The following Technical data shall be furnished and filled by bidders for all items indicated in all
tables:
33 KV system
Description UNDP required Offered specification
specifications
Ambient temperature: +55/C
Maximum -10/C
Minimum
Relative Humidity : 92% maximum
Altitude: 1000M above MSL
System Voltage: 33/11KV
No of phase : 3PH
Frequency: 50Hz
Nominal Voltage : 33 K Volt
Highest system voltage : 36 K Volt
System : 3Ph , 3wire , 50Hz
Short circuit level: 31.5 KA r.m.s for 3 seconds
at 33000 voltage level
Minimum clearance in air 320 mm
between phase and earth:
Minimum clearance in air 320 mm
between different phases:
Minimum creep age distance 900 mm O/D, 720 mm indoor
of insulator and bushing:
Earthing system : Earthed through earthing TF
11 KV system
Description Offered specification
Ambient temperature:
Maximum +55/C
Minimum -10/C
Symmetrical
10- Rated insulation level
a) Impulse withstand voltage 75 KV
(peak)
b) One minute 50Hz withstand 28 KV
voltage (r.m.s.)
11- Insulation type of bus-bars Covered with Silicone
rubber tube
12- Degree of protection
a) Enclosure IP42
b) Partition IP40
13- Color and type of painting Light gray finish, Semi-
gloss, Melamine resin
14- Thermostat, Yes ,AC 240V
8- Nominal Voltage : 11 KV
c) Heater AC 240 V
8- Nominal Voltage : 11 KV
9- Rated insulation level 75 KV
c) Impulse withstand voltage
d) One minute 50 Hz withstand voltage 28 KV
(r.m.s.)
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project
2 Breaking time ms
3 Closing time ms
1 At rated current
2 At 31.5 KA
c) Motor DC 110 V
d) Thermostat AC 240 V
e) Heater AC 240 V
4- Country of origin
6- Nominal Voltage : 11 kV
4- Country of origin
6- Nominal Voltage : 11 kV
2) Protection winding-
a) Accuracy class 5P
b) Rated output 15 VA
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project
8- Nominal Voltage : 11 kV
9- Frequency 50 Hz
7- Rated frequency 50 Hz
A.9-Battery
2- Name of manufacturer
2- Name of manufacturer
4- Country of origin
A.12-Transformer Main Protection and Control Relay (On Load Tap Changer)
CU/EPR/PVC – incoming
feeder
4- Country of origin
5- Reference standard IEC 60502, IEC 60183, IEC
60228, IEC 60287, , IEC
60287, IEC 60811, IEC
60853,
6- Nominal Voltage : 18/30 (36) kV
7- Construction data
1) Number of conductor 1 Core
2) Cross sectional area (Phase) 150 mm2
3) Shape of conductor Circular stranded
compacted
4) Material of conductor Copper
6) Material of conductor shielding Semi conductive Compound
7) Thickness of conductor shielding
(Approx.)
8) Material of insulation XLPE/EPR
9) Thickness of insulation
(Nominal)
10) Material of insulation shielding
No Description 11KV
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer
3- Type : CU/XLPE/PVC –
4- Country of origin
5- Reference standard IEC 60502, IEC 60183, IEC
60228, IEC 60287, , IEC
60287, IEC 60811, IEC
60853,
6- Nominal Voltage : 11 kV
7- Construction data
1) Number of conductor 1 Core
2) Cross sectional area 2 x 400 mm2 / phase
3) Shape of conductor Circular stranded
compacted
4) Material of conductor Copper
5) Number of wires
6) Material of conductor shielding Semi conductive Compound
7) Thickness of conductor shielding
(Approx.)
8) Material of insulation XLPE
9) Thickness of insulation
(Nominal)
10) Material of insulation shielding
No Description 11KV
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer
No Description
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer
4- Country of origin
5- Reference standard IEC 62271part 1, IEC 62271-102,
6- Number of poles 3
7- Location of service Indoor
8- Nominal Voltage : 33 KV
9- Rated insulation levels
a) Impulse withstand voltage 170KV
3
Cable charging breaking current 400A
4
Line charging breaking current 10 A
5
Small inductive breaking current 110 A
13 Rated operating times
1 Opening time ms
2 Breaking time ms
3 Closing time ms
2 At 31.5 KA
c) Motor DC 110 V
d) Thermostat AC 240 V
e) Heater AC 240 V
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project
17 Overall dimensions(length/width/ mm
height)
18 Total weight of circuit breaker kg
4- Country of origin
5- Reference standard IEC 60044-1
6- Nominal Voltage : 33 kV
7- Rated primary current 600 A
Incomer
8- Rated secondary current 5 A,5A,1A
9 Rated short circuit current 31.5 kA – 3 seconds
10- Rated dynamic current KA
11- Rated insulation level
a) Impulse withstand 170kV
voltage(peak) 70KV
b) One minute 50Hz withstand
voltage r.m.s.)
