Você está na página 1de 15

12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.

org

Login / Register

Custom Search Search

lopol.org

Specification for Air Conditioning And Ventilation


Installations in MEP

In this sample MEP specification section, Air Conditioning And Ventilation Installations have been
described in detail under construction contract work.

Main Highlights of this MEP Specification


1.
2. Fans - General Requirements
3. Centrifugal Fans
4. Axial Flow Fans
5. Propeller Fans
6. Protectively Coated Fans and Special Enclosures
7. Mechanical Roof Extract Units
8. In-Line Centrifugal and Mixed Flow Fans
9. Twin Fan Units
10. Cooling Coils
11. Air Heater Batteries
12. Air Filters
13. Fan Coil Units
14. Packaged Air Conditioners

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 1/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

1. Air Handling Units (AHU) of Air Conditioning And Ventilation


Installations

General Requirements for AHU


All individual components of packaged air handling units shall comply with the appropriate Sections of this
Specification unless otherwise specified within the Schedules or on the drawings.

Construction of AHU
Each AHU assembly shall be of compact construction and shall consist of a rigid metal framework, with
insulated double skin sheet metal panels. The metal shall be 1.2mm minimum thickness strengthened as
necessary to prevent distortion and drumming. The insulation shall be 25mm thick and comply with the
relevant clauses in the section covering insulation.

The panels shall be easily removable using quick release fasteners to obtain access for inspection and
maintenance. All items shall be assembled by means of bolts, anti-vibration lockwashers and nuts or
accepted quick release fastenings. All units shall be mounted on accepted type anti-vibration mountings.

Dampers, Filters and Fans Used in AHU


Where air mixing sections are required the damper controls shall be suitable for connection to a single
damper motor; a motor mounting bracket shall be provided. The arrangement of dampers shall ensure
adequate mixing. Dampers shall be of the opposed blade multi-leaf type.

Unless otherwise indicated in the Particular Specification, a flat panel pre-filter and bag type main filter
shall be provided, each in accordance with Clause 12 of this Specification.

Both fresh air and recirculated air shall be filtered.

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 2/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Fans shall be of either forward or backward bladed centrifugal type; unless otherwise indicated fan motors
shall be mounted internally in the unit and there shall be means of adjusting the motor position. The fan and
motor assembly shall be provided with anti-vibration mountings to isolate vibration from the casing.

Fans fitted to all air handling units shall be provided with external lubricators arranged to terminate adjacent
to the access door to the fan section of the air handling unit.

Anti-Condensation Features for AHU


Where units incorporate humidifying plant and/or cooling coils the internal surfaces of the units liable to be
affected by any free water produced shall be protected by anti-corrosion paint or a similar finish. Such units
shall have adequate drain trays to collect water; the drain trays shall be extended, or other means of
collection shall be provided, to ensure the removal of any water deposited or condensed in adjacent sections.
Trays collecting cooled water shall be insulated to prevent condensation on the outer surface, and shall be
provided with a trapped outlet to drain.

Thermal Insulation of AHU


Thermal insulation shall be provided between the inner and outer members of the double skin panels and in
any hollow members of the framework. The insulation shall be of the closed-cell foamed plastic type, with a
minimum thickness of 25mm, and a maximum conductivity of 0.036W/m oC.

Additional insulation shall be provided as required to prevent any risk of condensation on the external
surfaces.

Back to Highlights

2. Fans - General Requirements in Air conditioning and Ventilation


System
Fans shall be capable of giving the specified performance when tested in accordance with BS 848. Although
estimated values of the resistance to airflow of items of equipment may be indicated this does not relieve the
Contractor of the responsibility for providing fans capable of delivering the required air volume through the
system.

The make and design of fans shall be accepted by the Engineer and evidence supporting claimed noise
levels and fan efficiencies shall be submitted for acceptance prior to placing the order. Where fans are
supplied with noise attenuators full details of the attenuators shall be given.

