Você está na página 1de 7

Paper accepted for presentation at 2003 IEEE Bologna Power Tech Conference, June 23th-26th, Bologna, Italy

Considerations for the Application of Thyristor


Controlled Series Capacitors to Radial Power
Distribution Circuits
M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior Member, IEEE

 Increased power transmission capability by a decreased


Abstract—This paper deals with the application of Thyristor total circuit reactance and improved voltage profile along
Controlled Series Capacitors (TCSCs) suitably rated for radial the circuit
distribution circuits. The various problems existing on long  Decreased circuit losses
distribution lines that can be alleviated by the connection of
 Support during start of large asynchronous and
variable series compensation, as a TCSC provides, are discussed.
An important feature is the capability of the TCSC to operate as a synchronous motors
short circuit current limiter. Thus, sensitive loads connected to  Reduction of required reactive power input at the sending
nearby substations will not experience any voltage sags caused by end of a radial circuit
faults on the distribution line where the TCSC is connected. The  Reduced voltage fluctuations and voltage imbalance due to
benefits of the connection of a TCSC on a radial distribution load variations
system are verified by means of the ElectroMagnetic Transients
for DC (EMTDC) simulation package.
In distribution systems, reactive power compensation is
Index Terms—Series compensated distribution lines, TCSC, typically provided by shunt-connected components, such as
fault current limiter, thyristor switches, power quality, power SVC and STATCOM devices. Fixed series capacitors are
system simulation, sensitive loads, voltage sags. clearly the most economical solution, but their optimal
location is not easy to determine, when many loads are
connected to the distribution system. An appropriately rated
I. INTRODUCTION TCSC device can also be applied in radial power systems in

T HYRISTOR controlled series capacitors (TCSCs) have


been used in transmission networks to control the
equivalent impedance of transmissions lines, and therefore
order to keep load voltage within given limits for several load
variations or to provide short circuit current limitation. More
specifically, the TCSC appears as variable impedance that
the power flow in the network [1], [2]. They have renewed the depends on thyristor firing angle. In this way the control
interest in transmission line series compensation because of system sends firing order to the thyristors according to basic
their control system flexibility. Although mechanical switching scenarios in order to keep the load voltage between given
could, in principle, be applied to achieve some flexibility, the limits.
fast electronic control and proven reliability of the thyristors Furthermore, TCSC can operate in the inductive region to
lead to maximum controllability of the transmission system. reduce short-circuit currents. TCSC capability to operate as a
As regards distribution systems, many different solutions
fault current limiter in transmission systems has already been
have been proposed. Miske [3] and Souza et al [4] proposed
proposed. Karady [5] proposed a new configuration of TCSC
the use of fixed and GTO-controlled series capacitors in radial
to obtain a combined short circuit current limiter, interrupter
distribution circuits, respectively. GTO or thyristor-controlled
and series compensator in steps. The series compensation is
series capacitors have the advantage of self-regulating,
controlled by the capacitors switching on and off, while the
continuous and instantaneous response. Some of the positive
current limitation and interruption is achieved by the insertion
effects of series compensation on a long radial power
of a resonant LC circuit in the transmission line. Godart et al
distribution circuit when operating as a varying series
[6] conducted a study about the feasibility of TCSC for
capacitance are:
distribution substations enhancement taking into consideration
load expansion. The capability of TCSC to operate as short
circuit current limiter when connected upstream the
M. N. Moschakis is with the Department of Electrical and Computer distribution substation, was confirmed. Moreover, Yamazaki et
Engineering, National Technical University of Athens, Athens, Greece, al [7] proposed and produced a prototype of a combined
(e-mail: mosxakis@power.ece.ntua.gr).
E. A. Leonidaki is with the Department of Electrical and Computer
TCSC system with an additional series current limiting reactor.
Engineering, National Technical University of Athens, Athens, Greece, In this paper, a TCSC model that operates both as a series
(e-mail: eleonid@central.ntua.gr). compensator and fault current limiter is studied. The TCSC
N. D. Hatziargyriou is with the Department of Electrical and Computer can be installed on a long distribution line, where the number
Engineering, National Technical University of Athens, Athens, Greece,
(e-mail: nh@power.ece.ntua.gr). of faults is expected to be high to decrease the short-circuit

0-7803-7967-5/03/$17.00 ©2003 IEEE


effect on neighboring loads. Thus, sensitive loads connected to
nearby substations do not experience voltage sags caused by
faults on the TCSC supported distribution line.

