Você está na página 1de 59

Wilbert Rey D.

Tarnate
Instructor

1
LOAD
SIDE
service branch
SOURCE circuits
SIDE entrance Lighting
Panelboard
Distribution
Panel branch
Main circuits
Panelboard
Distribution sub-feeders
Panel

branch
sub-feeders circuits
Lighting
feeders Panelboard
Distribution
Panel

branch
circuits
This diagram is a single-line diagram used
for power flow analysis
Design Flow
SOURCE LOAD
SIDE SIDE

service branch
entrance Lighting circuits
Panelboard
Distribution
Panel branch
Main circuits
Panelboard
Distribution sub-feeders
Panel

branch
sub-feeders Lighting
circuits
feeders Panelboard
Distribution
Panel

branch
circuits
2 4
•Loads •Branch •Feeders
•Outlets Circuits •Panel
•Switches Boards
1 3 5

7
•Service •Grounding
•Conduits
•Other Devices
6 8

4
2 4
•Loads • Branch •Feeders
•Outlets Circuits •Panel
•Switches Boards
1 3 5

7
•Service •Grounding
•Conduits
•Other Devices
6 8

5
 Define branch circuits
 Identify the conductors in a branch circuit
 Select overcurrent protection for a branch circuit
 Understand why branch circuits are used
 Select type and size of conductors for a branch circuit
 Distribute loads among branch circuits

6
 Define branch circuits
 Identify the conductors in a branch circuit
 Select overcorrect protection for a branch circuit
 Understand why branch circuits are used
 Select type and size of conductors for a branch circuit
 Distribute loads among branch circuits

7
SOURCE SIDE
L Overcurrent
Device
N

8
SOURCE SIDE
L Overcurrent
Device
N

BRANCH CIRCUIT

“A branch circuit is any segment of


a wiring system extending beyond
the final automatic overcurrent
protective device that is approved
for use as branch circuit protection.”

Automatic – does not need human


intervention to act

9
SOURCE SIDE
L Overcurrent
Device
N

BRANCH CIRCUIT
RATING

“A branch circuit is rated according


to the setting or rating of the
overcurrent device used to protect
the circuit.”

Rating - the smallest current where


the protective device will respond

11
 Define branch circuits
 Identify the conductors in a branch circuit
 Select overcorrect protection for a branch circuit
 Understand why branch circuits are used
 Select type and size of conductors for a branch circuit
 Distribute loads among branch circuits

12
SOURCE SIDE
L Overcurrent
Device
N

IDENTIFICATION OF
CONDUCTORS

Neutral/Grounded Conductor (N) – White,


gray, or any color except green with
three white stripes

Grounding Conductor (G) – (not part of a


branch circuit) Bare, green, or green with
yellow stripes

Ungrounded Conductor (L) – Any other


color, usually red, black, or blue

13
 Define branch circuits
 Identify the conductors in a branch circuit
 Select overcurrent protection for a branch circuit
 Understand why branch circuits are used
 Select type and size of conductors for a branch circuit
 Distribute loads among branch circuits

14
SOURCE SIDE
L Overcurrent
Device
N

OVERCURRENT
PROTECTION
FUSE

If I ≥ fuse rating, fuse filament


melts. Fuse must be replaced
afterwards.

15
SOURCE SIDE
L Overcurrent
Device
N

OVERCURRENT
PROTECTION
CIRCUIT BREAKER
(CB)

If I ≥ CB rating, CB opens the


circuit. CBs can also be used
to manually open or close the
circuit.

16
SOURCE SIDE
L Overcurrent
Device
N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without
overcoming obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except


when it opens the ungrounded and neutral
conductors simultaneously.