Belt driven fans shall be fitted with pulleys suitable for V-belts; pulleys of the taper lock type may be used
for drives up to 30 kW output. Alternatively, and in any case above 30 kW output, pulleys shall be secured
to the fan and the motor shafts by keys fitted into machined key-ways. Pulleys shall be keyed to the fan shaft
in the overhung position. Keys shall be easily accessible so that they can be withdrawn or tightened and they
shall be accurately fitted so that the gib head does not protrude beyond the end of the shaft.

Machined bolts, nuts and washers only shall be used for the assembly of fans; all bearing surfaces for the
https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 3/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

heads of bolts or washers shall be counter-faced. Holding-down bolts for fans and motors shall be square
section under the head or be fitted with lugs to prevent them turning in the fan baseplate when the nuts are
tightened. Any fan which is too large or too heavy for safe manhandling shall be provided with eye-bolts or
other lifting facilities to enable mechanical lifting equipment to be used.

Back to Highlights

3. Centrifugal Fans in Air-conditioning and Ventilation System


Unless otherwise indicated centrifugal fans larger than 7.5 kW output shall be of the backward curved blade
type having fan total efficiencies of not less than 78%. Below 7.5 kW fans may be either forward curved or
backward curved type. Fan casings shall be constructed of mild steel plates with angle stiffeners and base
angles to ensure freedom from drumming and shall be suitable for operation at the maximum static pressure
of the system. Fan casings shall be constructed so that impellers can be easily withdrawn after installation.
Outlets shall be flanged and inlets shall be flanged or spigotted as indicated except that for suction pressures
greater than 1000 Pa inlets shall be flanged.

A drain and plug shall be fitted to the fan casing at its lowest point. For all kitchen extract ventilation fans an
access door, for inspection and cleaning, shall be fitted to the scroll casing in an accessible position; it shall
be the full width of the impeller.

Impellers shall be of mild steel (or aluminium where indicated) of riveted or welded construction, with
spiders or hubs of robust design, and shall be capable of running continuously at ten per cent in excess of
normal speed. Impellers shall be keyed to a substantial mild steel shaft and the impeller with shaft shall be
statically and dynamically balanced and tested for over-speed before leaving the maker's works.

Shaft bearings of belt driven single inlet fans shall be truly aligned and rigidly mounted on a pedestal
common to both bearings.

Double inlet, double width fans shall have a pedestal mounted bearing at each side of the fan.

Fan bearings shall be ring oiled sleeve bearings, or ball or roller type. Where silence is important the bearing
pedestal shall not be attached to the fan casing, and ring oiled sleeve bearings shall be applied.

Unless otherwise indicated centrifugal fans shall be driven by electric motors through V-belt drives.

The maximum fan outlet velocity shall be 10 m/s.

Back to Highlights

4. Axial Flow Fans in Air-conditioning and Ventilation System


Axial flow fans shall be either the single stage type or the multi-stage contra-rotating type with each
impeller mounted on an independent motor, and having an efficiency of not less than 60%. Casings shall be
rigidly constructed of mild steel stiffened and braced to obviate drumming and vibration. Cast iron or
fabricated steel feet shall be provided where necessary for bolting to the base of supports. Inlet and outlet

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 4/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

ducts shall terminate in flanged rings for easy removal. The length of the duct casing shall be greater than
the length of the fan(s) and motor(s) in order that the complete section may be removed without disturbing
adjacent ductwork. Electrical connections to the motor(s) shall be through an external terminal box secured
to the casing.

Impellers shall be of steel or aluminium; the blades shall be secured to the hub or the blades and the hub
shall be formed in one piece.

The hub shall be keyed to a substantial mild steel shaft and the whole statically balanced. Blades shall be of
aerofoil section. Shafts shall be carried in two bearings which may be ball, roller or sleeve type. Lubricators
shall be extended to the outside of the casing.

Where axial flow fans are driven by a motor external to the fan casing the requirements for pulleys and V-
belt drives and guards as specified elsewhere shall be met. Unless otherwise indicated a guard is not
required for any part of a drive which is inside the fan casing. An access door of adequate size shall be
provided.

Where axial flow fans of the bifurcated type are indicated the motors shall be out of the airstream. Motors
may be placed between the two halves of the casing in the external air or may be placed within the fan
casing provided that effective ventilation is given to the motor. Where hot gases or vapours are being
handled the motor and the bearings shall be suitable for operation at the temperature they may experience.