II. TCSC STEADY-STATE OPERATION


The basic circuit of TCSC is illustrated in Figure 1. It
consists of a capacitor in parallel with a thyristor-controlled
inductor. The control variable is the firing angle α of the
thyristors, with reference to the capacitor voltage zero
crossings. The thyristors are fired when the capacitor voltage
and current are opposite in polarity. This is equivalent to
thyristor firing angles between 90° and 180°.

Fig. 2. Apparent impedance of TCSC.

behavior for at least one angle is observed. This asymptote


corresponds to the firing angle where resonance between
inductor and the capacitor reactance occurs. This firing angle
must be avoided, because it results in excessively high
voltages and currents in TCSC circuit. By changing the reactor
inductance, it is possible to increase the effective bandwidth of
control and have a lower circulating current through the
Fig. 1. One-line diagram for TCSC circuit
components [8][9].
Emphasis must be given on the rating of all parameters of a
The TCSC can operate in three different modes. In the
real TCSC not only to achieve the desired capacitive range,
bypassed mode, the thyristor path is conducting continuously,
but also to select the appropriate components that are designed
the capacitor is bypassed and the apparent impedance becomes
to withstand system contingencies that cause high current
inductive. In the blocked mode, the thyristor path is blocked peaks without damage. The control system should take care to
continuously, which is equivalent to the fixed capacitor bypass the TCSC, in case these ratings are exceeded.
reactance. Finally in the Vernier mode, the thyristor path is Additional protection schemes are applied [2]. The thyristors
partially conducting resulting in a flow current circulating in have a Break-over Diode protection scheme for overvoltage
the TCSC loop. Depending on the conduction time of the protection. The capacitor is equipped with a gapless metal-
thyristors, this current may have the same or opposite direction oxide varistor (MOV) surge arrester connected in parallel,
with the internal capacitor current. In this way the TCSC which operates whenever the capacitor voltage overcomes a
appears as an apparent reactance that may be capacitive or set limit. The behaviour of MOV across conventional
inductive. capacitor banks is extensively described in [10]. Finally, a
The steady-state curve of the apparent reactance of the bypass breaker exists that operates whenever the device has to
TCSC at fundamental frequency versus the firing angle is be removed from the system.
equal to:

ZTCSC = - XC + (XC+XLC)[(2σ+sin2σ)/ π ] -
4X2LCcos2σ [(ktankσ-tanσ)/π] /XL (1)

XLC =XC . XL / (XC-XL)


σ = π-α
wo 2 = 1/LC , w = 2πf , k=wo/w

The apparent impedance of a typical TCSC versus the firing


angle α is plotted in Fig. 2. In this figure an asymptotic

Fig. 3.1 TCSC voltage and current waveforms in capacitive region.


During normal operation, the TCSC generally operates in III. STUDY CASE
the capacitive region. The capacitor voltage and current as
well as the thyristor current for this operation are illustrated in A. Power system and TCSC characteristics
Fig. 3.1. During system faults, it is desirable to operate in the The test system consists of two feeders fed by 150/20 kV
inductive region to lower the fault current contribution (Fig. substations. At feeder 1 a nominal load of 10 MVA is
3.2). connected through a long line. This load fluctuates from 9 to
15 MVA at a regular basis leading to voltage fluctuations and
rapid voltage changes [13], which affect both this load and the
loads connected to nearby substations. At feeder 2, a sensitive
to voltage sags load is connected. The installation of this load
contains protection systems that trip immediately after even
shallow sags with only a short duration.
The optimal position to connect a TCSC is at the sending
end of feeder 1. In this location, it enables reactive power
compensation and also reduces short-circuit currents
introduced by faults that occur on feeder 1. The number of
faults on feeder 1 is expected to be high, assumed
proportionally related with the length of a line.
As a basis for the specification of the design parameters of
the TCSC model, the parameters of a real TCSC of 15÷50 Ω at
Fig. 3.2 TCSC voltage and current waveforms in inductive region.
400kV have been used. The scaling factor applied to all the
constituent components is defined as the ratio of the model
Regarding the harmonic content of TCSC device, the
impedance base to the system impedance base at the same
harmonic content of thyristor current is equal to:
point of the circuit, as follows:
2A  sin(n + 1)σ sin(n − 1)σ  2Acosσ  sin(k + n)σ sin(k − n)σ  Z b mod
IT ( n ) = + − + (2)
π  n + 1 n − 1  π coskσ  k + n k − n  λ= (5)
Z bsyst
where n=3,5,7,...
The resistors and reactors of the real system are multiplied
These harmonic currents circulate mainly inside the LC by this scaling factor, while the capacitances are divided by it.
circuit, because the system impedance for harmonic Consequently, each phase of the TCSC model consists of a
frequencies is much greater than the capacitor impedance. This 4760 µF capacitor and a 52 mH inductor with quality factor
can be derived considering that capacitor and system equal to 110. The TCSC apparent impedance varies between -
impedance form a current divider for the thyristor current at 0.668 Ω (α=180°) and 0.1324 Ω (α=90°). The apparent
harmonic frequencies. In this way the capacitor and system impedance of the applied TCSC versus the firing angle α is
currents are given by the equations: shown in Fig. 2. Attention has been paid, so that only one
resonant point in the range of 90° to 180° exists, equal to
iC = i T . ZSYST/(ZSYST + ZC) 135.4°. In addition, the reactor size was properly selected, in
order to increase the effective control bandwidth in the
iac = i T . ZC/(ZSYST + ZC) (3) inductive range.

Assuming that the system impedance is infinite, the


harmonic thyristor currents flow only through the capacitor, so
the capacitor voltage at the n-harmonic is equal to:

VC(n) = iT(n) XC(n) = iT(n)/(n.w.C) (4)

The harmonic content and magnitude of circulating currents


increases essentially as firing angle α gets nearer to the
resonant point. It is shown in [11] that the Total Harmonic
Distortion (THD) of transmission line current is below the
current distortion limits recommended in IEEE Std 519-1992
[12].
Fig. 4. Single-line diagram of the test network
B. TCSC as a varying series capacitance after the first load variation at 0.1 sec, the TCSC circuit
When TCSC operates in the capacitive region, it can be gradually approaches steady state, which is reached when the
controlled so that the voltage at the terminals of load 1 and the half of the inductor current is exactly symmetrical about the
voltage across the feeder 2 (assuming that other consumers are zero crossings of capacitor voltage.
also connected to that feeder or will be connected in the
future) are kept constant. Simulations were performed using
EMTDC to demonstrate the ability of TCSC to alleviate
voltage fluctuations caused by load fluctuations. The
simulation results are shown in Fig. 5. The load varies in steps
from 9 to 15 MVA, as shown in the upper diagram of Fig. 5.1.
The voltage at the terminals of load 1 with and without TCSC,
are shown in the middle diagram. The instantaneous response
of TCSC and the ability to control even rapid voltage changes
can be easily seen. The lower diagram of Fig. 5.1 presents the
variation of the control angle in order to keep the voltage at
the load terminals constant. Furthermore, as voltage across the
TCSC is proportional to the current, the higher current is
flown on the feeder, the more benefits are gained by the
connection of TCSC.

Fig. 5.3 Capacitor voltage and current, line current and control angle
following a load variation

C. TCSC as fault current limiter


Some of the positive effects of fault current limitation are:

 Mitigation of voltage sags, swells and outages


 Longer life with higher reliability for nearby transformers
 Limited inrush current (soft start), even for capacitive loads
 Mitigation of the effects of distributed generation at lower
Fig. 5.1 Voltage with and without TCSC after extreme symmetrical voltages within Distribution Systems
load fluctuations
When TCSC operates in the inductive region, it represents a
In Fig 5.2, THD of the load phase voltage and the line varying inductance, which can reach values much higher than
current are presented. It can be seen that the harmonics the nominal inductor value, as the control angle increases
injected in the voltage and current are acceptable, according to towards the resonance value (Fig. 2). In cases of excessive
European Standard EN50160 [13]. currents flowing in feeder 1, significant damping can be
effected by regulating accordingly the TCSC angle. Thus,
although operation near the resonance area should be avoided,
such operation of TCSC during a short circuit, lasting
essentially no longer than a few periods, e.g. 5 periods (100 ms
for a 50 Hz system) is very beneficial. This time period
corresponds also to the required time for the normal operation
of a distribution protection system. This strategy is used in the
following simulations investigating the effect of fault current
Fig. 5.2 THD of phase voltage and line current.
limitation via TCSC. It is assumed that the TCSC model is
equipped with a MOV appropriate selected for overcurrent and
In Fig 5.3 the capacitor voltage and current inside the
overvoltage protection of the device components.
TCSC in the first 0.3 sec are shown. It should be noted that
The fault detection strategy used is based on the rate of clearly shown that the voltage sag experienced by the sensitive
current increase. In this way, a fault is detected within a few µs load 2 is significantly lower when TCSC is present. The two
and the fault current limitation begins even before the first middle diagrams show the line current with and without a
peak is reached. The detection strategy is shown in Fig. 6.1. TCSC. The lower diagram shows harmonic injection, when
The rate of the line current is compared with the instantaneous TCSC operates in the current limiting mode. It can be seen that
line current. When this rate is above a preset limit (set to 200 the THD is about 5%, well below the limits set in EN50160,
pu/s for this case), the output of the rate limiter is presented in verifying the fact that TCSC does not inject significant
Fig. 6.2. Thus, a signal is issued almost instantaneously and harmonics into the system.
after the first zero crossing of the thyristor current the
operation of the TCSC in the current limiting mode is initiated.

Fig. 6.1 Fault detection strategy

Fig.7. TCSC operation sequence in current limiting mode

The TCSC can also operate independently at each phase,


hence, it can deal with asymmetrical faults. This means that the
faulted phase will operate in the current limiting mode while
the healthy phases will operate in the capacitive region. To
demonstrate the ability of TCSC to deal with asymmetrical
faults, the following simulations were performed.

1) Single- phase fault

The simulation results when a single-phase fault occurs


Fig. 6.2 Fault detection logic in a three-phase fault immediately after the TCSC are shown in Figures 8.1 and 8.2.
The fault occurs at t=0.025 sec and is cleared after 100 ms.
In Fig.7, the repetitive operation of TCSC in a three-phase The load 1 at pre-fault time is 10 MVA. In Fig. 8.1 the load 2
fault is shown. In the beginning, TCSC operates in the voltage with and without TCSC is presented. In Fig. 8.2 it is
capacitive region, a fault immediately after the TCSC (which observed that the phase –c is also affected but continues to
is the worst case) occurs at t=0.1 sec and it lasts until t=0.8 operate in capacitive region. The voltage sag magnitude with
sec. The TCSC operates for 100 ms and the protection breaker the TCSC reaches a value of 72.2% and lasts for 25.66 ms.
opens. The breaker recloses after 300 ms, the fault is still Furthermore, the THD of load 2 voltage is again within
present and TCSC operates again for 100 ms limiting the fault acceptable limits.
current until the breaker opens for the second time. The
breaker recloses again after 300 ms, the fault has been cleared
and the TCSC returns in the capacitive region.
In the upper diagram in Fig. 7, the voltage at the terminals
of the sensitive load 2 with and without a TCSC is shown. It is
Fig. 8.1 Load 2 phase voltages with and without TCSC

Fig. 9.1 Load 2 phase voltages with and without TCSC

Fig. 8.2 Load 2 phase –a and –c line currents, THD of voltage Va

2) Phase-to-phase fault

Phase-to-phase faults (between phase -a and -b) are also


examined. The pre-fault conditions are the same as in the
previous case. Fault occurs at t=0.03 sec and is cleared after
100 ms. The voltage sag magnitude experienced by the load is
Fig. 9.2 Load 2 phase –a and –b line currents, THD of voltage Va
62.9% and its duration is 69 ms. The simulation results are
shown in Figures 9.1 and 9.2.
IV. CONCLUSIONS VI. BIOGRAPHIES
To date, TCSC systems have been proposed as an effective
means to increase power transfer capability of transmission M. N. Moschakis was born in 1974. He received the Diploma in Electrical
Engineering from the National Technical University of Athens (NTUA),
lines and rapid controllability for power swing damping and Greece, in 1998. Currently he is a Ph.D student in NTUA. His scientific
stability in transmission systems. In addition, the ability of interests mainly concern Custom Power Device Modeling and Evaluation,
TCSC to operate as a fault current limiter has been mentioned. and Voltage Sag Stochastic Assessment.
In this paper the application of an appropriately rated TCSC
E. A. Leonidaki received her Electrical Engineering degree in 1992 from
system in distribution networks is proposed. A suitable TCSC
NTUA. She is now with Public Power Corporation of Greece and she works
model is applied in a distribution test system and its towards a PhD degree in Electrical Engineering Department of NTUA. Her
effectiveness in the mitigation of several power quality interests include FACTS modeling and control for power system dynamic
problems is investigated. It is shown that TCSC operating as a analysis and transient phenomena. She is student member of IEEE, member
of CIGRE and member of Technical Chamber of Greece.
varying series capacitance can effectively alleviate load
voltage sags due to load fluctuations. In addition, it is shown N. D. Hatziargyriou received a Diploma in Electrical and Mechanical
that TCSC operating in the inductive region contributes to Engineering from NTUA, and an Msc and PhD degree from UMIST,UK. He
fault current limitation and maintenance of voltage at sensitive is currently Professor at Power Division of the Electrical Engineering
Department of NTUA. His research interests include Modeling and Digital
loads in neighboring feeders close to its nominal value. Techniques for Power System Analysis and Control. He is Senior member of
In general, it is believed that TCSC systems can provide an IEEE and secretary of IEEE Greek section, member of CIGRE SC C6 and of
important control tool to distribution system engineers. Their Technical Chamber of Greece.
ability to reduce short-circuit currents can provide solutions to
many operational and power quality problems. However,
because of its high cost, the viability of such a device should
be further investigated.

V. REFERENCES
[1] E. Larsen, C. Bowler, B. Damsky, S. Nilsson, “Benefits of Thyristor-
Controlled Series Compensation”, CIGRE Paper 14/37/38-04, Paris
1992.
[2] N. Christl, R. Hedin, et al. “Advanced Series Compensation (ASC) with
Thyristor Controlled Impedance”, CIGRE Session 1992, Paper
14/37/38-05, Paris, 1992.
[3] S. Miske, “Considerations for the Application of Series Capacitors to
Radial Power Distribution Circuits”, IEEE Trans. Power Delivery, vol.
16, No.2, pp. 306-318, April 2001.
[4] L. Souza, E. Watanabe, M. Aredes, “A GTO Controlled Series Capacitor
for Distribution Lines”, CIGRE Paper 14-201, Paris 1998.
[5] G. Karady, “Concept of a Combined Short Circuit Limiter and Series
Compensator”, IEEE Trans. Power Delivery, vol. 6, No.3, pp. 1031-
1037,, July 1991.
[6] T. Godart, A. Imece, J. McIver, E. Chebli, “Feasibility of Thyristor
Controlled Series Capacitor for Distribution Substation Enhancements”,
IEEE Trans. Power Delivery, vol. 10, No.1, pp. 203-209, January 1995.
[7] Y. Yamazaki, S. Sugimoto, S. Ogawa, H. Konishi and A. Kikuchi,
“Development of TCSC application to Fault Current Limiters”,
Electrical Engineering in Japan, vol. 140, No. 3, 2002, Translated from
Denki Gakkai Ronbunshi, vol. 121-B, No. 4, April 2001, pp. 514-519.
[8] S. Helbing, G. Karady, “Investigation of an Advanced Form of Series
Compensation”, IEEE Trans. Power Delivery, vol. 9, No.2, pp. 939-
947, April 1994.
[9] E. Larsen, K. Clark, S. Miske, J. Urbanek, “Characteristics and Rating
Considerations of Thyristor Controlled Series Compensation”, IEEE
Trans. Power Delivery, vol. 9, No.2, pp. 992-1000, April 1994.
[10] G.J. Georgantzis, N.D.Hatziargyriou, E.A. Leonidaki, “Transient
Simulation of Series Compensated EHV Transmission Lines for Short-
circuit Studies”, IEEE MELECON ‘96, p. 1584-1587, Bari, Italy, May
1996.
[11] E.A Leonidaki., N.D.Hatziargyriou, B.C.Papadias, G.J.Georgantzis,
"Investigation of Power System Harmonics and SSR Phenomena
Related to Thyristor Controlled Series Capacitors" , Proceedings of the
8th International Conference on Harmonics and Quality of Power
(ICHQP ’98), Athens, Greece, October 1998, pp. 848-852.
[12] IEEE Std. 519-1992, "IEEE Recommended Practices and Requirements
for harmonic Control in Electrical Power systems", 1992.
[13] European Standard EN 50160, Voltage characteristics of electricity
supplied by public electricity distribution networks, November 1994.

Você também pode gostar