17
SOURCE SIDE
L Overcurrent

Device
N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

18
SOURCE SIDE
L ✔
N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

19
SOURCE SIDE
L

N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

20
SOURCE SIDE
L

N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

21
SOURCE SIDE
L ✔
N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

22
SOURCE SIDE
L

N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

23
SOURCE SIDE
L ✔
N

OVERCURRENT
PROTECTION
RATING ≤ CURRENT-CARRYING CAPACITY OF
BRANCH CIRCUIT CONDUCTORS
1. Readily accessible – can be reached without
aid of ladders and tools and without overcoming
obstacles
2. Required for each ungrounded conductor.

3. Prohibited in neutral conductors except when


it opens the ungrounded and neutral conductors
simultaneously.

24
VI. Branch Circuit Overcurrent Protection

1. General Rule
- The rating or setting of an overcurrent device in any branch circuit must
not exceed the current-carrying capacity of the circuit conductors.
2. Specific Rules
1. An overcurrent device must be placed at the supply end of each
ungrounded conductor of the circuit to be protected.
2. An overcurrent device must not be placed in a permanently-grounded
conductor, except where the device simultaneously opens all conductors
of the circuit.
3. Where the device protecting a conductor has a rating or setting that also
provides protection for smaller conductors, there is no need to provide
protection at the point where the smaller conductors are tapped from
the larger conductor.
4. Non-motor-operated appliance branch circuit protective devices shall
not exceed 150% of the appliance rating.
5. Overcurrent devices must be located such that they are readily
accessible.
 Define branch circuits
 Identify the conductors in a branch circuit
 Select overcorrect protection for a branch circuit
 Understand why branch circuits are used
 Select type and size of conductors for a branch circuit
 Distribute loads among branch circuits

27
Subfeeder

Branch Circuits
Why distribute loads
among branch circuits?

Reliability
Diff. load requirements
Standardization Panel Board –
contains devices
Reduction of wire size for overcurrent
protection

28
Allowable BC
Type of BC Permissible Loads
Rating (A)
Individual Any Any
- serving one
outlet
General-purpose lighting load
15 or 20
Rating of any one Cord-and-plug attached equipment ≤ 0.8 (BC
Rating)

If supplying other loads, total rating of equipment fastened in


place (not including luminaires) ≤ 0.5 (BC Rating)

Multioutlet Luminaires with heavy-duty lamp holders not in dwelling units


- Serving 30
multiple outlets Cord-and-plug attached equipment ≤ 0.8 (BC Rating)

40 or 50 Cooking appliances fastened in place.

Luminaires with heavy-duty lamp holders not in dwelling units,


infrared heating units, etc.
>50 Non-lighting outlets
29
 Define branch circuits
 Identify the conductors in a branch circuit
 Select overcorrect protection for a branch circuit
 Understand why branch circuits are used
 Select type and size of conductors for a branch
circuit
 Distribute loads among branch circuits

30
Maximum load of
Branch Circuits

Non-continuous load + 1.25


(Continuous load) ≤ BC Rating

* Continuous load – maximum current (RMS) is


expected to continue for 3 hrs.
Maximum Rating of
Individual BC

If appliance is non-motor operated: BC


rating ≤ 1.5 (appliance rating)
Selection of Conductors

General Rule:
Branch circuit conductors shall have an ampacity of not
less than the rating of the branch circuit and not less than
the load to be served.

Ampacity – current that a conductor can carry continuously under the conditions
of use without exceeding its temperature rating.

Conditions:
Ambient temp.
Neighboring conductors
Surrounding materials

33
Selection of Conductors

 The type of insulation of conductors must be suited to the desired


operation.
 Where ambient temperature exceeds 30°C, the ampacities of the
conductors shall be derated according to correction factors given at the
bottom of each of the ampacity tables (Tables 3.10.1.16 to 3.10.1.21).
 Where more than three (3) conductors are used in a raceway or cable, the
conductor ampacities must be derated from the ampacity values to
compensate for increased heating due to reduced ventilation of an
enclosed group of closely-spaced conductors (see Note No.8).
 A 1% to 2% voltage drop is recommended for branch circuit conductors.
Table 3.10.1.6 Allowable Ampacities of Insulated Conductors
Rated 0 - 2000 Volts, 60º to 90º C