Fans which do not connect to a suction duct shall be supplied with a bellmouth inlet.

Back to Highlights

5. Propeller Fans in Airconditioning and Ventilation System


Impellers shall be of steel or aluminium; the blades shall be fastened to the hub or the blades and hub shall
be formed in one piece. The bearings may be ball, roller, or sleeve type. Propeller fans may be ring mounted
or diaphragm mounted in a casing, as indicated. Where they are mounted in a casing the casing shall be
longer than the length of the fan and motor.

The casing shall be of steel, shall have flanged ends and shall incorporate an inspection door. A terminal box
shall be mounted externally on the casing. The tip speed of fans shall not exceed 20 m/s.

Propeller fans shall not be installed to work against a resistance of more than 50 Pa.

Back to Highlights

6. Protectively Coated Fans and Special Enclosures


Protectively coated fans shall meet the appropriate requirements of the preceding clauses relating to fans
generally and to particular types of fans; the form of protection shall be as indicated. Where a protective
coating is required for use with corrosive gases the coating shall cover all parts of the complete fan, motor
and casing assembly which will be in contact with the corrosive gases.

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 5/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

No fan shall be installed if the protective coating has been damaged in any way. Flame-proof enclosures
shall comply with the requirements of BS 229 for the appropriate gas group.

Back to Highlights

7. Mechanical Roof Extract Units in Airconditioning and


Ventilation System
The fans used in roof extract units shall meet the appropriate requirements of the preceding clauses relating
to fans generally and to particular types of fans. Cowls and bases shall be of aluminium construction unless
otherwise stated in the Particular Specification. Cases shall be formed so as to ensure a weatherproof fitting
to the building structure.

Adequate access to motor terminals and lubricating points shall be provided by means of hinged cowls or
otherwise as appropriate. Backdraught dampers and/or fire release dampers shall be provided where
indicated.

Back to Highlights

8. In-Line Centrifugal and Mixed Flow Fans in Airconditioning and


Ventilation System
In-Line centrifugal and mixed flow fans may be incorporated subject to the acceptance of the Engineer
provided that full details of ratings, noise level, dimensions and construction are given in the tender. Fans of
these types above 7.5 kW output will not normally be accepted.

Back to Highlights

9. Twin Fan Units in Airconditioning and Ventilation System


Duplicate fan assemblies shall comply with the appropriate sections of this Specification for the fans
themselves and shall incorporate an automatic or manual changeover facility as indicated.

A non-return damper arrangement shall be fitted to prevent short circuiting.

Back to Highlights

10. Cooling Coils in Airconditioning and Ventilation System


All air cooling coil casings shall be of sheet steel not less than 1.2mm thick with angle framing at each end
drilled ready to receive the counter flanges on the connecting ductwork and shall be galvanised after
manufacture. Cooler batteries shall be constructed of copper tubes with aluminium fins, unless otherwise
stated in the Particular Specification.

The secondary extended cooling surfaces shall be bonded to the primary cooling tubes. Headers for copper
tube batteries shall be of copper or bronze. The bottom of a casing shall be made in the form of a watertight
drip tray complete with drain connection.

The drain shall be fitted with a water seal to prevent the ingress and discharge of air to and from the system;
https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 6/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

the drain pipe shall be run to the nearest sump or gully.

A separate drain trough shall be provided for at least each 1.2 m height of coil. Water shall not be carried
over from a cooler into the airstream; an eliminator section shall be fitted where necessary to prevent carry-
over.

The resistance to air flow shall not exceed 125 Pa and the face velocity shall not exceed 2.5 m/s. Before
leaving the maker's works coolers shall be tested to 1½ times the working pressure or to 7 bar whichever is
the greater.

Eliminator plates shall be fitted if the face velocity exceeds 2.25 m/s.

Cooling Coils shall be supported so that their weight is not transmitted to ductwork and so that they can be
removed without disturbing adjacent ductwork. Inspection doors shall be provided on both the upstream and
downstream sides of the cooler. On any system where the air static pressure at the cooler exceeds 750 Pa
airtight cover boxes shall be provided over the headers and bends; provisions shall be made for draining the
cover boxes.

Coils with fins which have been badly damaged during transport or erection or which have become fouled
or coated with builders materials will not be accepted.

Chilled Water Coils


Coils shall be arranged in a contra-flow pattern, with the flow of chilled water entering at the leaving air end
and leaving at the entering air end. The flow and return connections and headers shall be so arranged to
ensure an equal flow of water through all the tubes. Provision shall be made for expansion of the tubes, for
effective venting of the cooler battery and connections and for draining of the cooler battery headers and
tubes.

Connections up to and including 65mm bore shall be screwed or flanged; connections 80mm diameter and
above shall be flanged. Isolating valves shall be provided on inlet and outlet connections, arranged so as to
facilitate removal of the cooler.

Refrigerant Direct Expansion Air Cooling Coils


Coils shall be provided with refrigerant distributors, and connections to the tubes shall be designed to ensure
an equal flow of refrigerant to each tube. Return (or suction) connections shall be arranged so as to ensure
complete drainage of any oil in the cooler. Coolers shall be dehydrated and sealed after manufacture.

The thermostatic expansion valve which shall incorporate an external equaliser line shall maintain the
design degree of superheat at the evaporator outlet; the remote sensing bulb shall be securely fixed to the
evaporator outlet piping in a position where the degree of superheat can be correctly sensed.

All refrigerant spaces shall be tested at the maker's works to 1400 kPa for use with refrigerant 12 and to
2100 kPa for use with refrigerant 22.

Back to Highlights
https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 7/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

11. Air Heater Batteries in Airconditioning and Ventilation System


Casings shall be of galvanised sheet steel no less than 1.2mm thick with angle framing at each end drilled
ready to receive the counter flanges on the connecting ductwork. Heaters shall be supported so that their
weight is not transmitted to ductwork and so that they can be removed without disturbing adjacent
ductwork. Inspection doors shall be provided on both the upstream and the downstream sides of the heater.

The casing shall be airtight to meet the air pressure requirements of the system with appropriate
arrangements to accommodate expansion where applicable.

Electric Type
Electric air heaters shall consist of a number of heating elements of the enclosed non corrodable type
mounted in a steel casing. The elements shall be so installed that they can be removed for cleaning or
renewal without dismantling ductwork. The surface temperature of the elements shall not exceed 150oC. A
high temperature limit device with hand reset button shall be incorporated.

Each element shall be complete with a second set of terminals to operate a failure warning light.

The control of electric air heaters shall be interlocked with an air flow control of the vane or pressure type
which shall isolate the heating elements from the electricity supply in the event of failure of air flow.

The heater shall be arranged with elements of the same number, or a multiple of the number, of steps as the
control required. All heaters and heater sections of more than 3 kW loading shall be balanced over three
phases and the complete heater bank shall be arranged for balanced operation on a 3- phase 4-wire system
and be stepped by he controller in 3kW stages, unless otherwise indicated in the Schedules.

Below 3 kW the stepped loadings shall be in 1 kW increments. The connections from each element shall be
taken to a readily accessible terminal box arranged for conduit entry. Each heater section shall be separately
fused and the neutral point of all 3-phase star-connection sections shall be brought out to a link in the
terminal box. Near any hot areas the wiring insulation shall be of appropriate quality.

The total resistance of the heater to air flow shall not exceed 25 Pa and the velocity through the free area
shall not exceed 6 m/s.

The installation of electric heater batteries shall comply in all respects with the requirements of the local
Fire Authority.

Back to Highlights

12. Air Filters in Airconditioning and Ventilation System


Filters shall operate to at least the efficiencies specified in this Section. They shall be complete with holding
frames sufficiently robust to ensure that no distortion occurs in operation. All filters shall be installed with
edge seals which shall prevent air bypassing the filters. The seals shall, remain effective even though the
cells are periodically removed and refitted.

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 8/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Filters shall be arranged so that there is easy access for cleaning and/or removal. A differential pressure
gauge of the dial or inclined manometer type shall be provided for each filter bank and shall be fixed in such
a position outside the duct system that it is accessible and easily read. The gauge shall be marked to show
maximum pressure differential indicating a filter change requirement. Air velocity through filters shall be
such that the clean resistance (or operating resistance of automatic filters) as indicated is not exceeded and
that filter fabric or oil is not carried over into the system.

Filter assemblies shall be of a standard type and dimensions and shall be such that replacement filter
medium is readily available from a number of manufacturers.

Fire Precautions
Where a flameproof filter medium is specified the material shall comply with the following requirements
when tested in accordance with the relevant standard.

1. Duration of flaming: No test specimen shall continue to flame for more than 8 seconds after the igniting
flame has been removed.
2. Extent of after-glow: After-glow shall not spread beyond the area of material damaged by flaming.
3. Length of material which chars or melts: The average length of material which chars or melts on the
six specimens shall not exceed 85mm and the maximum length of the charred or melted material in any
one specimen shall not exceed 115mm.

Where washable type flameproof filters are offered or specified the filter medium shall comply with the
requirements of clause (2) above both before and after the washing treatment prescribed in BS 3120
Appendix A.

Where the filter medium is required to be flameproof the casing shall be not less than 1.6mm thick for at
least 1.8 m upstream and 1.8 m downstream of the filter; the immediate frames or cases of the filter
elements shall be of material complying with BS 746 Part 1, Clause 7, Class 1.

Dry Replacement Media Type Filters


The filter shall be of the flat panel type contained in a galvanised steel front or side withdrawal frame. Each
cell shall comprise a pad of glass fibre or synthetic fibre filter media, 50mm thick, retained within a rigid
frame of durable cardboard. The filter shall have an efficiency of not less than 92% based on the tests
specified in BS 2831 with test Dust No. 2, a maximum face velocity of 2 m/s and an initial pressure drop not
exceeding 70 Pa.

Sufficient spares cells shall be provided to replace all of the filter bank.

Regenerative Filters
The filter medium shall be processed washable open cell foamed plastic or plastic bonded synthetic fibre
and shall have a minimum thickness of 15mm. The element shall be supported on plastic coated steel wire
formers with a metal frame. The face velocity shall not exceed 2.25 m/s. Filters of this type shall have an
efficiency of not less than 90% based on the tests specified in BS 2831 with test dust No. 2.

Bag Filters
https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 9/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

The filter shall comprise one or more 600 x 600 filter bag modules fitted into a purpose made galvanised
steel side or front withdrawal frame.

Each module shall comprise a minimum of four separate bags banded or clipped into a galvanised steel
header.

The bags shall have a minimum length of 600mm. and shall be of the fine medium to give an efficiency of
not less than 99.6% based on the tests specified in BS 2831 with test dust No. 2. The medium shall be of
multi-layer type with high mechanical strength. The maximum initial resistance shall be 100 Pa.

One complete set of spare bags shall be supplied.

Automatic Fabric Roll Type Filters


The filter shall comprise the complete assembly of filter frame, motor and drive and filter medium. The
filter shall operate automatically, with provision for manual starting and stopping of filter movements;
unless otherwise indicated automatic filter movement shall be controlled by the resistance across the filter.
Provision shall be made for visual warning that the end of the clean filter medium is approaching. The
driving motor shall be automatically switched off when the end of the filter medium is reached.

Unless otherwise indicated the resistance of the filter shall not exceed 125 Pa under normal operating
conditions; the air velocity through the filter medium shall not exceed 2.5 m/s. Filters of this type shall have
an efficiency of 95% based on the tests specified in BS 2831 with test dust No. 2.

Where the motor and/or gearbox is mounted in the air stream the electrical insulation and/or lubricants shall
be suitable for the temperature range experienced.

A spare roll of filter medium shall be provided for every installed roll.

Grease Eliminators
Grease eliminators shall be of the impingement type comprising fluoropolymer coated adjustable vertical
baffles contained within a stainless steel casing. The bottom of the casing shall comprise a grease collecting
trough, from which a drain shall be provided into a removable stainless steel grease collector.

