Escolar Documentos
Profissional Documentos
Cultura Documentos
II. DESIGN OF LFA-M lower piece of the same resistance applies the low potential 0
to the surface of the upper piece, also at its center. In this way,
An LFA-M arrester consists of two cable-like pieces with a
the total voltage is applied to each flashover module at the
semiconductive core of resistance . The cable pieces are ar-
same moment, and all three modules are assured conditions for
ranged so as to form three flashover modules 1, 2, 3 as shown
simultaneous initiation of creeping discharges developing into
in Fig. 1.
a single long flashover channel.
The semiconductive core of the upper piece, whose resistance
Tests have shown that, as the line conductor is stressed by
is , applies the high potential to the surface of the lower
a lightning overvoltage impulse, flashover channels develop at
piece at its middle. Similarly, the semiconductive core of the
different rates. Modules 1 and 3 flashover first, followed by
module 2, and thus, forming a rather long flashover channel
Manuscript received March 8, 2001; revised February 4, 2002. along the LFA.
The authors are with Streamer Electric Company, St. Petersburg 194902,
Russia (e-mail: georgij@pod.spb.su). Due to the long flashover path, a flashover does not give rise
Digital Object Identifier 10.1109/TPWRD.2003.813597 to a power arc as the arc extinguishes when the power frequency
0885-8977/03$17.00 © 2003 IEEE
782 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003
TABLE I
COEFFICIENTS a AND b OF FUNCTIONS U = at APPROXIMATING MEASURED
VOLTAGE-TIME CHARACTERISTICS OF INSULATOR UNITS AND ARRESTERS
(0:2 s : t 2 s)
(1)
(2)
ductors and is the probability of a lightning current application of the total arrester-stressing voltage simul-
with steepness greater or equal to . taneously to all the modules.
The efficiency of LFA lightning protection against direct 2) The voltage-time characteristics of this modular arrester
lightning strokes can be expressed as the ratio of the number assure reliable protection of medium voltage overhead
of lightning outages for unprotected lines according to (6) lines against both induced overvoltages and direct light-
and for lines protected by LFA arresters according to (7), ning strokes.
as following: 3) To protect a line against induced overvoltages, a single
arrester must be mounted on a pole.
(8) 4) The conditions for the efficient protection of a medium
voltage (e.g., 10-kV) overhead line against direct light-
ning strokes, are as follows:
where is the outage reduction factor of lightning outages
• delta configuration of phase conductors;
caused by direct lightning strokes.
• mounting of LFA-M arresters on all poles in parallel with
Fig. 6 shows the outage reduction factor of a line protected
each insulator;
by LFA10-M arresters ( m; m), versus
• a relatively short flashover path (for example, 1 m for a
the grounding resistance for the INS160 and INS130 insulators.
10-kV line) for the top phase LFA-M arrester;
A line with LFA arresters and INS160 insulators is shown to
• a longer flashover path (for example, 2 m for a 10-kV line)
have good lightning protection performance for direct lightning
for the bottom phases LFA-M arresters.
strokes. For grounding resistance , LFA10-M ar-
resters assure a 200-fold decrease of lightning outages, virtu-
APPENDIX
ally ruling them out. As the grounding resistance increases, the
CALCULATION OF THE PROPAGATION RATE OF FLASHOVER
outage reduction factor decreases faster up to and
CHANNELS ON THE LFA SURFACE
then more slowly. For , is approximately equal to
20 and for , . Thus, the number of outages The propagation rate of flashover channels on arresters and
caused by direct lightning strokes can be lowered with the use insulators can be estimated from the voltage-time characteristic.
of LFA arresters by an order of magnitude or more even for high The average channel propagation rate is
values of grounding resistance.
As shown by calculations, in the case of INS160 insulators, it (A.1)
is important to coordinate the performance of phase B arrester where is the flashover path length and is the flashover time.
and insulator because the voltage rate of rise, and thus, the light- It is assumed that the channel propagation rate is a function
ning protection efficiency at direct lightning strokes depends of the voltage steepness (i.e., the voltage rate of rise) . Based
heavily on the grounding resistance (see Fig. 6). on (1), can be written as
With the INS130 insulators (see Fig. 6, Curve , INS130) the
number of lightning outages is lowered by a factor of five, the (A.2)
outage reduction factor being practically independent of whence
the grounding resistance. In this case, it is essential to coordi-
nate the arrester and the insulator on the lightning-struck phase
(A.3)
A. As indicated before, the coordination of arrester LFA is not
dependent on the grounding resistance because the pole does
Substituting (A3) into (A1), we obtain
not get involved in the path of the lightning current until the
insulator or the arrester have flashed over. It was shown by cal-
(A.4)
culation that a 1-m-long arrester LFA is coordinated with an
INS130 insulator at much lower values of the lightning current For illustration, (A4) is used to calculate the channel propaga-
steepness than with an INS160 unit. It was also shown that, after tion rate for arrester LFA-L with a flashover length cm,
the LFA arrester has successfully operated, the voltage rate of stressed by a standard 1.2/50 s, 100-kV lightning impulse. The
rise on phase B insulator and its arrester becomes low and this voltage steepness is kV/ s. For a positive
facilitates successful operation of the LFA arrester, at least, polarity impulse, and (see Table I)
over the 10 to 100- grounding resistance range.
It should also be remembered that even large lightning cur- cm s
rents do not present any hazard to these arresters because the
discharge develops in the air and not inside the device [2]. For a negative polarity impulse, and
Therefore, this new lightning protection system is thought to
feature simple design, low cost, and high reliability. cm c
ductors [11], showing that flashover channels are always longer Georgij V. Podporkin (SM’94) was born on August
and flashover voltages lower for negative lightning impulses. 26, 1950. He received the B.S., Ph.D., and Doctor of
Science degrees in electrical engineering from St. Pe-
tersburg Technical University, Russia, in 1973, 1977,
REFERENCES and 1990, respectively.
Currently, he is Managing Director of the
[1] G. V. Podporkin and A. D. Sivaev, “Electric power transmission line Streamer Electric Company, St. Petersburg, Russia,
with protection devices against lightning overvoltages,” US Patent no. and Part-Time Professor at the St. Petersburg
6,108,187, Date of Patent August 22, 2000, PCT Pub. no. WO 97/19456, Technical University. From 1973 until 1991, he
Russian Federation Application Priority Data Nov. 17, 1995. was a Research Scientist with the Extra High
[2] , “Lightning protection of overhead distribution lines by long Voltage Laboratory of the St. Petersburg Technical
flashover arresters,” IEEE Trans. Power Delivery, vol. 13, pp. 814–823, University. He was also a Scientific Consultant of CEPEL, Rio de Janeiro,
July 1998. Brazil, from 1992 to 1995. His fields of interest include lightning protection
[3] G. V. Podporkin, A. D. Sivaev, and V. E. Pilshikov, “Application of and insulation of overhead transmission and distribution lines.
long flashover arresters for lightning protection of overhead distribution
lines,” in Proc. 24th Int. Conf. Lightning Protection, Birmingham, U.K.,
Sept. 14–18, 1998, pp. 605–610.
[4] G. V. Podporkin, V. E. Pilshikov, and A. D. Sivaev, “Application of long
flashover arresters for improvement of lightning protection and oper- Vladimir E. Pilshikov was born on January 24,
ating voltage reliability of distribution lines,” in Proc. Elect. Dist. 15th 1950. He received the B.S. and Ph.D. degrees in
Int. Conf., Nice, France, June 1–4, 1998, Rep. 1p-9. electrical engineering from St. Petersburg Technical
[5] , “Semiconducting-core long flashover arresters for lightning University, Russia, in 1973 and 1979, respectively.
overvoltage protection of overhead distribution lines,” in Proc. 25th Int. Currently, he is a Research Scientist with the High
Conf. Lightning Protection, Sept. 18–20, 2000, Rep. 6.35, pp. 581–586. Voltage Department of St. Petersburg Technical Uni-
[6] Y. Morooka et al., “Line breakage prevention capitalizing on creeping versity in the field of internal and external insulation
discharge characteristics of insulated power wires,” in Proc. 10th Int. of high voltage apparatus.
Symp. High Voltage Eng., vol. 5, Aug. 1997, pp. 261–267.
[7] M. V. Kostenko et al., Lightning Discharge Physics and Lightning Pro-
tection of Overhead Power Transmission Lines (in Russian): Leningrad
Polytechnic Inst., 1982.
[8] P. L. Bellaschi, “Lightning and 60-cycle power tests on wood pole line
insulation,” Amer. Inst. Elect. Electron. Eng. Trans., vol. 66, pp. 838–50,
Alexander D. Sivaev was born on July 22, 1955. He
1947.
received the B.S. and Ph.D. degrees in electrical en-
[9] V. V. Burgsdorf, “Lightning protection of overhead transmission lines
gineering from St. Petersburg Technical University,
and operating experience in the U.S.S.R.,” in CIGRE, Paris, France,
Russia, in 1978 and 1999, respectively.
1958, Paper no. 326, p. 29.
Currently, he is Technical Director of the Streamer
[10] H. R. Armstrong, H. O Stoelting, and E. F. Veverka, “Impulse studies on
Electric Company, St. Petersburg, Russia. He was a
distribution line construction,” IEEE Trans. Power Apparat. Syst., vol.
Research Scientist at the Extra High Voltage Labora-
PAS-86, pp. 206–214, Feb. 1967.
tory of the St. Petersburg Technical University from
[11] T Yamashita et al., “Propagation characteristics of a surface discharge on
1981 to 1995 in the field of insulation and lightning
covered conductors and cylindrical dielectric materials,” in Proc. 10th
protection of overhead transmission lines.
Int. Symp. High Voltage Eng., Aug. 25–29, 1997.