25MVA 33/11.

5 kV Mobile Substation for Ifraz Water Project

Annex (A) Technical Compline Sheet

25MVA Mobile Substation

The following Technical data shall be furnished and filled by bidders for all items indicated in all
tables:

33 KV system
Description UNDP required Offered specification
specifications
Ambient temperature: +55/C
Maximum -10/C
Minimum
Relative Humidity : 92% maximum
Altitude: 1000M above MSL
System Voltage: 33/11KV
No of phase : 3PH
Frequency: 50Hz
Nominal Voltage : 33 K Volt
Highest system voltage : 36 K Volt
System : 3Ph , 3wire , 50Hz
Short circuit level: 31.5 KA r.m.s for 3 seconds
at 33000 voltage level
Minimum clearance in air 320 mm
between phase and earth:
Minimum clearance in air 320 mm
between different phases:
Minimum creep age distance 900 mm O/D, 720 mm indoor
of insulator and bushing:
Earthing system : Earthed through earthing TF

11 KV system
Description Offered specification
Ambient temperature:
Maximum +55/C
Minimum -10/C

Relative Humidity : 92% maximum


Altitude: 1000M above MSL
System Voltage: 33/11KV
No of phase : 3PH
Frequency: 50Hz
Nominal Voltage : 11KV
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

Highest system voltage : 12 KV


System: 3Ph. 3wire ,50Hz
Short circuit level : 31.5 r.m.s for 3 seconds at 11000
volts
Minimum clearance in air 150 mm
between phase and earth:
Minimum clearance in air 150 mm
between different phases:
Minimum creep age distance 300 mm O/D, 240 mm indoor
of insulator and bushing:
Earthing system: Earthed through earthing resistor

Axillary AC and DC system


Description UNDP required specifications Offered specification
Ambient temperature:
Maximum +55/C
Minimum -10/C
Relative Humidity : 92% maximum
Altitude: 1000M above MSL
System Voltage: 33/11KV
No of phase : 3PH
Frequency: 50Hz
AC : 416/240 3Ph , 4wire ,with neutral
solidly earthed
DC : 110- 2 wire

A-11 kV Medium Voltage Metal Clad Switchgear:

No Description UNDP required Offered specification


specifications
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens or
equivalent
3- Type : Air-insulated metal clad
type
4- Country of origin

5- Reference standard IEC 62271part 1, IEC


62271-100, IEC 62271-102,
IEC 62271-200 & 301, IEC
60529
6- Nominal Voltage : 11 KV
7- Rated current : 1600/630A
8- Rated frequency 50Hz
9-- Rated Short-circuit withstand current 31.5 kA for 1 seconds
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

Symmetrical
10- Rated insulation level
a) Impulse withstand voltage 75 KV
(peak)
b) One minute 50Hz withstand 28 KV
voltage (r.m.s.)
11- Insulation type of bus-bars Covered with Silicone
rubber tube
12- Degree of protection
a) Enclosure IP42
b) Partition IP40
13- Color and type of painting Light gray finish, Semi-
gloss, Melamine resin
14- Thermostat, Yes ,AC 240V

15- Heater Yes, AC 240 V

16- Ventilation Yes, with filter

17- Bus bars system Single bus bar

18- Submit Manufacturer certification :

19- Submit Detail drawings, brochures and catalogues:

20- Certificate or report of type tests:

A.1- 11 kV Disconnecting switches / Earthing Switch


No Description UNDP required Offered specification
specifications
1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider,


Siemens or equivalent
3- Type:
Disconnecting switch /Earthing Air-insulated, Vertical,
switches single throw, manual
operation type
4- Country of origin

5- Reference standard IEC 62271-102

6- Number of poles 3 poles for earthing


switches of feeders,
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

1pole for neutral


earthing of main
transformer
7- Location of service Indoor

8- Nominal Voltage : 11 KV

9- Rated insulation level 75KV


a) Impulse withstand voltage

b) One minute 50 Hz withstand 28KV


voltage (r.m.s.)

10- Space between open contacts


a) Impulse withstand voltage (peak 85 kV
b) One minutes withstand 50 Hz 32 kV
voltage (r.m.s.)
11- Rated current 400A for neutral
earthing DS and 630A
for feeders ES
12- Rated short circuit current at time 31.5 kA
duration of 3sec.for contacts
13- Minimum Creep age distance 240 mm

14- Minimum Clearance in air to earth 150 mm

15- Type of operating mechanism Manual

16- Type of interlocking mechanism


a) Interlocked with CB Electrical
b) Interlocked with earthing switch Mechanical with pad
lock
17- Rated supply voltage for
a) Interlocking mechanism DC 110 V
b) Thermostat AC 240 V

c) Heater AC 240 V

18- Number and type of spare auxiliary 5 NO / 5NC


Switches
19- Auxiliary switch
a) Continuous current carrying A
capacity
b) Breaking capacity at 110V DC A
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

20 Type of corrosion protection of steel Hot dipped


parts galvanized
21- Certificate or report of type tests

22- Submit Manufacturer certification :

23- Submit Detail drawings, brochures and catalogues:

24 Submit certification or report of type test

A.2,3, and 4-11 kV Circuit Breakers:


No Description UNDP required Offered specification
specifications
1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider,


Siemens or
equivalent
3- Type: Air-insulated,
motor charged
spring, triple pole
operation Vacuum
Circuit Breaker
4 Country of origin
5- Reference standard IEC 62271part 1,
IEC 62271-100,
IEC 62271-301,
IEC 60529
6- Number of poles 3

