Você está na página 1de 1

To crane

TABLE-1 : SAFE LOAD CARRYING CAPACITY

Links at 75mm c/c


Safe Load (KN)
3000 Lifting beam
Cut off level (EL: - 4.60 M)
at 4400mm From Head

Size of Pile
Vertical Lateral / Horizontal
Lifting Point

01 01 (mm) Pull-Out / Tension


Compression Fixed End
350 X 350 400 100 50
Links at 125mm c/c

20mmØ main bar


Note:
1100

1. Description of Pile
Pile type : Pre-cast driven R.C.C. pile
10Ø Link thoughout Pile size : (350x350)mm
0.2L 0.3L 0.3L 0.2L Pile length : 21m (from cut off level)
During Shifting (L=Length of pile) 2. All dimensions are in mm & elevation/level are in meter
Links at 175mm c/c

unless noted otherwise.


22.00m

13800

3. EL (±) 0.00m corresponds to R.L. (±) 5.60m


4. Grade of concrete shall be C40/50 conforming to BS EN
21.00m

206:2013 with minimum cement content of 400 kg/cum.


20mmØ main bar 5. Ordinary Portland cement with C3A content limited to 5
to 8% shall be used.
Links at 125mm c/c

6. Reinforcement steel shall be of grade B500B conforming


1100

to BS 4449:2005+A:2009.
Pile driving rig 7. Lap length shall be 50 times diameter of bar. Laps shall
at 4400mm From Bottom

01 01
To crane be staggered alternatively.
Lifting Point

8. Clear cover to longitudinal reinforcement shall be 70


Links at 75mm c/c

mm.
3000

9. Test shall be conducted at pile cut-off level.


10. Test result shall be submitted to owner/owner's
consultant/BHEL-PEM immediately after completion of
0.30L
0.30L the same.
0.2L
300mm

11. Routine load test shall be conducted on 0.5% of job


0.2L piles
100mm
350mm
Ground each in vertical compression (by maintained load
LONG SECTION OF PRE-CAST
DRIVEN R.C.C PILE method) and in lateral mode as per ASTM-D1143 &
During Pitching (L=Length of pile) ASTM-D3966 respectively and as per specification
12. Table-01 demonstrates the safe load carrying capacity
350 20mmØ main bar of the Job piles.
10Ø Link thoughout
350

Section 1-1

SCALE:

POWER SECTOR
DATE NAME SHEET
PROJECTS ENGINEERING MANAGEMENT
DRAWN BY PRIODEEP OF
NOIDA
DESIGN BY PRIODEEP TITLE
CHECKED BY
APPROVED BY
SUPERSEDES:

SUPERSEDED BY: SIZE: PROJECT NO.: FILE: RC DETAILS OF PRECAST DRIVEN PILE

SYSTEM: ANNEX: DRAWING NO.: MAITREE-00-UMA-LC-421607C009PEM