Input

Case 1
Refrigerant type Propane
Normal Refrig duty 0.7897 MW 2.694568 MMbtu/h
Rated factor 120 %
Approach Temp. 10 °F 10 °F
Chiller Effluent Temp. 10 °C 50 °F
CW temp., supply 32 °C 89.6 °F
CW temp., max return 42 °C 107.6 °F
Cp of water at supply temp. 1.00649 btu/lb*°F

Use these values with GPSA manual charts


Evaporator temperature 40 °F
Refrig. Condensing temp 99.6 °F
Gas HP per MMbtu/h
Refrigeration duty 80 HP

MMbtu/h condenser duty per


MMbtu/h Refrigeration duty 1.21 MMbtu/h 3.2604275796

Normal HP Requirement 216 HP


Rated HP Requirement 259 HP
Normal CW Requirement 297 gpm
Rated CW Requirement 357 gpm