7- Class: indoor or outdoor Indoor

8- Nominal Voltage : 11 KV
9- Rated insulation level 75 KV
c) Impulse withstand voltage
d) One minute 50 Hz withstand voltage 28 KV
(r.m.s.)
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

10 Rated Frequency 50Hz

11 Rated normal current 1600/630A

12- 3 phase short circuit capacity 31.5 kA for 1


seconds
13- Rated Short-circuit breaking current 11-
a) Symmetrical- r.m.s 31.5 kA
b) Asymmetrical- peak kA
14- Short circuit making current kA
15- Cable charging breaking current 400A
16- Line charging breaking current 10 A
17- Small inductive breaking current 110 A
18- Rated operating times
1 Opening time ms

2 Breaking time ms

3 Closing time ms

19- Maximum total breaking time (from trip


initiation to arc extinction )
20- Number of operations without maintenance

1 At rated current

2 At 31.5 KA

21- Motor spring charge operating mechanism

1 Rated voltage closing coil/tripping coil

2 Rated voltage of motor

3 Number of tripping coils/power 1/ W


consumption
4 Number of closing coils/power consumption 1/ W

5 Spring charging time

6 Total number of auxiliary contracts (


NO+NC)
7 Total number of spare contacts ( NO + NC) 5 +5

8 Rated supply voltage for


a)Closing coil DC 110 V
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

b) Shunt opening release DC 110 V

c) Motor DC 110 V

d) Thermostat AC 240 V

e) Heater AC 240 V

22- Manual spring discharge facility Yes

23 Interlocking facility complying with the Yes


requirement of the specification
24- Type of power device
a) For closing Motor-spring
b) For opening Spring
25 Hand charging facility Yes

26- Auxiliary switch


a) Continuous current carrying capacity A
b) Breaking capacity at 110V DC A
27- Number and type of spare auxiliary Switches 5NO / 5 NC
28- Guaranteed number of operations with no 10000
load before being necessary to inspect the
circuit breaker poles & operating device
29- Type of corrosion protection of steel parts Zinc hot dip
galvanized and
painting
30- Overall dimensions(length/width/ height) mm
31- Total weight of circuit breaker kg
32- Certificate or report of type test
33- Submit Manufacturer certification :
34- Submit Detail drawings, brochures and
catalogues:
35- Submit certification or report of type test

A.2- 11 kV incoming feeder Current Transformers:


No. Description UNDP required Offered specification
specifications
1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider, Siemens


or equivalent
3- Type Molded and bushing type
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

4- Country of origin

5- Reference standard IEC 60044-1

6- Nominal Voltage : 11 kV

7- Rated primary current


Incomer 1600

8- Rated secondary currents 5 A/5A/1A

9- Rated short circuit current 31.5 kA for 3 seconds

10- Rated dynamic current

11- Rated insulation level


a) Impulse voltage withstand 75 kV
voltage(peak)
b) One minute 50Hz withstand voltage 28 KV
r.m.s.)
12- Characteristics of Current Transformer

12-1 Measuring winding 1 5A


a) Accuracy class 1
b) Rated output 15VA
c)Instrument security factor 5
12-2 First protection secondary core- OC&
EF 5A
a) Accuracy class 5P
b) Accuracy limit factor 10
c) Rated output 15 VA
12-3 Second protection secondary core –
Differential protection 1A
a) Accuracy class 5P
b) Accuracy limit factor 20
c) Rated output 15 VA
13- Neutral Current Transformer
Protection winding( on neutral point of
main transformer )
a) Ratio 300-150/5A
b) Accuracy class 5P
c) Accuracy limit factor 10
d) Rated output 15 VA
14- Submit Manufacturer certification :

15- Submit Single line diagram :


25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

16- Submit Detail drawings, brochures


and catalogues:
17- Submit certification or report of type
tests

A.3- 11 kV Outgoing Feeder Current Transformers:


No. Description UNDP required Offered specification
specifications
1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider, Siemens


or equivalent
3- Type Molded and bushing type

4- Country of origin

5- Reference standard IEC 60044-1

6- Nominal Voltage : 11 kV

7- Rated primary current


600-300A

8- Rated secondary current 5 A/5A

9- Rated short circuit withstand current 31.5 kA for 1 seconds

10- Rated dynamic current KA

11- Rated insulation level


a) Impulse voltage withstand 75 kV
voltage(peak)
b) One minute 50Hz withstand voltage 28 KV
r.m.s.)
12- Characteristics of Current Transformer

12-1 Line Current Transformer for incomer


1) Measuring winding
a) Accuracy class 1
b) Rated output 15VA
c) Instrument security factor 5

2) Protection winding-
a) Accuracy class 5P
b) Rated output 15 VA
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

c) Accuracy limit factor 10

13- Submit Manufacturer certification :

14- Submit Single line diagram :

15- Submit Detail drawings, brochures


and catalogues:
16 Submit certification or report of type
tests

A.2.3- 11 kV Voltage Transformers

No. Description UNDP required Offered specification


specifications
1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider, Siemens


or equivalent
3- Type Molded type with residual
winding
4- Country of origin

5- Reference standard IEC 60044-2

6- Rated primary voltage 11 kV /√3

7- Rated Secondary voltage 110V/ √3, 110V/ √3

8- Nominal Voltage : 11 kV

9- Frequency 50 Hz

10- Over voltage factor 1.9 for 8hour

11- Short circuit withstand capacity for 3 31.5 KA r.m.s


seconds
12- Rated insulation level
a) Impulse voltage withstand 75kV
voltage(peak) 28KV
b) One minute 50Hz withstand voltage
r.m.s.)
13 Accuracy class 1.0/3P
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

14- Rated output 200VA

15- Submit Manufacturer certification :

16- Submit Single line diagram :

17- Submit Detail drawings, brochures


and catalogues:
18- Submit certification or report of type
tests

A.14- 7.2 kV Lightning Arrester:

No Description Main transformer neutral


UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider,
Siemens or equivalent
3- Type: Metal oxide
Gapless
4- Country of origin

5- Reference standard IEC 60099-4, IEC


60099-5, IEC 62271-part
1
6- Rated Voltage : 7.2 KV

7- Rated frequency 50 Hz

8- Material of arrester element Zinc oxide

9- Normal discharge current (crest) 10 kA

10- Long duration discharge class Class 2

11- Pressure relief current (r.m.s.)