Not More Then Three Conductors in Raceway or Cable or Earth


(Directly Based), Based on Ambient Temperature of 30º C

Size Temperature Rating of Conductor. See Table 3.10.1.13 Size


60º C 75º C 85º C 90º C 60º C 75º C 85º C 90º C
Types Types Types Types Types Types Types Types
RUW, FEPW, V, TA, RUW, RH, V, TA,
T, RH, MI TBS, T, RHW, MI TBS,
TW, RHW, SA, TW, RUH, SA,
2
mm UF RUH, AVB, UF THW, AVB, mm2
(mm. dia.) THW, SIS, THWN, SIS, (mm. dia.)
THWN, †FEP, XHHW, †RHH,
XHHW, †FEPB, USE †THHN,
USE, †RHH, †XHHW*
ZW †THHN,
†XHHW*
ALUMINUM OR COPPER-
COPPER
CLAD ALUMINUM
2.0(1.6) 15 15 25 25 …. …. …. …. ….
3.5(2.0) 20 20 30 30 15 15 25 25 3.5(2.0)
5.5(2.6) 30 30 40 40 25 25 30 30 5.5(2.6)
8.0(3.2) 40 45 50 50 30 40 40 40 8.0(3.2)
14 55 65 70 70 40 50 55 55 14
22 70 85 90 90 55 65 70 70 22
30 90 110 115 115 70 85 90 90 30
38 100 125 130 130 80 95 100 100 38
50 120 145 150 150 95 115 120 120 50
60 135 160 170 170 105 125 135 135 60
80 160 195 205 205 125 150 160 160 80
100 185 220 225 225 145 170 180 180 100
125 210 255 265 265 170 200 210 210 125
150 240 280 295 295 190 230 240 240 150
200 280 330 355 355 225 270 290 290 200
250 315 375 400 400 260 305 330 330 250
325 370 435 470 470 295 355 380 380 325
400 405 485 515 515 330 395 420 420 400
500 445 540 580 580 370 440 475 475 500
Size Temperature Rating of Conductor. See Table 3.10.1.13 Size
60º C 75º C 85º C 90º C 60º C 75º C 85º C 90º C
Types Types Types Types Types Types Types Types
RUW, FEPW, V, TA, RUW, RH, V, TA,
T, RH, MI TBS, T, RHW, MI TBS,
TW, RHW, SA, TW, RUH, SA,
mm2 UF RUH, AVB, UF THW, AVB, mm2
(mm. dia.) THW, SIS, THWN, SIS, (mm. dia.)
THWN, †FEP, XHHW, †RHH,
XHHW, †FEPB, USE †THHN,
USE, †RHH, †XHHW*
ZW †THHN,
†XHHW*
COPPER ALUMINUM OR COPPER-CLAD
ALUMINUM
CORRECTION FACTORS
Ambient For ambient temperature over 30º C, multiply the ampacities Ambient
Temp. ºC shown above by the appropriate correction factor to determine Temp. ºC
31-40 0.82 0.88 0.90 0.91 0.82 0.88 0.90 0.91 31-40
41-50 0.58 0.75 0.80 0.82 0.58 0.75 0.80 0.82 41-50
51-60 …. 0.58 0.67 0.71 …. 0.58 0.67 0.71 51-60
61-70 …. 0.35 0.52 0.58 …. 0.35 0.52 0.58 61-70
71-80 …. …. 0.30 0.41 …. …. 0.30 0.41 71-80
† The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes
for 2 mm2 (1.6 mm. dia.) 20 amperes for 3.5 mm2 (2.0 mm. dia.), and 30 amperes for 5.5 mm2 (2.6 mm. dia.)
copper; or 15 amperes for 3.5 mm2 (2.0 mm. dia.) and 25 amperes for 5.5 mm2 (2.6 mm. dia.) aluminum and
copper-clad aluminum.
* For dry locations only. See 75º C column for wet locations.
Table 3.10.1.17 Allowable Ampacities of Insulated Conductors
Rated 0 - 2000 Volts, 60º to 90º C

Single Conductor in Free Air, Based on Ambient Temperature of 30º C

Size Temperature Rating of Conductor. See Table 3.10.1.3 Size


60º C 75º C 85º C 90º C 60º C 75º C 85º C 90º C
Types Types Types Types Types Types Types Types
RUW, FEPW, V, TA, RUW, RH, V, TA,
T, RH, MI TBS, T, RHW, MI TBS,
TW RHW, SA, TW, RUH, SA,
mm2 RUH, AVB, THW, AVB, mm2
(mm. dia.) THW, SIS, THWN, SIS, (mm. dia.)
THWN, †FEP, XHHW †RHH,
XHHW, †FEPB, †THHN,
ZW †RHH, †XHHW*
†THHN,
†XHHW*
ALUMINUM OR COPPER-
COPPER
CLAD ALUMINUM
2.0(1.6) 20 20 30 30 …. …. …. …. ….
3.5(2.0) 30 30 40 40 20 20 30 30 3.5(2.0)
5.5(2.6) 40 45 55 55 30 30 45 45 5.5(2.6)
8.0(3.2) 55 60 70 70 45 50 55 55 8.0(3.2)
14 80 95 105 105 60 75 80 80 14
22 105 130 140 140 80 100 110 110 22
30 130 160 170 170 100 125 130 130 30
38 155 185 195 195 120 145 155 155 38
50 180 220 235 235 145 170 180 180 50
60 205 250 260 260 160 195 205 205 60
80 250 300 320 320 195 230 245 245 80
100 290 355 370 370 220 270 285 285 100
125 335 400 420 420 260 310 325 325 125
150 375 440 475 475 290 350 370 370 150
200 440 540 570 570 350 420 445 445 200
250 505 620 655 655 400 480 510 510 250
325 600 720 770 770 475 570 610 610 325
400 675 810 875 875 535 645 695 695 400
500 770 930 995 995 620 745 795 795 500
Size Temperature Rating of Conductor. See Table 3.10.1.17 Size
60º C 75º C 85º C 90º C 60º C 75º C 85º C 90º C
Types Types Types Types Types Types Types Types
RUW, FEPW, V, TA, RUW, RH, V, TA,
T, RH, MI TBS, T, RHW, MI TBS,
TW RHW, SA, TW, RUH, SA,
mm2 RUH, AVB, THW, AVB, mm2
(mm. dia.) THW, SIS, THWN, SIS, (mm. dia.)
THWN, †FEP, XHHW †RHH,
XHHW, †FEPB, †THHN,
ZW †RHH, †XHHW*
†THHN,
†XHHW*
ALUMINUM OR COPPER-CLAD
COPPER
ALUMINUM
CORRECTION FACTORS
Ambient For ambient temperature over 30º C, multiply the ampacities Ambient
Temp. ºC shown above by the appropriate correction factor to determine Temp. ºC
31-40 0.82 0.88 0.90 0.91 0.82 0.88 0.90 0.91 31-40
41-50 0.58 0.75 0.80 0.82 0.58 0.75 0.80 0.82 41-50
51-60 …. 0.58 0.67 0.71 …. 0.58 0.67 0.71 51-60
61-70 …. 0.35 0.52 0.58 …. 0.35 0.52 0.58 61-70
71-80 …. …. 0.30 0.41 …. …. 0.30 0.41 71-80

† The load current rating and the overcurrent protection for these conductors shall
not exceed 20 amperes for 2 mm2 (1.6 mm. dia.), 25 amperes for 3.5 mm2 (2.0 mm.
dia.), and 40 amperes for 5.5 mm2 (2.6 mm. dia.) copper; or 20 amperes for 3.5 mm2
(2.0 mm. dia.) and 30 amperes for 5.5 mm2 (2.6 mm. dia.) aluminum and copper-
clad aluminum.
Notes to tables 3.10.1.6 through 3.10.1.13

