LANKA MARITIME SERVICES LIMITED

Revision 1 Issued/Approved by: ROCHEM SEPARATION SYSTEMS (INDIA) PVT.LTD.

REVERSE OSMOSIS PLANT ISO: Form Code: ROP

Vessel: M.V.AVANT GARDE Date: 23.12.2014 Ref. No: ROP / 10 / 05 TPD

GENERAL FAULT
LAMP TEST
FAULT INDICATION
1 2 3 4 5

START
PRESSURE STOP CLEANING SAND FILTER FAULT RESET
P1 60 increase BACK WASH P1 60 decrease

SEMI MANUAL OPERATION-


THE BUTTONS PRESS, IT SHOWS HIGHLIGHTS BY GREEN COLOR……….

 WHEN PLANT IS RUNNING IN AUTOMATICALLY, TO INCREASE PRESSURE OF PP 60


PRESS AND HOLD NO 1

1 2 3 4 5
 IF NEED TO DECREASE PRESSURE OF PP 60 , PRESS AND HOLD NO 5

1 2 3 4 5
 TO FILL UP TK 10, CLOSE TK 10 VALVE AND PRESS NO 1 AND NO 5 BUTTONS TOGETHER
WITH ONE TIME

1 2 3 4 5
 TO STOP FILLING TK 10, PRESS NO 1 AND NO 5 BUTTONS TOGETHER WITH ONE TIME

1 2 3 4 5

FULL MANUAL OPERATION-

WARNING –
WHEN USING FULL MANUAL MODE ALL SAFETY DEVICES WILL BE
BYPASS.

ENSURE THAT FULL MANUAL OPERATION WHICH MODE USING, WHICH PUMPS HAVE TO RUN
AND STOP, WHICH VALVES HAVE TO OPEN AND CLOSE.

 TO CHANGE FROM AUTOMATICALLY OPERATION TO FULL MANUAL OPERATION


SWITCHED ON MAIN SWITCH ON THE PLANT, THEN PRESS AND HOLD NO 2 BUTTON
UNTIL ALL LAMPS ARE LIGHTNING.

1 2 3 4 5
 TO START PK 20 , PRESS NO 1 THEN NO 4 BUTTONS

1 2 3 4 5
 TO STOP PK 20 , PRESS NO 1 THEN NO 4 BUTTONS

1 2 3 4 5

 TO START PK 30 , PRESS TWICE NO 1 BUTTON

1 2 3 4 5
 TO STOP PK 30 , PRESS TWICE NO 1 BUTTON

1 2 3 4 5

 TO START PP 60 , PRESS NO 1 THEN NO 2 BUTTON

1 2 3 4 5
 TO STOP PP 60 , PRESS NO 1 THEN NO 2 BUTTON

1 2 3 4 5
 TO OPEN VS 60 , PRESS NO 2 THEN NO 1 BUTTON

1 2 3 4 5
 TO STOP OPENING VS 60 , PRESS NO 2 THEN NO 1 BUTTON

1 2 3 4 5

 TO CLOSE VS 60 , PRESS NO 2 BUTTON TWICE

1 2 3 4 5
 TO STOP CLOSING VS 60 , PRESS NO 2 BUTTON TWICE

1 2 3 4 5

Você também pode gostar