Você está na página 1de 5

Date: 02-09-2016 Dist: PT SKINS

Proj. Ref: EXACTA 21 - MIDAS - Class 1 Div-2 Mgr TS: ADRIAN

SYSTEM
ENGINEERING & SERVICES
End-User Petrochina Jabung - Jambi E-Mail: adrian@skins.co.id
Country Indonesia Cell:
Location PCI Jambi
Unit # CP- 5000 TS Team: Andry F Sitepu
Application WAUK. F3521 GSI/CEC - ARIEL 2 THROW-2STG E-Mail: andry@skins.co.id
EXACTA 21 ANALOG I/O TERMINAL BOARD # (1) Chan. # Input Signal End-Device Range Units Action S/D Class Notes
a. Analog input
Engine air manifold 1 4-20mA -14.7-50 PSIA S/D
Engine oil pressure 2 4-20mA 0-100 PSIG S/D
Compressor Oil Pressure 3 4-20mA 0-100 PSIG S/D
Engine Fuel Gas Supply Pressure 4 4-20mA 0-200 PSIG S/D
Suction pressure 1st stage 5 4-20mA 0-300 PSIG S/D
Discharge 1st stage 6 4-20mA 0-300 PSIG S/D
Suction 2nd stage 7 4-20mA 0-500 PSIG S/D
Discharge 2nd stage 8 4-20mA 0-1000 PSIG S/D
Instrument air 9 4-20mA 0-200 PSIG S/D
Jacket Water Pressure 10 4-20mA 0-100 PSIG S/D
Spare 11
Cooler Vibration 12 4-20mA 0-2 INS INS S/D A
Engine Vibration cooler end 13 4-20mA 0-2 INS INS S/D A
Engine Vibration flywheel end 14 4-20mA 0-2 INS INS S/D A
Compressor Vibration right side 15 4-20mA 0-2 INS INS S/D A
Compressor Vibration left side 16 4-20mA 0-2 INS INS S/D A

b. Analog output
Recycle valve position 1 4-20mA I/P (3-15 psi) to positioner
Engine speed 2 4-20mA I/P (3-15 psi) to governor
Spare 3 4-20mA
spare 4 4-20mA

c. Frequency
MPU engine speed

EXACTA 21 ANALOG Input TERMINAL BOARD # (2)


Engine jacket water temp 1 T/C Type K/J termocouple Deg F S/D A
Engine oil temp 2 T/C Type K/J termocouple Deg F S/D A
Discharge Temperature Cyl 1 3 T/C Type K/J termocouple Deg F S/D A
Discharge Temperature Cyl 2 4 T/C Type K/J termocouple Deg F S/D A
Suction Stage #1 5 T/C Type K/J termocouple Deg F S/D A
Suction Stage #2 6 T/C Type K/J termocouple Deg F S/D A
spare 7 T/C Type K/J termocouple Deg F S/D A
spare 8 T/C Type K/J termocouple Deg F S/D A
spare 9 T/C Type K/J termocouple Deg F S/D A
spare 10 T/C Type K/J termocouple Deg F S/D A
Date: 02-09-2016 Dist: PT SKINS
Proj. Ref: EXACTA 21 - MIDAS - Class 1 Div-2 Mgr TS: ADRIAN

SYSTEM
ENGINEERING & SERVICES
End-User Petrochina Jabung - Jambi E-Mail: adrian@skins.co.id
Country Indonesia Cell:
Location PCI Jambi
Unit # CP- 5000 TS Team: Andry F Sitepu
Application WAUK. F3521 GSI/CEC - ARIEL 2 THROW-2STG E-Mail: andry@skins.co.id
spare 11 T/C Type K/J termocouple Deg F S/D A
spare 12 T/C Type K/J termocouple Deg F S/D A
spare 13 T/C Type K/J termocouple Deg F S/D A
spare 14 T/C Type K/J termocouple Deg F S/D A
spare 15 T/C Type K/J termocouple Deg F S/D A
spare 16 T/C Type K/J termocouple Deg F S/D A

b. Analog output
Spare 1 4-20mA
Spare 2 4-20mA
Spare 3 4-20mA
Spare 4 4-20mA

EXACTA 21 ANALOG Input TERMINAL BOARD # (3)


spare 1
spare 2
spare 3
spare 4
spare 5
spare 6
spare 7
spare 8
spare 9
spare 10
spare 11
spare 12
spare 13
spare 14
spare 15
spare 16

b. Analog output
Spare 1
Spare 2
Spare 3
Spare 4

EXACTA 21 Discrete Input TERMINAL BOARD # (4)


HIgh high level - suction scrubber stage 1 1 D/I
High high level - suction scrubber stage 2 2 D/I
Low low level - engine jacket water surge tank 3 D/I
Low low level - auxilary water 4 D/I
Low low level - engine oil 5 D/I
Low low level - compressor oil 6 D/I
Metal detector engine oil 7 D/I
Metal detector compressor oil 8 D/I
No flow - lube 9 D/I
Emergency stop - local (on side of panel) 10 D/I
Emergency stop - engine (on side of engine) 11 D/I
spare 12 D/I
Date: 02-09-2016 Dist: PT SKINS
Proj. Ref: EXACTA 21 - MIDAS - Class 1 Div-2 Mgr TS: ADRIAN

SYSTEM
ENGINEERING & SERVICES
End-User Petrochina Jabung - Jambi E-Mail: adrian@skins.co.id
Country Indonesia Cell:
Location PCI Jambi
Unit # CP- 5000 TS Team: Andry F Sitepu
Application WAUK. F3521 GSI/CEC - ARIEL 2 THROW-2STG E-Mail: andry@skins.co.id
b. Discrete output
Engine pre/post - lube 1 D/O
Compressor pre-lube 2 D/O
Crank engine 3 D/O
Fuel supply valve 4 D/O
Engine ignition 5 D/O
Fuel valve engine (shutoff valve) 6 D/O
spare 7 D/O
spare 8 D/O
spare 9 D/O
spare 10 D/O
spare 11 D/O
spare 12 D/O

EXACTA 21 Discrete input TERMINAL BOARD # (5)


a. Discrete input
Suction valve - OPEN 1 D/I
Suction valve - CLOSE 2 D/I
Discharge valve - OPEN 3 D/I
Discharge valve - CLOSE 4 D/I
Vent valve - OPEN 5 D/I
Vent valve - CLOSE 6 D/I
Bypass valve - OPEN 7 D/I
Bypass valve - CLOSE 8 D/I
Fuel supply valve - OPEN 9 D/I
Fuel supply valve - CLOSE 10 D/I
Spare 11 D/I
Spare 12 D/I
b. Discrete output
Fuel supply valve - open 1 D/O
Suction valve - open 2 D/O
Discharge valve - open 3 D/O
Bypasss valve - close 4 D/O
Vent valve - close 5 D/O
Starting Valve 6 D/O
PCV-602 7 D/O
Spare 8 D/O
Spare 9 D/O
Spare 10 D/O
Spare 11 D/O
Spare 12 D/O

EXACTA 21 Discrete input TERMINAL BOARD # (6)


CPU-95 Ignition Fault 1 D/I
Detonation fault 2 D/I
DSM Fault 3 D/I
Motor status - fault - compressor lube 4 D/I
Motor status - run - compressor lube 5 D/I
Motor status - fault - engine lube 6 D/I
Motor status - run - engine lube 7 D/I
Date: 02-09-2016 Dist: PT SKINS
Proj. Ref: EXACTA 21 - MIDAS - Class 1 Div-2 Mgr TS: ADRIAN

SYSTEM
ENGINEERING & SERVICES
End-User Petrochina Jabung - Jambi E-Mail: adrian@skins.co.id
Country Indonesia Cell:
Location PCI Jambi
Unit # CP- 5000 TS Team: Andry F Sitepu
Application WAUK. F3521 GSI/CEC - ARIEL 2 THROW-2STG E-Mail: andry@skins.co.id
Motor status - fault - compressor coolant 8 D/I
Motor status - run - compressor coolant 9 D/I
Motor status - fault - crankcase blower 10 D/I
Motor status - run - crankcase blower 11 D/I
Spare 12 D/I

b. Discrete output
Engine blower motor 1 D/O
Packing coolant pump (if used) 2 D/O
Visual alarm indication 3 D/O
Visual fault indication 4 D/O
Spare 5 D/O
Spare 6 D/O
Spare 7 D/O
Spare 8 D/O
Spare 9 D/O
Spare 10 D/O
Spare 11 D/O
Spare 12 D/O

DSM -43924 DUS


Engine air manifold temp 1 T/C Type K/J termocouple Deg F S/D A
Compressor Oil Temperature 2 T/C Type K/J termocouple Deg F S/D A
Engine Exhaust Temperature Cylinder # 1 3 T/C Type K/J termocouple Deg F S/D A
Engine Exhaust Temperature Cylinder # 2 4 T/C Type K/J termocouple Deg F S/D A
Engine Exhaust Temperature Cylinder # 3 5 T/C Type K/J termocouple Deg F S/D A
Engine Exhaust Temperature Cylinder # 4 6 T/C Type K/J termocouple Deg F S/D A
Engine Exhaust Temperature Cylinder # 5 7 T/C Type K/J termocouple Deg F S/D A
Engine Exhaust Temperature Cylinder # 6 8 T/C Type K/J termocouple Deg F S/D A
Pre Turbo Temp Turbo 9 T/C Type K/J termocouple Deg F S/D A
Post Turbo Temp Turbo 10 T/C Type K/J termocouple Deg F S/D A
spare 11 T/C Type K/J termocouple Deg F S/D A
spare 12 T/C Type K/J termocouple Deg F S/D A
spare 13 T/C Type K/J termocouple Deg F S/D A
spare 14 T/C Type K/J termocouple Deg F S/D A
spare 15 T/C Type K/J termocouple Deg F S/D A
spare 16 T/C Type K/J termocouple Deg F S/D A
spare 17 T/C Type K/J termocouple Deg F S/D A
spare 18 T/C Type K/J termocouple Deg F S/D A
spare 19 T/C Type K/J termocouple Deg F S/D A
spare 20 T/C Type K/J termocouple Deg F S/D A
spare 21 T/C Type K/J termocouple Deg F S/D A
spare 22 T/C Type K/J termocouple Deg F S/D A
spare 23 T/C Type K/J termocouple Deg F S/D A
spare 24 T/C Type K/J termocouple Deg F S/D A

Switches Note Note Note


Panel Power ON / OFF EX Type 2-POS MM 2 Set Contacts Panel Package
ESD Panel Push Button 2-POS MM 2 Set Contacts Panel Package
Date: 02-09-2016 Dist: PT SKINS
Proj. Ref: EXACTA 21 - MIDAS - Class 1 Div-2 Mgr TS: ADRIAN

SYSTEM
ENGINEERING & SERVICES
End-User Petrochina Jabung - Jambi E-Mail: adrian@skins.co.id
Country Indonesia Cell:
Location PCI Jambi
Unit # CP- 5000 TS Team: Andry F Sitepu
Application WAUK. F3521 GSI/CEC - ARIEL 2 THROW-2STG E-Mail: andry@skins.co.id

Power Supply
Customer Will Provide 220 Or 110 VAC 20 Amp Minimum