The baffles shall be supplied in modules with a maximum size of 500mm x 500mm, each readily removable
for cleaning. The use of mesh type grease eliminators will not be permitted.

High Efficiency Filters


High efficiency filters shall consist of asbestos cellulose or glass fibre pleated paper media in a rigidly
constructed case with a completely positive seal.

The efficiency of the filter shall be equal to or better than that indicated and in any case shall be not more
than 0.5% penetration based on the tests specified in BS 2831 with methylene blue or the sodium flame test
specified in BS 3928.

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 10/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Where fire protection is required or the air temperature may exceed 200oC the filtering medium shall be
glass fibre paper, and the casing, spacers and seals shall all be of fire-resistant material.

The air velocity at the face of the filter shall not exceed 1.25 m/s. Filter changing arrangements must be such
that dust is not released into the room during the changing operation. Two, or 10% whichever is the greater
spares shall be provided.

Activated Carbon Type Filters


The cell casing shall be of steel protected against corrosion. The internal arrangement shall include a
corrosion-proof framework of supports to ensure an equal disposition of individual panels across the cell,
through sealing between panels and mechanical protection to the front and rear of the panels.

The carbon shall be of uniform bed thickness in the panels and shall be sufficiently densely packed to ensure
that no settling down or gaps occur in use. For each rated 0.5m3/s capacity, 20 kg of carbon shall be
provided. The resistance to air flow shall not exceed 125 N/m2.

Back to Highlights

13. Fan Coil Units (FCU) in Airconditioning and Ventilation System


Fans, filters, cooling coils, heating coils, motors and thermal and acoustic insulation shall comply with the
appropriate Sections of this Specification, with the following exceptions or alternatives:

1. Fans shall be of the forward curved centrifugal type and may be of aluminium, reinforced glass fibre or
rigid plastic material.

2. Air Filters may be of washable synthetic fibre or cellular plastic material with a minimum thickness of
15mm and shall have a minimum efficiency of 90% when tested in accordance with BS 2831 using test dust
No. 2.

3. Motors shall be quiet running and shall have sleeve bearings factory lubricated for life. Motor windings
and electrical components shall be impregnated or protected to avoid trouble from condensation.

Casings of FCU
Casings shall be of sheet steel not thinner than 1.2mm and shall be protected against corrosion and finished
inside and outside with stoved primer.

Casings of exposed units shall provide sufficient internal space to accommodate valves, controls etc. and
shall incorporate return air grille and directional supply grille. The front panel shall be readily removable for
access.

Concealed units shall be complete with supply air duct spigot and return air plenum. Valves and controls
shall be external to the casing.

Components

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 11/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Cooling and heating coils shall be at least two-row and shall include an air cock. All units shall include an
easily removable and replaceable air filter capable of treating the total air volume. Drain pans shall be either
of sheet steel protected against corrosion or of plastic or reinforced glass fibre material and shall be
arranged, and insulated where necessary, so as to ensure that no condensation is formed on the underside.
Drain pans shall be large enough to collect all condensate from the coil, return bends and pipework
connections; they shall be removable and shall have a slight fall to the drain connection.

Arrangement of Units
The arrangement of units, i.e. whether they be wall, floor or ceiling mounted, the position of inlet and outlet
grilles if any, the need for sheet metal casing etc., shall be as indicated elsewhere.

Where units are concealed, the Contractor shall ensure that adequate access is provided for the removal of a
complete unit.

Controls and Grilles


Fan coil units shall have a control giving three running speeds and an 'OFF' position. The specified duty
shall be achieved using medium or low speed. Outlet grilles shall be adjustable to enable the direction of
airflow to be reset. On floor mounted units, supply grilles shall be on the top of the unit.

Noise Levels
Casings shall be lined with material to act as both thermal and acoustic insulation (Sections 10 and 11). Fan
and motor assemblies shall be complete with anti-vibration mountings. Noise data shall be provided and
shall be based on tests in accordance with the HVRA Test Code, or similar tests; full details of the testing
technique and procedure shall be given. The data given shall include an octave band analysis of the sound
power level of the unit.

