Escolar Documentos
Profissional Documentos
Cultura Documentos
- The TAPCON® 240 voltage regulator continuously compares the actual value U actual (output
voltage at the transformer) with a fixed or load-depending desired voltage level U desired that
you can specify.
- Depending on the difference between actual and desired value, TAPCON® 240 provides the
actuating pulse for the on- load tap-changer of the transformer.
- If the measuring voltage ( the measured actual value ) falls outside the specified bandwidth,
after the set delay time an output pulse is issued, and the on-load tap- changer switches up
or down accordingly.
Band width B%
Means the positive and negative percentage deviation from the desired voltage level.
[+ B %] ≥ 0.6 • ΔU Step
ΔU Step = 1.09 KV
Time delay T1
If the deviation in voltage ( ±B/2 ) is still present after the delay time (T1) has elapsed, an output
pulse is issued, and the on-load tap-changer initiates a switching operation.
1- Linear time:
2- Integral time
1- Make two page from FREJA first page normal voltage (U desired ) for 3 sec after that inject in
the second page with voltage less than U desired but not more than the U/V setting. And take
stop contact with order raise from the relay
2- For Integral time setting compare your result with this curves.
Time delay T2
In case of voltage drop required more than one tap-changer operation for returning with the
transformer output voltage to within the limit of bandwidth (accepted deviation)
The first output pulse is issued after the specified delay time T1. Further pulses required are issued
after the specified delay time T2 and not waiting to T1.so any more operation have to wait T2 time
delay.
1- Make two page from FREJA first page normal voltage (U desired ) for 3 sec after that inject in
the second page with voltage less than U desired but more than bandwidth setting ( two times)
And do not connect the raise contact to FREJA until the relay make the first raise order.
- Over current blocking prevents tap-change operations in the presence of overload. The
voltage regulator output pulses are blocked and the red LED ">l" illuminates as soon as the
load current falls below.
Overvoltage detection
- In the event of an overvoltage detection response, the on- load tap-changer keeps getting
activated by periodic pulses to the motor-drive mechanism until the overvoltage falls
below the response threshold.
- In this case, voltage regulation has to take account of the feeder impedance (in the cables or
overhead lines to the customers). These feeder lines have voltage drop.
- This voltage drop depends on the impedance of the line, the current and the phase angle ф
at the customers.
Two different options for compensating a load-dependent voltage drop between transformer and
consumer.
2- Z compensation