12- Energy absorption

13- Rated insulation level


a) Impulse withstand voltage (peak) 60 kV

b) One minute 50Hz withstand 20 kV


voltage (r.m.s.)
14- Material of insulator Porcelain
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

15- Color of insulator Brown

16- Submit Manufacturer certification :

17 Submit Detail drawings, brochures and catalogues:

18 Submit certification or report of type tests

A.9-Battery

No Description UNDP required Offered specification


specifications
1- Make/Brand/Model:

2- Name of manufacturer

3- Type of Battery panel Air-insulated metal


enclosed type
4- Country of origin

5- Reference standard IEC 60623

6- Location of service : Indoor

7-- Type of battery Ni-Cd Alkaline type

8- Rated capacity for 5 hours 80 AH

9-- Nominal discharge current for 5 hours 12 A

10- Rated voltage of battery 110.4 V

11- Nominal voltage of battery cell 1.2 V/cell

12- Number of cells 92

13- Final discharge-end voltage 1.0 V/cell


25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

14- Type of mounting rack Steel painted with


. alkaline resistant paint
15- Submit Manufacturer certification :

16- Certificate or report of type tests

17- Submit Detail drawings, brochures and catalogues:

A.9- Battery Charger

No Description UNDP required Offered specification


specifications
1- Make/Brand/Model:

2- Name of manufacturer

3- Type of Battery panel Air-insulated metal


enclosed type
4- Country of origin

5- Reference standard IEC 60146-1

6- Location of service : Indoor

7- Type of battery charger Full automatic constant


voltage DC power
source
8- AC input voltage 240V

9-- Number of phase of AC input 3

10- Type of cooling for rectifier Self-air-cooled by


metallic fins
11- a) Charge voltage range 118-156.5V
b) Float voltage (adjustable) 118-132
c)Boost voltage 133 – 156.5
12- Regulated voltage range on DC bus bar 110+- 10%

13- Continuous output current of battery


charger 40 A current rating

14- Die-electric strength (50Hz for one


minute)
a) Between AC phases and earth 2000 V
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

b) Between AC and DC circuit 2000 V


15- Setting range of DC under-voltage relay 85-95 V

16- RMS ripple voltage on d c side < 1% of mean DC


voltage
17- Setting current range of DC earth fault Not less than 10 mA
relay
18- Degree of protection IP 51
19- Submit Manufacturer certification :
20- Certificate or report of type tests:
21- Submit Detail drawings, brochures and catalogues:

A.13-Meters for 33 Incoming, 11 kV Incoming and 11 kV Feeders:

No Description UNDP required specifications Offered specification


1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider, Siemens or


equivalent
3- Type : Digital type with LCD monitor

4- Country of origin

5- Reference standard As per IEC standards


6- Kind of measurement 1) AC Current
2) AC Voltage
3) Active power with Max.
demand indicator
4) Reactive power
5) Energy value
6) Frequency
7) Power factor
7-- Rated Current : 5A

8- Rated AC input voltage 110V/ √3

9-- Input consumption


a) Current circuit
b) Voltage circuit
10- Accuracy class Class 1.0 for all measurement

11- Number of AC input


a) Current 3 (R,Y,B, N)
b) Voltage 3 (R,Y, B, N)
12- Display of measurement Simultaneous display
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

13- Change-over of display of phase


quantity
a) AC Current Push button
b) AC voltage Push button
14- Display updating time 1.0 sec.

15- Overload capacity


a) Current circuit 40 times rated current for 1
sec.,1.2 times for continuous
operation
b) Voltage circuit 2 times rated voltage for10 sec.,
1.2 times for continuous
operation
16- Auxiliary power supply DC110V

17- Auxiliary power consumption

18- Submit Manufacturer certification :

19- Submit Detail drawings, brochures and catalogues:

20- Certificate or report of type test

A.12-Transformer Main Protection and Control Relay (On Load Tap Changer)

No Description UNDP required specifications Offered specification


1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens or
equivalent
3- Type : Numerical & multiple relay
function
4- Country of origin
5- Reference standard As per IEC standards

6- Rated AC input current 1A

7-- Rated AC input voltage 110V/ √3

8- Auxiliary power supply DC110 V

9-- Auxiliary power consumption W

10- Mounting Flush mounting


25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

11- Degree of protection IP52


12- Operating temperature range
for a single 6 hour duration -10_C to +65_C
within any 24hour period
13-1 Differential Protection
a) Type of compensation for Software
ratio and vector difference
between primary and
secondary side
b) Base differential setting
range (Idif.)
c) 2nd harmonics inrush
restraint setting range
d) Non restraint differential
setting range
e) Operating time, restrained
setting range
f) Reset time, restrained
setting range
g) Operating time,
unrestrained setting range
h) Reset time, unrestrained
setting range
13-2 TF L.V. Neutral Earth Fault
Relay
a) Current setting range
(IDMTL)
b)Current setting range
(Instantaneous)
c) Time-current characteristics

13-3 TF L.V. Earth Fault Over


Voltage Relay
a) Over voltage setting range
(IDMTL)
b) Over voltage setting range
(Instantaneous)
c) Time-current characteristics

13-4 Trip circuit supervision


(TCS)
a) Quantity
b) Alarm delay time setting ms
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

14- Auxiliary relay or signal


output
a).Rated voltage of contacts

b) Rated current of contacts


- Continuous
- Make and carry for 3 sec.
15- Submit Manufacturer certification :

16- Submit Single line diagram :

17- Submit Detail drawings, brochures and catalogues:

18- Certificate or report of type tests:

A.11-Transformer Backup & Control Relay

No Description UNDP required specifications Offered specification


1- Make/Brand/Model:

2- Name of manufacturer ABB, Schneider, Siemens or


equivalent

3- Type : Numerical & multiple relay


function
4- Country of origin

5- Reference standard As per IEC standards

6- Rated AC input current 5A

7-- Rated AC input voltage 110V/ √3

8- Auxiliary power supply DC110 V

9-- Auxiliary power consumption W

10- Mounting Flush mounting

11- Degree of protection IP52

12- Operating temperature range


for a single 6 hour duration -10_C to +65_C
within any 24hour period
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

13-1 TF 33kV. Overcurrent relay


a) Current setting range
(IDMTL)
b) Current setting range
(Instantaneous)
c) Time-current characteristics

13-2 TF 11 kV Overcurrent relay


a) Current setting range
(IDMTL)
b) Current setting range
(Instantaneous)
c) Time-current characteristics

13-3 TF 33 kV Earth fault relay


a) Current setting range
(IDMTL)
b) Current setting range
(Instantaneous)
c) Time-current characteristics

13.4 TF 11 kV Earth fault relay


a) Current setting range
(IDMTL)
b) Current setting range
(Instantaneous)
c) Time-current characteristics

14- Submit Manufacturer certification :

15- Submit Single line diagram :

16- Submit Detail drawings, brochures and catalogues:

17- Certificate or report of type tests:

A.11-11 kV Feeder Protection Relay:

No Description UNDP required Offered specification


specifications
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens
or equivalent
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

3- Type : Numerical & multiple relay


function
4- Country of origin
5- Reference standard As per IEC standards
6- Rated AC input current 5A
7-- Rated AC input voltage 110V/ √3
8- Auxiliary power supply DC110 V
9-- Auxiliary power consumption W
10 Mounting Flush mounting
11- Degree of protection IP52
12- Operating temperature range for a
single 6 hour duration within any
24hour period -10_C to +65_C
13 Protection Relays:
13-1 Over current relay
a) Current setting range (IDMTL)
b) Current setting range
(Instantaneous)
c) Time-current characteristics
13-2 Earth fault relay
a) Current setting range(IDMTL)
b) Current setting range
(Instantaneous)
c) Time-current characteristics
14- Auxiliary relay or signal output
Rated voltage of contacts
15- Submit Manufacturer certification :
16- Submit Single line diagram :

17- Submit Detail drawings, brochures and catalogues:

18- Certificate or report of type test

A.5 -33 kV Power Cables for Incoming and transformer connection

No Description 36KV incoming


UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer
3- Type : CU/XLPE/PVC -
transformer connection
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

CU/EPR/PVC – incoming
feeder
4- Country of origin
5- Reference standard IEC 60502, IEC 60183, IEC
60228, IEC 60287, , IEC
60287, IEC 60811, IEC
60853,
6- Nominal Voltage : 18/30 (36) kV
7- Construction data
1) Number of conductor 1 Core
2) Cross sectional area (Phase) 150 mm2
3) Shape of conductor Circular stranded
compacted
4) Material of conductor Copper
6) Material of conductor shielding Semi conductive Compound
7) Thickness of conductor shielding
(Approx.)
8) Material of insulation XLPE/EPR
9) Thickness of insulation
(Nominal)
10) Material of insulation shielding

11) Thickness (Approx.)


12) Material of metallic screen
13) Thickness of metallic screen
(Approx.)
14) Material of sheath PVC
15) Thickness of sheath (Nominal)
16) Material of armor N.A
17) Color of sheath Black
18) Overall diameter of cable
(Approx.)
19) Marking of cable
20) Net weight (Approx.) (kg/km) To be filled in
8- `Electrical data:
1) AC. withstand voltage for 5 63 kV
minutes
2) Impulse withstand voltage 170KV
3) Max. DC. conductor resistance at 0.124 ohm/km
20_C
4) Max. Temperature rating of 90 _C
conductor
5) Rated Frequency 50 Hz
6) Max. Partial discharge at 31.2kV 5 pC
9 Submit Manufacturer certification :
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

10- Certificate or report of type test


11- Submit Detail drawings, brochures and catalogues:

A.5-11 kV Power Cables for Transformer Connection

No Description 11KV
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer

3- Type : CU/XLPE/PVC –
4- Country of origin
5- Reference standard IEC 60502, IEC 60183, IEC
60228, IEC 60287, , IEC
60287, IEC 60811, IEC
60853,
6- Nominal Voltage : 11 kV
7- Construction data
1) Number of conductor 1 Core
2) Cross sectional area 2 x 400 mm2 / phase
3) Shape of conductor Circular stranded
compacted
4) Material of conductor Copper
5) Number of wires
6) Material of conductor shielding Semi conductive Compound
7) Thickness of conductor shielding
(Approx.)
8) Material of insulation XLPE
9) Thickness of insulation
(Nominal)
10) Material of insulation shielding

11) Thickness (Approx.)