Back to Highlights

14. Packaged Air Conditioners in Airconditioning and Ventilation


System
Each unit shall comprise the following components, each of which shall comply with the appropriate
sections of this Specification, except as otherwise indicated:

Casing
This shall consist of a heavy gauge steel chassis with sheet metal casing, minimum thickness 1.2mm and the
whole shall be protected against corrosion and finished inside and outside with stoved primer. Casings shall
include removable panels to provide ready access to all component parts.

Casings shall be lined with material to act as both thermal and acoustic insulation. Fan and motor assembles
shall be complete with anti-vibration mountings. Noise data shall be provided and shall be based on tests in
accordance with the HVRA Test Code, or similar tests; full details of the testing technique and procedure
shall be given. The data shall include an octave band analysis of the sound power level of the unit.

Fans

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 12/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Evaporator fans shall be of the belt driven forward curved centrifugal type and be of aluminium or
galvanised steel construction. Split pulleys shall be provided to allow the fan speed to be adjusted.

Condenser fans shall be of the direct driven propeller type, with weatherproof motors.

Air Filters
Air filters shall be 50mm thick synthetic fibre or glass fibre material and shall have a minimum efficiency of
92% when tested in accordance with BS 2831 using test Dust No. 2.

Motors
Motors shall be quiet running and shall have sleeve bearings factory lubricated for life. Motor windings and
electrical components shall be impregnated or protected to avoid trouble from condensation.

Compressors
Compressors shall be hermetic or semi-hermetic type complete with resilient mountings.

Coils
Unless otherwise indicated condenser/evaporator coils shall be formed of copper primary surface tubes with
aluminium secondary surfaces.

Drain trays and condensate disposal shall be as described in the relevant sections of this Specification.

Tags

Mechanical Specification
Sample MEP Specification

‹ Soil Survey And Calculations for up Specification for Mechanical General Plant
Electrical Earthing or Grounding System in and Machines in MEP Work ›
Building Construction

Add New Comment

Related Posts To Mechanical Specification:

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 13/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Refrigeration Plant in MEP


Construction Work Specification for Mechanical General Plant and
Machines in MEP Work

Fire Fighting Services in MEP Construction


Mechanical Ductwork, Grilles
Contract
And Diffusers

SBI Bank Loan Electrical Installation Construction


Engineering Bank Loan Electrical Engineering Banking
Services Agriculture Bank Loan Electrical Specification Construction Project
Construction Control Guidelines SBI SME Loan Electrical Earthing or Grounding System
SME Bank Loan State Bank of India (SBI) Building Services Sample MEP Specification SBI
Business Loan Lighting System Home Loan Engineering Services Mechanical Specification Construction
Quality Plan Conduit Installation Car Loan Bank Loan For Farmers Bank Home Loan Wiring Method Testing
and Commissioning Quality Plan Loan Documents General Awareness Branch Banking Bank Loan Products Auto
Loan SBI Home Loan Documents SBI Home Loan Panel Board Installation Online Application Lightning
Protection Kisan Credit Card (KCC)

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 14/15
12/26/2017 Specification for Air Conditioning And Ventilation Installations in MEP | lopol.org

Latest Content
Find Company Master Data Using Company CIN No. in www.mca.gov.in

State Bank Of India (SBI) Corporate Internet Banking (CINB) For Current Account Holders

Google Local Guides: 10 Levels To Reach, More Points, Rewards, and New Badges

Today's popular
Method of Earthing or Grounding for Diesel Generator Plant

Corporate Identification Number or Company CIN No. in India

Kerala MLA Salary, Benefits, Allowances, Perks and Pension

Recent comments
LPG Subsidy and Aadhaar Based Bank Transactions

LPG Subsidy to Other Bank Without Consent on Linking Aadhaar

regardig gas subsidy

Try Out
Private Sector Commercial Banks in India

Types of Construction contracts: Lumpsum contract

SBI SME Supply Chain Loan For Vendors and Dealers

Google+ || Facebook.com

© 2017. Lopol.org. All Rights Reserved.

https://www.lopol.org/article/specification-for-air-conditioning-and-ventilation-installations-in-mep#fans-general-requirements 15/15

Você também pode gostar