12- Characteristics of Current
Transformer
12-1 Measuring winding 5A
a) Accuracy class 1
b) Rated output 15VA
c)Instrument security factor 5
12-2 First protection secondary core- 5A
OC & EF 5P
a) Accuracy class 10
b) Accuracy limit factor 15 VA
c) Rated output
12-3 Second protection secondary core
– 1A
Differential 5P
a) Accuracy class 20
b) Accuracy limit factor 15 VA
c) Rated output
13- Submit Manufacturer
certification :
14- Submit Single line diagram :
15- Submit Detail drawings,
brochures and catalogues:
16- Submit certification or report
of type tests:
4 Country of origin
5 Reference standard IEC 60076-1, 2,3,5,8,
IEC 60214
6- Number of poles 3
7- Class: indoor or outdoor Outdoor
8 Type of cooling ONAF
9 Earthing of neutral point of LV Through resistor
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project
1-2 Make/Brand/Model:
1-3 Rated voltage
2 OLTC protective relay
2-1 Name of manufacturer
2-2 Make/Brand/Model:
2-3 Rated voltage
3 Pressure relief device
3-1 Name of manufacturer
4-2 Make/Brand/Model:
4-3 Adjustable range of tripping deg. C
contracts-winding
4-4 Adjustable range of alarm and deg. C
control contacts -oil
5 Breathers
5-2 Make/Brand/Model:
36 33 kV bushings
1 Name of manufacturer
2 Make/Brand/Model:
3 Reference standard IEC 60137
4 Type of bushing
5 Rated current A
6 Rated voltage KV
7 Material Porcelain
8 Color Brown
9 Creepage distance mm
37 11 kV bushings
1 Name of manufacturer
2 Make/Brand/Model:
3 Type of bushing
4 Rated current A
5 Rated voltage KV
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project
6 Material Porcelain
7 Color Brown
8 Creepage distance mm
38 Weight and dimensions
1 Weight of core and windings kg
2 Weight of oil kg
3 Weight of tank, conservator and kg
OLTC
4 Total weight of complete kg
transformer ready for service
5 Dimensions of transformer
Length mm
Width mm
Height mm
6 Type of corrosion protection on
steel parts Oil resistance paint
a) Inside tank
b) Outside tank Primary coat, Alkyd resin
paint and aluminum metallic
paint
39 Transformer oil
1 Type of oil IEC60296 class 1
Shell Diala B
2 Manufacturer
3 Place of manufacture
4 Manufacturer's type designation
5 Applied IEC standard IEC 60296
6 Kinematic viscosity mm2/s
At 40 deg ≤ 16.5
At -15 deg ≤ 800
7 Flash point ≥ 140 C
8 Pour point ≤ - 30 C
9 Density at 20 deg C – kg/dm3 ≤ 0.895
25MVA 33/11.5 kV Mobile Substation for Ifraz Water Project
4- Country of origin
5- Reference standard IEC 60076-1, 2,3,5,8,
IEC 60214
6- Number of poles 3
7- Class: indoor or outdoor Outdoor
8- Voltage Ratio 11/0.416 KV
9- Rated power
- Continuous 100 kVA Dyn11
10- Rated Frequency 50Hz
11- Nominal Voltage of winding
a) H.V. 33 kV
b) L.V 0.416 kV
12- Insulation level
a) Lightning Impulse 75 kV
b) AC power frequency 28 kV
No Description 30 KV
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer ABB, Schneider,
Siemens or equivalent
3- Type : Metal oxide
gapless
4- Country of origin
Trailer:
UNDP required Offered specification
specifications
1- Make/Brand/Model:
2- Name of manufacturer According to Iraq standard
3- Type : Drop-bed semi-trailer
4- Country of origin
5- Number of Semi-trailer per substation 2 numbers
Reference standard
6- Principal dimension and weight
a) Overall length H.V trailer 16.5m
M.V trailer 12.5m
b) Overall width
3m
c) Overall height (unladed) 1050 mm
d) Floor height 1050 mm
e) Trailer weight (without load ) H.V trailer 9 tons
M.V trailer 10 tons
g) Maximum load 25 to 38tons
h) Gross vehicle weight 35 to 47 tons
b) Laden
- King pin (front axle) kg
- Rear axle kg
7- Construction Frame type
a) Voltage 24 V
b) Receptacle type 7 poles (SAE)
14- Submit Manufacturer certification :
15- Submit Detail drawings, brochures and catalogues: