW)
TC — Total Capacity (kW) total capacity (kW)
hldb = hedb –
NOTES: 1.20 x 10-3 x (L/s)
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil (kJ/kg).
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. 6. Combination ratings are based on a 1.1° C line loss. For a close-coupled sys-
4. Gross capacities shown do not include a deduction for evaporator-fan motor tem (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
heat. Sizes table are based on 1.1° C line loss.

36
38AH/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — SI (cont)
38AH028 AND 40RM028 WITH STANDARD 3-ROW COIL 38AH034 AND 40RM028 WITH STANDARD 3-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 3500 4700 5900 Air 35000 4700 5900
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 20 16 22 20 16 22 20 16 (Edb) 22 20 16 22 20 16 22 20 16
TC 84.1 78.3 70.6 87.3 80.6 74.8 89.3 83.5 78.2 TC 93.1 88.9 78.1 97.3 90.2 82.5 99.8 93.5 86.2
24 SHC 45.8 53.8 70.6 52.0 63.2 74.8 57.9 70.9 78.2 24 SHC 49.1 56.8 78.1 55.5 67.3 82.5 61.4 75.3 86.2
kW 15.64 15.22 14.67 15.87 15.39 14.97 16.01 15.60 15.22 kW 18.80 18.47 17.63 19.13 18.57 17.97 19.32 18.83 18.26
TC 82.1 75.9 68.9 85.0 78.4 73.0 86.9 81.3 76.4 TC 90.8 86.1 76.1 94.8 87.7 80.4 97.2 90.9 84.1
28 SHC 45.0 53.1 68.9 51.2 62.3 73.0 57.1 69.9 76.4 28 SHC 48.2 56.0 76.1 54.6 66.2 80.4 60.5 74.2 84.1
kW 16.63 16.28 15.89 16.79 16.42 16.12 16.89 16.58 16.31 kW 20.03 19.66 18.86 20.35 19.79 19.21 20.54 20.04 19.50
TC 79.6 73.2 67.0 82.3 75.9 70.9 83.9 78.6 74.3 TC 88.5 83.4 74.2 92.2 85.3 78.5 94.4 88.3 82.1
32 SHC 44.1 52.3 67.0 50.2 61.2 70.9 56.1 68.7 74.3 32 SHC 47.4 55.2 74.2 53.7 65.2 78.5 59.6 73.1 82.1
kW 17.85 17.35 16.86 18.06 17.56 17.17 18.19 17.77 17.43 kW 21.40 20.89 19.97 21.77 21.08 20.40 21.99 21.38 20.76
TC 77.4 70.6 65.0 79.9 73.5 68.9 81.4 76.2 72.2 TC 86.0 80.5 72.1 89.4 82.6 76.4 91.5 85.6 79.9
36 SHC 43.3 51.6 65.0 49.4 60.1 68.9 55.2 67.7 72.2 36 SHC 46.5 54.4 72.1 52.7 64.0 76.4 58.6 71.9 79.9
kW 19.12 18.44 17.88 19.37 18.73 18.27 19.52 19.00 18.60 kW 22.88 22.30 21.44 23.23 22.52 21.87 23.44 22.83 22.24
TC 75.0 67.9 63.0 77.2 71.0 66.8 78.7 73.6 70.1 TC 83.6 77.6 70.1 86.7 80.0 74.2 88.7 82.9 77.7
40 SHC 42.4 50.9 63.0 48.4 59.1 66.8 54.3 66.5 70.1 40 SHC 45.6 53.6 70.1 51.8 62.9 74.2 57.7 70.7 77.7
kW 20.35 19.46 18.84 20.63 19.85 19.33 20.81 20.18 19.74 kW 24.24 23.49 22.55 24.63 23.79 23.07 24.87 24.15 23.50
TC 72.5 65.2 60.9 74.5 68.5 64.7 75.9 71.0 67.9 TC 81.1 74.7 67.9 84.0 77.3 72.1 85.8 80.2 75.5
44 SHC 41.4 50.1 60.9 47.5 58.0 64.7 53.4 65.3 67.9 44 SHC 44.6 52.8 67.9 50.8 61.8 72.1 56.7 69.5 75.5
kW 21.52 20.56 20.00 21.78 20.99 20.50 21.96 21.32 20.92 kW 25.66 24.72 23.71 26.09 25.11 24.32 26.35 25.53 24.83
TC 70.1 62.6 58.9 71.9 66.0 62.6 73.1 68.4 65.7 TC 78.4 71.7 65.7 80.9 74.5 69.8 82.6 77.2 73.1
48 SHC 40.6 49.4 58.9 46.6 56.9 62.6 52.4 64.2 65.7 48 SHC 43.6 51.9 65.7 49.7 60.6 69.8 55.6 68.1 73.1
kW 22.49 21.46 20.96 22.73 21.92 21.47 22.90 22.25 21.89 kW 27.17 25.99 24.94 27.62 26.49 25.65 27.91 26.97 26.24
TC 67.0 59.4 56.5 68.5 62.9 60.1 69.5 65.1 63.0 TC 75.8 68.7 63.4 78.2 71.8 67.4 79.7 74.5 70.7
52 SHC 39.4 48.5 56.5 45.4 55.6 60.1 51.2 62.8 63.0 52 SHC 42.7 51.1 63.4 48.8 59.4 67.4 54.7 66.9 70.7
kW 24.77 23.07 22.41 25.10 23.84 23.21 25.33 24.34 23.87 kW 28.74 27.45 26.51 29.16 28.01 27.23 29.44 28.50 27.83

38AH028 AND 40RM034 WITH STANDARD 3-ROW COIL 38AH034 AND 40RM034 WITH STANDARD 3-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 4250 5650 7050 Air 4250 5650 7050
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 20 16 22 20 16 22 20 16 (Edb) 22 20 16 22 20 16 22 20 16
TC 90.2 81.9 75.9 92.7 85.5 80.5 94.4 88.5 84.3 TC 100.3 92.2 84.4 103.9 96.2 89.4 106.2 99.5 93.4
24 SHC 50.5 61.0 75.9 58.3 70.8 80.5 65.4 79.8 84.3 24 SHC 54.4 65.3 84.4 62.2 75.4 89.4 69.3 84.8 93.4
kW 16.07 15.48 15.05 16.25 15.73 15.38 16.37 15.95 15.63 kW 19.36 18.73 18.12 19.65 19.04 18.51 19.82 19.30 18.82
TC 87.8 79.6 73.9 90.2 83.1 78.5 91.7 86.0 82.2 TC 97.8 89.6 82.1 101.2 93.4 87.1 103.3 96.7 91.1
28 SHC 49.6 60.0 73.9 57.4 69.7 78.5 64.5 78.7 82.2 28 SHC 53.4 64.2 82.1 61.2 74.2 87.1 68.3 83.5 91.1
kW 16.95 16.49 16.17 17.08 16.68 16.43 17.16 16.84 16.63 kW 20.59 19.93 19.34 20.86 20.24 19.74 21.02 20.50 20.06
TC 85.0 76.9 71.7 87.1 80.2 76.1 88.5 82.9 79.7 TC 95.1 86.9 80.0 98.2 90.7 84.8 100.1 93.8 88.8
32 SHC 48.5 58.9 71.7 56.3 68.4 76.1 63.4 77.4 79.7 32 SHC 52.4 63.1 80.0 60.2 73.0 84.8 67.3 82.2 88.8
kW 18.27 17.64 17.23 18.43 17.89 17.58 18.55 18.11 17.86 kW 22.06 21.24 20.55 22.37 21.62 21.03 22.56 21.93 21.43
TC 82.5 74.4 69.5 84.4 77.6 73.9 85.8 80.3 77.5 TC 92.3 84.1 77.6 95.1 87.7 82.4 96.9 90.8 86.2
36 SHC 47.6 57.9 69.5 55.4 67.3 73.9 62.5 76.2 77.5 36 SHC 51.3 61.9 77.6 59.1 71.7 82.4 66.2 80.9 86.2
kW 19.63 18.82 18.33 19.82 19.14 18.77 19.96 19.41 19.13 kW 23.53 22.67 22.01 23.82 23.05 22.50 24.00 23.37 22.90
TC 79.9 71.7 67.3 81.5 74.9 71.6 82.7 77.5 75.1 TC 89.6 81.3 75.3 92.1 84.8 80.0 93.8 87.8 83.8
40 SHC 46.5 56.8 67.3 54.4 66.1 71.6 61.5 74.9 75.1 40 SHC 50.3 60.7 75.3 58.1 70.5 80.0 65.2 79.5 83.8
kW 20.96 19.94 19.38 21.17 20.33 19.92 21.32 20.66 20.36 kW 24.99 23.95 23.20 25.30 24.39 23.78 25.51 24.77 24.26
TC 77.1 69.0 65.0 78.6 72.1 69.2 79.7 74.6 72.6 TC 86.8 78.5 72.9 89.1 81.9 77.5 90.6 84.8 81.2
44 SHC 45.5 55.6 65.0 53.3 64.9 69.2 60.5 73.6 72.6 44 SHC 49.2 59.6 72.9 57.0 69.2 77.5 64.1 78.2 81.2
kW 22.12 21.07 20.53 22.31 21.46 21.08 22.45 21.79 21.53 kW 26.50 25.28 24.45 26.84 25.78 25.13 27.07 26.21 25.68
TC 74.4 66.4 62.7 75.7 69.4 66.8 76.7 71.8 70.1 TC 83.7 75.5 70.4 85.6 78.7 74.9 87.0 81.5 78.5
48 SHC 44.4 54.6 62.7 52.3 63.7 66.8 59.5 72.4 70.1 48 SHC 48.0 58.3 70.4 55.8 67.8 74.9 62.9 76.7 78.5
kW 23.08 21.99 21.48 23.25 22.39 22.04 23.38 22.72 22.49 kW 28.11 26.66 25.77 28.45 27.24 26.55 28.70 27.72 27.19
TC 70.9 63.2 60.0 71.8 65.9 63.8 72.6 68.1 67.0 TC 80.9 72.6 67.9 82.6 75.8 72.3 83.9 78.5 75.9
52 SHC 43.1 53.2 60.0 51.0 62.2 63.8 58.2 68.1 67.0 52 SHC 46.9 57.1 67.9 54.7 66.5 72.3 61.9 75.4 75.9
kW 25.63 23.91 23.19 25.85 24.51 24.05 26.03 25.02 24.76 kW 29.65 28.16 27.31 29.97 28.74 28.11 30.20 29.22 28.75

LEGEND 5. Formulas (cooling)


Edb — Entering Dry Bulb sensible heat capacity (kW)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.23 x 10-3 x (L/s)
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (kW)
TC — Total Capacity (kW) total capacity (kW)
hldb = hedb –
NOTES: 1.20 x 10-3 x (L/s)
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil (kJ/kg).
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. 6. Combination ratings are based on a 1.1° C line loss. For a close-coupled sys-
4. Gross capacities shown do not include a deduction for evaporator-fan motor tem (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
heat. Sizes table are based on 1.1° C line loss.

37
Performance data (cont)
38AH/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — ENGLISH
38AH024 AND 40RM016 WITH STANDARD 3-ROW COIL 38AH024 AND 40RM028 WITH STANDARD 3-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 4500 6000 7500 Air 7,500 10,000 12,500
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 211.3 191.6 173.6 221.7 203.6 186.3 229.2 211.4 195.4 TC 252.4 229.4 214.3 261.8 239.0 229.0 266.4 248.1 241.2
85 SHC 106.1 131.1 166.6 118.5 151.3 186.3 130.3 169.2 195.4 85 SHC 140.1 181.8 212.5 160.6 212.9 229.0 180.5 240.6 241.2
kW 13.46 13.13 12.83 13.63 13.33 13.04 13.75 13.46 13.19 kW 14.14 13.76 13.50 14.30 13.92 13.75 14.37 14.07 13.95
TC 202.6 184.4 167.6 211.9 195.4 179.6 218.9 202.5 188.3 TC 240.2 218.3 205.3 248.7 227.1 219.4 252.6 235.7 230.9
95 SHC 103.0 127.9 161.4 114.9 147.4 179.6 126.6 164.7 188.3 95 SHC 135.6 177.3 204.2 155.9 208.0 219.4 175.9 235.2 230.9
kW 14.70 14.28 13.90 14.91 14.53 14.17 15.06 14.69 14.37 kW 15.55 15.05 14.76 15.74 15.25 15.08 15.83 15.45 15.34
TC 198.0 180.5 164.3 206.8 191.0 175.8 213.5 197.8 184.4 TC 234.0 212.6 200.5 242.1 221.0 214.3 245.7 229.4 225.6
100 SHC 101.4 126.1 158.5 112.9 145.2 175.8 124.7 162.4 184.4 100 SHC 133.3 175.0 199.9 153.6 205.5 214.3 173.6 229.4 225.6
kW 15.32 14.82 14.36 15.57 15.12 14.69 15.75 15.31 14.93 kW 16.34 15.73 15.39 16.56 15.97 15.78 16.67 16.21 16.10
TC 193.2 176.4 160.8 201.5 186.4 172.0 208.0 192.9 180.3 TC 227.7 206.7 195.6 235.3 214.8 209.1 238.6 223.0 220.1
105 SHC 99.7 124.3 155.4 111.0 143.0 172.0 122.7 160.0 180.3 105 SHC 131.0 172.6 195.3 151.2 202.9 209.1 171.2 223.0 220.1
kW 16.00 15.51 15.05 16.25 15.80 15.38 16.43 15.99 15.62 kW 17.01 16.40 16.07 17.24 16.63 16.47 17.34 16.88 16.79
TC 183.5 167.7 153.1 191.0 177.0 163.7 197.0 183.0 171.8 TC 215.5 195.1 185.6 222.6 202.6 198.8 225.4 210.6 209.5
115 SHC 96.3 120.4 148.6 107.0 138.5 163.7 118.8 155.0 171.8 115 SHC 126.6 167.9 186.2 146.8 197.9 198.8 166.8 210.6 209.5
kW 17.26 16.61 16.01 17.57 17.00 16.45 17.82 17.24 16.78 kW 18.58 17.74 17.35 18.87 18.05 17.89 18.99 18.38 18.33
TC 173.2 158.7 145.1 179.8 167.2 155.1 185.4 172.5 162.9 TC 202.4 182.9 175.0 208.8 189.8 187.7 211.2 197.4 197.9
125 SHC 92.7 116.3 141.6 102.8 133.7 155.1 114.6 149.8 162.9 125 SHC 121.8 163.0 176.5 141.9 189.8 187.7 162.1 197.4 197.9
kW 18.63 17.91 17.23 18.96 18.33 17.73 19.23 18.60 18.11 kW 20.08 19.11 18.72 20.40 19.45 19.35 20.52 19.83 19.86

38AH024 AND 40RM024 WITH STANDARD 3-ROW COIL 38AH028 AND 40RM024 WITH STANDARD 3-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 6,000 8,000 10,000 Air 6,000 8,000 10,000
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 234.5 214.7 196.5 244.6 224.8 209.7 249.6 232.7 220.2 TC 256.2 235.7 215.7 267.1 247.0 228.8 273.1 255.0 239.4
85 SHC 123.6 158.1 191.1 140.2 183.3 209.7 154.6 206.1 220.2 85 SHC 131.8 166.7 207.8 148.3 192.7 228.8 162.9 216.3 239.4
kW 13.84 13.51 13.21 14.01 13.68 13.43 14.09 13.81 13.60 kW 16.65 16.14 15.64 16.93 16.42 15.97 17.08 16.63 16.24
TC 223.9 205.4 188.9 233.0 214.5 201.4 237.2 221.8 211.5 TC 246.0 225.8 206.6 256.5 236.5 219.8 262.0 244.5 230.4
95 SHC 119.5 154.3 184.5 136.0 179.0 201.4 150.2 201.1 211.5 95 SHC 127.9 162.6 200.0 144.5 188.3 219.8 159.0 211.5 230.4
kW 15.18 14.76 14.38 15.39 14.96 14.67 15.48 15.13 14.90 kW 18.20 17.70 17.22 18.46 17.96 17.54 18.60 18.16 17.81
TC 218.4 200.4 184.7 227.0 209.1 196.9 230.9 216.2 206.8 TC 240.9 220.9 202.1 251.2 231.3 215.3 256.5 239.3 225.9
100 SHC 117.4 152.2 180.9 133.9 176.7 196.9 148.0 198.6 206.8 100 SHC 126.0 160.6 196.1 142.6 186.1 215.3 157.0 209.1 225.9
kW 15.89 15.39 14.94 16.14 15.63 15.29 16.25 15.83 15.57 kW 18.97 18.38 17.84 19.27 18.69 18.22 19.42 18.92 18.53
TC 212.7 195.4 180.4 220.9 203.5 192.4 224.4 210.4 202.0 TC 234.4 215.6 198.2 243.9 225.2 210.7 248.5 232.6 220.8
105 SHC 115.3 150.2 177.1 131.7 174.4 192.4 145.7 195.9 202.0 105 SHC 123.5 158.5 192.7 139.9 183.5 210.7 154.2 206.1 220.8
kW 16.57 16.06 15.62 16.82 16.30 15.98 16.92 16.51 16.26 kW 19.79 19.10 18.47 20.13 19.45 18.93 20.30 19.72 19.29
TC 201.6 185.1 171.4 209.2 192.5 183.0 212.1 199.1 192.3 TC 223.6 205.8 189.8 232.3 214.5 201.9 236.3 221.6 211.6
115 SHC 111.0 145.9 169.3 127.4 169.7 183.0 141.4 190.8 192.3 115 SHC 119.4 154.4 185.3 135.8 179.0 201.9 149.9 201.0 211.6
kW 18.01 17.33 16.76 18.32 17.6 17.24 18.44 17.91 17.63 kW 21.29 20.61 19.99 21.63 20.94 20.46 21.78 21.22 20.83
TC 189.8 174.3 162.0 196.6 180.8 173.1 198.9 187.1 182.0 TC 196.6 180.3 167.0 203.9 187.4 178.6 206.6 193.9 187.8
125 SHC 106.5 141.5 161.1 122.8 164.8 173.1 136.7 185.3 182.0 125 SHC 109.1 144.0 165.5 125.5 167.5 178.6 139.4 188.4 187.8
kW 19.45 18.68 18.07 19.79 19.01 18.62 19.90 19.32 19.07 kW 23.11 22.43 21.88 23.41 22.72 22.36 23.52 23.00 22.74

LEGEND 5. Formulas
Edb — Entering Dry Bulb sensible heat capacity (Btuh)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.1 x cfm
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) total capacity (Btuh)
hldb = hedb –
NOTES: 4.5 cfm
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator 6. Combination ratings are based on a 2° F line loss. For a close-coupled sys-
coil. tem (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
4. Gross capacities shown do not include a deduction for evaporator-fan motor table are based on 2° F line loss.
heat.

