ELECTRICAL LOAD CALCUTATIONS AND EQUIPMENT SIZING.

S. No. Description Connected Diversity Demand Load Connected Load Diversity Demand Load (kW)
Load (kW) (kW) (kW)

Grid Power Back-up Power - DG set


1 Tower-A, Load for 2BHK Units (100No.
3BHK Unit @ 7 kW each for Grid Power
and 0.8 kW for DG power )
700 0.6 420 80 0.5 40
2 Tower-B, Load for 2BHK Units (460No.
2BHK Unit @ 6 KW each for Grid
Power and 0.8KW for DG power )
2760 0.6 1656 2208 0.5 1104
3 Tower-C, Load for 1BHK Units (180No
1BHK Unit @ 4 KW each for Grid
Power and 0.8KW for DG power )
360 0.6 216 144 0.5 72
4 Tower-D, Load for 1BHK Units (64 No
1BHK EWS Unit @ 4 KW each for
Normal Power and 0.8KW for DG
power )
192 0.6 115.2 80 0.5 40
5 Common Area and stair case Lighting
& Power Load 30 0.8 24 80 0.5 40
7 Fire Fighting System (Dead Load 142
kW) 142 1 80 0.5 40
8 Fire Fighting System (Jockey Pump) 20 0.8 16 80 0.5 40
9 Elevator @ 10 KW 370 0.8 296 80 0.5 40
10 External Lighting 15 0.8 12 80 0.5 40
11 STP 30 0.8 24 80 0.5 40
Total Load 4619 2779.2 2992 1496.00
Over all Demand on load factor @ 0.8 2223.36
on Normal Power
Power factor@ 0.95 for grid supply 2340.38 1496
Power factor@ 0.8 for DG supply 825.08
Required kVA at 85% Loading 2753.39 970.68

Transformer Selection 1 Nos. of 3150KVA, 33/0.433KV Oil


Filled Transformers with OLTC. 2 No. 500KVA 1 No., 415V DG sets.