12) Material of metallic screen
13) Thickness of metallic screen
(Approx.)
14) Material of sheath PVC
15) Thickness of sheath (Nominal)
16) Material of armor NA
17) Color of sheath Black
18) Overall diameter of cable
(Approx.)
19) Marking of cable
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

20) Net weight (Approx.) (kg/km)


8- `Electrical data:
1) AC. withstand voltage for 5 42 kV
minutes
2) Impulse withstand voltage 75KV
3) Max. DC. conductor resistance at 0.0470 ohm/km
20_C
4) Max. Temperature rating of 90 _C
conductor
6) Rated Frequency 50 Hz
7) Max. Partial discharge at 10.4 kV 5 pC
9- Submit Manufacturer certification :
10- Submit Detail drawings, brochures and catalogues:
11- Certificate or report of type test

A.5 -11 kV Power Cables for Outgoing Feeders

No Description 11KV
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer

3- Type : CU/ EPR /PVC - for


outgoing feeders
4- Country of origin
5- Reference standard IEC 60502, IEC 60183, IEC
60228, IEC 60287, , IEC
60287, IEC 60811, IEC
60853,
6- Nominal Voltage : 11 kV
7- Construction data
1) Number of conductor 1 Core
2) Cross sectional area (Phase) 150
3) Shape of conductor Circular stranded
compacted
4) Material of conductor Copper
5) Number of wires
6) Material of conductor shielding Semi conductive Compound
7) Thickness of conductor shielding
(Approx.)
8) Material of insulation EPR
9) Thickness of insulation
(Nominal)
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

10) Material of insulation shielding

11) Thickness (Approx.)


12) Material of metallic screen
13) Thickness of metallic screen
(Approx.)
14) Material of sheath PVC
15) Thickness of sheath (Nominal)
16) Material of armor NA
17) Color of sheath Black
18) Overall diameter of cable
(Approx.)
19) Marking of cable
20) Net weight (Approx.) (kg/km)
8- `Electrical data:
1) AC. withstand voltage for 5 42 kV
minutes
2) Impulse withstand voltage 75KV
3) Max. DC. conductor resistance at 0.124 ohm/km
20_C
4) Max. Temperature rating of 90 _C
conductor
6) Rated Frequency 50 Hz
7) Max. Partial discharge at 10.4 kV 5 pC
9- Submit Manufacturer certification :
10- Submit Detail drawings, brochures and catalogues:
11- Certificate or report of type test

A.6- Low Voltage Power Cables

No Description
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer

3- Type : CU/XLPE/PVC With armor


4- Country of origin
5- Reference standard IEC 60502, IEC 60228, IEC
60227, IEC 60287, , IEC
60287, IEC 60724, IEC
60811, IEC 60853, IEC
60885
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

6 Location Of service Outdoor


7- Nominal Voltage : 1000 V
8- Type of insulation XLPE
9- Number of conductor 4 Core
10- Type of sheath materials PVC
11- Cable size
12- Conductor:
a) Materials
b) Strands
c) Outer diameter (Approx.)
13- Thickness of insulation (Nominal)
14- Thickness of sheath (Nominal)
15- Overall diameter (Approx. )
16- Conductor resistance at 20_C
(Maximum)
17- Insulation resistance (Minimum)
18- AC. withstand voltage
19- Submit Manufacturer certification :
20- Submit Detail drawings, brochures and catalogues:
21- Certificate or report of type test

A.6- Plug in Type Connectors for Control Cables


No Description
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer

3- Type : Plug in with water proof &


dust proof type
4- Country of origin
5- Reference standard
6 Location Of service Outdoor
7- Applicable temperature
a) Minimum temperature -10 °C
b) Maximum temperature +85 °C
8- Number of pins
9- Type of contact Crimp pin & crimp socket
contact
10- Applicable wire size
11- Rated voltage AC 1000 V
12- Rated current (Max.)
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

13- Submit Manufacturer certification :


14- Submit Detail drawings, brochures and catalogues:
15- Certificate or report of type test

B-4,5-33 kV Medium Voltage Switchgear:

No Description UNDP required specifications Offered specification


1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens or
equivalent
3- Type: Air-insulated metal clad
type
4- Country of origin

5- Reference standard IEC 62271part 1, IEC 62271-100,


IEC 62271-102, IEC 62271-200 &
301, IEC 60529
6- Nominal Voltage : 33 KV
7- Rated normal current : 1250 A
8- Rated frequency 50Hz
9 Rated Short-circuit withstand
current 31.5 kA for 1 seconds
Symmetrical
10- Rated insulation level on the
assembly
a) Impulse withstand 170KV
voltage (peak)
b) One minute 50Hz 70KV
withstand
voltage (r.m.s.)
11- Insulation type of bus bars Covered with Silicone
rubber tube
12- Degree of protection
a) Enclosure IP42
b) Partition IP40
13 Color and type of painting Light gray finish, Semi-gloss,
Melamine resin
14- Thermostat, Yes ,AC 240V
15- Heater Yes, AC 240 V
16- Ventilation Yes, with filter
17- Bus bars system Single bus bar
18- Submit Manufacturer certification :
19- Submit Detail drawings, brochures and catalogues:
20- Certificate or report of type tests:
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

B.2--33 kV Disconnecting Switch and Earthing Switch


No Description UNDP required specifications Offered specification
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens or
equivalent
3- Type:
a) Disconnecting switch Air-insulated, Vertical, single
b) Earthing switch throw, manual
operation type

4- Country of origin
5- Reference standard IEC 62271part 1, IEC 62271-102,
6- Number of poles 3
7- Location of service Indoor
8- Nominal Voltage : 33 KV
9- Rated insulation levels
a) Impulse withstand voltage 170KV

b) One minute 50 Hz 70KV


withstand voltage (r.m.s.)

10- Space between open contacts


a) Impulse withstand voltage 195 kV
(peak)
b) One minutes withstand 50 Hz 80 kV
voltage (r.m.s.)
11- Rated current 1250A
12- Rated short circuit current for a 31.5 kA
time duration of 3sec.for main
contacts and earthing switch
13- Minimum Clearance in air to earth 320 mm

14- Type of operating mechanism Manual


15- Type of interlocking mechanism
a) Interlocked with CB Electrical
b) Interlocked with earthing Mechanical with pad lock
switch
16- Rated supply voltage for
a) Interlocking mechanism DC 110 V
b) Thermostat AC 240 V
c) Heater AC 240 V
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

17 Number and type of spare 5 NO / 5NC


auxiliary Switches
18 Auxiliary switch
a) Continuous current carrying A
capacity A
b) Breaking capacity at 110V DC
19 Type of corrosion protection of Hot dipped
steel parts galvanized
20- Certificate or report of type test
21 Submit Manufacturer certification :
22- Submit Detail drawings, brochures and catalogues:
23 Submit certification or report of type tests:

B.4, and B.5 -33 kV Circuit Breakers:


No Description UNDP required specifications Offered specification
1- Make/Brand/Model:
Name of manufacturer ABB, Schneider, Siemens or
equivalent
2- Type: Air-insulated,
motor charged
spring, triple pole
operation Vacuum
Circuit Breaker
3 Country of origin
4 Reference standard IEC 62271part 1, IEC 62271-100,
IEC 62271-301, IEC 60529
5- Number of poles 3
6- Class: indoor or outdoor Indoor
7- Nominal Voltage : 33 KV
8- Rated insulation level
a) Impulse withstand voltage 170 KV
b) One minute 50 Hz 70 KV
withstand voltage (r.m.s.)
9- Rated Frequency 50Hz
10- Rated current 1250A
11 3 phase short circuit capacity 31.5 kA for 1 seconds
12 3 phase short circuit breaking
capabilities
1 Rated Short-circuit breaking 11-
current 31.5 kA
a) Symmetrical- rms kA
b) Asymmetrical- peak
2 Short circuit making current kA
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

3
Cable charging breaking current 400A
4
Line charging breaking current 10 A
5
Small inductive breaking current 110 A
13 Rated operating times
1 Opening time ms

2 Breaking time ms

3 Closing time ms

14 Maximum total breaking time ms


(from trip initiation to arc
extinction )
15 Number of operations without
maintenance
1 At rated current

2 At 31.5 KA

16 Motor spring charge operating


mechanism
1 Rated voltage of closing V
coil/tripping coil
2 Rated voltage of motor V

3 Number of tripping coils/power 1/ W


consumption
4 Number of closing coils/power 1/ W
consumption
5 Spring charging time s

6 Total number of auxiliary


contracts ( NO+NC)
7 Total number of spare contacts ( 4 +4
NO + NC)
8 Rated supply voltage for
c) Closing coil DC 110 V
b) Shunt opening release DC 110 V

c) Motor DC 110 V

d) Thermostat AC 240 V

e) Heater AC 240 V
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

17 Overall dimensions(length/width/ mm
height)
18 Total weight of circuit breaker kg

19 Manual spring discharge facility Yes

20 Interlocking facility complying Yes


with the requirement of the
specification
21 Type of power device
a) For closing Motor-spring
b) For opening Spring
22 Hand charging facility Yes

23 Type of operating mechanism 3 pole

24- Partial discharge test voltage As per IEC

25- Auxiliary switch


a) Continuous current carrying A
capacity
b) Breaking capacity at 110V DC A
26 Number and type of spare 5NO / 5 NC
auxiliary Switches
27 Guaranteed number of operations 10000
with no load before being
necessary to inspect the circuit
breaker poles & operating device
28 Type of corrosion protection of Zinc hot dip galvanized and
steel parts painting
29- Certificate or report of type test
30- Submit Manufacturer
certification :
31- Submit Detail drawing brochure
catalogue:
32- Submit certification or report of
type tests:

B.4, and B5- 33 kV Current Transformers:

No. Description UNDP required specifications Offered specification


1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens or
equivalent
3- Type Molded and bushing type
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

4- Country of origin
5- Reference standard IEC 60044-1
6- Nominal Voltage : 33 kV
7- Rated primary current 600 A
Incomer
8- Rated secondary current 5 A,5A,1A
9 Rated short circuit current 31.5 kA – 3 seconds
10- Rated dynamic current KA
11- Rated insulation level
a) Impulse withstand 170kV
voltage(peak) 70KV
b) One minute 50Hz withstand
voltage r.m.s.)
12- Characteristics of Current
Transformer
12-1 Measuring winding 5A
a) Accuracy class 1
b) Rated output 15VA
c)Instrument security factor 5
12-2 First protection secondary core- 5A
OC & EF 5P
a) Accuracy class 10
b) Accuracy limit factor 15 VA
c) Rated output
12-3 Second protection secondary core
– 1A
Differential 5P
a) Accuracy class 20
b) Accuracy limit factor 15 VA
c) Rated output
13- Submit Manufacturer
certification :
14- Submit Single line diagram :
15- Submit Detail drawings,
brochures and catalogues:
16- Submit certification or report
of type tests:

