Você está na página 1de 5

PM2-C

MOTOR PROTECTION MODULE

MANUAL:
• INSTALLATION
• USE
• MAINTENANCE

FILE VERSION DATE LANGUAGE PAGE


PM2INGn B/1 18/01/07 ING 1 of 5
PM2-C
INDEX
MOTOR PROTECTION MODULE PAGE

FOREWORD 3

WORKING 3

COSTRUCTION 3

TECHNICAL FEATURES 4

STOP PREARRENGEMENT 4

WIRINGSYSTEM 5

FOREWORD

PM2-C module has been designed to control all parameters of motor while running.

WORKING

While motor is still, the pilot lights of LOW OIL PRESSURE and BATTERY CHARGING
GENERATOR are on. On starting, protections are enabled with a 2-minute delay. During that time,
the operator may start without PM2-C turning to emergency and stopping motor.

If starting operation exceeds the preset delay time, the led BLOCCO of PM2-C, will turn on.
In this case, position key to OFF again and repeat.

When starting up motor, the first delay time is cut out and a 10 second delay time is set. Should
failure occur while running, the relevant led will turn on PM2-C will turn to emergency and block
motor. All pilot lights on the panel that are on when the motor is still remain on.

FILE VERSION DATE LANGUAGE PAGE


PM2INGn B/1 18/01/07 ING 2 of 5
CONSTRUCTION

PM2-C is made of oxidized aluminum panel, protection class IP 42 and is provided with:

‰ 0 = it disconnected
‰ AUTOMATIC AUTOM. protections connected
‰ STARTING AVV. (position with spring return) for starting motor

STOP BUTTON

This taste is always able to stop the motor at any time

PILOT LIGHTS

When on, they signal the following failures:

‰ LOW OIL PRESSURE


‰ GENERATOR BATTERY CHARGER: battery down or belt broken
‰ HIGH MOTOR TEMPERATURE
‰ FUEL RESERVE
‰ LOCK: signals that PM2-C is locked

TECHNICAL FEATURES
PROTECTION DEGREE IP 42
SUPPLY VOLTAGE 12V/24Vdc
MAX STOP RATING 16A
PROTECTION ENABLING TIME AFTER STARTING 10sec
STOP DELAY 30-60sec
WORKING TEMPERATURE -20°C + 60°C
CONNECTIONS Faston 6,3 mm
PANEL SIZES 96x96 mm.
DEPTH 72 mm.
BOX NORYL DIN43700

FILE VERSION DATE LANGUAGE PAGE


PM2INGn B/1 18/01/07 ING 3 of 5
STOP PREARRANGEMENT

Through PM2-C module is possible setting the following types of stopping:


P: jumper absent: stopping time
60s.

STOPPING DEVICE ALWAYS FEEDED


DURING MOTOR RUNNING.

PM2-B

JP1

A CONNECTION

B P

JP1: jumper 1 in A position


P: stopping time inexistent

STOPPING DEVICE ONLY FEEDED


DURING STOPPING MOTOR.

PM2-B

JP1
A CONNECTION
B P

JP1: jumper 1 in B position


P: jumper present: stopping time
20s.

FILE VERSION DATE LANGUAGE PAGE


PM2INGn B/1 18/01/07 ING 4 of 5
WIRING DIAGRAM

KEY GROUP
30 50 15/54

PM2
FAST.8

STARTING

+ BATTERY

G
P
STOP STOP STOP
M
1 16A 16A
2
2
B
1 2 3 4 5 6 7 8 9

-B W
15/54
K
I
E
Y R
30 50 I
N
FUS
G
1 1 1
1

30A
2

+
2 2 2

STOP FUEL WAT. GEN. LOW OIL STOP BATT START STOP
RES. TEMP. PRESS. EM EV

FILE VERSION DATE LANGUAGE PAGE


PM2INGn B/1 18/01/07 ING 5 of 5