8. More than 3 Conductors in a raceway or cable. Where the number of conductors In


a raceway or cable exceed 3, the maximum allowable load current of each conductor
shall be reduced as shown in the following table

Percent of Values in
Number of
Tables 5.3.2.4 and
Conductors
5.3.2.6

4 thru 6 80

7 thru 24 70
25 thru 42 60
43 and above 50
Where single conductors of multi-conductor cables are stacked or bundled without
maintaining spacing and are not installed in raceways, the maximum allowable load
current of each conductor shall be reduced as shown in the above table.

41
Exceptions
a. When conductors of different systems, as provided in Section 3.0.1.3, are
installed in a common raceway, the derating factors shown above shall
apply to the number of power and lighting conductors only (Articles 2.10,
2.15, 2.20 and 2.30).
b. The derating factors of Sections 3.1.2.4(c), 3.3.1.2(a) and 3.3.2.1(b) shall not
apply when the above derating factors are also required.
c. For conductors installed in cable trays, the provisions of Section 3.18.1.11
shall apply.
 In dwelling units, at least one (1)
◦ 20-A Small-appliance BC(one per kitchen)
◦ 20-A Bathroom BC (for equipment in bathroom)
◦ 20-A Laundry BC

 For a dwelling unit not more 50sqm., it shall be permitted


to have only one 20-A BC provided that the total load
shall not exceed 3680 VA.

43
Small-Appliance BC (kitchen, pantry, etc.) Bathroom BC
May include:
receptacle outlets, outlets not in the bathroom
countertops, and
may not be included
refrigerator
no other except outlets for clock
and a supplementary equipment Individual BC

Other BC
Laundry BC
depending on the BC rating
other outlets not for laundry may not
allowed for specific loads;
be included
designers’ way & the rules of
thumb

44
 Step 1: List down groups of similar branch circuits and
their ratings.
◦ E.g. lighting bc, receptacle bc, small-appliance bc, individual
bc
 Step 2: Do load calculation for each group
 Step 3: Determine the number of branch circuits per
group based on the BC ratings, allowances, and the
load to be served

45
1. Lighting and Receptacle Branch Circuits for General Illumination

- Larger of: VA/sqm of listed occupancies (Table 2.20.1.3(a)) and actual load, if
known
- branch circuit rating: 15 or 20 A
Table 2.20.1.3(a) General Lighting Loads by Occupancies

Type of Occupancy Unit Load per Sq. M. (VA/m 2)


Armories and Auditoriums 8
Banks 28**
Barber Shops and Beauty Parlors 24
Churches 8
Clubs 16
Court Rooms 16
*Dwelling Units 24
Garages-Commercial (storage) 4
Hospitals 16
*Hotels and Motels, including apartment
16
houses without provisions for cooking by tenants
Industrial Commercial (Loft) Buildings 16
Lodge Rooms 12
Office Buildings 28**
Restaurants 16
Schools 24
Stores 24
Warehouses (storage) 2
' In any of the above occupancies except one -
family dwelling and individual dwelling units of two-
family and of multifamily dwellings:
Assembly Halls and Auditoriums 8
Halls, Corridors, Closets, Stairways 4
Storage Spaces 2
Notes:
* All receptacle outlets of rating 20 A or less in one-family, two-family and
multifamily dwellings and guest rooms of hotels and motels except those
connected to the receptacle circuits specified in Section 2.20.1.3(b) shall be
considered outlets for general illumination.
No additional load calculations shall be required for such outlets.

… but you may.

Lighting loads in 2.20.1.3(a) includes


 all general-use receptacles rated 20-A or less including receptacles connected to the circuits in
(2.10.1.11.c.3.) bathroom branch circuits
 receptacle outlets in 2.10.3.3(e) – (g). outdoor outlets, laundry areas, basements and garages
 lighting outlets in (2.10.3.21.a - b) dwelling units and guest rooms
Notes:
**In addition, a unit load of 8 volt-ampere per square meter shall be included for
general purpose receptacle outlets when the actual number of general purpose
receptacle outlets is unknown.
2. Heavy-duty Lamp-holders in Fixed Lighting Units
Larger of:
- 600 volt-amperes per unit (sec2.20.1.3(b)),
or
- Actual load, if known
Branch Circuit Rating: 30, 40, or 50 A

3. General Receptacles
- 180 volt-amperes per receptacle (sec2.20.1.3(b))
Branch Circuit Rating: 15 or 20 A

50
4. Show Window Illumination
Larger of:
- 600 volt-amperes per linear meter (sec 2.20.1.3(c)
except .3), or
- Actual load, if known
Branch Circuit Rating: depends on type of
lamp-holder

51
5. Specific Appliance
- Ampere rating of appliance
Branch Circuit Rating: depends of FLC of appliance

6. Small Appliance for Dwelling Unit (sec 2.20.2.7(a))


- Branch Circuit Rating: 20 A

52
7. Laundry Loads for Dwelling Unit
Branch Circuit Rating: 20 A

8. Electric Ranges and Cooking Equipment


- Ampere rating of equipment
Branch Circuit Rating: 40 or 50 A

9. Motor Loads
- 1.25 * Motor Full-load current specified by the code
Branch Circuit Rating: Any

53
10. Motor Loads
- Full load current of motor x 230 V x 125%
Branch Circuit Rating: any rating

54
Minimum number of Branch Circuits per Load Group

Total computed load in VA


=
Branch Circuit Rating

55
Determine the minimum number of branch circuits
required for an office building with the following lighting
and receptacle loads:

a. Floor area of 30 meters by 60 meters


b. 400 150-W incandescent lamps
c. 15 meter long show window
d. Special lighting load of 100 fluorescent lighting
fixtures; each unit draws 2.5 amperes
e. 200 duplex receptacles

Use 20-Amp Branch Circuits

56
Solution:

a. General Illumination

Larger of:
- 30m x 60m x 28 VA/sq.m. x 1.25 = 63,000 VA,
or
- 400 units x 150 VA/unit x 1.25 = 75,000 VA

No. of B.C. = ___75,000VA___


(20A) (230V)
= 16.3
therefore, use 17 B.C. (min)
Or 400 UNITS/17 = 23 outlets per BC (MAX)

57
b. Show Window

-15 m x 600 VA/m x 1.25 = 11,250 VA


No. of B.C. = 11,250 = 3 B.C.
230 x 20 (minimum)

c. Special Lighting Load

-100 units x 2.5 A/unit x 230 V x 1.25


= 71,875 VA
No. of B.C. = 71,875 = 16 B.C.
230 x 20 (minimum)

58
d. General Receptacles

- 200 units x 180 VA/unit x 1.25 = 45,000 VA

No. of B.C. = 36,000 x 1.25 = 10 B.C.


230 x 20 (minimum)

59
Single Family Dwelling Unit: (30 deg. Celsius ambient)
The dwelling has a floor area of 145 m2. It has the typical household
appliances including one 8-kW electric range, two 1-Hp room air-
conditioning unit, one 1.5 Hp room air-conditioning unit, and one 1-Hp
water pump. For this unit
a. Determine the minimum number of branch circuits and the size of
THW conductors to be used considering that:
 20-ampere BC will be used as much as possible.
 At least two 20-ampere BCs will be provided for general illumination.
 Individual BCs will supply power to the range, air-conditioning units,
and water pump
 The unit has one kitchen with a countertop
 The unit has laundry appliances.
 There are no receptacle outlets in any bathroom.

60

Você também pode gostar