B.4, and B.5- 33 kV Voltage Transformers

No. Description UNDP required Offered specification


specifications
1- Make/Brand/Model:
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

2 Name of manufacturer ABB, Schneider, Siemens or


equivalent
3- Type Molded type with residual
winding
4- Country of origin
5- Reference standard IEC 60044-2
6- Nominal Voltage : 33 kV /√3
7- Rated Secondary voltage 110V/ √3
8- Frequency 50 Hz
9- Highest system voltage 36 kV
10- Short circuit withstand capacity 31.5 KA r.m.s
for 3 seconds
11 Over voltage factor 1.9 for 8 hour
12- Rated insulation level
a) Impulse withstand 170kV
voltage(peak) 70KV
b) One minute 50Hz withstand
voltage r.m.s.)
13- Accuracy class 1.0
14- Rated output 200VA

15- Submit Manufacturer


certification :
16- Submit Single line diagram :
17- Submit Detail drawings,
brochures and catalogues:
18- Submit certification or report
of type tests:

B.1-25 MVA 33/11.5 kV Main Transformer


No Description UNDP required Offered specification
specifications
1- Make/Brand/Model:
2 Name of manufacturer ABB, Schneider, Siemens or
equivalent
3- Type: Core , double wound, three
phase, box type, oil immersed

4 Country of origin
5 Reference standard IEC 60076-1, 2,3,5,8,
IEC 60214
6- Number of poles 3
7- Class: indoor or outdoor Outdoor
8 Type of cooling ONAF
9 Earthing of neutral point of LV Through resistor
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

10- Rated voltage Ratio 33/11.5 KV


11- Rated power at maximum 25MVA
temperature
12- Rated Frequency 50Hz
13-1 Short circuit capacity ….KA
13-2 Duration of short circuit …..S
14- Nominal Voltage of winding
a) H.V. 33 kV
b) L.V. 11.5 kV
15-1 Insulation level: Impulse
withstand voltage f 170KV
a) H.V
b) LV 75 KV
c) LV neutral 75 KV
15-2 Insulation level: One minute 50
Hz withstand voltage
a) H.V. 70KV
b) L.V 28KV
c) L.V neutral 28KV
16- Winding connection
a) H.V. Delta
b) L.V Star (neutral brought out)
17- Vector group symbol Dyn 11
18- Maximum design outdoor 55_C
temperature
19- Winding temperature rise at rated 50 _C
power
20- Top oil temperature rise at rated 45-C
power
21 Maximum temperature of C
windings after short circuits
22 Voltage regulation at 75 Deg,
rated power and ratio
1) Unity power factor
2) 0.8 lagging power factor

23- Maximum flux density in iron at


rated Tesla
frequency and rated voltage ratio
at nominal voltage
24- Magnetizing current at nominal A
ratio for nominal voltage
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

25- Guaranteed Losses


a) No load loss at rated voltage kW
and frequency at nominal tap
b) Load loss at rated power and kW
75 _C at nominal tap
26- Type neutral current transformer
27- Impedance voltage at rated power
for H.V. -L.V. winding 7-10% at 75 deg and nominal
tap
28 Core sheath material
29 No load current at nominal
voltage
30 Windings
1- Type of winding
a) H.V.
b) L.V.
2- Cross section area of winding
a) H.V.
b) L.V.
3- Maximum current density in
windings at rated power
a) H.V. winding
b) L.V. winding
4 Type of insulation of winding
a) H.V.
b) L.V.
31- Type of insulation of
a) Tapping
b) Tapping connections
c) Core assembly
d) Core laminations
32 Tap changer
1 Type of tap changer MR
2 Number of taps 7.5% to - 10% kV
in equal 13-17 taps, 1.25%
step
3 Rated current of tap changer at
nominal tap and at 55 deg
4 Rated power of motor 416 V AC
5 Rated voltage of motor
6 Impulse withstand voltage
7 Power frequency withstand
voltage
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

33- Noise level at 3 meter, rated


voltage, rated frequency and no-
load
34 Transformer valves and tanks
Thickness of transformer tank
a) Sides 9 mm
b) Bottom 12 mm
c).Top cover 9 mm
d) Materials used for gaskets for
oil tight joints , radiators and
valves
e) Types of valves and materials
1)Valves
2) Oil and gas sampling
devices
f) Maximum operating pressure of
tank Pa
1. Top of tank Pa
2. Bottom of tank
g) Design hydraulic pressure
1. Top of tank Pa
2. Bottom of tank Pa
3. conservators Pa
35 Protection and indication
equipment
1 Buchloz relay

1-1 Name of manufacturer

1-2 Make/Brand/Model:
1-3 Rated voltage
2 OLTC protective relay
2-1 Name of manufacturer

2-2 Make/Brand/Model:
2-3 Rated voltage
3 Pressure relief device
3-1 Name of manufacturer

3-2 Make/Brand/Model: Main tank


25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

3-3 Make/Brand/Model: OLTC


3-4 Operational pressure for main Pa
/OL
TC tanks
4 Temperature indicating, control
and alarm devices
4-1 Name of manufacturers

4-2 Make/Brand/Model:
4-3 Adjustable range of tripping deg. C
contracts-winding
4-4 Adjustable range of alarm and deg. C
control contacts -oil
5 Breathers

5-1 Name of manufacturer

5-2 Make/Brand/Model:
36 33 kV bushings
1 Name of manufacturer

2 Make/Brand/Model:
3 Reference standard IEC 60137
4 Type of bushing
5 Rated current A
6 Rated voltage KV
7 Material Porcelain
8 Color Brown
9 Creepage distance mm
37 11 kV bushings
1 Name of manufacturer

2 Make/Brand/Model:
3 Type of bushing
4 Rated current A
5 Rated voltage KV
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

6 Material Porcelain
7 Color Brown
8 Creepage distance mm
38 Weight and dimensions
1 Weight of core and windings kg
2 Weight of oil kg
3 Weight of tank, conservator and kg
OLTC
4 Total weight of complete kg
transformer ready for service
5 Dimensions of transformer

Length mm
Width mm
Height mm
6 Type of corrosion protection on
steel parts Oil resistance paint
a) Inside tank
b) Outside tank Primary coat, Alkyd resin
paint and aluminum metallic
paint
39 Transformer oil
1 Type of oil IEC60296 class 1
Shell Diala B
2 Manufacturer
3 Place of manufacture
4 Manufacturer's type designation
5 Applied IEC standard IEC 60296
6 Kinematic viscosity mm2/s
At 40 deg ≤ 16.5
At -15 deg ≤ 800
7 Flash point ≥ 140 C
8 Pour point ≤ - 30 C
9 Density at 20 deg C – kg/dm3 ≤ 0.895
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

40- Certificate or report of type


tests:
41- Submit Manufacturer
certification :
42- Submit Detail drawings,
brochures and catalogues:

B.3 -100 kVA 33/0.416 kV Auxiliary and Earthling Transformer:


No Description UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider, Siemens
or equivalent
3- Type: Oil-immersed hermetically
sealed

4- Country of origin
5- Reference standard IEC 60076-1, 2,3,5,8,
IEC 60214
6- Number of poles 3
7- Class: indoor or outdoor Outdoor
8- Voltage Ratio 11/0.416 KV
9- Rated power
- Continuous 100 kVA Dyn11
10- Rated Frequency 50Hz
11- Nominal Voltage of winding
a) H.V. 33 kV
b) L.V 0.416 kV
12- Insulation level
a) Lightning Impulse 75 kV

b) AC power frequency 28 kV

13- Short circuit withstand capacity …..KA for


…….seconds
14- Winding temperature rise at rated power 50 C

15- Top oil temperature rise at rated power 45 C

16- Maximum flux density in iron at rated


Frequency and at rated voltage ratio
at normal voltage
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

17- Maximum current density in windings at


rated
power
a) H.V. winding
b) L.V. winding
18- Zero sequence impedance
19- No load current at rated voltage
20- Impedance voltage at continuous rated
power
21- Type of winding
a) H.V.
b) L.V.
22- Type of insulation of winding
a) H.V.
b) L.V.
23- Type of insulation of
a) core assembly
b) Core laminations
24- Thickness of transformer tank
a) sides 5 mm
b) bottom 5 mm
25- Thickness of radiator plates and for mm
cooling tube
26 Winding connection
a) H.V. Delta

b) L.V. Star (Neutral brought out)

27- Vector group symbol Dyn11

28- Test pressure of oil leak test of tank

29- Type of core

30- Type of oil IEC60296 class 1


Shell Diala B
31- Core sheet materials

32- Type of corrosion protection on steel parts


a) Inside tank Oil resistant paint
Primary coat, Alkyd resin
b) Outside tank paint and aluminum metallic
paint
33- Submit Manufacturer certification :
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

34- Submit certification or report of type


tests:
35- Submit Detail drawings, brochures and
catalogues:

B.6 30 kV Lightning Arrester

No Description 30 KV
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider,
Siemens or equivalent
3- Type : Metal oxide
gapless
4- Country of origin

5- Reference standard IEC 60099-4, IEC


60099-5, IEC 62271-part
1
6- Rated Voltage : 30 KV
7- Rated frequency 50 Hz
8- Material of arrester element Zinc oxide
9- Normal discharge current (crest) 10 kA
10- Long duration discharge class Class 2
11- Pressure relief current (r.m.s.)
12 Energy absorption
13- Rated insulation level
a) Impulse withstand voltage (peak) 75 kV

b) One minute 50Hz withstand 28 kV


voltage (r.m.s.)
14- Type of corrosion protection of Hot-dipped
steel parts galvanized
15 Material of insulator Porcelain
16- Submit Manufacturer certification :
17- Submit Detail drawings, brochures and catalogues:
18- Submit certification or report of type tests
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

Trailer:
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer According to Iraq standard
3- Type : Drop-bed semi-trailer
4- Country of origin
5- Number of Semi-trailer per substation 2 numbers
Reference standard
6- Principal dimension and weight
a) Overall length H.V trailer 16.5m
M.V trailer 12.5m
b) Overall width
3m
c) Overall height (unladed) 1050 mm
d) Floor height 1050 mm
e) Trailer weight (without load ) H.V trailer 9 tons
M.V trailer 10 tons
g) Maximum load 25 to 38tons
h) Gross vehicle weight 35 to 47 tons
b) Laden
- King pin (front axle) kg
- Rear axle kg
7- Construction Frame type

8- Size and quantity of Tire & wheel


a) Tire H.V =14Tirs
M.V =10Tiers
b) Front axle H.V =3
- M.V= 2
- Fear axle
b) wheel
- Front axle
- Rear axle
9- Type of parking brake Air compress air

10- Number of landing gear H.V =3


M.V= 5
11- Type of landing gears Left and right combined
operation, high and low
speed range, manual
operation with square pads
12- Type of vehicle coupling device SAE 3.5 inches
(king pin)
13- Electric system
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project

a) Voltage 24 V
b) Receptacle type 7 poles (SAE)
14- Submit Manufacturer certification :
15- Submit Detail drawings, brochures and catalogues: