S. No. SAMPLE CALCULATION Project: Emami Papaers Ltd.
A Generator Data Sheet
1 Make of Alternator TDPS
2 KW rating of alternator(KW) 15000
3 FLC of alternator(A) In 984
4 Rated voltage(V) Un 11000
5 Rated frequency (Hz) 50
6 Combined variation 10
7 Power factor(lag) 0.8
8 Excitation current 600
9 NGR value(OHM) 63.5
E/F current(A) 100
10 Ambient temperature( deg C) 50
11 Sudden short ckt. Peak current 11130
12 Overload Capacity(%) 50 for 30 sec
13 Reactance(%) Unsat Sat
Xd 210 185
Xd' 36 32
Xd" 25
Xn(Grid Impedance) 20
14 Continuously permissible
unbalanced load(%) K2 20%
15 Thermal genertator Constant K1 15 sec
B Current transformer details: Primary Secondary
1 CT Ratio(A) 1200 1
2 Burden(VA) 15
3 CT Ratio Ki 1200
C Potential transformer details: Primary Secondary
1 PT Ratio(A) 11000 110
2 Burden(VA)
3 PT Ratio Ku 100
D DIFFERENTIAL CT DETAILS Primary Secondary
1 For differential protection(A) 1200 1
2 Class PS
3 Rct 6
4 Excitation current at Vk/2 0.03
5 Leads length between CTs(M) 60
6 Therefore RI(say 8 ohms/km) 0.48
CSPC make Relay Settings for 15 MW Generator
Machine Data :
Make of Alternator TDPS
Rated Capaity of Alternator (KW) 15000
Rated Capaity of Alternator (KVA) 18750
FLC of alternator(A) In 984
Rated voltage(V) Un 11000
Rated frequency (Hz) 50
Combined variation 10
Power factor(lag) 0.8
Excitation current 600
NGR value(OHM) 63.5
E/F current(A) 100
Phase CT Core 1 1200/ 1 Amp, 5 P 10
Phase CT Core 2 1200/ 1 Amp, PS, Ie@Vk/2 = 30 ms, Rct - 6 Ohm, 2RL = 1 Ohm
Neutral CT 100/ 1 Amp, 5 P 10, 15 VA
PT 11000/ 100v
CTR - Core 1 1200
CTR - Core 2 1200
PTR 100
secondary value of Phase Current a 0.82
secondary value of Neutral Current 1
Machine Data :
Make of Alternator TDPS
Rated Capaity of Alternator (KW) 15000
Rated Capaity of Alternator (KVA) 18750
FLC of alternator(A) In 984
Rated voltage(V) Un 11000
Rated frequency (Hz) 50
Combined variation 10
Power factor(lag) 0.8
Excitation current 600
NGR value(OHM) 63.5
E/F current(A) 100
Phase CT Core 1 1200/ 1 Amp, 5 P 10
Phase CT Core 2 1200/ 1 Amp, PS, Ie@Vk/2 = 30 ms, Rct - 6 Ohm, 2RL = 1 Ohm
Neutral CT 100/ 1 Amp, 5 P 10, 15 VA
PT 11000/ 100v
CTR - Core 1 1200
CTR - Core 2 1200
PTR 100
secondary value of Phase Current at 0.82
secondary value of Neutral Current a 1
. CALCULTAIONS:
For warning stage I2w, a somewhat smaller value than I2s can be used.
Machine Data :
Make of Alternator TDPS
Rated Capaity of Alternator (KW) 15000
Rated Capaity of Alternator (KVA) 18750
FLC of alternator(A) In 984
Rated voltage(V) Un 11000
Rated frequency (Hz) 50
Combined variation 10
Power factor(lag) 0.8
Excitation current 600
NGR value(OHM) 63.5
E/F current(A) 100
Phase CT Core 1 1200/ 1 Amp, 5 P 10
Phase CT Core 2 1200/ 1 Amp, PS, Ie@Vk/2 = 30 ms, Rct - 6 Ohm, 2RL = 1 Ohm
Neutral CT 100/ 1 Amp, 5 P 10, 15 VA
PT 11000/ 100v
CTR - Core 1 1200
CTR - Core 2 1200
PTR 100
secondary value of Phase Current at Full load 0.82
secondary value of Neutral Current at Full load 1
Time settings:
Tz1 : 2 sec
Tz2 : 0.5 sec
Under-voltage setting:
U< : 80% of Un
88 volts
Machine Data :
Make of Alternator TDPS
Rated Capaity of Alternator (KW) 15000
Rated Capaity of Alternator (KVA) 18750
FLC of alternator(A) In 984
Rated voltage(V) Un 11000
Rated frequency (Hz) 50
Combined variation 10
Power factor(lag) 0.8
Excitation current 600
NGR value(OHM) 63.5
E/F current(A) 100
Phase CT Core 1 1200/ 1 Amp, 5 P 10
Phase CT Core 2 1200/ 1 Amp, PS, Ie@Vk/2 = 30 ms, Rct - 6 Ohm, 2RL = 1 Ohm
Neutral CT 100/ 1 Amp, 5 P 10, 15 VA
PT 11000/ 110v
CTR - Core 1 1200
CTR - Core 2 1200
PTR 100
secondary value of Phase Current at Full load 0.82
secondary value of Neutral Current at Full load 1