38
38AH/40RM COMBINATION RATINGS — STANDARD 3-ROW COIL — ENGLISH (cont)
38AH028 AND 40RM028 WITH STANDARD 3-ROW COIL 38AH034 AND 40RM028 WITH STANDARD 3-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 7,500 10,000 12,500 Air 7,500 10,000 12,500
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 275.2 252.7 234.7 285.3 262.8 249.2 290.6 271.7 261.4 TC 307.8 283.0 258.8 320.5 295.3 274.6 327.8 305.2 288.2
85 SHC 148.5 191.1 231.2 168.8 222.6 249.2 188.5 250.9 261.4 85 SHC 160.5 203.4 253.3 181.2 236.0 274.6 200.9 265.5 288.2
kW 17.13 16.57 16.12 17.38 16.82 16.48 17.52 17.04 16.78 kW 20.50 19.90 19.32 20.81 20.20 19.70 20.99 20.44 20.03
TC 264.5 241.8 225.1 274.3 251.6 239.7 279.2 260.6 251.9 TC 295.9 271.4 249.2 307.9 283.1 264.9 314.6 292.9 278.2
95 SHC 144.5 186.7 222.4 164.9 218.0 239.7 184.7 246.1 251.9 95 SHC 156.1 198.7 244.5 176.8 231.0 264.9 196.5 260.2 278.2
kW 18.66 18.09 17.68 18.91 18.34 18.04 19.03 18.56 18.35 kW 22.57 21.78 21.06 22.95 22.15 21.57 23.17 22.47 22.00
TC 259.1 236.3 220.3 268.7 246.0 235.0 273.5 255.0 247.2 TC 289.5 265.4 244.4 301.0 276.7 259.9 307.3 286.3 272.9
100 SHC 142.6 184.5 218.0 163.0 215.7 235.0 182.8 243.6 247.2 100 SHC 153.7 196.3 240.2 174.3 228.3 259.9 194.1 257.3 272.9
kW 19.50 18.83 18.37 19.78 19.12 18.79 19.92 19.38 19.15 kW 23.38 22.58 21.88 23.77 22.96 22.40 23.98 23.28 22.83
TC 251.2 229.6 215.2 260.0 238.6 229.2 264.3 247.1 240.8 TC 283.7 259.5 239.3 295.0 270.6 254.8 301.0 280.3 267.8
105 SHC 139.7 181.8 213.4 159.9 212.7 229.2 179.8 240.2 240.8 105 SHC 151.6 193.9 235.4 172.2 225.8 254.8 192.0 254.6 267.8
kW 20.40 19.61 19.09 20.72 19.94 19.60 20.87 20.25 20.02 kW 24.41 23.52 22.77 24.83 23.93 23.34 25.05 24.28 23.82
TC 239.3 218.3 205.6 247.4 226.7 219.2 251.1 234.9 230.4 TC 271.0 247.4 229.4 281.4 257.8 244.5 286.8 267.2 257.2
115 SHC 135.3 177.2 204.6 155.5 207.8 219.2 175.4 234.8 230.4 115 SHC 146.9 189.0 226.4 167.5 220.6 244.5 187.3 248.9 257.2
kW 21.89 21.09 20.60 22.21 21.41 21.12 22.35 21.73 21.55 kW 26.32 25.30 24.52 26.77 25.75 25.18 27.00 26.15 25.72
TC 210.1 189.8 180.9 217.0 197.1 194.0 219.6 205.1 204.6 TC 257.9 234.9 219.0 267.5 244.6 233.7 272.3 253.7 246.0
125 SHC 124.6 1165.7 181.9 144.8 195.7 194.0 164.9 221.8 204.6 125 SHC 142.1 184.0 216.8 162.6 215.2 233.7 182.4 243.1 246.0
kW 23.67 22.82 22.45 23.96 23.13 23.00 24.07 23.46 23.44 kW 28.29 27.15 26.36 28.76 27.63 27.09 29.00 28.08 27.70

38AH028 AND 40RM034 WITH STANDARD 3-ROW COIL 38AH034 AND 40RM034 WITH STANDARD 3-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 9,000 12,000 15,000 Air 9,000 12,000 15,000
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 291.7 266.7 251.6 300.7 276.9 267.5 305.2 286.3 280.5 TC 328.6 301.1 279.6 340.3 313.3 297.3 346.7 324.0 311.8
85 SHC 162.4 214.9 249.7 189.9 251.2 267.5 211.7 283.4 280.5 85 SHC 176.4 228.6 275.2 203.3 265.9 297.3 225.6 300.0 311.8
kW 17.54 16.92 16.54 17.77 17.17 16.94 17.88 17.41 17.26 kW 21.00 20.34 19.82 21.29 20.64 20.25 21.44 20.89 20.60
TC 280.4 255.1 241.3 289.1 265.1 257.4 293.2 274.5 270.3 TC 315.5 288.3 268.9 326.5 300.0 286.3 332.2 310.4 300.5
95 SHC 158.1 210.3 240.4 186.0 246.5 257.4 207.7 274.5 270.3 95 SHC 171.4 223.5 265.4 198.6 260.5 286.3 220.7 294.0 300.5
kW 19.06 18.43 18.08 19.28 18.68 18.48 19.38 18.91 18.81 kW 23.19 22.32 21.70 23.55 22.70 22.26 23.73 23.03 22.71
TC 274.7 249.3 236.2 283.2 259.2 252.3 287.2 268.7 265.2 TC 308.2 281.5 263.3 318.6 292.8 280.4 324.0 303.0 294.4
100 SHC 156.0 208.0 235.8 184.0 244.1 252.3 205.7 268.7 265.2 100 SHC 168.7 220.8 260.4 196.0 257.6 280.4 218.0 290.8 294.0
kW 19.95 19.21 18.83 20.20 19.50 19.30 20.32 19.78 19.68 kW 24.01 23.12 22.51 24.35 23.49 23.08 24.53 23.83 23.55
TC 265.5 241.5 229.0 273.2 250.6 245.1 276.7 259.5 257.4 TC 302.1 275.2 257.8 312.3 286.4 275.0 317.5 296.6 288.9
105 SHC 152.5 204.9 230.1 180.6 240.6 245.1 202.2 259.5 257.4 105 SHC 166.3 218.3 255.4 193.9 255.0 275.0 215.8 287.9 288.9
kW 20.92 20.04 19.62 21.20 20.38 20.18 21.32 20.70 20.62 kW 25.09 24.10 23.45 25.47 24.51 24.09 25.66 24.89 24.60
TC 252.4 229.1 219.2 259.4 237.6 234.0 262.2 246.2 245.8 TC 287.9 261.8 246.6 297.3 272.3 263.2 301.8 282.1 276.7
115 SHC 147.5 200.0 220.4 175.9 235.4 234.0 197.5 246.2 245.8 115 SHC 161.0 213.0 245.2 188.8 249.4 263.2 210.6 281.6 276.7
kW 22.40 21.50 21.12 22.67 21.83 21.69 22.78 22.16 22.14 kW 27.05 25.92 25.26 27.45 26.37 25.98 27.65 26.80 26.56
TC 221.1 198.5 192.2 226.8 206.2 206.4 228.9 214.4 217.6 TC 273.5 247.9 234.8 282.0 257.8 251.1 — 267.4 264.1
125 SHC 135.6 187.9 195.9 164.9 206.2 206.4 186.3 214.4 217.6 125 SHC 155.5 207.5 234.6 183.6 243.5 251.1 — 267.4 264.1
kW 24.13 23.19 22.92 24.37 23.51 23.52 24.45 23.85 23.98 kW 29.06 27.79 27.14 29.48 28.28 27.95 — 28.76 28.59

LEGEND 5. Formulas
Edb — Entering Dry Bulb sensible heat capacity (Btuh)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.1 x cfm
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) total capacity (Btuh)
hldb = hedb –
NOTES: 4.5 cfm
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator 6. Combination ratings are based on a 2° F line loss. For a close-coupled sys-
coil. tem (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
4. Gross capacities shown do not include a deduction for evaporator-fan motor table are based on 2° F line loss.
heat.

39
Performance data (cont)
38AH/40RM COMBINATION RATINGS — HIGH-CAPACITY 4-ROW COIL — SI
38AH024 AND 40RM016 WITH HIGH-CAPACITY 4-ROW COIL 38AH024 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 2100 2800 3500 Air 3540 4720 5900
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 19 17 22 19 17 22 19 17 (Edb) 22 19 17 22 19 17 22 19 17
TC 64.9 59.5 54.3 68.5 63.0 57.8 71.0 65.5 60.2 TC 75.3 69.3 63.6 78.0 72.0 68.1 79.9 73.8 71.5
29 SHC 31.2 38.2 44.9 34.5 43.5 52.2 37.5 48.4 58.0 29 SHC 39.3 51.1 61.7 44.4 59.3 68.1 49.1 66.6 71.5
kW 13.92 13.52 13.11 14.16 13.78 13.37 14.32 13.96 13.57 kW 14.64 14.27 13.87 14.82 14.45 14.18 14.94 14.58 14.41
TC 62.1 56.8 51.8 65.3 60.1 55.0 67.6 62.4 57.3 TC 71.7 66.0 60.6 74.3 68.5 65.2 76.0 69.9 68.6
35 SHC 30.1 37.0 43.8 33.3 42.3 50.6 36.3 47.3 56.2 35 SHC 38.1 49.9 60.6 43.2 58.0 65.2 47.9 65.1 68.6
kW 15.26 14.75 14.25 15.56 15.08 14.57 15.76 15.28 14.80 kW 16.13 15.65 15.17 16.34 15.88 15.58 16.48 15.95 15.88
TC 61.2 55.5 50.6 63.8 58.6 53.7 65.9 60.7 55.8 TC 70.0 64.3 59.1 72.4 66.4 63.8 73.9 68.1 67.0
38 SHC 29.8 36.4 43.1 32.7 41.7 50.1 35.7 46.7 55.8 38 SHC 37.5 49.2 59.1 42.5 57.2 63.8 47.3 64.2 67.0
kW 16.18 15.36 14.81 16.22 15.70 15.17 16.44 15.92 15.40 kW 16.85 16.33 15.80 17.08 16.48 16.27 17.21 16.67 16.58
TC 59.1 54.0 49.3 62.1 57.1 52.3 64.2 59.1 54.5 TC 68.1 62.6 57.9 70.5 64.6 62.3 71.9 66.3 65.4
41 SHC 28.8 35.8 42.6 32.1 41.2 49.4 35.2 46.0 54.5 41 SHC 36.9 48.6 57.9 41.8 56.5 62.3 46.5 63.5 65.4
kW 16.54 15.95 15.35 16.88 16.32 15.73 17.11 16.54 16.00 kW 17.56 16.98 16.45 17.80 17.15 16.94 17.94 17.36 17.28
TC 56.0 51.3 46.7 58.8 54.0 49.4 60.6 55.7 51.9 TC 64.5 59.2 55.2 66.5 61.2 59.4 67.8 62.6 62.2
46 SHC 27.6 34.7 41.4 30.9 39.9 48.1 33.9 44.7 51.9 46 SHC 35.6 47.3 55.2 40.5 55.1 59.4 45.3 61.5 62.2
kW 17.78 17.11 16.43 18.18 17.50 16.85 18.41 17.74 17.21 kW 18.93 18.25 17.70 19.17 18.50 18.26 19.33 18.68 18.63

38AH024 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL 38AH028 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 2830 3780 4720 Air 2830 3780 4720
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 19 17 22 19 17 22 19 17 (Edb) 22 19 17 22 19 17 22 19 17
TC 70.6 64.9 59.4 73.7 67.9 62.4 75.7 69.8 66.7 TC 78.1 71.8 65.6 81.8 75.4 69.2 84.4 77.8 72.0
29 SHC 34.7 44.3 53.5 38.9 51.0 62.4 42.8 57.3 66.6 29 SHC 37.6 47.2 56.4 41.8 54.0 65.4 45.7 60.3 72.0
kW 14.33 13.95 13.54 14.53 14.16 13.77 14.65 14.29 14.22 kW 17.38 16.84 16.29 17.67 17.16 16.62 17.88 17.38 16.85
TC 67.4 61.9 56.7 70.2 64.6 60.6 72.0 66.0 63.1 TC 74.7 68.6 62.8 78.2 72.0 66.3 80.5 74.2 69.2
35 SHC 33.6 43.2 52.2 37.7 49.8 60.6 41.6 55.8 63.1 35 SHC 36.3 45.9 55.1 40.5 52.7 63.8 44.4 58.9 69.2
kW 15.76 15.28 14.78 15.98 15.53 15.28 16.13 15.58 15.38 kW 18.95 18.31 17.67 19.31 18.69 18.07 19.54 18.91 18.36
TC 65.8 60.3 55.1 68.4 62.9 58.4 70.1 64.7 61.7 TC 73.0 67.0 61.3 76.4 70.3 64.7 78.5 72.4 67.8
38 SHC 33.0 42.5 51.5 37.1 49.2 58.4 40.9 55.3 61.7 38 SHC 35.7 45.2 54.4 39.9 52.0 63.0 43.7 58.2 67.8
kW 16.46 15.91 15.35 16.69 16.17 15.70 16.85 16.35 16.04 kW 19.72 19.03 18.35 20.11 19.43 18.76 20.34 19.66 19.12
TC 64.1 58.7 53.7 66.6 61.2 57.1 68.2 62.6 60.3 TC 71.3 65.5 59.9 74.5 68.6 63.0 76.5 70.5 66.4
41 SHC 32.4 41.9 50.8 36.5 48.6 57.1 40.3 54.5 60.3 41 SHC 35.0 44.6 53.7 39.2 51.4 62.5 43.1 57.5 66.4
kW 17.12 16.53 15.93 17.38 16.81 16.34 17.55 16.91 16.69 kW 20.48 19.74 19.01 20.90 20.15 19.43 21.12 20.39 19.86
TC 60.6 55.5 50.8 62.9 57.8 54.4 64.4 59.1 57.4 TC 67.9 62.3 57.0 70.7 65.0 60.0 72.5 66.9 63.5
46 SHC 31.1 40.7 49.3 35.3 47.3 54.4 39.1 53.2 57.4 46 SHC 33.7 43.3 52.4 37.9 50.0 60.0 41.7 56.1 63.5
kW 18.41 17.73 17.06 18.71 18.04 17.58 18.91 18.18 17.97 kW 22.03 21.21 20.38 22.45 21.62 20.85 22.70 21.89 21.39

LEGEND 5. Formulas (cooling)


Edb — Entering Dry Bulb sensible heat capacity (kW)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.23 x 10-3 x (L/s)
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (kW)
TC — Total Capacity (kW) total capacity (kW)
hldb = hedb –
NOTES: 1.20 x 10-3 x (L/s)
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil (kJ/kg).
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. 6. Combination ratings are based on a 1.1° C line loss. For a close-coupled sys-
4. Gross capacities shown do not include a deduction for evaporator-fan motor tem (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
heat. Sizes table are based on 1.1° C line loss.

40
38AH/40RM COMBINATION RATINGS — HIGH-CAPACITY 4-ROW COIL — SI (cont)
38AH028 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL 38AH034 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 3500 4700 5900 Air 3500 4700 5900
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 19 17 22 19 17 22 19 17 (Edb) 22 19 17 22 19 17 22 19 17
TC 83.7 77.1 70.8 87.1 80.3 74.5 89.3 82.5 78.6 TC 93.3 85.7 78.5 97.6 89.9 82.8 100.3 92.6 87.2
29 SHC 41.9 53.9 65.4 47.1 62.3 74.5 51.9 69.9 78.6 29 SHC 45.6 57.6 69.0 50.9 66.1 79.5 55.7 73.9 86.7
kW 17.85 17.34 16.79 18.11 17.59 17.09 18.28 17.77 17.45 kW 22.08 21.29 20.50 22.53 21.74 20.97 22.83 22.04 21.51
TC 80.0 73.6 67.5 83.1 76.6 71.6 85.1 78.6 75.5 TC 89.5 82.2 75.2 93.3 86.0 79.5 95.9 88.5 83.3
35 SHC 40.5 52.6 63.8 45.7 60.9 71.6 50.5 68.4 75.5 35 SHC 44.2 56.1 67.4 49.4 64.5 77.1 54.2 72.3 83.3
kW 19.53 18.89 18.23 19.81 19.20 18.66 20.00 19.40 19.06 kW 23.91 23.00 22.08 24.37 23.48 22.63 24.70 23.82 23.10
TC 78.1 71.8 65.9 81.1 74.7 70.2 83.0 76.7 73.9 TC 87.5 80.3 73.5 91.2 84.0 78.3 93.7 86.5 81.6
38 SHC 39.9 51.9 63.0 45.0 60.2 70.2 49.8 67.7 73.9 38 SHC 43.5 55.3 66.7 48.6 63.8 76.4 53.4 71.5 81.6
kW 20.34 19.64 18.94 20.64 19.97 19.45 20.85 20.20 19.86 kW 24.80 23.82 22.87 25.28 24.33 23.56 25.62 24.69 23.96
TC 76.2 70.1 64.3 79.0 72.9 68.7 81.0 74.8 72.3 TC 85.4 78.4 71.8 89.0 82.0 76.2 91.4 84.4 79.9
41 SHC 39.2 51.2 62.3 44.3 59.5 68.7 49.1 67.0 72.3 41 SHC 42.7 54.6 65.9 47.8 63.0 74.8 52.7 70.7 79.9
kW 21.13 20.37 19.63 21.45 20.73 20.20 21.68 20.97 20.64 kW 25.70 24.67 23.67 26.21 25.21 24.33 26.57 25.58 24.86
TC 72.4 66.5 61.0 75.0 69.1 66.7 76.7 70.7 69.1 TC 81.3 74.7 68.4 84.6 78.0 72.7 86.9 80.1 76.6
46 SHC 37.9 49.8 61.0 43.0 58.1 66.7 47.7 65.2 69.1 46 SHC 41.2 53.1 64.3 46.4 61.5 72.3 51.2 69.0 76.6
kW 22.72 21.88 21.05 23.11 22.27 22.38 23.34 22.50 22.26 kW 27.46 26.34 25.23 28.03 26.93 25.98 28.40 27.28 26.63

38AH028 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL 38AH034 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL
Temp (C) Evaporator Air — L/s Temp (C) Evaporator Air — L/s
Air 4250 5660 7080 Air 4250 5660 7080
Entering Entering
Condenser Evaporator Air — Ewb (C) Condenser Evaporator Air — Ewb (C)
(Edb) 22 19 17 22 19 17 22 19 17 (Edb) 22 19 17 22 19 17 22 19 17
TC 88.2 81.2 74.6 91.3 84.3 80.8 93.3 86.3 84.0 TC 98.9 91.0 83.5 102.9 95.0 88.6 105.6 97.5 93.0
29 SHC 45.7 60.2 73.0 51.9 70.1 80.8 57.6 78.8 84.0 29 SHC 49.6 64.0 77.6 55.9 74.1 87.6 61.6 83.3 93.0
kW 18.23 17.70 17.16 18.48 17.96 17.72 18.66 18.12 17.91 kW 22.70 21.89 21.08 23.12 22.33 21.61 23.40 22.60 22.06
TC 84.2 77.5 71.5 87.1 80.4 76.8 88.9 82.0 80.7 TC 94.7 87.1 80.0 98.5 90.8 85.4 100.8 93.0 89.9
35 SHC 44.4 58.8 71.5 50.5 68.6 76.8 56.2 77.2 80.7 35 SHC 48.1 62.5 76.0 54.3 72.6 85.4 60.1 81.5 89.9
kW 19.97 19.33 18.70 20.26 19.63 19.24 20.44 19.76 19.63 kW 24.58 23.66 22.75 25.06 24.14 23.43 25.34 24.41 24.03
TC 82.2 75.6 70.0 85.0 78.4 75.2 86.7 80.0 78.9 TC 92.6 85.1 78.2 96.2 88.6 83.3 98.4 90.8 87.7
38 SHC 43.7 58.1 70.0 49.8 67.9 75.2 55.5 76.3 78.9 38 SHC 47.3 61.8 74.7 53.6 71.8 83.3 59.3 80.6 87.7
kW 20.81 20.12 19.46 21.13 20.43 20.06 21.29 20.57 20.46 kW 25.50 24.53 23.57 25.99 25.01 24.22 26.28 25.30 24.84
TC 80.2 73.7 68.6 82.8 76.3 73.6 84.4 78.0 77.1 TC 90.4 83.1 76.7 93.8 86.4 81.6 96.0 88.6 85.9
41 SHC 43.0 57.4 68.6 49.1 67.1 73.6 54.8 75.3 77.1 41 SHC 46.6 61.0 73.6 52.8 70.9 81.6 58.5 79.7 85.9
kW 21.64 20.90 20.23 21.96 21.21 20.86 22.14 21.39 21.28 kW 26.44 25.42 24.45 26.94 25.91 25.13 27.24 26.21 25.77
TC 76.1 70.0 66.6 78.4 72.2 70.4 79.9 73.9 73.6 TC 86.1 79.1 73.2 89.1 81.8 78.2 91.1 84.1 82.1
46 SHC 41.6 56.0 62.0 47.7 65.4 70.4 53.4 73.1 73.6 46 SHC 45.1 59.5 71.2 51.2 68.3 78.2 56.9 77.7 82.1
kW 23.33 22.47 21.97 23.63 22.79 22.50 23.83 23.01 22.95 kW 28.30 27.16 26.10 28.80 27.57 26.95 29.11 27.99 27.60

LEGEND 5. Formulas (cooling)


Edb — Entering Dry Bulb sensible heat capacity (kW)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.23 x 10-3 x (L/s)
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (kW)
TC — Total Capacity (kW) total capacity (kW)
hldb = hedb –
NOTES: 1.20 x 10-3 x (L/s)
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil (kJ/kg).
3. The SHC is based on 26.7 C db temperature of air entering the indoor unit. 6. Combination ratings are based on a 1.1° C line loss. For a close-coupled sys-
4. Gross capacities shown do not include a deduction for evaporator-fan motor tem (less than 4.5 m), add 2% to ratings. Piping sizes in Refrigerant Pipe
heat. Sizes table are based on 1.1° C line loss.

41
Performance data (cont)
38AH/40RM COMBINATION RATINGS — HIGH-CAPACITY 4-ROW COIL — ENGLISH
38AH024 AND 40RM016 WITH HIGH-CAPACITY 4-ROW COIL 38AH024 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 4500 6000 7500 Air 7,500 10,000 12,500
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 221.8 203.3 185.6 234.0 215.3 197.3 242.4 223.6 205.5 TC 257.1 236.6 217.2 266.5 245.9 232.4 272.7 252.2 244.3
85 SHC 106.7 130.4 153.4 117.7 148.7 178.2 128.1 165.2 198.2 85 SHC 134.3 174.6 210.8 151.6 202.4 232.4 167.7 227.4 244.3
kW 13.92 13.52 13.11 14.16 13.78 13.37 14.32 13.96 13.57 kW 14.64 14.27 13.87 14.82 14.45 14.18 14.94 14.58 14.41
TC 212.2 194.1 177.0 223.2 205.3 187.7 231.0 213.0 195.6 TC 245.0 225.2 207.0 253.8 234.0 222.7 259.5 238.9 234.2
95 SHC 102.8 126.3 149.4 113.6 144.6 172.7 124.1 161.5 191.8 95 SHC 130.1 170.3 207.0 147.5 198.0 222.7 163.7 222.3 234.2
kW 15.26 14.75 14.25 15.56 15.08 14.57 15.76 15.28 14.80 kW 16.13 15.65 15.17 16.34 15.88 15.58 16.48 15.95 15.88
TC 209.1 189.4 172.7 217.8 200.2 183.4 225.2 207.3 190.7 TC 238.9 219.5 202.0 247.4 226.8 217.7 252.5 232.6 228.8
100 SHC 101.7 124.4 147.2 111.6 142.5 171.0 122.1 159.4 190.7 100 SHC 128.1 168.0 202.0 145.2 195.4 217.7 161.4 219.3 228.8
kW 16.18 15.36 14.81 16.22 15.70 15.17 16.44 15.92 15.40 kW 16.85 16.33 15.80 17.08 16.48 16.27 17.21 16.67 16.58
TC 201.7 184.5 168.3 212.1 195.1 178.5 219.2 201.7 186.2 TC 232.7 213.7 197.8 240.7 220.6 212.7 245.6 226.5 223.3
105 SHC 98.3 122.3 145.4 109.5 140.6 168.7 120.1 157.0 186.2 105 SHC 126.0 165.8 197.8 142.9 193.0 212.7 158.8 216.8 223.3
kW 16.54 15.95 15.35 16.88 16.32 15.73 17.11 16.54 16.00 kW 17.56 16.98 16.45 17.80 17.15 16.94 17.94 17.36 17.28
TC 191.3 175.0 159.5 200.8 184.4 168.9 206.9 190.3 177.3 TC 220.2 202.0 188.4 227.0 208.9 202.7 231.7 213.6 212.3
115 SHC 94.4 118.4 141.3 105.6 136.4 164.2 115.8 152.7 177.3 115 SHC 121.6 161.5 188.4 138.3 188.2 202.7 154.8 210.1 212.3
kW 17.78 17.11 16.43 18.18 17.50 16.85 18.41 17.74 17.21 kW 18.93 18.25 17.70 19.17 18.50 18.26 19.33 18.68 18.63

38AH024 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL 38AH028 AND 40RM024 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 6,000 8,000 10,000 Air 6,000 8,000 10,000
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 241.2 221.6 203.0 251.8 231.8 213.2 258.5 238.5 227.7 TC 266.7 245.1 224.2 279.5 257.5 236.4 288.2 265.9 245.9
85 SHC 118.7 151.5 182.7 133.0 174.3 213.2 146.1 195.6 227.6 85 SHC 128.3 161.2 192.7 142.7 184.5 223.3 156.1 205.9 245.9
kW 14.33 13.95 13.54 14.53 14.16 13.77 14.65 14.29 14.22 kW 17.38 16.84 16.29 17.67 17.16 16.62 17.88 17.38 16.85
TC 230.3 211.4 193.6 239.8 220.6 207.0 245.9 225.5 215.5 TC 255.2 234.3 214.3 267.1 246.1 226.3 274.9 253.4 236.3
95 SHC 114.7 147.4 178.4 128.8 169.9 207.0 142.0 190.4 215.5 95 SHC 123.9 156.6 188.0 138.3 180.0 218.0 151.6 201.2 236.3
kW 15.76 15.28 14.78 15.98 15.53 15.28 16.13 15.58 15.38 kW 18.95 18.31 17.67 19.31 18.69 18.07 19.54 18.91 18.36
TC 224.7 206.1 188.2 233.6 214.9 199.4 239.5 220.9 210.8 TC 249.4 229.0 209.5 260.9 240.2 220.9 268.1 247.2 231.5
100 SHC 112.7 145.3 175.8 126.7 168.1 199.4 139.7 188.8 210.8 100 SHC 121.8 154.5 185.7 136.2 177.7 215.1 149.3 198.9 231.5
kW 16.46 15.91 15.35 16.69 16.17 15.70 16.85 16.35 16.04 kW 19.72 19.03 18.35 20.11 19.43 18.76 20.34 19.66 19.12
TC 218.9 200.6 183.3 227.4 209.1 195.1 233.1 213.9 205.8 TC 243.5 223.6 204.5 254.6 234.2 215.2 261.2 240.9 226.7
105 SHC 110.6 143.1 173.4 124.7 165.9 195.1 137.8 186.1 205.8 105 SHC 119.5 152.2 183.5 133.9 175.4 213.3 147.1 196.4 226.7
kW 17.12 16.53 15.93 17.38 16.81 16.34 17.55 16.91 16.69 kW 20.48 19.74 19.01 20.90 20.15 19.43 21.12 20.39 19.86
TC 207.0 189.6 173.5 214.8 197.5 186.0 220.0 202.0 195.9 TC 231.8 212.7 194.7 241.5 222.1 205.1 247.6 228.4 216.9
115 SHC 106.3 138.9 168.5 120.5 161.5 186.0 133.6 181.8 195.9 115 SHC 115.2 147.8 179.0 129.4 170.8 205.1 142.5 191.6 216.9
kW 18.41 17.73 17.06 18.71 18.04 17.58 18.91 18.18 17.97 kW 22.03 21.21 20.38 22.45 21.62 20.85 22.70 21.89 21.39

LEGEND 5. Formulas
Edb — Entering Dry Bulb sensible heat capacity (Btuh)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.1 x cfm
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) total capacity (Btuh)
hldb = hedb –
NOTES: 4.5 cfm
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator 6. Combination ratings are based on a 2° F line loss. For a close-coupled sys-
coil. tem (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
4. Gross capacities shown do not include a deduction for evaporator-fan motor table are based on 2° F line loss.
heat.

42
38AH/40RM COMBINATION RATINGS — HIGH-CAPACITY 4-ROW COIL — ENGLISH (cont)
38AH028 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL 38AH034 AND 40RM028 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 7,500 10,000 12,500 Air 7,500 10,000 12,500
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 285.9 263.2 241.7 297.4 274.3 254.4 304.8 281.7 268.6 TC 318.7 292.7 268.2 333.2 307.0 282.7 342.6 316.4 297.8
85 SHC 143.0 184.1 223.3 160.7 212.8 254.4 177.1 238.7 268.6 85 SHC 155.8 196.5 235.8 173.7 225.6 271.4 190.2 252.2 296.2
kW 17.85 17.34 16.79 18.11 17.59 17.09 18.28 17.77 17.45 kW 22.08 21.29 20.50 22.53 21.74 20.97 22.83 22.04 21.51
TC 273.4 251.4 230.4 283.7 261.6 244.6 290.6 268.5 257.8 TC 305.5 280.6 256.7 318.6 293.6 271.4 327.6 302.4 284.3
95 SHC 138.5 179.5 218.0 156.1 207.9 244.6 172.4 233.6 257.8 95 SHC 150.9 191.6 230.3 168.6 220.4 263.4 185.1 246.8 284.3
kW 19.53 18.89 18.23 19.81 19.20 18.66 20.00 19.40 19.06 kW 23.91 23.00 22.08 24.37 23.48 22.63 24.70 23.82 23.10
TC 266.9 245.3 225.0 276.9 255.2 239.9 283.5 262.0 252.4 TC 298.8 274.2 251.1 311.3 286.8 267.4 319.9 295.4 278.7
100 SHC 136.2 177.1 215.3 153.7 205.6 239.9 170.0 231.2 252.4 100 SHC 148.4 189.0 227.7 166.0 217.8 260.9 182.5 244.2 278.6
kW 20.34 19.64 18.94 20.64 19.97 19.45 20.85 20.20 19.86 kW 24.80 23.82 22.87 25.28 24.33 23.56 25.62 24.69 23.96
TC 260.3 239.3 219.6 269.9 248.8 234.7 276.5 255.4 246.9 TC 291.8 267.8 245.3 303.9 280.0 260.3 312.2 288.2 273.0
105 SHC 133.9 174.8 212.9 151.3 203.2 234.7 167.8 228.8 246.9 105 SHC 145.8 186.4 224.9 163.4 215.2 255.3 179.9 241.6 273.0
kW 21.13 20.37 19.63 21.45 20.73 20.20 21.68 20.97 20.64 kW 25.70 24.67 23.67 26.21 25.21 24.33 26.57 25.58 24.86
TC 247.1 227.1 208.3 256.1 235.9 227.7 261.9 241.4 236.1 TC 277.7 255.0 233.7 289.1 266.4 248.4 296.6 273.4 261.4
115 SHC 129.3 170.1 208.3 146.8 198.4 227.7 163.1 222.7 236.1 115 SHC 140.8 181.4 219.5 158.4 210.0 247.1 174.9 235.7 261.4
kW 22.72 21.88 21.05 23.11 22.27 22.38 23.34 22.50 22.26 kW 27.46 26.34 25.23 28.03 26.93 25.98 28.40 27.28 26.63

38AH028 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL 38AH034 AND 40RM034 WITH HIGH-CAPACITY 4-ROW COIL
Temp (F) Evaporator Air — Cfm Temp (F) Evaporator Air — Cfm
Air 9,000 12,000 15,000 Air 9,000 12,000 15,000
Entering Entering
Condenser Evaporator Air — Ewb (F) Condenser Evaporator Air — Ewb (F)
(Edb) 72 67 62 72 67 62 72 67 62 (Edb) 72 67 62 72 67 62 72 67 62
TC 301.1 277.2 254.8 311.7 287.8 275.9 318.8 294.6 287.0 TC 337.9 310.7 285.0 351.6 324.3 302.5 360.6 333.0 317.7
85 SHC 156.2 205.6 249.4 177.2 239.4 275.9 196.8 269.2 287.0 85 SHC 169.4 218.7 264.9 190.8 253.2 299.1 210.5 284.4 317.7
kW 18.23 17.70 17.16 18.48 17.96 17.72 18.66 18.12 17.91 kW 22.70 21.89 21.08 23.12 22.33 21.61 23.40 22.60 22.06
TC 287.5 264.6 244.2 297.5 274.5 262.4 303.7 280.0 275.5 TC 323.5 297.4 273.2 336.2 310.0 291.7 344.3 317.7 306.9
95 SHC 151.5 200.9 244.2 172.5 234.3 262.4 191.9 263.6 275.5 95 SHC 164.3 213.6 259.5 185.4 247.8 291.7 205.1 278.3 306.9
kW 19.97 19.33 18.70 20.26 19.63 19.24 20.44 19.76 19.63 kW 24.58 23.66 22.75 25.06 24.14 23.43 25.34 24.41 24.03
TC 280.7 258.2 239.1 290.3 267.7 256.9 296.0 273.4 269.5 TC 316.2 290.7 267.1 328.5 302.6 284.3 336.0 310.2 299.6
100 SHC 149.2 198.4 239.1 170.1 231.9 256.9 189.4 260.6 269.5 100 SHC 161.6 210.9 255.2 182.9 245.1 284.3 202.4 275.3 299.6
kW 20.81 20.12 19.46 21.13 20.43 20.06 21.29 20.57 20.46 kW 25.50 24.53 23.57 25.99 25.01 24.22 26.28 25.30 24.84
TC 273.8 251.8 234.2 282.9 260.7 251.5 288.4 266.5 263.5 TC 308.8 283.9 261.8 320.5 295.2 278.5 327.8 302.6 293.3
105 SHC 146.7 196.0 234.2 167.7 229.2 251.5 187.2 257.1 263.5 105 SHC 159.0 208.3 251.5 180.3 242.3 278.5 199.8 272.1 293.3
kW 21.64 20.90 20.23 21.96 21.21 20.86 22.14 21.39 21.28 kW 26.44 25.42 24.45 26.94 25.91 25.13 27.24 26.21 25.77
TC 259.9 239.0 227.5 267.9 246.6 240.4 272.9 252.5 251.2 TC 294.0 270.2 249.9 304.3 279.3 267.0 311.0 287.3 280.5
115 SHC 142.1 191.4 211.8 162.9 223.5 240.4 182.4 249.8 251.2 115 SHC 153.9 203.1 243.2 174.9 233.1 267.0 194.5 265.3 280.5
kW 23.33 22.47 21.97 23.63 22.79 22.50 23.83 23.01 22.95 kW 28.30 27.16 26.10 28.80 27.57 26.95 29.11 27.99 27.60

LEGEND 5. Formulas
Edb — Entering Dry Bulb sensible heat capacity (Btuh)
Ewb — Entering Wet-Bulb tldb = tedb –
kW — Compressor Motor Power Input 1.1 x cfm
Ldb — Leaving Dry Bulb tlwb = wet-bulb temperature corresponding to enthalpy of air leaving evapora-
Lwb — Leaving Wet Bulb tor coil (hlwb)
SHC — Sensible Heating Capacity (1000 Btuh)
TC — Total Capacity (1000 Btuh) total capacity (Btuh)
hldb = hedb –
NOTES: 4.5 cfm
1. All combination ratings are based on refrigerant R-22.
2. Direct interpolation is permissible. Do not extrapolate. where hewb = enthalpy of air entering evaporator coil
3. The SHC is based on 80 F dry-bulb temperature of air entering the evaporator 6. Combination ratings are based on a 2° F line loss. For a close-coupled sys-
coil. tem (less than 15 ft), add 2% to ratings. Piping sizes in Refrigerant Pipe Sizes
4. Gross capacities shown do not include a deduction for evaporator-fan motor table are based on 2° F line loss.
heat.

43
Performance data (cont)
40RM HYDRONIC HEATING CAPACITIES — SI 40RM HYDRONIC HEATING CAPACITIES — ENGLISH
1-ROW 2-ROW 1-ROW 2-ROW
STEAM* HOT WATER COIL† STEAM* HOT WATER COIL†
UNIT AIRFLOW UNIT AIRFLOW
40RM (L/s) Water 40RM (Cfm) Water
Cap. Cap. PD
Ldb Ldb Flow Cap. Ldb Cap. Ldb Flow PD
(kW) (kW) (kPa)
(L/s) (Gpm)
2100 117 61 120 62 2.6 13.3 4,500 402 141 412.0 145 41.2 4.5
016 2800 129 53 137 55 3.0 16.2 016 6,000 458 129 471.0 133 47.1 5.5
3500 140 48 154 51 3.3 19.5 7,500 479 118 529.0 125 52.9 6.6
2900 135 53 150 58 3.3 15.6 6,000 458 129 506.0 138 50.6 5.1
024 3800 140 46 170 52 3.7 18.6 024 8,000 487 115 584.0 128 58.4 6.3
4700 146 41 191 49 4.1 22.3 10,000 499 105 652.0 120 65.2 7.5
3500 149 50 189 60 4.1 16.9 7,500 511 122 649.0 140 64.9 5.7
028 4700 166 44 218 53 4.7 20.8 028 10,000 575 112 752.0 130 75.2 7.1
5900 183 41 247 50 5.4 25.4 12,500 626 106 842.0 122 84.2 8.5
4250 164 47 215 57 4.7 18.5 9,000 560 117 735.0 136 73.5 6.2
034 5650 180 41 247 51 5.4 22.8 034 12,000 621 107 850.0 126 85.0 7.8
7050 196 38 278 48 6.0 27.7 15,000 670 101 950.0 119 95.0 9.3

LEGEND LEGEND
Cap. — Capacity (kW) Cap. — Capacity (Btuh in thousands)
Ldb — Leaving-Air Dry-Bulb Temp (C) Ldb — Leaving-Air Dry-Bulb Temp (F)
PD — Pressure Drop (kPa) PD — Pressure Drop (ft water)
*Based on 34.5 kPag steam, 15.6 C entering-air temperature. All steam coils are *Based on 5 psig steam, 60 F entering-air temperature. All steam coils are non-
non-freeze type. freeze type.
†Based on 93.3 C entering-water temperature, 11.1 C water temperature drop, †Based on 200 F entering-water temperature, 20 F water temperature drop, 60 F
15.6 C entering-air temperature. entering-air temperature.
NOTES: NOTES:
1. Maximum operating limits for heating coils: 138 kPag at 126.7 C. 1. Maximum operating limits for heating coils: 20 psig at 260 F.
Capacity (kW) Capacity (Btuh)
2. Leaving db = ent db (C) + 2. Leaving db = ent db (F) +
1.23 x 10-3 x L/s 1.1 x cfm
3. See Heating Correction Factors table. 3. See Heating Correction Factors table.

40RM HEATING CORRECTION FACTORS — SI 40RM HEATING CORRECTION FACTORS — ENGLISH


HOT WATER COIL HOT WATER COIL
Water Temp Ent Water Entering-Air Temp (C) Water Temp Ent Water Entering-Air Temp (F)
Drop Temp Drop Temp
(C) (C) 4 10 16 20 25 (F) (F) 40 50 60 70 80
60 0.72 0.64 0.55 0.50 0.43 140 0.72 0.64 0.57 0.49 0.41
70 0.87 0.79 0.71 0.65 0.58 160 0.89 0.81 0.74 0.66 0.58
5 80 1.02 0.94 0.86 0.80 0.73 10 180 1.06 0.98 0.90 0.83 0.75
90 1.17 1.09 1.01 0.95 0.89 200 1.22 1.15 1.07 1.00 0.92
100 1.32 1.24 1.16 1.10 1.04 220 1.39 1.32 1.24 1.17 1.09
60 0.65 0.56 0.48 0.42 0.35 140 0.64 0.57 0.49 0.41 0.33
70 0.80 0.72 0.63 0.58 0.51 160 0.81 0.74 0.66 0.58 0.51
11 80 0.95 0.87 0.79 0.73 0.66 20 180 0.98 0.91 0.83 0.75 0.68
90 1.10 1.02 0.94 0.89 0.82 200 1.15 1.08 1.00 0.93 0.85
100 1.26 1.18 1.09 1.04 0.97 220 1.32 1.25 1.17 1.10 1.02
60 0.56 0.48 0.39 0.33 0.26 140 0.56 0.49 0.41 0.33 0.24
70 0.72 0.63 0.55 0.49 0.42 160 0.74 0.66 0.58 0.51 0.43
16 80 0.87 0.79 0.70 0.65 0.58 30 180 0.91 0.83 0.76 0.68 0.60
90 1.02 0.94 0.86 0.81 0.74 200 1.08 1.00 0.93 0.85 0.78
100 1.18 1.10 1.02 0.97 0.90 220 1.25 1.18 1.10 1.03 0.95

STEAM COIL STEAM COIL


Steam Pressure Entering-Air Temp (C) Steam Pressure Entering-Air Temp (F)
(kPag) 4 10 16 20 25 (psig) 40 50 60 70 80
0 1.07 0.99 0.91 0.86 0.80 0 1.06 0.98 0.91 0.85 0.78
14 1.10 1.02 0.95 0.90 0.84 2 1.09 1.02 0.95 0.89 0.82
35 1.14 1.07 0.99 0.95 0.89 5 1.13 1.06 1.00 0.93 0.87
NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by NOTE: Multiply capacity given in the Coil Accessory Heating Capacities table by
the correction factor for conditions at which unit is actually operating. Correct the correction factor for conditions at which unit is actually operating. Correct
leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capac- leaving-air temperature using formula in Note 2 of Coil Accessory Heating Capac-
ities table. ities table.

44
40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 0-300 Pa ESP — SI

UNIT EXTERNAL STATIC PRESSURE (Pa)


(Std 3-Row AIRFLOW 0 50 100 150 200 250 300
(L/s)
Coil) r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
2120 7.13 0.44 7.91 0.52 9.50 0.74 10.94 0.99 12.17 1.25 13.26 1.51 14.26 1.77
2500 8.13 0.68 8.80 0.78 10.15 1.00 11.48 1.27 12.70 1.57 13.78 1.87 14.76 2.18
40RM016 2830 9.03 0.96 9.63 1.07 10.81 1.30 12.01 1.58 13.18 1.90 14.25 2.24 15.23 2.58
3210 10.07 1.37 10.62 1.48 11.66 1.73 12.71 2.01 13.77 2.35 14.80 2.71 15.76 3.09
3540 10.99 1.81 11.50 1.93 12.45 2.20 13.40 2.49 14.35 2.83 15.31 3.20 16.24 3.60
2830 8.86 0.94 9.48 1.04 10.65 1.26 11.84 1.53 13.01 1.85 14.10 2.19 15.08 2.53
3300 10.14 1.44 10.69 1.56 11.70 1.81 12.71 2.08 13.73 2.41 14.74 2.77 15.71 3.15
40RM024 3780 11.43 2.11 11.93 2.25 12.84 2.52 13.71 2.81 14.60 3.14 15.49 3.51 16.39 3.91
4250 12.74 2.96 13.19 3.12 14.02 3.43 14.81 3.74 15.59 4.08 16.37 4.45 17.17 4.85
4720 14.05 4.01 14.47 4.19 15.23 4.54 15.96 4.88 16.66 5.24 17.36 5.62 18.07 6.03
3540 7.60 0.96 8.16 1.09 9.27 1.38 10.34 1.68 11.30 1.97 12.15 2.28 12.97 2.68
4130 8.68 1.47 9.18 1.62 10.13 1.94 11.07 2.29 11.99 2.63 12.84 2.97 13.60 3.32
40RM028 4720 9.78 2.15 10.23 2.32 11.07 2.67 11.89 3.05 12.72 3.45 13.53 3.84 14.29 4.23
5310 10.89 3.01 11.30 3.20 12.06 3.59 12.80 4.00 13.53 4.43 14.27 4.88 14.99 5.33
5900 12.00 4.07 12.38 4.29 13.09 4.72 13.75 5.17 14.41 5.63 15.07 6.11 15.74 6.61
4250 8.68 1.48 9.17 1.68 10.27 2.07 11.27 2.41 12.19 2.77 13.03 3.13 13.81 3.50
4960 9.93 2.35 10.38 2.53 11.21 2.90 11.99 3.28 12.78 3.68 13.56 4.10 14.32 4.51
40RM034 5660 11.21 3.45 11.63 3.66 12.38 4.07 13.08 4.49 13.76 4.93 14.45 5.39 15.14 5.87
6370 12.51 4.85 12.89 5.08 13.58 5.54 14.22 6.01 14.83 6.49 15.44 6.99 16.05 7.51
7080 13.82 6.59 14.17 6.85 14.81 7.36 15.40 7.88 15.97 8.40 16.52 8.94 17.06 9.49

See legend and notes on page 49.

40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 350-600 Pa ESP — SI

UNIT EXTERNAL STATIC PRESSURE (Pa)


AIRFLOW
(Std 3-Row (L/s) 350 400 450 500 550 600
Coil) r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
2120 15.20 2.05 16.12 2.33 16.98 2.62 17.83 2.92 18.67 3.24 19.47 3.57
2500 15.67 2.49 16.53 2.80 17.35 3.12 18.13 3.44 18.90 3.77 19.65 4.12
40RM016 2830 16.13 2.92 16.97 3.27 17.77 3.62 18.53 3.97 19.26 4.33 19.97 4.69
3210 16.66 3.48 17.50 3.87 18.29 4.26 19.03 4.65 19.75 5.04 — —
3540 17.13 4.02 17.97 4.45 18.75 4.88 19.50 5.30 — — — —
2830 15.90 2.86 16.75 3.18 17.53 3.52 18.30 3.89 19.03 4.23 — —
3300 16.50 3.53 17.33 3.91 18.17 4.32 18.92 4.70 19.60 5.10 — —
40RM024 3780 17.13 4.32 17.97 4.76 18.83 5.22 19.55 5.67 — — — —
4250 17.88 5.30 18.67 5.76 19.48 6.24 — — — — — —
4720 18.77 6.52 19.43 6.99 — — — — — — — —
3540 13.85 3.29 14.50 3.80 15.22 4.40 15.83 5.13 16.42 5.74 — —
4130 14.31 3.71 15.01 4.17 15.74 4.79 16.33 5.37 17.00 6.04 — —
40RM028 4720 14.99 4.62 15.65 5.02 16.27 5.46 16.88 5.97 17.50 6.57 — —
5310 15.68 5.77 16.34 6.20 16.95 6.64 17.53 7.09 18.09 7.58 — —
5900 16.39 7.10 17.03 7.60 17.64 8.08 18.22 8.57 — — — —
4250 14.43 3.88 14.98 4.36 15.84 4.96 16.48 5.50 17.16 6.21 17.96 7.26
4960 15.04 4.92 15.71 5.32 16.33 5.74 16.93 6.20 17.51 6.70 18.09 7.29
40RM034 5660 15.81 6.34 16.47 6.81 17.10 7.28 17.69 7.74 18.26 8.21 — —
6370 16.66 8.04 17.27 8.57 17.88 9.10 — — — — — —
7080 17.61 10.06 18.16 10.64 — — — — — — — —

See legend and notes on page 49.

45
Performance data (cont)
40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 0.0-1.2 in. wg ESP — ENGLISH

UNIT EXTERNAL STATIC PRESSURE (in. wg)


AIRFLOW
(Std 3-Row 0.0 0.2 0.4 0.6 0.8 1.0 1.2
(Cfm)
Coil) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
4,500 428 0.59 475 0.70 570 0.99 656 1.33 730 1.68 796 2.02 856 2.38
5,300 488 0.92 528 1.04 609 1.34 689 1.71 762 2.11 827 2.51 886 2.92
40RM016 6,000 542 1.29 578 1.43 649 1.74 721 2.11 791 2.55 855 3.00 914 3.46
6,800 604 1.83 637 1.99 700 2.32 763 2.70 826 3.15 888 3.64 946 4.15
7,500 660 2.42 690 2.59 747 2.95 804 3.34 861 3.79 919 4.29 975 4.83
6,000 532 1.25 569 1.39 639 1.69 711 2.06 781 2.48 846 2.93 905 3.39
7,000 608 1.93 641 2.09 702 2.42 763 2.80 824 3.23 885 3.71 943 4.23
40RM024 8,000 686 2.83 716 3.01 770 3.38 823 3.77 876 4.21 930 4.70 983 5.24
9,000 764 3.97 791 4.18 841 4.59 888 5.02 935 5.47 982 5.96 1030 6.51
10,000 843 5.38 868 5.62 914 6.09 957 6.55 1000 7.02 1042 7.53 1084 8.08
7,500 456 1.29 490 1.47 556 1.85 621 2.25 678 2.64 729 3.06 778 3.60
8,750 521 1.98 551 2.18 608 2.61 664 3.07 720 3.53 770 3.99 816 4.45
40RM028 10,000 587 2.88 614 3.11 664 3.59 714 4.09 763 4.62 812 5.15 857 5.68
11,250 653 4.03 678 4.29 724 4.82 768 5.37 812 5.95 856 6.54 899 7.14
12,500 720 5.46 743 5.75 785 6.33 825 6.93 865 7.55 904 8.20 944 8.86
9,000 521 1.99 550 2.25 616 2.77 676 3.23 731 3.72 782 4.20 829 4.70
10,500 596 3.16 623 3.40 672 3.89 720 4.40 767 4.94 814 5.50 859 6.05
40RM034 12,000 673 4.63 698 4.90 743 5.45 785 6.02 826 6.62 867 7.23 908 7.87
13,500 751 6.51 773 6.82 815 7.44 853 8.06 890 8.71 927 9.38 963 10.07
15,000 829 8.84 850 9.19 888 9.88 924 10.57 958 11.27 991 11.99 1024 12.73

See legend and notes on page 49.

40RM WITH STANDARD COIL FAN PERFORMANCE DATA — 1.4-2.4 in. wg ESP — ENGLISH

UNIT EXTERNAL STATIC PRESSURE (in. wg)


AIRFLOW
(Std 3-Row (Cfm) 1.4 1.6 1.8 2.0 2.2 2.4
Coil) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
4,500 912 2.75 967 3.13 1019 3.52 1070 3.92 1120 4.35 1168 4.79
5,300 940 3.33 992 3.75 1041 4.18 1088 4.61 1134 5.06 1179 5.52
40RM016 6,000 968 3.92 1018 4.38 1066 4.85 1112 5.32 1156 5.80 1198 6.29
6,800 1000 4.67 1050 5.19 1097 5.71 1142 6.23 1185 6.76 — —
7,500 1028 5.39 1078 5.97 1125 6.54 1170 7.11 — — — —
6,000 954 3.83 1005 4.27 1052 4.72 1098 5.22 1142 5.67 — —
7,000 990 4.74 1040 5.24 1090 5.80 1135 6.30 1176 6.84 — —
40RM024 8,000 1028 5.79 1078 6.38 1130 7.00 1173 7.60 — — — —
9,000 1073 7.11 1120 7.72 1169 8.37 — — — — — —
10,000 1126 8.75 1166 9.37 — — — — — — — —
7,500 831 4.41 870 5.10 913 5.90 950 6.88 985 7.70 — —
8,750 859 4.97 901 5.59 944 6.42 980 7.20 1020 8.10 — —
40RM028 10,000 900 6.20 939 6.74 976 7.33 1013 8.00 1050 8.82 — —
11,250 941 7.73 980 8.32 1017 8.90 1052 9.51 1086 10.16 — —
12,500 984 9.53 1022 10.19 1058 10.84 1093 11.49 — — — —
9,000 866 5.20 899 5.85 950 6.65 989 7.38 1029 8.32 1077 9.74
10,500 902 6.60 942 7.14 980 7.70 1016 8.31 1051 8.99 1085 9.77
40RM034 12,000 949 8.50 988 9.14 1026 9.76 1062 10.38 1095 11.01 — —
13,500 1000 10.78 1036 11.49 1073 12.21 — — — — — —
15,000 1057 13.49 1090 14.28 — — — — — — — —
See legend and notes on page 49.

46
FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —
0-300 Pa ESP — SI

UNIT EXTERNAL STATIC PRESSURE (Pa)


40RM AIRFLOW 0 50 100 150 200 250 300
(High-Capacity (L/s)
4-Row Coil) r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
2120 7.28 0.45 8.05 0.54 9.60 0.75 11.00 1.00 12.21 1.26 13.28 1.51 14.27 1.78
2500 8.32 0.71 8.97 0.80 10.29 1.02 11.59 1.30 12.78 1.59 13.84 1.89 14.80 2.19
016 2830 9.25 1.00 9.83 1.10 10.99 1.33 12.16 1.62 13.29 1.93 14.34 2.27 15.30 2.60
3210 10.33 1.42 10.85 1.54 11.87 1.78 12.90 2.07 13.93 2.40 14.93 2.76 15.87 3.14
3540 11.29 1.88 11.77 2.01 12.69 2.27 13.62 2.56 14.56 2.90 15.49 3.27 16.40 3.67
2830 9.03 0.96 9.62 1.06 10.77 1.29 11.94 1.56 13.08 1.87 14.15 2.20 15.12 2.54
3300 10.34 1.48 10.86 1.60 11.85 1.85 12.84 2.12 13.85 2.45 14.84 2.80 15.78 3.18
024 3780 11.67 2.17 12.14 2.31 13.02 2.58 13.88 2.87 14.75 3.20 15.63 3.56 16.50 3.96
4250 13.01 3.05 13.44 3.21 14.23 3.51 15.00 3.82 15.77 4.16 16.54 4.53 17.32 4.94
4720 14.36 4.15 14.75 4.32 15.48 4.66 16.18 4.99 16.87 5.35 17.56 5.73 18.26 6.14
3540 7.94 1.04 8.51 1.18 9.65 1.48 10.73 1.79 11.68 2.10 12.53 2.46 13.40 2.95
4130 9.08 1.59 9.57 1.75 10.55 2.10 11.52 2.46 12.45 2.81 13.28 3.17 14.04 3.55
028 4720 10.24 2.33 10.68 2.51 11.53 2.88 12.39 3.29 13.24 3.70 14.05 4.11 14.80 4.51
5310 11.42 3.26 11.81 3.46 12.57 3.88 13.33 4.32 14.09 4.77 14.85 5.24 15.58 5.70
5900 12.60 4.42 12.96 4.64 13.65 5.09 14.33 5.57 15.01 6.07 15.70 6.58 16.38 7.10
4250 8.99 1.62 9.49 1.78 10.44 2.12 11.39 2.49 12.32 2.86 13.18 3.22 13.95 3.59
4960 10.33 2.51 10.77 2.70 11.59 3.08 12.40 3.49 13.22 3.92 14.03 4.35 14.79 4.78
034 5660 11.68 3.68 12.07 3.90 12.81 4.33 13.52 4.77 14.23 5.25 14.95 5.74 15.66 6.23
6370 13.04 5.18 13.40 5.42 14.07 5.90 14.71 6.39 15.34 6.90 15.97 7.44 16.61 7.98
7080 14.42 7.05 14.74 7.31 15.36 7.84 15.94 8.38 16.51 8.93 17.08 9.51 17.65 10.10

See legend and notes on page 49.

FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —


350-600 Pa ESP — SI
UNIT EXTERNAL STATIC PRESSURE (Pa)
40RM AIRFLOW 350 400 450 500 550 600
(High-Capacity (L/s)
4-Row Coil) r/s kW r/s kW r/s kW r/s kW r/s kW r/s kW
2120 15.21 2.05 16.11 2.33 16.98 2.62 17.83 2.93 18.66 3.24 19.47 3.57
2500 15.69 2.49 16.54 2.80 17.35 3.12 18.14 3.44 18.90 3.77 19.64 4.11
016 2830 16.18 2.94 17.01 3.28 17.79 3.63 18.54 3.97 19.27 4.33 19.97 4.69
3210 16.75 3.52 17.57 3.90 18.34 4.29 19.08 4.67 19.78 5.06 — —
3540 17.26 4.09 18.07 4.50 18.84 4.93 19.57 5.35 — — — —
2830 16.01 2.88 16.85 3.22 17.64 3.56 18.39 3.91 19.12 4.26 — —
3300 16.67 3.57 17.50 3.96 18.28 4.36 19.03 4.75 19.73 5.15 — —
024 3780 17.35 4.39 18.17 4.82 18.95 5.27 19.68 5.72 — — — —
4250 18.11 5.37 18.88 5.83 19.63 6.31 — — — — — —
4720 18.96 6.58 19.67 7.05 — — — — — — — —
3540 14.57 3.97 14.95 4.41 15.67 5.07 16.50 5.59 — — — —
4130 14.76 3.99 15.51 4.57 16.36 5.46 17.00 6.04 — — — —
028 4720 15.49 4.92 16.15 5.37 16.78 5.88 17.42 6.50 — — — —
5310 16.26 6.15 16.91 6.61 17.51 7.08 18.10 7.58 — — — —
5900 17.04 7.61 17.68 8.11 18.28 8.62 — — — — — —
4250 14.68 4.00 15.38 4.49 16.12 5.14 17.00 6.15 — — — —
4960 15.51 5.20 16.17 5.63 16.80 6.09 17.41 6.61 — — — —
034 5660 16.35 6.72 17.01 7.21 17.64 7.69 18.23 8.18 — — — —
6370 17.24 8.54 17.87 9.10 — — — — — — — —
7080 18.22 10.70 — — — — — — — — — —

See legend and notes on page 49.

47
Performance data (cont)
FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —
0.0-1.2 in. wg ESP — ENGLISH
UNIT EXTERNAL STATIC PRESSURE (in. wg)
40RM AIRFLOW 0.0 0.2 0.4 0.6 0.8 1.0 1.2
(High-Capacity (Cfm)
4-Row Coil) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
4,500 437 0.61 483 0.72 576 1.01 660 1.35 732 1.69 797 2.03 856 2.38
5,300 499 0.95 538 1.07 617 1.37 696 1.74 767 2.13 830 2.53 888 2.94
016 6,000 555 1.34 590 1.48 659 1.79 730 2.17 798 2.59 860 3.04 918 3.49
6,800 620 1.91 651 2.06 712 2.39 774 2.78 836 3.22 896 3.71 952 4.21
7,500 677 2.52 706 2.69 761 3.04 817 3.44 873 3.89 929 4.39 984 4.93
6,000 542 1.29 577 1.42 646 1.72 716 2.09 785 2.51 849 2.95 907 3.40
7,000 620 1.99 652 2.15 711 2.48 771 2.85 831 3.28 890 3.76 947 4.27
024 8,000 700 2.92 728 3.10 781 3.46 833 3.85 885 4.29 938 4.78 990 5.32
9,000 781 4.10 806 4.30 854 4.71 900 5.13 946 5.58 993 6.08 1039 6.62
10,000 862 5.56 885 5.79 929 6.24 971 6.70 1012 7.18 1054 7.69 1096 8.24
7,500 476 1.39 510 1.58 579 1.99 644 2.40 701 2.81 752 3.29 804 3.96
8,750 545 2.14 574 2.35 633 2.81 691 3.29 747 3.77 797 4.25 842 4.76
028 10,000 615 3.12 641 3.36 692 3.87 743 4.41 794 4.96 843 5.51 888 6.05
11,250 685 4.37 709 4.64 754 5.20 800 5.79 845 6.40 891 7.02 935 7.64
12,500 756 5.92 778 6.22 819 6.83 860 7.47 901 8.14 942 8.83 983 9.52
9,000 539 2.18 569 2.39 626 2.85 683 3.34 739 3.83 791 4.32 837 4.82
10,500 620 3.37 646 3.62 695 4.13 744 4.68 793 5.25 842 5.83 888 6.41
034 12,000 701 4.94 724 5.22 769 5.80 811 6.40 854 7.04 897 7.69 940 8.36
13,500 783 6.95 804 7.27 844 7.91 883 8.57 920 9.26 958 9.97 996 10.71
15,000 865 9.45 884 9.81 921 10.52 956 11.24 991 11.98 1025 12.75 1059 13.54

See legend and notes on page 49.

FAN PERFORMANCE DATA — 40RM WITH HIGH-CAPACITY COIL —


1.4-2.4 in. wg ESP — ENGLISH

UNIT EXTERNAL STATIC PRESSURE (in. wg)


40RM AIRFLOW 1.4 1.6 1.8 2.0 2.2 2.4
(High-Capacity (Cfm)
4-Row Coil) Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
4,500 912 2.75 967 3.12 1019 3.52 1070 3.92 1120 4.35 1168 4.79
5,300 942 3.34 992 3.76 1041 4.18 1088 4.61 1134 5.06 1179 5.52
016 6,000 971 3.95 1020 4.40 1067 4.86 1112 5.33 1156 5.81 1198 6.29
6,800 1005 4.72 1054 5.23 1101 5.75 1145 6.27 1187 6.79 — —
7,500 1036 5.48 1084 6.04 1131 6.61 1174 7.17 — — — —
6,000 961 3.86 1011 4.31 1058 4.77 1104 5.24 1147 5.71 — —
7,000 1000 4.79 1050 5.32 1097 5.85 1142 6.38 1184 6.91 — —
024 8,000 1041 5.88 1090 6.47 1137 7.07 1181 7.67 — — — —
9,000 1086 7.21 1133 7.82 1178 8.47 — — — — — —
10,000 1138 8.83 1180 9.46 — — — — — — — —
7,500 874 5.33 897 5.91 940 6.80 990 7.50 — — — —
8,750 886 5.36 930 6.13 982 7.32 1020 8.10 — — — —
028 10,000 930 6.60 969 7.20 1007 7.89 1045 8.71 — — — —
11,250 976 8.25 1014 8.86 1051 9.49 1086 10.17 — — — —
12,500 1023 10.20 1061 10.88 1097 11.56 — — — — — —
9,000 881 5.37 923 6.03 967 6.89 1020 8.25 — — — —
10,500 930 6.97 970 7.55 1008 8.17 1045 8.86 — — — —
034 12,000 981 9.02 1021 9.67 1058 10.32 1094 10.97 — — — —
13,500 1035 11.45 1072 12.20 — — — — — — — —
15,000 1093 14.35 — — — — — — — — — —

See legend and notes on page 49.

48
LEGEND AND NOTES FOR STANDARD AND HIGH-CAPACITY COIL
FAN PERFORMANCE DATA TABLES (SI)
LEGEND FACTORY-SUPPLIED FILTER PRESSURE DROP
ESP — External Static Pressure — SI
Bold indicates field-supplied drive is required. AIRFLOW PRESSURE DROP
Plain type indicates standard motor and standard drive. UNIT (L/s) (Pa)
Underline indicates a different motor and drive combination other than
the standard motor and standard drive combination is required. Refer to 40RM 2100 20
fan motor and drive tables to complete the selection. 2800 30
016
3500 42
NOTES: 2900 32
1. Maximum allowable fan speed is 18.3 r/s for unit sizes 028 and 40RM
3800 47
034; 20 r/s for all other sizes. 024 4700 64
2. Fan performance is based on deductions for wet coil, clean 51-mm 3500 36
filters, and unit casing. See table at right for factory-supplied filter 40RM
4700 55
pressure drop. 028 5900 76
3. The medium-static drive and standard motor combination is not
available for 016-028 sizes. Use alternate motor if medium-static 4250 47
40RM 5650 71
drive is required for these sizes. 034
7050 98

LEGEND AND NOTES FOR STANDARD AND HIGH-CAPACITY COIL


FAN PERFORMANCE DATA TABLES (English)
LEGEND FACTORY-SUPPLIED FILTER PRESSURE DROP
Bhp — Brake Horsepower Input to Fan — ENGLISH
ESP — External Static Pressure
AIRFLOW PRESSURE DROP
Bold indicates field-supplied drive is required. UNIT (Cfm) (in. wg)
Plain type indicates standard motor and standard drive.
Underline indicates a different motor and drive combination other than 40RM 4,500 0.08
the standard motor and standard drive combination is required. Refer to 6,000 0.12
016 7,500 0.17
fan motor and drive tables to complete selection.
40RM 6,000 0.12
NOTES: 8,000 0.19
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 024
10,000 0.26
034; 1200 rpm for all other sizes. 7,500 0.15
2. Fan performance is based on deductions for wet coil, clean 2-in. 40RM
028 10,000 0.22
filters, and unit casing. See table at right for factory-supplied filter 12,500 0.30
pressure drop.
3. The medium-static drive and standard motor combination is not 9,000 0.19
40RM
available for 016-028 sizes. Use alternate motor if medium-static 034 12,000 0.29
drive is required for these sizes. 15,000 0.40

49
Performance data (cont)
40RM PLENUM ACCESSORY AIR THROW DATA — 40RM PLENUM ACCESSORY AIR THROW DATA —
SI (m) ENGLISH (Ft)

UNIT AIRFLOW VANE DEFLECTION UNIT AIRFLOW VANE DEFLECTION


40RM (L/s) Straight 221/2° 45° 40RM (Cfm) Straight 221/2° 45°
016 2800 15.41 13.25 9.55 016 6,000 50 43 31
024 3800 18.17 15.44 11.20 024 8,000 60 51 37
028 4700 23.26 19.89 14.38 028 10,000 76 65 47
034 5650 25.97 22.00 15.89 034 12,000 85 72 52
NOTE: Throw distances shown are for 0.381 m/sec terminal velocity. Use the fol- NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following
lowing multipliers to determine throw values for other terminal velocities. multipliers to determine throw values for other terminal velocities.

TERMINAL VELOCITY TERMINAL VELOCITY


THROW FACTOR THROW FACTOR
(m/sec) (Fpm)
0.254 X 1.50 50 X 1.50
0.508 X 0.75 100 X 0.75
0.762 X 0.50 150 X 0.50

40RM ACCESSORY PRESSURE DROP — SI (Pa)

UNIT AIRFLOW DISCHARGE RETURN AIR HEATING COILS


40RM (L/s) PLENUM GRILLE ECONOMIZER
Hot Water Steam Electric
2100 24 2 36 36 14 15
016 2800 39 5 57 57 24 22
3500 56 7 82 82 37 37
2900 41 5 60 60 26 23
024 3800 64 10 93 93 43 43
4700 91 15 132 132 65 69
3500 37 5 67 67 22 15
028 4700 59 7 109 109 39 22
5900 86 12 157 157 60 35
4250 50 7 92 92 32 20
034 5650 80 12 147 147 56 35
7050 114 17 210 210 85 52

40RM ACCESSORY PRESSURE DROP — ENGLISH (in. wg)

UNIT AIRFLOW DISCHARGE RETURN AIR HEATING COILS


ECONOMIZER
40RM (Cfm) PLENUM GRILLE Hot Water Steam Electric
4,500 0.10 0.01 0.15 0.15 0.06 0.06
016 6,000 0.16 0.02 0.23 0.23 0.10 0.09
7,500 0.23 0.03 0.33 0.33 0.15 0.15
6,000 0.16 0.02 0.23 0.23 0.10 0.09
024 8,000 0.26 0.04 0.37 0.37 0.17 0.17
10,000 0.37 0.06 0.53 0.53 0.26 0.28
7,500 0.15 0.02 0.28 0.28 0.09 0.06
028 10,000 0.24 0.03 0.44 0.44 0.16 0.09
12,500 0.34 0.05 0.63 0.63 0.24 0.14
9,000 0.20 0.03 0.37 0.37 0.13 0.08
034 12,000 0.32 0.05 0.59 0.59 0.22 0.14
15,000 0.46 0.07 0.85 0.85 0.34 0.21

50
Typical piping and wiring
ROOFTOP INSTALLATION — 38AKS028-044

LEGEND NOTES:
TXV — Thermostatic Expansion Valve 1. All piping must follow standard refrigerant piping techniques.
Refer to Carrier System Design Manual for details.
Piping 2. All wiring must comply with the applicable local and national
codes.
*Field supplied. 3. Wiring and piping shown are general points-of-connection
†Double riser may be required. See Application Data on page 66. guides only and are not intended for, or to include all details for,
a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recom-
mended to prevent refrigerant migration to the compressor.
5. Internal factory-supplied TXVs not shown.

51
Typical piping and wiring (cont)
GROUND-LEVEL INSTALLATION — 38AKS028-044

LEGEND
TXV — Thermostatic Expansion Valve
Piping

*Field supplied.
NOTES:
1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System
Design Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not
intended for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refriger-
ant migration to the compressor.

52
ROOFTOP INSTALLATION — 38AH024-034

LEGEND NOTES:
LLSV — Liquid Line Solenoid Valve 1. All piping must follow standard refrigerant piping techniques. Refer
TXV — Thermostatic Expansion Valve to Carrier System Design Manual for details.
Piping 2. All wiring must comply with the applicable local and national
codes.
Double Riser Piping (If Required) 3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
*Field supplied. installation.
†If double suction riser is required for piping system, size pipe 4. Liquid line solenoid valve (solenoid drop control) is recommended
diameter of 3 ft (.9144 m) (maximum) riser according to appli- to prevent refrigerant migration to the compressor.
cation data on page 68. 5. Internal factory-supplied TXVs not shown.

53
Typical piping and wiring (cont)
GROUND LEVEL INSTALLATION — 38AH024-034

NOTES:
LEGEND
1. All piping must follow standard refrigerant piping techniques. Refer
TXV — Thermostatic Expansion Valve to Carrier System Design Manual for details.
Piping 2. All wiring must comply with the applicable local and national
codes.
*Field supplied. 3. Wiring and piping shown are general points-of-connection guides
only and are not intended for, or to include all details for, a specific
installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended
to prevent refrigerant migration to the compressor.

54
Electrical data
38AKS028-044

UNIT NOMINAL VOLTAGE VOLTAGE RANGE* COMPRESSOR FAN MOTOR POWER SUPPLY
38AKS (V-Ph-Hz) Min Max RLA LRA Qty FLA (ea) MCA MOCP†
346-3-50 311 380 44.9 155 2 4.4 64.9 100
028 230-3-50 198 254 76.9 205 2 6.4 109.0 175
400-3-50 342 440 43.6 223 2 3.0 60.5 100
346-3-50 311 380 53.9 176 2 4.4 76.1 125
034 230-3-50 198 254 85.9 220 2 6.4 120.2 200
400-3-50 342 440 50.0 253 2 3.0 68.5 110
346-3-50 311 380 79.5 240 3 4.4 112.6 175
044 230-3-50 198 254 105.1 327 3 6.4 150.6 250
400-3-50 342 440 65.4 345 3 3.0 90.8 150

LEGEND NOTES:
FLA —
Full Load Amps 1. MCA and MOCP values are calculated in accordance with NEC
HACR —
Heating, Air Conditioning, Refrigeration (National Electric Code) (U.S.A. Standard), Article 440.
LRA —
Locked Rotor Amps 2. Motor FLA and RLA values are established in accordance with UL
MCA —
Minimum Circuit Amps per (Underwriters’ Laboratories) Standard 1995 (U.S.A. standard).
NEC Section 430-24 3. 230-v and 346-v units are part-wind-start units; the value under
MOCP — Maximum Overcurrent Protection compressor LRA is for the first winding energized. The 400-v units
NEC — National Electrical Code (U.S.A. Standard) are across-the-line-start units; value shown is for all windings
RLA — Rated Load Amps (Compressor) energized.

*Units are suitable for use on electrical systems where voltage supplied
to unit terminals is not below or above listed minimum and maximum
limits.
†Fuse or HACR circuit breaker.

FIELD POWER WIRE SIZE


UNIT VOLTAGE FIELD POWER WIRE SIZE
38AKS (3 Ph, 50 Hz) TB1 WILL ACCEPT
346
028 230 14 to 2/0 AWG
400
346 14 to 2/0 AWG
034 230 6 AWG to 350 kcmil
400 14 to 2/0 AWG
346 14 to 2/0 AWG
044 230 6 AWG to 350 kcmil
400 14 to 2/0 AWG

LEGEND
AWG — American Wire Gage
kcmil — Thousand circular mils (formerly MCM)
TB — Terminal Block

55
Electrical data (cont)
38AH024-034
VOLTAGE
NOMINAL RANGE* COMPRESSOR FAN MOTORS† (Qty 2) POWER SUPPLY
UNIT
VOLTAGE
38AH RLA LRA FLA Nominal Nominal
(V-Ph-Hz) Min Max MCA MOCP ICF
Ckt 1 Ckt 2 Ckt 1 Ckt 2 (ea) Hp kW
230-3-50 198 254 39.3 39.3 128 128 6.3 101.0 125 268.8
024 346-3-50 311 380 24.0 24.0 93 93 4.4 1 0.75 62.8 80 194.8
400-3-50 342 440 18.0 18.0 99 99 3.0 46.5 60 204.0
230-3-50 198 254 43.6 43.6 143 143 6.3 110.7 150 298.8
028 346-3-50 311 380 26.4 26.4 104 104 4.4 1 0.75 68.2 90 216.8
400-3-50 342 440 22.1 22.1 114 114 3.0 55.7 70 234.0
230-3-50 198 254 43.6 63.6 143 200 6.3 135.7 175 355.8
034 346-3-50 311 380 26.4 34.3 104 145 4.4 1 0.75 78.1 110 257.8
400-3-50 342 440 22.1 30.0 114 120 3.0 65.6 90 240.0
LEGEND *Units are suitable for use on electrical systems where voltage supplied
FLA — Full Load Amps to unit terminals is not below or above listed minimum and maximum.
ICF — Maximum Instantaneous Current Flow During Starting. †All fans are protected by a single circuit breaker.
(The point in the starting sequence where the sum of NOTES:
the LRA for the starting compressor, plus the total RLA 1. MCA and MOCP values are calculated in accordance with NEC
for all running compressors, plus the total FLA for all (National Electrical Code) (U.S.A. standard), Article 440.
running fan motors is maximum.) 2. Motor FLA values are established in accordance with UL (Under-
LRA — Locked Rotor Amps writers’ Laboratories) Standard 1995 (U.S.A. standard).
MCA — Minimum Circuit Amps (complies with National Electri-
cal Code [NEC] Section 430-24) (U.S.A. Standard)
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps

40RM STANDARD MOTORS


NOMINAL VOLTAGE RANGE FAN MOTOR POWER SUPPLY
UNIT VOLTAGE
40RM Min Max Nominal Nominal FLA MCA MOCP
(V*-Ph-Hz) kW Hp
230-3-50 207 253 2.16 2.9 7.5 9.4 15
016
400-3-50 360 440 2.16 2.9 3.4 4.3 15
230-3-50 207 253 3.73 5.0 13.2 16.5 25
024
400-3-50 360 440 3.73 5.0 7.6 9.5 15
230-3-50 207 253 5.59 7.5 19.8 24.8 40
028
400-3-50 360 440 5.59 7.5 11.4 14.3 25
230-3-50 207 253 7.46 10.0 28.0 35.0 60
034
400-3-50 360 440 7.46 10.0 16.1 20.1 30
LEGEND Determine maximum deviation from average voltage.
FLA — Full Load Amps (AB) 397 – 393 = 4 v
MCA — Minimum Circuit Amps (complies with National Electrical (BC) 403 – 397 = 6 v
Code [NEC] Section 430-24) (U.S.A. Standard) (AC) 397 – 396 = 1 v
MOCP — Maximum Overcurrent Protection Maximum deviation is 6 v.
*Motors are designed for satisfactory operation within 10% of nominal Determine percent voltage imbalance.
voltages shown. Voltages should not exceed the limits shown in the 6
Voltage Range column. % Voltage Imbalance = 100 x
397
NOTES: = 1.5%
1. MCA and MOCP values are calculated in accordance with NEC
(National Electrical Code) (U.S.A. standard), Article 440. This amount of phase imbalance is satisfactory as it is below the maxi-
2. Motor FLA values are established in accordance with UL (Under- mum allowable 2%.
writers’ Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage IMPORTANT: If the supply voltage phase imbalance is more than 2%,
Never operate a motor where a phase imbalance in supply voltage contact your local electric utility company immediately.
is greater than 2%. Use the following formula to determine the per-
cent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v

Average Voltage = 393 + 403 + 396


3
1192
=
3
= 397

56
40RM ALTERNATE MOTORS
VOLTAGE RANGE FAN MOTOR POWER SUPPLY
UNIT
V*-PH-Hz Nominal Nominal
40RM Min Max FLA MCA MOCP
kW Hp
230-3-50 207 253 3.73 5.0 13.2 16.5 25
016
400-3-50 360 440 3.73 5.0 7.6 9.5 15
230-3-50 207 253 5.59 7.5 19.8 24.8 40
024
400-3-50 360 440 5.59 7.5 11.4 14.3 25
230-3-50 207 253 7.46 10.0 28.0 35.0 60
028
400-3-50 360 440 7.46 10.0 16.1 20.1 30

LEGEND Determine maximum deviation from average voltage.


FLA — Full Load Amps (AB) 397 – 393 = 4 v
MCA — Minimum Circuit Amps (BC) 403 – 397 = 6 v
MOCP — Maximum Overcurrent Protection (AC) 397 – 396 = 1 v
Maximum deviation is 6 v.
*Motors are designed for satisfactory operation within 10% of nominal
voltages shown. Voltages should not exceed the limits shown in the Determine percent voltage imbalance.
Voltage Range column. 6
% Voltage Imbalance = 100 x
NOTES: 397
1. Minimum circuit amp and MOCP values are calculated in accor- = 1.5%
dance with NEC (National Electrical Code) (U.S.A. standard), Arti-
cle 440. This amount of phase imbalance is satisfactory as it is below the maxi-
2. Motor FLA values are established in accordance with UL (Under- mum allowable 2%.
writers’ Laboratories) Standard 1995 (U.S.A. standard).
3. Unbalanced 3-Phase Supply Voltage IMPORTANT: If the supply voltage phase imbalance is more than 2%,
Never operate a motor where a phase imbalance in supply voltage contact your local electric utility company immediately.
is greater than 2%. Use the following formula to determine the per-
cent voltage imbalance.
% Voltage Imbalance
max voltage deviation from average voltage
= 100 x
average voltage
EXAMPLE: Supply voltage is 400-3-50.
AB = 393 v
BC = 403 v
AC = 396 v
393 + 403 + 396
Average Voltage =
3
1192
=
3
= 397

40RM FAN CONTACTOR COIL

UNIT VOLTAGE MAXIMUM


HOLDING
40RM (vac)
VA
016-034 24 10

57
Electrical data (cont)
40RM ELECTRIC HEATER ACCESSORY DATA
ELECTRIC HEATER(S)
FAN MOTOR
UNIT HEATER V-PH-Hz Nominal Actual Capacity (kW) MCA* MOCP*
40RM PART NO. Capacity FLA
Hp kW FLA (kW) Stage 1 Stage 2 Total
2.9 2.16 7.5 10 10.0 — 10.0 24.1 39.4 40
CAELHEAT016A00 240-3-50 5.0 3.73 13.2 10 10.0 — 10.0 24.1 46.6 50
7.5 5.59 19.8 10 10.0 — 10.0 24.1 54.8 60
2.9 2.16 3.4 10 6.9 — 6.9 10.0 16.8 20
CAELHEAT017A00 400-3-50 5.0 3.73 7.6 10 6.9 — 6.9 10.0 22.0 25
7.5 5.59 11.4 10 6.9 — 6.9 10.0 26.8 35
2.9 2.16 7.5 20 19.9 — 19.9 47.9 69.2 70
CAELHEAT019A00 240-3-50 5.0 3.73 13.2 20 19.9 — 19.9 47.9 76.3 80
7.5 5.59 19.8 20 19.9 — 19.9 47.9 84.6 90
2.9 2.16 3.4 20 13.9 — 13.9 20.0 29.3 30
CAELHEAT020A00 400-3-50 5.0 3.73 7.6 20 13.9 — 13.9 20.0 45.1 50
7.5 5.59 11.4 20 13.9 — 13.9 20.0 49.2 50
016,024
2.9 2.16 7.5 30 20.0 10.0 30.0 72.2 99.6 100
CAELHEAT022A00 240-3-50 5.0 3.73 13.2 30 20.0 10.0 30.0 72.2 106.7 110
7.5 5.59 19.8 30 20.0 10.0 30.0 72.2 115.0 125
2.9 2.16 3.4 30 13.9 6.9 20.8 30.1 41.8 50
CAELHEAT023A00 400-3-50 5.0 3.73 7.6 30 13.9 6.9 20.8 30.1 47.1 50
7.5 5.59 11.4 30 13.9 6.9 20.8 30.1 51.8 60
2.9 2.16 7.5 50 30.0 20.0 50.0 120.3 159.7 175
CAELHEAT025A00 240-3-50 5.0 3.73 13.2 50 30.0 20.0 50.0 120.3 166.9 175
7.5 5.59 19.8 50 30.0 20.0 50.0 120.3 175.1 200
2.9 2.16 3.4 50 20.8 13.9 34.7 50.1 66.9 70
CAELHEAT026A00 400-3-50 5.0 3.73 7.6 50 20.8 13.9 34.7 50.1 72.1 80
7.5 5.59 11.4 50 20.8 13.9 34.7 50.1 76.9 80
CAELHEAT028A00 240-3-50 7.5 5.59 19.8 20 20.0 — 19.9 47.9 84.6 90
10.0 7.46 28.0 20 20.0 — 19.9 47.9 94.8 110
CAELHEAT029A00 400-3-50 7.5 5.59 11.4 20 13.9 — 13.9 20.0 39.3 40
10.0 7.46 16.1 20 13.9 — 13.9 20.0 45.2 50
CAELHEAT031A00 240-3-50 7.5 5.59 19.8 40 20.0 20.0 40.0 96.2 145.9 150
10.0 7.46 28.0 40 20.0 20.0 40.0 96.2 153.3 175
CAELHEAT032A00 400-3-50 7.5 5.59 11.4 40 13.9 13.9 27.8 39.9 64.1 70
028,034 10.0 7.46 16.1 40 13.9 13.9 27.8 39.9 70.0 80
CAELHEAT034A00 240-3-50 7.5 5.59 19.8 50 30.0 20.0 50.0 120.3 175.1 200
10.0 7.46 28.0 50 30.0 20.0 50.0 120.3 185.4 200
CAELHEAT035A00 400-3-50 7.5 5.59 11.4 50 20.8 13.9 34.7 50.1 76.9 80
10.0 7.46 16.1 50 20.8 13.9 34.7 50.1 82.8 90
CAELHEAT037A00 240-3-50 7.5 5.59 19.8 70 40.0 30.0 70.0 168.4 193.1 200
10.0 7.46 28.0 70 40.0 30.0 70.0 168.4 203.4 225
CAELHEAT038A00 400-3-50 7.5 5.59 11.4 70 27.8 20.8 48.6 70.2 84.4 90
10.0 7.46 16.1 70 27.8 20.8 48.6 70.2 90.3 100

LEGEND NOTES:
FLA — Full Load Amps 1. Electric resistance heaters are rated at 240 v and 480 v. To deter-
Hp — Horsepower mine heater capacity (kW) at unit nameplate voltage multiply the
MCA — Minimum Circuit Amps capacity (kW) by the factor shown in the table below.
MOCP — Maximum Overcurrent Protection 2. The following equation converts kW of heat energy to Btuh: kW x
3,412 = Btuh.
*Values shown are for single-point connection of electric heat acces- 3. Heater contactor coils are 24 v and require 8 va holding current.
sory and air handler. 4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 480 Pa (1.9 in. wg).
5. MCA and MOCP values apply to both standard and alternate
factory-supplied motors.
6. Approximate shipping weight for CAELHEAT016A00-026A00 is
27 kg (60 lb) each. Approximate shipping weight for
CAELHEAT028A00-038A00 is 34 kg (75 lb) each.

HEATER RATING ACTUAL HEATER VOLTAGE


VOLTAGE 200 208 230 240 400 440 460 480
240 0.694 0.751 0.918 1 — — — —
480 — — — — 0.694 0.84 0.918 1

58
Controls
Operating sequence — 38AKS028-044 starts. The oil switch and low-pressure switch for circuit
When space thermostat calls for cooling, the no. 1 con- no. 2 are bypassed during start-up.
denser fan and compressor starts after control module As the cooling load is satisfied, the thermostat stops the
(CM) initial time delay of 7 seconds. If an optional airflow call for the second stage of cooling, which in turn deener-
switch is used, compressor and no. 1 condensing fan will gizes compressor no. 2, closes the no. 2 liquid line sole-
not start until sufficient indoor airflow has closed the noid (if installed) and energizes the compressor no. 2
switch. After 7 seconds the compressor starts and the liq- crankcase heater.
uid line solenoid valve (for solenoid drop control) opens. If the space temperature continues to decrease, then the
The crankcase heater is deenergized. If the head pressure thermostat stops the call for the first stage of cooling,
reaches 1793 kPag (260 psig), the second condenser fan which then deenergizes compressor no. 1 and the outdoor
starts. fans, closes the no. 1 liquid line solenoid valve (if installed),
If cooling demand is low, suction pressure at the com- and energizes the compressor no. 1 crankcase heater.
pressor drops. As the pressure drops, the compressor The unit controls prevent both compressors from reener-
unloads 1 or 2 banks of cylinders, as required. If cooling gizing within 3 minutes from a previous call for operation.
demand is high and 2-stage operation is used, the second
If the unit safeties trip during operation, refer to the
step of the thermostat activates the capacity control liquid
line solenoid which activates the second stage evaporator Installation, Start-Up and Service instructions. To reset the
lockout mode, cycle the unit power.
coil. The compressor cylinders load or unload in response
to compressor suction pressure to meet evaporator load. NOTE: If the thermostat fan switch is in the auto position,
For two and a half minutes after the compressor starts, the indoor fan cycles on and off as the thermostat calls for
cooling (or heating). If the switch is in the continuous posi-
the low-pressure switch (LPS) ignored. If the LPS trips dur-
tion, the fan runs when the outdoor unit is powered.
ing the first 2 minutes of operation, the compressor
remains operational. If a high-pressure switch (HPS) trips 38AH024-034 optional variable air volume unit
at any time, or the LPS trips after 21/2 minutes, the com- with ModuPanel™ control — The ModuPanel control
pressor cannot restart until the 3-minute CM anti-short regulates up to 10 stages of cooling to maintain a leaving-
cycle timer expires. air temperature for variable air volume (VAV) applications.
When connected to one 38AH condensing unit, only
As the space cooling load is satisfied, the second stage of
6 stages are used. See the table on page 60 for unit load-
the thermostat opens, and closes the field-supplied capac-
ity control liquid line solenoid valve to deactivate the sec- ing and compressor operating sequence.
ond stage coil. The compressor adjusts the number of When the timeclock connected to the panel closes, the
active cylinders to meet the new load. When the space indoor-fan contactor is energized through a field-supplied
temperature is satisfied, the first stage of the thermostat relay. (The relay must be a pilot-duty SPST relay with
opens and the control relay and opens. This closes the 115-v coil and 30 va maximum coil draw.) After the time
solenoid drop control valve. The compressor stops and the delays programmed into the ModuPanel control have
crankcase heater is energized, preventing refrigerant from elapsed, and with the leaving air above the set point, the
migrating to the compressor during the off cycle (solenoid stages of mechanical cooling are sequenced as follows:
drop refrigerant control). The CM anti-short-cycling timer 1. Stage 1 starts compressor no. 1 with 2 banks of cylin-
is energized and runs for approximately 3 minutes. During ders unloaded (1/3 loaded). Both unloader solenoids
this time, the compressor is not able to restart. are energized.
38AH024-034 standard constant volume unit with 2. Stage 2 loads one bank of compressor no. 1 cylinders
2-stage cooling thermostat — Seven seconds after a (2/3 loaded) by deenergizing unloader solenoid no. 1.
thermostat call for the first stage of cooling, compressor 3. Stage 3 loads the second bank of compressor no. 1
no. 1 and the outdoor fans start. The no. 2 fan only starts by deenergizing unloader solenoid no. 2.
if the outdoor ambient temperature is above (21.1 C) 70 F.
The oil-pressure switch and the low-pressure switch are by- 4. Stage 4 starts compressor no. 2 and unloads 2 banks
passed for the 1 and 21/2 minutes, respectively. If either of compressor no. 1 cylinders unloaded (1/3 loaded).
the low-pressure switch or oil pressure switch remain open Both unloader solenoids are energized.
after the delay, the unit shuts down and goes into alarm 5. Stage 5 loads one bank of compressor no. 1 cylinders
mode. The indoor-fan motor starts immediately whenev- (2/3 loaded) by deenergizing unloader solenoid no. 1.
er there is a call for cooling. If a liquid line solenoid valve 6. Stage 6 loads one bank of compressor no. 1 cylinders
has been installed (for refrigerant control during the off cy- (fully loaded) by deenergizing unloader solenoid no. 2.
cle), then the solenoid valve for compressor no. 1 opens
immediately upon a call for cooling.
On standard units, compressor no. 1 operates either ful-
ly loaded or at one step of unloading, depending on the
suction pressure, which is dependent on the evaporator
load conditions.
As the cooling demand increases, the thermostat calls
for the second stage of cooling. Within 7 seconds from a
call for the second stage of cooling, compressor no. 2

59
Controls (cont)
Two 38AH024-034 optional variable air volume 7. Stage 7 starts unit no. 2 compressor no. 1 with 2
units with a single ModuPanel™ control — The banks of cylinders unloaded (1/3 loaded). Both
ModuPanel control regulates up to 10 stages of cooling to unloader solenoids are energized.
maintain a leaving-air temperature for variable air volume 8. Stage 8 turns off unit no. 2 compressor no. 1 and
(VAV) applications. When connected to two 38AH con- starts compressor no. 2 fully loaded.
densing units, all 10 stages are used. See the table below
for unit loading and compressor operating sequence. 9. Stage 9 starts unit no. 2 compressor no. 1 with
2 banks of cylinders unloaded (1/3 loaded). Both
When the timeclock connected to the panel closes, the unloader solenoids are energized.
indoor-fan contactor is energized through a field-supplied
relay. (The relay must be a pilot-duty SPST relay with 10. Stage 10 loads 2 banks of unit no. 2 compressor
115-v coil and 30 va maximum coil draw.) After the time no. 1 cylinders (fully loaded) by deenergizing both
delays programmed into the ModuPanel control have unloader solenoids.
elapsed, and with the leaving air above the set point, the Restart — Manual reset of the 24-v control circuit is re-
stages of mechanical cooling are sequenced as follows: quired if unit is shut down by any of the safety devices. Ap-
1. Stage 1 starts unit no. 1 compressor no. 1 with plicable devices include the high pressure switch (HPS),
2 banks of cylinders unloaded (1/3 loaded). Both low-pressure switch (LPS), oil-pressure switch (OPS), and
unloader solenoids are energized. compressor overtemperature protection (COTP) switch.
To restart the unit after the unit has been shut down, raise
2. Stage 2 loads one bank of unit no. 1 compressor the thermostat set point above the space temperature
no. 1 cylinders (2/3 loaded) by deenergizing unloader (thereby removing the call for cooling) and then lower the
solenoid no. 1. set point back to the desired setting.
3. Stage 3 turns off unit no. 1 compressor no. 1 and If unit circuit breakers trip during unit shutdown, they
starts compressor no. 2 fully loaded. must be reset manually.
4. Stage 4 starts unit no. 1 compressor no. 1 with 2
banks of cylinders unloaded (1/3 loaded). Both Causes of complete unit shutdown:
unloader solenoids are energized. • interruption of supplied power
• open compressor overtemperature protection (COTP)
5. Stage 5 loads one bank of unit no. 1 compressor
• compressor electrical overload protection (CB1 or CB2)
no. 1 cylinders (2/3 loaded) by deenergizing unloader
• open high-pressure or low-pressure safety switches
solenoid no. 1.
• open oil pressure switch
6. Stage 6 loads one bank of unit no. 1 compressor
no. 1 cylinders (fully loaded) by deenergizing unloader
solenoid no. 2.

38AH UNIT LOADING SEQUENCE WITH MODUPANEL™ CONTROL


LOADED CYLINDERS
STAGE NO. CYLINDERS CAPACITY STEP (%)
Compressor No. 1 Compressor No. 2
1 2 2 — 17
2 4 4 — 33
3 6 6 — 50
4 8 2 6 67
5 10 4 6 83
6 12 6 6 100

LOADING SEQUENCE, TWO 38AH CONDENSING UNITS WITH MODUPANEL CONTROL


UNIT 1 LOADED CYLINDERS UNIT 2 LOADED CYLINDERS
STAGE NO. CYLINDERS Compressor Compressor Compressor Compressor CAPACITY STEP (%)
No. 1 No. 2 No. 1 No. 2
1 2 2 — — — 8
2 4 4 — — — 17
3 6 — 6 — — 25
4 8 2 6 — — 33
5 10 4 6 — — 41
6 12 6 6 — — 50
7 14 6 6 2 — 58
8 18 6 6 — 6 75
9 20 6 6 2 6 83
10 24 6 6 6 6 100

60
CARRIER CONTROLS

DEBONAIR® COMMERCIAL PROGRAMMABLE COMMERCIAL ELECTRONIC THERMOSTAT


THERMOSTAT

Carrier
®

Pm
COOL
AUTO
HEAT

PREMIERLINK™ COMMUNICATING CONTROLS

61
Typical control wiring schematic
38AKS028-044

62
38AKS028-044 (cont)

LEGEND
AFS — Airflow Switch NEC — National Electrical Code
ATS — Air Temperature Switch (U.S.A. Standard)
C — Contactor, Compressor OPS — Oil Pressure Switch
CB — Circuit Breaker TB — Terminal Block
CH — Crankcase Heater TC — Thermostat-Cooling
CM — Control Module TDR — Time Delay Relay
COMP — Compressor TRAN — Transformer
CR — Control Relay
EQUIP — Equipment Terminal Block Connection
FC — Fan Contactor
FCPS — Fan Cycling Pressure Switch Marked Terminal
FM — Fan Motor Unmarked Terminal
FR — Fan Relay
FU — Fuse Marked Splice
GND — Ground
HPS — High-Pressure Switch Unmarked Splice
LLSV — Liquid Line Solenoid Valve Factory Wiring
LPS — Low-Pressure Switch Field Control Wiring
MM — Motormaster
MMF — Motormaster Fuse Field Power Wiring
MMPT — Motormaster Pressure Transducer Indicates Common Potential, Does Not Represent Wiring

63
Typical control wiring schematic (cont)
38AH024-034

SEE MODUPANEL™ ACCESSORY INSTALLATION FOR SCHEMATIC

64
38AH024-034 (cont)

LEGEND
ATS — Air Temperature Switch PL — Plug Assembly
C — Contactor, Compressor TB — Terminal Block
CB — Circuit Breaker TRAN — Transformer
CH — Crankcase Heater U — Unloader
CM — Control Module VAV — Variable Air Volume
COMP — Compressor Plug
COTP — Compressor Overtemperature
Protection Receptacle
CR — Control Relay Terminal Block Connection
EQUIP — Equipment
FC — Fan Contactor Marked Terminal
FIOP — Factory-Installed Option
FM — Fan Motor Unmarked Terminal
FR — Fan Relay
FU — Fuseblock Marked Splice
GND — Ground
HPS — High-Pressure Switch Unmarked Splice
IFC — Indoor-Fan Contactor
LLSV — Liquid Line SolenoidValve Factory Wiring
LPS — Low-Pressure Switch
MM — Motormaster Field Control Wiring
MMF — Fuse
MMPT — Pressure Transducer Field Power Wiring
MPR — ModuPanel Relay
NEC — National Electrical Code (U.S.A. Standard) Indicates Common Potential,
OPS — Oil Pressure Switch Does Not Represent Wiring

65
Application data — 38AKS units
Installation MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE
Select equipment to match or to be slightly less than peak
load. This provides better humidity control, less unit MIN OUTDOOR
cycling, and less part-load operation. COM- SATURATED TEMPERATURE
UNIT PRESSOR CONDENSING With
When selecting vapor line sizes, oil return should be 38AKS CAPACITY TEMPERATURE Base Low Ambient
Unit
evaluated, particularly at part-load conditions. (%) Control
The evaporator fan must always be operating when out- C F C F C F
door fan is operating. 100 32 90 –6 31
028 67 27 80 1.7 35
Unit cycles should be limited to 3 or less. 33 21 70 1 34
100 32 90 –1 30
Multiple outdoor units may be used with a single indoor 034 67 27 80 1 34 –29 –20
unit. This involves multiple refrigeration circuits. 33 21 70 5.5 42
100 32 90 –3.9 25
IMPORTANT: When application is in a variable air vol- 044 67 27 80 –1 30
33 21 70 1.7 35
ume (VAV) system, total building load is not the sum of
the individual peak loads. If individual peak loads are
summed, the equipment tends to be oversized for the MAXIMUM LIQUID LIFT
load. MAXIMUM LIQUID LIFT
UNIT 38AKS
m ft
To minimize return-air temperature extremes, use the 028 23 76
equipment room as a return-air plenum when applying 034 20 67
VAV systems with supply-to-return air recycle as used with 044 23 76
Carrier VVT® (variable volume and temperature) Control
Systems.
Indoor equipment should be selected at no less than SUCTION LINE PIPING
40 L/s per kW (300 cfm/ton).

IMPORTANT: Condensing units applied in VVT or VAV


systems must have a field-supplied and installed accumu-
lator. Order part number 38AK500410 from Service
Parts.

OPERATING LIMITS
Maximum Outdoor Ambient 46 C (115 F)
Minimum Cooling Load Additional head pressure con- LEGEND
trol may be required below
1.7 C (35 F) outdoor ambient. A — Suction riser without trap
B — Suction riser with trap
Minimum Return-Air C — Suction line to condensing unit
12.8 C (55 F)
Temperature D — Short vertical riser:
Maximum Return-Air 38AKS028 — 15/8 in. OD
35 C (95 F) 38AKS034,044 — 21/8 in. OD
Temperature
Normal Acceptable Saturation 1.1 to 12.8 C (30 to 55 F)
Suction Temperature Range
Maximum Discharge
146 C (295 F)
Temperature
Minimum Discharge
15.6 C (60 F)
Superheat

66
REFRIGERANT PIPE SIZES (Single Suction Risers)
LENGTH OF INTERCONNECTING PIPING — m (ft)
UNIT
38AKS 4.9-7.6 (16-25) 7.9-15.2 (26-50) 15.5-22.8 (51-75) 23.2-30.5 (76-100) 30.8-60.9 (101-200)
L S L S L S L S L S
028 7/ 15 / 8 7/ 21/8* 7/ 21/8* 7/ 21 / 8 * 7/ 21 / 8 *
8 8 8 8 8
034 7/ 21 / 8 7/8 21 / 8 7/8 21 / 8 11 / 8 21 / 8 11 / 8 25 / 8 *
8
044 7/8 21 / 8 7/8 21 / 8 11 / 8 25/8* 11 / 8 25 / 8 * 11 / 8 25 / 8 *

LEGEND NOTE: All line sizes are inches OD.


L — Liquid Line
*IMPORTANT — If condensing unit is above air handler, a double
S — Suction Line
suction riser is required. See table below for sizing.

REFRIGERANT PIPING SIZES (Double Suction Risers)


LENGTH OF INTERCONNECTING PIPING — m (ft)
UNIT
38AKS 7.9-15.2 (26-50) 15.5-22.8 (51-75) 23.2-30.5 (76-100) 30.8-60.9 (101-200)
A B C A B C A B C A B C
028 15 / 8 15 / 8 21 / 8 15 / 8 15 / 8 21 / 8 15 / 8 15 / 8 21 / 8 15 / 8 15 / 8 21 / 8
034 — — — — — — — — — 15 / 8 21 / 8 25 / 8
044 — — — 15 / 8 21 / 8 25 / 8 15 / 8 21 / 8 25 / 8 15 / 8 21 / 8 25 / 8
NOTE: A, B, C dimensions relate to reference diagram.

Multiple condensing unit arrangements*

38AKS028-044 38AKS028-044

38AKS028-044 ONLY
Space for Service and Airflow

*For clearances between controls and grounded surfaces,


check local codes.
†Observe minimum recommended space requirements.

38AKS DIMENSIONS m (ft)


A B
028-044
1.2 (4) 1.2 (4)

67
Application data — 38AH units
Installation To minimize the possibility of air recirculation, avoid the
Select equipment to match or to be slightly less than peak use of concentric supply/return grilles.
load. This provides better humidity control, less unit cy- Indoor equipment should be selected at no less than
cling, and less part-load operation. 40 L/s per kW (300 cfm/ton).
When selecting vapor line sizes, oil return must be evalu-
ated, particularly at part-load conditions. IMPORTANT: Condensing units applied in VVT or
VAV systems must have field-supplied and installed ac-
The indoor fan must always be operating when outdoor cumulators. Order 2 part number --KH--73LZ-001
unit is operating. from Service Parts (1 required for each refrigerant
IMPORTANT: When application is in a VAV (variable
air volume) system, total building load is not the sum of OPERATING LIMITS
the individual peak loads. If individual peak loads are
Maximum Outdoor Ambient 52 C (125 F)
summed, the equipment tends to be oversized for the
See Minimum Outdoor-Air
load. Minimum Outdoor Ambient Operating Temperature
table below.
To minimize return-air temperature extremes, use the Minimum Return-Air Temperature 12.8 C (55 F)
equipment room as a return-air plenum when applying Maximum Return-Air Temperature 35 C (95 F)
VVT® (variable volume temperature) systems with supply- Normal Acceptable Saturation
–6.6 to 10.0 C (20 to 50 F)
Suction Temperature Range
to-return air recycle as used with Carrier VVT control Maximum Discharge Temperature 135 C (275 F)
systems. Minimum Discharge Superheat 15.6 C (60 F)
Ductwork should be sized according to unit size, not
building load.

UNLOADING SEQUENCES

UNIT CAPACITY/STAGE (%)


38AH CV Units (Standard)* VAV Units (Optional)
024 100, 83, 50, 33 100, 83, 67, 50, 33, 17
028 100, 83, 50, 33 100, 83, 67, 50, 33, 17
034 100, 85, 43, 28 100, 85, 71, 43, 28, 14
LEGEND
CV — Constant Volume
VAV — Variable Air Volume
*Additional unloading available with field-installed accessory unloader.
NOTE: Capacities are based on 7.2 C (45 F) saturated suction temperature and 35 C
(95 F) outdoor air temperature.

MINIMUM OUTDOOR-AIR OPERATING


TEMPERATURE AND UNLOADING SEQUENCES
MINIMUM OUTDOOR-AIR TEMP
UNIT SYSTEM
38AH CAPACITY (%) Standard Unit Low Ambient Control
C F C F
100 –29 –20
83 –29 –20
024 67† 11.7 53 * *
50 –29 –20
33 –29 –20
17† * *
100 –29 –20
83 –29 –20
028 67† 10.0 50 * *
50 –29 –20
33 –29 –20
17† * *
100 –29 –20
85 –29 –20
034 71† 9.4 49 * *
43 –29 –20
28 –29 –20
14† * *
*Motormaster® V cannot be used with 2 unloaders.
†VAV or accessory unloader on Circuit 1.
NOTE: Minimum outdoor-air operating temperature is based on 32 C (90 F) saturated condensing
temperature and 100% capacity.

68
REFRIGERANT PIPE SIZES
SINGLE SUCTION RISERS

LENGTH OF INTERCONNECTING PIPING, FOR EACH CIRCUIT — FT (M)


UNIT
0-25 (0-7.6) 25-50 (7.6-15.2) 50-75 (15.2-22.9) 75-100 (22.9-30.5) 100-200 (30.5-61.0)
38AH
L S L S L S L S L S
024 Ckt 1 1/ 11 / 8 5/8 13 / 8 5/8 13 / 8 5/8 13 / 8 7/8 15/8*†
2
Ckt 2 1/ 11 / 8 5/ 13 / 8 5/ 13 / 8 5/ 13 / 8 7/ 15/8*†
2 8 8 8 8

028 Ckt 1 1/2 11 / 8 5/8 13 / 8 5/8 13 / 8 5/8 13 / 8 7/8 15/8*†


Ckt 2 1/ 11 / 8 5/ 13 / 8 5/ 13 / 8 5/ 13 / 8 7/ 15/8*†
2 8 8 8 8

034 Ckt 1 1/ 11 / 8 5/ 13 / 8 5/ 13 / 8 5/ 13 / 8 7/ 15/8*†


2 8 8 8 8
Ckt 2 5/8 13 / 8 5/8 15 / 8 5/8 15 / 8 7/8 15 / 8 7/8 21/8*†

LEGEND NOTES:
L — Liquid Line 1. All line sizes are inches OD.
S — Suction Line 2. Standard unit comes with one pressure-operated unloader on cir-
cuit no. 1. If unit serves one air handler, an additional unloader
*Double suction riser required if evaporator is below condensing unit may be field installed on circuit no. 1 compressor only. If the unit
and 2 unloaders are used on that circuit. serves 2 separate air handlers and low ambient operation is
†Double suction riser required if evaporator is below condensing unit required (Motormaster V control), each circuit’s compressor may
and compressor is equipped with 2 unloaders. Note the only time only be equipped with one unloader.
circuit no. 2 may be equipped with 2 unloaders is if it is serving its own 3. Equivalent line sizes in mm follow:
air handler and the unit does not require low ambient operation
(Motormaster® control). in. mm in. mm
1/2 12.7 13/8 34.9
5/8 15.9 15/8 41.3
7/ 22.2 21/8 54.0
8
11/8 28.6

DOUBLE SUCTION RISERS


LENGTH OF INTERCONNECTING PIPING — FT (M)
UNIT
100-200 (30.5-61.0)
38AH
A B C
024 Ckt 1 11/8 13/8 15/8
Ckt 2 13/8 13/8 15/8
028 Ckt 1 11/8 13/8 15/8
Ckt 2 11/8 13/8 15/8
034 Ckt 1 11/8 13/8 15/8
Ckt 2 13/8 15/8 21/8

MAXIMUM LIQUID LIFT LEGEND


— Suction Riser without Trap
UNIT MAXIMUM LIQUID LIFT
38AH PER CIRCUIT — M (Ft) — Suction Riser with Trap
024 23.2 ( 76) — Suction Line to Condensing Unit
028 22.3 ( 73)
034 30.5 (100) — Pipe Diameter to be Same Size as Riser A

69
Application data — 38AH units (cont)
MULTIPLE CONDENSING UNIT ARRANGEMENTS

Space for Service and Airflow


*For clearances between controls and grounded sur-
faces, check local codes.

DIMENSIONS m (ft)
38AH
A B
024
028 1.2 (4) 1.2 (4)
034

70
Application data — 40RM units
Operating limits The air handler fan must always be operating when the
Maximum fan speed — condensing unit is operating.
40RM016,024 . . . . . . . . . . . . . . . .20 r/s (1200 rpm) Ductwork should be sized according to unit size, not build-
Maximum fan speed — ing load. For larger units with two fans, a split duct transition
40RM028,034 . . . . . . . . . . . . . . 18.3 r/s (1100 rpm) is recommended at the fan outlets, but a plenum can be used
with slight reduction in external static pressure capability.
General For variable air volume (VAV) systems with supply-to-
Select equipment to match or to be slightly less than peak return air recycling, use the equipment room as a return air
load. This provides better humidity control, less unit cycling, plenum.
and less part-load operation. Equipment should be selected
to perform at no less than 40 L/s per kW (300 cfm/ton).

FACTORY-INSTALLED NOZZLE AND DISTRIBUTOR DATA

UNIT FEEDER TUBES


COIL TXV DISTRIBUTOR PER DISTRIBUTOR
NOZZLE
40RM TYPE Qty...Part No.* Qty...Part No.† Qty...Part No.
Qty...Size (in.)
016 3 Row 2...TDEBX8 2...1116 12...1/4 2...E6
4 Row 2...TDEBX8 2...1126 16...1/4 2...C6
024 3 Row 2...TDEBX11 2...1116 13...1/4 2...E8
4 Row 2...TDEBX11 2...1126 18...3/16 2...C8
028 3 Row 2...TDEBX11 2...1126 15...1/4 2...C10
4 Row 2...TDEBX11 2...1126 20...3/16 2...C15
034 3 Row 2...TDEBX16 2...1126 18...1/4 2...C12
4 Row 2...TDEBX16 2...1126 24...3/16 2...C17
*Danfoss part numbers shown.
†Sporlan Valve Co. part numbers shown.
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

40RM FAN MOTOR DATA


STANDARD MOTOR — SI STANDARD MOTOR — ENGLISH

UNIT UNIT
016 024 028 034 016 024 028 034
40RM 40RM
230-3-50 and 400-3-50 230-3-50 and 400-3-50
Speed (r/s) 23.75 23.75 23.75 23.75 Speed (rpm) 1425 1425 1425 1425
Shaft kW 2.16 3.73 5.59 7.46 Hp 2.9 5.0 7.5 10.0
Frame (NEMA) 56Y 184T S213T S215T Frame (NEMA) 56Y 184T S213T S215T
Shaft Dia (mm) 22.2 28.6 34.9 34.9 Shaft Dia (in.) 7/8 11 / 8 13 / 8 13/8

NEMA — National Electrical Manufacturers Association (U.S.A.) NEMA — National Electrical Manufacturers Association (U.S.A.)

ALTERNATE MOTOR — SI ALTERNATE MOTOR — ENGLISH

UNIT UNIT
016 024 028 016 024 028
40RM 40RM
230-3-50 and 400-3-50 230-3-50 and 400-3-50
Speed (r/s) 23.75 23.75 23.75 Speed (rpm) 1425 1425 1425
Shaft kW 3.73 5.59 7.46 Hp 5.0 7.5 10.0
Frame (NEMA) S184T S213T S215T Frame (NEMA) S184T S213T S215T
Shaft Dia (mm) 28.6 34.9 34.9 Shaft Dia (in.) 11/8 13/8 13/8

NEMA — National Electrical Manufacturers Association (U.S.A.) NEMA — National Electrical Manufacturers Association (U.S.A.)

71
Application data — 40RM units (cont)
40RM DRIVE DATA
STANDARD DRIVE — SI HIGH-STATIC DRIVE — SI

UNIT UNIT
016 024 028 034 016 024 028 034
40RM 40RM
MOTOR DRIVE MOTOR DRIVE
Motor Pulley Pitch Diameter 86.4- 109.2- 109.2- 109.2- Motor Pulley Pitch Diameter 101.6- 101.6- 109.2- 109.2-
(mm) 111.8 134.6 134.6 134.6 (mm) 127.0 127.0 134.6 134.6
Pulley Factory Setting Pulley Factory Setting
2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Full Turns Open Full Turns Open
FAN DRIVE FAN DRIVE
Pulley Pitch Dia (mm) 229 218 279 279 Pulley Pitch Dia (mm) 178 163 203 218
Pulley Bore (mm) 36.5 36.5 49.2 49.2 Pulley Bore (mm) 36.5 36.5 49.2 49.2
Belt No. — Section 1—A 1—B 2—B 2—B Belt No. — Section 2—A 2—A 2—B 2—B
Belt Pitch (mm) 1074 1062 1113 1113 Belt Pitch (mm) 998 871 935 960
FAN SPEEDS (r/s) FAN SPEEDS (r/s)
Factory Setting 10.3 13.3 10.4 10.4 Factory Setting 15.3 16.7 14.3 13.3
Range 9.0- 11.9- 9.3- 9.3- Range 13.6- 14.9- 12.8- 11.9-
11.6 14.6 11.5 11.5 17.0 18.6 15.7 14.6
Max Allowable Speed (r/s) 20.0 20.0 18.3 18.3 Max Allowable Speed (r/s) 20.0 20.0 18.3 18.3
Change per 1/2 Turn of Change per 1/2 Turn of
Moveable Motor Pulley 0.265 0.230 0.180 0.180 Moveable Motor Pulley 0.283 0.308 0.247 0.230
Flange Flange
MAX FULL TURNS FROM MAX FULL TURNS FROM
CLOSED POSITION 5 6 6 6 CLOSED POSITION 6 6 6 6
SHAFTS CENTER DISTANCE 265- 232- 169- 169- SHAFTS CENTER DISTANCE 232- 207- 169- 169-
(mm) 313 279 240 240 (mm) 279 255 240 240

MEDIUM-STATIC DRIVE — SI

UNIT
40RM 016 024 028 034
MOTOR DRIVE
Motor Pulley Pitch Diameter 94.0- 101.6- 109.2- 109.2-
(mm) 119.4 127.0 134.6 134.6
Pulley Factory Setting 3.0 2.5 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (mm) 201 178 239 239
Pulley Bore (mm) 36.5 36.5 49.2 49.2
Belt No. — Section 1—B 2—A 2—B 2—B
Belt Pitch (mm) 1011 922 1011 1011
FAN SPEEDS (r/s)
Factory Setting 12.6 15.3 12.1 12.1
Range 11.1- 13.6- 10.9- 10.9-
14.1 17.0 13.4 13.4
Max Allowable Speed (r/s) 20.0 20.0 18.3 18.3
Change per 1/2 Turn of
Moveable Motor Pulley 0.252 0.340 0.210 0.210
Flange
MAX FULL TURNS FROM
6 5 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 232- 232- 169- 169-
(mm) 279 279 240 240

72
40RM DRIVE DATA (cont)
STANDARD DRIVE — ENGLISH HIGH-STATIC DRIVE — ENGLISH

UNIT UNIT
016 024 028 034 016 024 028 034
40RM 40RM
MOTOR DRIVE MOTOR DRIVE
Motor Pulley Pitch Diameter Motor Pulley Pitch Diameter
3.4-4.4 4.3-5.3 4.3-5.3 4.3-5.3 4.0-5.0 4.0-5.0 4.3-5.3 4.3-5.3
(in.) (in.)
Pulley Factory Setting Pulley Factory Setting
2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Full Turns Open Full Turns Open
FAN DRIVE FAN DRIVE
Pulley Pitch Dia (in.) 9.0 8.6 11.0 11.0 Pulley Pitch Dia (in.) 7.0 6.4 8.0 8.6
Pulley Bore (in.) 17/16 17/16 115/16 115/16 Pulley Bore (in.) 17/16 17/16 115/16 115/16
Belt No. — Section 1—A 1—B 2—B 2—B Belt No. — Section 2—A 2—A 2—B 2—B
Belt Pitch (in.) 42.3 41.8 43.8 43.8 Belt Pitch (in.) 39.3 34.3 36.8 37.8
FAN SPEEDS (rpm) FAN SPEEDS (rpm)
Factory Setting 618 795 622 622 Factory Setting 916 1002 855 795
538- 713- 557- 557- 814- 891- 766- 713-
Range Range
697 878 687 687 1018 1113 944 878
Max Allowable Speed (rpm) 1200 1200 1100 1100 Max Allowable Speed (rpm) 1200 1200 1100 1100
Change per 1/2 Turn of Change per 1/2 Turn of
Moveable Motor Pulley 15.9 13.8 10.8 10.8 Moveable Motor Pulley 17.0 18.5 14.8 13.8
Flange Flange
MAX FULL TURNS FROM MAX FULL TURNS FROM
5 6 6 6 6 6 6 6
CLOSED POSITION CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 9.12- 6.67- 6.67- SHAFTS CENTER DISTANCE 9.16- 8.16- 6.67- 6.67-
(in.) 12.32 10.99 9.43 9.43 (in.) 10.99 10.02 9.43 9.43

MEDIUM-STATIC DRIVE — ENGLISH

UNIT 016 024 028 034


40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.7-4.7 4.0-5.0 4.3-5.3 4.3-5.3
(in.)
Pulley Factory Setting
Full Turns Open 3.0 2.5 3.0 3.0
FAN DRIVE
Pulley Pitch Dia (in.) 7.9 7.0 9.4 9.4
Pulley Bore (in.) 17/16 17/16 115/16 115/16
Belt No. — Section 1—B 2—A 2—B 2—B
Belt Pitch (in.) 39.8 36.8 39.8 39.8
FAN SPEEDS (rpm)
Factory Setting 756 916 728 728
667- 814- 652- 652-
Range 848 1018 803 803
Max Allowable Speed (rpm) 1200 1200 1100 1100
Change per 1/2 Turn of
Moveable Motor Pulley 15.1 20.4 12.6 12.6
Flange
MAX FULL TURNS FROM
6 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 9.16- 9.16- 6.67- 6.67-
(in.) 10.99 10.99 9.43 9.43

73
Guide specifications — 38AKS units
Commercial Air-Cooled Condensing Units C. Fans:
HVAC Guide Specifications 1. Condenser fans shall be direct-driven propeller
type, discharging air vertically upward.
Size Range: 82.8 to 127.0 kW (23.5 to 35.8 Tons),
Nominal 2. Condenser fan motors shall be totally enclosed,
3-phase type with class B insulation and with
Carrier Model Number: 38AKS permanently lubricated bearings.
Part 1 — General 3. Shafts shall have inherent corrosion resistance.
1.01 SYSTEM DESCRIPTION 4. Fan blades shall be statically and dynamically
Outdoor-mounted, air-cooled condensing unit suitable balanced.
for on-the-ground or rooftop installation. Unit shall 5. Condenser fan openings shall be equipped with
consist of a semi-hermetic reciprocating compressor, PVC-coated steel wire safety guards.
an air-cooled coil, propeller-type condenser fans, and
a control box. Unit shall discharge supply air upward D. Compressor:
as shown on contract drawings. Unit shall be used in 1. Compressor shall be reciprocating, serviceable,
a refrigeration circuit to match a packaged air- semi-hermetic type.
handling unit. 2. Compressor shall be equipped with an automati-
1.02 QUALITY ASSURANCE cally reversible oil pump, operating oil charge,
A. Unit shall be rated in accordance with ARI Standard suction and discharge shutoff valves, and an
360 (U.S.A. standard). insert-type, factory-sized crankcase heater to
control oil dilution.
B. Unit shall be manufactured in a facility registered to
ISO 9001:2000 manufacturing quality standard. 3. Compressor shall be mounted on spring vibra-
tion isolators with an isolation efficiency of no
C. Unit construction shall comply with ANSI/ASHRAE less than 95%.
15 latest revision safety code and comply with NEC
(U.S.A. standards). 4. Compressor speed shall not exceed 24.2 r/s
(1450 rpm).
D. Unit shall be constructed in accordance with UL
standards (U.S.A.). 5. Compressor shall unload using suction cutoff
unloading (electrical solenoid unloading shall be
E. Unit cabinet shall be capable of withstanding available as an accessory).
500-hour salt spray exposure per ASTM B117
(U.S.A.) (scribed specimen). E. Condenser Coil:
F. Air-cooled condenser coils shall be leak tested at 1. Condenser coil shall be air cooled, circuited for
1034 kPa (150 psig) and pressure tested at 3310 kPa integral subcooler.
(480 psig). 2. Coil shall be constructed of aluminum fins
1.03 DELIVERY, STORAGE AND HANDLING mechanically bonded to internally grooved,
seamless copper tubes which are then cleaned,
Unit shall be shipped as single package only, and dehydrated, and sealed. Epoxy phenolic fin coat-
shall be stored and handled per unit manufacturer’s ing shall be available as an option.
recommendations.
3. Coil shall be protected by a sheet metal casing to
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING eliminate the need for wind baffles for low ambi-
ENGINEER.) ent temperature operation.
Part 2 — Products 4. Coil shall be protected to avoid damage due to
2.01 EQUIPMENT the elements and vandalism.
A. General: F. Refrigeration Components:
Factory assembled, single piece, air-cooled condens- Refrigeration circuit components shall include hot gas
ing unit. Contained within the unit enclosure shall be muffler, high-side pressure relief device, liquid line shut-
all factory wiring, piping, controls, compressor, hold- off valve, suction and discharge shutoff valves, holding
ing charge (R-22), and special features required prior charge of refrigerant R-22, and compressor oil.
to field start-up. G. Controls and Safeties:
B. Unit Cabinet: 1. Minimum control functions shall include:
1. Unit cabinet shall be constructed of galvanized a. Power and control terminal blocks.
steel, bonderized and coated with a prepainted,
baked enamel finish. b. Three-minute recycle protection to prevent
compressor short-cycling.
2. End unit access panel shall be hinged for com-
pressor and control box service access. c. Lockout on auto-reset safety until reset from
thermostat.
3. Lifting holes shall be provided to facilitate
rigging.

74
d. Capacity control on the compressor shall be of the unit. The control shall be capable of main-
by suction cutoff unloaders in response to taining a condensing temperature of 37.8 C
compressor suction pressure. Electric (100 F) ± 5.6 C (10° F) with outdoor tempera-
solenoid unloading shall be available as an tures at –28 C (–20 F). (Motor change required.)
accessory. 2. Electric Solenoid Unloader:
e. A solenoid valve shall be provided for sole- Unloader valve piston, coil, and hardware shall
noid drop control. be supplied to convert any pressure-operated
f. Head pressure control to –6 C (31 F) by fan compressor unloader to 220-v electric unload-
cycling. One condenser fan shall be cycled by ing. Accessory ModuPanel™ control box or field-
discharge pressure to maintain proper head supplied step controller shall be provided for
pressure. electrical unloading.
g. Winter start control to prevent nuisance trip- 3. Hot-Gas Bypass:
outs at low ambient temperatures. A hot-gas bypass valve and a pilot line solenoid
2. Minimum safety devices shall include: valve shall be provided for low-load operation of
Automatic reset (after resetting first at control cir- the refrigeration system.
cuit power supply) 4. Part-Winding Start:
a. High discharge-pressure cutout. Part-winding start shall be provided to reduce
b. Low suction-pressure cutout. inrush current and locked rotor amps on
start-up.
c. Condenser fan motors to be protected
against overload or single-phase condition by 5. Gage Panel:
internal overloads. A gage panel package shall be provided which
Manual reset at the unit includes a suction and discharge pressure gage
for the refrigerant circuit.
a. Low oil-pressure cutout.
6. ModuPanel Control Box:
b. Compressor electrical overload protection
through the use of definite-purpose contac- Control box shall be provided to allow system to
tors and calibrated, ambient-compensated, operate as a VAV (variable air volume) system.
magnetic-trip circuit breakers. Circuit break- 7. Optional Condenser Coil Materials:
ers shall open all 3 phases in the event of an a. Pre-Coated Aluminum-Fin Coils:
overload in any one of the phases or a
Shall have a durable epoxy-phenolic coating
single-phase condition.
to provide protection in mildly corrosive
H. Operating Characteristics: coastal environments. Coating shall be
1. The capacity of the condensing unit shall meet applied to the aluminum fin stock prior to the
or exceed at a suction temperature of fin stamping process to create an inert barrier
. The power consumption at full load shall between the aluminum fin and copper tube.
not exceed kW. Epoxy-phenolic barrier shall minimize gal-
2. The combination of the condensing unit and the vanic action between dissimilar metals.
evaporator or fan coil unit shall have a total net b. Copper-Fin Coils:
cooling capacity of or greater at condi- Shall be constructed of copper-fins mechani-
tions of: entering-air temperature at the cally bonded to copper-tubes All copper con-
evaporator at wet bulb and dry struction shall provide protection in moderate
bulb, and air entering the condensing unit at coastal environments.
.
c. E-Coated Aluminum-Fin Coils:
I. Electrical Requirements:
Shall have a flexible epoxy polymer coating
1. Nominal unit electrical characteristics shall be uniformly applied to all coil surface areas
v, 3-ph, 50 Hz. The unit shall be capable without material bridging between fins.
of satisfactory operation within voltage limits of Coating process shall ensure complete coil
v to v. encapsulation. Color shall be high gloss
2. Unit electrical power shall be single point black with gloss requirements of 60° of 65
connection. to 90% per ASTM D523-89. Uniform dry
3. Unit control circuit shall contain a 24-v trans- film thickness from 0.8 to 1.2 mil on all sur-
former for unit control, with capacity to operate face areas including fin edges. Superior
an indoor fan interlock. hardness characteristics of 2H per ASTM
D3363-92A and cross hatch adhesion of
J. Special Features:
4B-5B per ASTM D3359-93. Impact resis-
1. Low-Ambient Control: tance shall be up to 160 in./lb (ASTM
Control shall regulate fan motor speed in D2794-93). Humidity and water immersion
response to the saturated condensing temperature resistance shall be up to a minimum of 1000

75
Guide specifications — 38AKS units (cont)
and 250 hours respectively (ASTM D2247- tube sheets shall not be acceptable. A poly-
92 and ASTM D870-92). Corrosion durabil- mer strip shall prevent coil assembly from
ity shall be confirmed through testing to no contacting sheet metal coil pan to maintain
less than 1000 hours salt spray per ASTM coating integrity and minimize corrosion
B117-90. Coil construction shall be alumi- potential between the coil and pan. (U.S.A.
num fins mechanically bonded to copper standards.)
tubes. (U.S.A. standards.) 8. Thermostat Controls:
d. E-Coated Copper-Fin Coils: a. Debonair® programmable multi-stage ther-
Shall have a flexible epoxy polymer coating mostat with 7-day clock, holiday scheduling,
uniformly applied to all coil surface areas large Thermoglow™ display, remote sensor
without material bridging between fins. capability, and Title 24 compliance.
Coating process shall ensure complete coil b. Commercial Electronic Thermostat with
encapsulation. Color shall be high gloss 7-day timeclock, auto-changeover, multi-
black with gloss requirements of 60° of 65 stage capability, and large LCD temperature
to 90% per ASTM D523-89. Uniform dry display.
film thickness from 0.8 to 1.2 mil on all sur-
face areas including fin edges. Superior c. Non-programmable thermostat with fan
switch subbase.
hardness characteristics of 2H per ASTM
D3363-92A and cross hatch adhesion of d. Carrier PremierLink™ Controls:
4B-5B per ASTM D3359-93. Impact resis- This control will function with CCN and
tance shall be up to 160 in./lb (ASTM ComfortVIEW™ software. It shall also be
D2794-93). Humidity and water immersion compatible with ComfortLink™ controllers.
resistance shall be up to a minimum of 1000 It shall be ASHRAE 62-99 (U.S.A.) compli-
and 250 hours respectively (ASTM D2247- ant and Internet ready. It shall accept a CO2
92 and ASTM D870-92). Corrosion durabil- sensor in the conditioned space and be
ity shall be confirmed through testing to no Demand Control Ventilation (DCV) ready.
less than 1000 hours salt spray per ASTM The communication rate must be 38.4K or
B117-90. Coil construction shall be copper- faster. It shall include an integrated econo-
fins mechanically bonded to copper tubes mizer controller.
with copper tube sheets. Galvanized steel

76
Guide specifications — 38AH units
Commercial Air-Cooled Condensing Units C. Fans:
HVAC Guide Specifications 1. Condenser fans shall be direct-drive propeller
type, discharging air vertically upward.
Size Range: 63 to 87 kW (18 to 25 Tons), Nominal
2. Condenser fan motors shall be 3-phase type
Carrier Model Number: 38AH with class B insulation and permanently lubri-
Part 1 — General cated bearings.
1.01 SYSTEM DESCRIPTION 3. Shafts shall have inherent corrosion resistance.
Outdoor-mounted, air-cooled condensing unit suit- 4. Fan blades shall be statically and dynamically
able for on-the-ground or rooftop installation. Unit balanced.
shall have 2 independent refrigeration circuits and 5. Condenser fan openings shall be equipped with
shall consist of dual semi-hermetic reciprocating PVC-coated steel wire safety guards.
compressors, air-cooled coils, propeller-type con-
denser fans, and a control box. Unit shall discharge D. Compressors:
supply air upward as shown on contract drawings. 1. Compressors shall be manufactured by the con-
Unit shall be used in refrigeration circuit matched densing unit manufacturer, and shall be service-
with a packaged fan-coil unit or direct-expansion able, reciprocating, semi-hermetic type.
cooler. 2. Compressors shall be equipped with an auto-
1.02 QUALITY ASSURANCE matically reversible oil pump, operating oil
A. Unit shall be rated in accordance with ARI Standard charge, suction and discharge shutoff valves,
365 (U.S.A. standard). and an insert-type factory-sized crankcase
heater to control oil dilution.
B. Unit construction shall comply with latest edition of
ANSI/ASHRAE and with NEC (U.S.A. standard). 3. Compressors shall be mounted on spring vibra-
tion isolators with an isolation efficiency of no
C. Unit shall be manufactured in a facility registered to less than 95%.
ISO 9001:2000 manufacturing quality standard.
4. Compressor speed shall not exceed 24.3 r/s
D. Unit shall be constructed in accordance with UL (1460 rpm).
standards (U.S.A.).
5. Lead compressor shall unload using suction cut-
E. Unit cabinet shall be capable of withstanding off unloading (electrical solenoid unloading shall
500-hour salt-spray exposure per ASTM B117 be available as an accessory).
(U.S.A) (scribed specimen).
E. Condenser Coils:
F. Air-cooled condenser coils shall be leak tested
at 1034 kPa (150 psig) and pressure tested at 1. Condenser coils shall be air cooled, circuited for
3310 kPa (480 psig). integral subcooler.
1.03 DELIVERY, STORAGE, AND HANDLING 2. Coil shall be constructed of aluminum fins
mechanically bonded to internally grooved,
Unit shall be shipped as single package only, and seamless copper tubes which are then cleaned,
shall be stored and handled per unit manufacturer’s dehydrated, and sealed. Copper fins, E-Coated
recommendations. or pre-coated aluminum fins shall be available
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING as options.
ENGINEER) F. Refrigeration Components:
Part 2 — Products Refrigeration circuit components shall include hot
2.01 EQUIPMENT gas muffler, high-side pressure relief device, liquid
A. General: line shutoff valve, suction and discharge shutoff
valves, holding charge, and compressor oil.
Factory assembled, single-piece, air-cooled condens-
ing unit. Contained within the unit enclosure shall be G. Controls and Safeties:
all factory wiring, piping, controls, compressors, 1. Minimum control functions shall include:
holding charge, and special features required prior a. Power and control terminal blocks.
to field start-up.
b. Three-minute recycle protection to prevent
B. Unit Cabinet: compressor short-cycling.
1. Unit cabinet shall be constructed of galvanized c. Lockout on auto-reset safety until reset from
steel, bonderized and coated with a prepainted, thermostat.
baked enamel finish.
d. Capacity control on the lead compressor
2. Unit access panels shall be hinged for control shall be by suction cutoff unloaders in
box service access. response to compressor suction pressure.
3. Lifting holes shall be provided to facilitate Electric solenoid unloading shall be available
rigging. as an accessory.

77
Guide specifications — 38AH units (cont)
e. Head pressure control for mild ambient tem- 2. Optional Condenser Coil Materials:
perature operation by fan cycling. One a. Pre-Coated Aluminum-Fin Coils:
condenser fan shall be cycled by ambient tem-
perature to maintain proper head pressure. Shall have a durable epoxy-phenolic coating
to provide protection in mildly corrosive
2. Minimum safety devices shall include: coastal environments. Coating shall be
Automatic reset (after resetting first at thermostat) applied to the aluminum fin stock prior to
a. High discharge-temperature cutout. the fin stamping process to create an inert
barrier between the aluminum fin and cop-
b. Low suction-pressure cutout.
per tube. Epoxy-phenolic barrier shall mini-
c. Condenser fan motors to be protected mize galvanic action between dissimilar
against overloads or single-phase condition metals.
by internal overloads.
b. Copper-Fin Coils:
d. Low oil-pressure cutout. Shall be constructed of copper fins mechani-
Manual reset at the unit cally bonded to copper tubes and copper
a. Electrical overload protection through the tube sheets. Galvanized steel tube sheets
use of definite-purpose contactors and cali- shall not be acceptable. All copper construc-
brated, ambient compensated, magnetic trip tion shall provide protection in moderate
circuit breakers. Circuit breakers shall open coastal applications.
all 3 phases in the event of an overload A polymer strip shall prevent the coil assem-
in any one of the phases or a single-phase bly from contacting the sheet metal coil pan
condition. to minimize the potential for galvanic corro-
b. High discharge-pressure cutout. sion between the coil and the pan. All cop-
H. Operating Characteristics: per construction shall provide protection in
moderate coastal environments.
1. The capacity of the condensing unit shall meet
or exceed __________ at a suction temperature c. E-Coated Aluminum-Fin Coils:
of __________ . The power consumption at full Shall be constructed of aluminum fins
load shall not exceed __________ kW. mechanically bonded to copper tubes. Coat-
2. The combination of the condensing unit and ing process shall have a flexible epoxy poly-
the evaporator or fan coil unit shall have a total mer coating uniformly applied to all coil
net cooling capacity of __________ or greater at surfaces without material bridging between
an airflow rate of __________ entering-air tem- the fins. The coating process shall ensure
perature at the evaporator at __________ wet complete coil encapsulation. Color shall be
bulb and __________ dry bulb, and air entering high-gloss black with gloss at 60° angle of
the condensing unit at __________ . 65% to 90% per ASTM D523-89. Uniform
dry film thickness shall be 0.8 mil to 1.2 mil
3. The system shall have an EER of __________ or on all surfaces, including the fin edges.
greater at standard ARI conditions. Superior hardness characteristics shall meet
I. Electrical Requirements: those requirements of 2H, per ASTM
1. Nominal unit electrical characteristics shall be D3363-92A. Cross-hatch adhesion shall
_____ v, 3-ph, 50 Hz. The unit shall be capable meet the requirements of 4B-5B, per ASTM
of satisfactory operation within voltage limits of D3359-93. Impact resistance shall be up to
_____ v to _____ v. 160 in./lb, per ASTM D2794-93. Humidity
2. Unit electrical power shall be single point resistance shall be up to a minimum of
1000 hours per ASTM D2247-92. Water
connection.
immersion resistance shall be up to a mini-
3. Unit control circuit shall be 230 v for 400 v and mum of 250 hours per ASTM D870-92.
230 v units, or 200 v for 346 v units. Durability shall be confirmed through testing
J. Special Features: to no less than 1000 hours of salt spray per
Certain standard features are not applicable when ASTM B117-90 (U.S.A. standards).
the features designated * are specified. For assis- d. E-Coated Copper Fin Coils:
tance in amending the specifications, your local Shall be copper fins mechanically bonded to
Carrier Sales Office should be contacted. copper tubes with copper tube sheets. Coat-
1. VAV (Variable Air Volume) Modification: ing process shall have a flexible epoxy poly-
Unit shall be supplied from the factory with nec- mer coating uniformly applied to all coil
essary wiring modifications for connection to a surfaces without material bridging between
field-supplied VAV discharge air controller. The the fins. The coating process shall ensure
VAV modification shall include 2 electric complete coil encapsulation. Shall be high-
unloaders on the lead compressor. gloss black with gloss at 60° angle of 65% to
90% per ASTM D523-89. Uniform dry film

78
thickness shall be 0.8 mil to 1.2 mil on all b. Commercial Electronic Thermostat with
surfaces, including the fin edges. Superior 7-day timeclock, auto-changeover, multi-
hardness characteristics shall meet those stage capability, and large LCD temperature
requirements of 2H, per ASTM D3363- display.
92A. Cross-hatch adhesion shall meet the c. Non-programmable thermostat with fan
requirements of 4B-5B, per ASTM D3359- switch subbase.
93. Impact resistance shall be up to
150 in./lb, per ASTM D2794-93. Humidity d. Carrier PremierLink™ Controls:
resistance shall be up to a minimum of This control will function with CCN and
1000 hours per ASTM D2247-92. Water ComfortVIEW™ software. It shall also be
immersion resistance shall be up to a mini- compatible with ComfortLink™ controllers.
mum of 250 hours per ASTM D980-92. It shall be ASHRAE 62-99 (U.S.A.) compli-
Durability shall be confirmed through testing ant and Internet ready. It shall accept a CO2
to no less than 1000 hours of salt spray per sensor in the conditioned space and be
ASTM B117-90 (U.S.A. standards). Demand Control Ventilation (DCV) ready.
The communication rate must be 38.4K or
* 3. Unloader Conversion Kit:
faster. It shall include an integrated econo-
Unloader valve, piston, and hardware shall be mizer controller.
supplied to convert any pressure-operated com-
6. Electric Unloader Package:
pressor unloader to electrical unloading. Acces-
sory ModuPanel™ or field-supplied step Electric unloader shall provide an additional
controller shall be provided for electrical step of electric unloading.
unloading. 7. Pressure Unloader Package:
* 4. Gage Panel: Pressure unloader shall provide an additional
A gage panel package shall be provided which step of pressure unloading.
includes a suction and discharge pressure gage * 8. ModuPanel Control:
for each refrigerant circuit. Control shall provide 10-step microprocessor-
5. Thermostat Controls: based control for variable air volume applications.
a. Debonair® programmable multi-stage ther- * 9. Low Ambient Control:
mostat with 7-day clock, holiday scheduling, Control shall maintain correct condensing pres-
large Thermoglow™ display, remote sensor sure at low ambient temperatures.
capability, and Title 24 compliance.

79
Guide specifications — 40RM units
Commercial Packaged Air-Handling Unit immobilized antimicrobial agent to effectively
resist the growth of bacteria and fungi as
HVAC Guide Specifications proven by tests in accordance with ASTM
Size Range: 2831 to 5663 L/s (6000 to 12,000 Cfm), standards G21 and 22 (U.S.A.).
Nominal Airflow 3. Unit shall contain corrosion resistant conden-
52 to 105 kW (15 to 30 Tons), sate drain pans for both vertical and horizontal
Nominal Cooling applications. Drain pans shall have connections
Carrier Model Number: 40RM on right and left sides of unit to facilitate field
Part 1 — General connection. Drain pans shall have the ability to
be sloped toward the right or left side of the
1.01 SYSTEM DESCRIPTION
unit to prevent standing water from accumulat-
A. Indoor, packaged air-handling unit for use in com- ing in pans.
mercial split systems. Unit shall have a multiposition
4. Unit shall have factory-supplied 51-mm (2-in.)
design and shall be capable of horizontal or vertical
(upflow) installation on a floor or in a ceiling, with or throwaway-type filters installed upstream from
the cooling coil. Filter access shall be from
without ductwork. (Only vertical units are to be
either the right or left side of the unit.
applied without ductwork).
B. Unit shall be used in a refrigerant circuit with a C. Coils:
matching air-cooled condensing unit. Coils shall consist of 3 rows (standard) or 4 rows
1.02 QUALITY ASSURANCE (high capacity) of 3/8-in. copper tubes with sine-
wave aluminum fins bonded to the tubes by mechan-
A. Coils shall be designed and tested in accordance ical expansion. Coil tubing shall be internally rifled
with ASHRAE 15 Safety Code for Mechanical to maximize heat transfer. Suction and liquid line
Refrigeration (U.S.A.), latest edition. connections shall be made on the same side of the
B. Unit shall be constructed in accordance with ETL coil. Direct-expansion coils shall feature factory-
(U.S.A.) and ETL, Canada standards. installed thermostatic expansion valves (TXVs) for
C. Unit insulation and adhesive shall comply with refrigerant control. The TXVs shall be capable of
NFPA 90A (U.S.A.) requirements for flame spread external adjustment.
and smoke generation. Insulation shall contain a D. Operating Characteristics:
U.S.A. EPA-registered immobilized antimicrobial Unit shall be capable of providing _____ L/s (cfm)
agent to effectively resist the growth of bacteria and airflow at an external static pressure of _____ kPag
fungi as proven by tests in accordance with ASTM (in. wg).
standards G21 and 22 (U.S.A.).
E. Motor:
D. Unit shall be manufactured in a facility registered to
the ISO 9001:2000 manufacturing quality standard. Fan motor of the size and electrical characteristics
specified on the equipment schedule shall be factory
E. Direct-expansion coils shall be burst tested at supplied and installed.
2999 kPag (435 psig) and leak tested at 1034 kPag
F. Special Features:
(150 psig).
1.03 DELIVERY AND STORAGE 1. Alternate Motor and Drive:
An alternate motor and/or medium- or high-
Units shall be stored and handled per manufacturer’s
recommendations. static drive shall be available to meet the airflow
and external static pressure requirements speci-
Part 2 — Products fied on the equipment schedule.
2.01 EQUIPMENT 2. High-Capacity Coil:
A. General: High-capacity coil consisting of 4 rows of
Indoor mounted, draw-thru, packaged air-handling 3/ -in. copper tubes with sine-wave aluminum
8
unit that can be used in a suspended horizontal con- fins bonded to the tubes by mechanical expan-
figuration or vertical (upflow) configuration. Unit sion. Coil tubing shall be internally rifled to
shall consist of forward-curved belt-driven centrifugal maximize heat transfer. Suction and liquid line
fan(s), motor and drive assembly, prewired fan connections shall be made on the same side of
motor contactor, factory-installed refrigerant meter- the coil. Direct-expansion coils shall feature
ing devices, cooling coil, 51 mm (2-in.) disposable factory-installed thermostatic expansion valves
air filters, and condensate drain pans for vertical or (TXVs) for refrigerant control. The TXVs shall
horizontal configurations. be capable of external adjustment.
B. Base Unit: 3. Painted Cabinet:
1. Cabinet shall be constructed of mill-galvanized Where conditions require, units shall be painted
steel. with an American Sterling Gray finish.
2. Cabinet panels shall be fully insulated with
12.7-mm (1/2-in.) fire-retardant material.
Insulation shall contain a U.S.A. EPA-registered

80
4. Hot Water Coil: 11. Thermostat Controls:
Coil shall be 2-row, U-bend coil with copper a. Debonair® programmable multi-stage ther-
tubes and aluminum plate fans bonded to the mostat with 7-day clock, holiday scheduling,
tubes by mechanical expansion. Coil shall be large Thermoglow™ display, remote sensor
mounted in a galvanized steel housing that shall capability, and Title 24 compliance.
be fastened to the unit’s fan deck for blow-thru b. Carrier PremierLink™ Controls:
heating operation. Coil shall have maximum
This control will function with CCN and
working pressure of 1034 kPag (150 psig).
ComfortVIEW™ software. It shall also be
5. Steam Distributing Coil: compatible with ComfortLink™ controllers.
Coil shall consist of 1 row of copper tubes with It shall be ASHRAE 62-99 (U.S.A.) compli-
aluminum plate fins, and shall have inner steam ant and Internet ready. It shall accept a CO2
distributing tubes. Coil shall be mounted in a gal- sensor in the conditioned space and be
vanized steel housing that shall be fastened to the Demand Control Ventilation (DCV) ready.
unit’s fan deck for blow-thru heating operation. The communication rate must be 38.4K or
Coil shall have maximum working pressure of faster. It shall include an integrated econo-
138 kpag at 126 C (20 psig at 260 F). mizer controller.
6. Electric Heaters: c. Commercial Electronic Thermostat with
Heaters for nominal 230 or 400-volt, 3-phase 7-day timeclock, auto-changeover, multi-
power supply shall be factory-supplied for field stage capability, and large LCD temperature
installation as shown on the equipment draw- display.
ings. Electric heat assembly shall be ETL (U.S.A.) d. Non-programmable thermostat with fan
and ETL, Canada agency approved, and shall switch subbase.
have single-point power wiring. Heater assembly 12. Overhead Suspension Brackets:
shall include contactors with 24-v coils, power
wiring, 24-v control wiring terminal blocks, and Package shall include necessary brackets to sup-
a hinged access panel. Electric heaters shall not port units in a horizontal ceiling installation.
be used with discharge plenum. 13. CO2 Sensor:
7. Air Discharge Plenum: Sensor shall provide the ability to signal the
Plenum shall be provided to provide free-blow economizer to open when the space CO2 level
air distribution for vertical floor-mounted units. exceeds the predetermined set point. Sensor
A grille with moveable vanes for horizontal or shall have the capability of being connected to
vertical airflow adjustment shall be included. comfort system relay pack or to economizer
Plenum shall be field-assembled and field- using field-supplied and installed Honeywell dc
installed on the unit’s fan deck for blow-thru air adapter no. Q769C1004.
distribution. Plenum shall not be used with elec- 14. Condensate Drain Trap:
tric heaters. Trap shall have transparent, serviceable design
8. Return-Air Grille: for easy cleaning. Kit shall include overflow
Grille shall be factory supplied for field installa- shutoff switch and wiring harness for connec-
tion on the unit’s return air opening. tion to an alarm if desired.
9. Unit Subbase: 15. UV-C Germicidal Lamps:
Subbase assembly shall be factory supplied for a. UV-C emitters and fixtures shall be specifi-
field installation. Subbase shall elevate floor- cally designed for use inside an HVAC sys-
mounted vertical units to provide access for cor- tem. An ASME nozzled test apparatus using
rect condensate drain connection. a 45 F (7.2 C) airstream moving at not less
than 400 fpm (189 liters/sec.) shall measure
10. Economizer:
individual lamp output. Lamp output at
Economizer for ventilation or ‘‘free’’ cooling 253.7 nm shall not be less than 10µW/cm2
shall be factory provided for field installation. per inch of arc length measured at a distance
For free cooling applications, economizer shall of one meter.
be compatible with factory-supplied thermostat;
b. UV-C power supplies shall be high effi-
economizer dampers shall open when outdoor
ciency, electric type which are matched to
air enthalpy is suitable for free cooling. Econo- the emitters and are capable of producing
mizer shall be compatible with separate CO2
the specified output intensity with an input
sensor accessory; economizer dampers shall
power no more than 80 watts.
open when indoor CO2 level rises above prede-
termined set point. Economizer shall include c. Emitters and fixtures shall be installed in
enthalpy control and damper actuator with sufficient quantity and arranged so as to
controls. provide an equal distribution of UV-C energy
on the coil and drain pan.

81
Guide specifications — 40RM units (cont)
d. The minimum UV-C energy striking the e. Emitters and fixtures shall be
leading edge of the coil fins shall be not less installed at right angles to the conforming
than 820 µW/cm2 at the closest point and lines of the coil fins, such that through inci-
through placement, not less than 60% of dent angle reflection, UV-C energy strikes
that value at the farthest point. Equal all target surfaces of the coil, drain pan,
amounts are to strike the drain pan, either and the available line of sight airstream.
directly or indirectly through reflection.

Carrier Corporation • Syracuse, New York 13221 7-04


Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2 Pg 82 Catalog No. 003-80020 Printed in U.S.A. Form 38A-C11PD