APM Series

NEMA-4X, IP65 Meter with Relays Option


Front Bezel

RELAY2 RELAY1 24V OUT POWER


6 5 4 3 2 1 2 1 2 1

NO NC COM NO NC COM P+ P-

+ -
RTD
TC

1 2 3 4 5 6
V+ mA+ EXC T+ COM
1 2 3 4 5 RTD TC

SWITCH

Rear View Gasket

Panel cutout required:


1.772" x 3.622" (45mm x 92mm)
1.76"
(45mm)

APM765 2.50"

Panel Meter 2.45"


(64mm)

(62mm) 3.61"
(92mm)

Description
The APM765 displays data collected from process 0.59"
(15mm)
3.20"
(81mm)
3.60" 4.68"
current, DC voltage and temperature inputs. (91mm) (119mm)

Several output options convert the display into a


transmitter with proportional 4-20mA output or
a serial communication interface. A relay output Special Features Applications
APM Series

option adds limit alarm and pump control ■ Universal input (TC, RTD, mA, V DC) ■ Process & temperature monitoring
capabilities.
■ Sunlight-readable display (adjustable intensity) ■ High & low alarms
Process inputs can be scaled with or without
applying an input for virtually any engineering ■ Push-button or PC programmable ■ Latching or non-latching relays
units. Temperature inputs can be programmed to ■ Dual relay option for limit alarms or ■ Pump alternation control
display in degrees Fahrenheit or Celsius. pump control (with alternation)
■ Time delay & fail-safe relays
Inputs ■ Isolated 4-20mA output options (sink/source)
■ Minimum & maximum readings
4-20mA DC, ±20mA DC, ±10V DC,
■ Single/dual 24V DC isolated power options
Type J, K, T, E thermocouples,
Modbus RTU communication option Data Logging
100 ohm platinum RTDs ■
Software provides a convenient way to collect
Outputs (optional) ■ Data acquisition and logging capabilities data generated by the APM765’s serial output.
4-20mA (sink/source) with MeterView software Users can select the logging time interval and
Dual SPDT (Form C) 3A relays ■ Universal power supply 90-265 VAC/VDC the engineering units for display on the com-
RS-232, RS-422/485 serial communication puter screen. Data is written to a file that can be
■ Shallow depth package (3.6” behind panel) imported into spreadsheets or other applications.
Power Requirements
Standard unit: 85-265V AC or 90-265V DC Easy Setup
Optional: 12-24V AC or 12-36V DC The APM765 is very easy to set up and program
using the simple four-button configuration
Operating Temperature
interface. There is only one switch on the entire
0 to 65°C
meter – no jumpers – and never any need to
Approvals open the case. The meter is also programmable
CE marked. UL, cUL listed. using a PC and the MeterView software. A copy
function quickly clones setups from other units.

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com


Digital Panel Meters

DC Process and Isolated 4-20mA Output MeterView Software


Temperature Inputs MeterView software enables PC programming of
Standard 4-20 mA Sinking Output
The APM765 is factory calibrated to accept 4-20 (powered externally) the APM765 and sets up data logger operation.
mA Out
mA, ±10 VDC, Type J, K, T, E thermocouples and I- I+ Remote Programming
100 ohm platinum RTDs. Process inputs can be 6 5
MeterView software allows all setup parameters
scaled with or without applying an input for DCS/PLC
to be programmed from a PC and saved to a file
virtually any engineering units. Temperature 24V
for reporting or programming other meters.
inputs can be programmed to display in degrees
Fahrenheit or Celsius and a type K thermocouple
can display up to 2300°F.

Current/Voltage Input Sourced 4-20 mA Output and


Setting up the meter to accept a current or Input Signal Powered by Panel Meter
(using dual 24V supplies)
voltage input is very easy. All setup steps are
SIGNAL
performed by pushbuttons or through software CONNECTOR mA Out 24V Out
so there are no switches or jumpers to adjust. V+
1
mA+ EXC
2 3
T+ COM
4 5
I-
6
I+
5
P1+ P1- P2+
4 3 2
P2-
1

Transmitter Powered by External Supply


SIGNAL SIGNAL
CONNECTOR CONNECTOR - + -
2-Wire Remote Display,
V+ mA+ EXC T+ COM V+ mA+ EXC T+ COM 4-20mA Chart Recorder, Data Acquisition
1 2 3 4 5 1 2 3 4 5 Transmitter etc.
+ MeterView software provides a convenient way
to collect the data generated from the serial
output of up to 100 panel meters. The user
- + + - + -
4-20mA
External
Voltage
can select the logging time interval and the
Transmitter
Power
Supply Signal Serial or Modbus Output engineering units that will be displayed on the
The APM765 can be used as a computer screen. Data is written to a file that

APM Series®
Transmitters Powered by Internal Supply data acquisition device, with Serial Adapter
could then be imported into a spreadsheet or
(Optional)
the added benefit of a digital other application.
SIGNAL 24V SIGNAL 24V
CONNECTOR OUT CONNECTOR OUT display, by connecting an optional Tx Rx P
V+ mA+ EXC T+ COM P+ P- V+ mA+ EXC T+ COM P+ P- RS-232 or RS-422/485 serial
1 2 3 4 5 2 1 1 2 3 4 5 2 1
communication adapter.
- + + - P Acromag offers MeterView software for simple
2-Wire
4-20mA
3-Wire
4-20mA
data acquisition and to program the meter.
Transmitter Transmitter
Serial Communications
METER ADDRESS
Modbus protocol: 1 - 247 (default 247).
Thermocouple/RTD Input
BAUD RATE
Setting up the APM765 to accept thermocouple 300 - 19,200 bps (default 2400).
or RTD input is simply a matter of setting a
switch at the rear of the case and selecting the TRANSMIT TIME DELAY Sample File Generated by MeterView
Programmable between 0 and 199mS or Transmitter PD765 Log File
input type from the menu. always on for RS422 communication (default 10mS). Name: C:\MV3Logfile.htm Created: 2/26/2004 5:34:12 PM

Meters accept J, K, T, or E type thermocouples DATA


Serial Port:
COM 1
Connection speed:
2400 Baud
Logging rate:
1 update every 10 seconds

as well as two, three, or four-wire 100 ohm 8 bit (1 start bit, 1 stop bit). Date & Time
2/26/2004 5:34:12 PM
Tag Number
Tank 1 Level
Address
06
Display
17.70
Units
Feet
Relay 1
P1 On
Relay 2
P2 Off

platinum RTDs. 2/26/2004 5:34:12 PM Tank 2 Level 07 18.18 Feet P3 Off P4 Off

PARITY 2/26/2004 5:34:12 PM


2/26/2004 5:34:12 PM
Tank 3 Level
Tank 1 Temp
08
09
20.54
74
Feet
°F
P5 On
Off
P6 Off
Off

SIGNAL SIGNAL None, even, or odd (default even). 2/26/2004 5:34:12 PM


2/26/2004 5:34:12 PM
Tank 2 Temp
Tank 3 Temp
10
11
72
72
°F
°F
Off
Off
Off
Off
CONNECTOR CONNECTOR 2/26/2004 5:34:22 PM Tank 1 Level 06 17.58 Feet P1 On P2 Off
V+ mA+ EXC T+ COM V+ mA+ EXC T+ COM BYTE-TO-BYTE TIMEOUT 2/26/2004 5:34:22 PM
2/26/2004 5:34:22 PM
Tank 2 Level
Tank 3 Level
07
08
18.04
19.79
Feet
Feet
P3 Off
P5 Off
P4 Off
P6 Off
1 2 3 4 5
RTD TC
1 2 3 4 5
RTD TC
0.01 - 2.54 seconds (default 0.01 seconds). 2/26/2004 5:34:22 PM
2/26/2004 5:34:22 PM
Tank 1 Temp
Tank 2 Temp
09
10
74
72
°F
°F
Off
Off
Off
Off
2/26/2004 5:34:22 PM Tank 3 Temp 11 72 °F Off Off
TURN AROUND DELAY 2/26/2004 5:34:32 PM
2/26/2004 5:34:32 PM
Tank 1 Level
Tank 2 Level
06
07
16.47
16.87
Feet
Feet
P1 On
P3 Off
P2 Off
P4 Off
Less than 2mS (fixed). 2/26/2004 5:34:32 PM Tank 3 Level 08 17.10 Feet P5 Off P6 Off
+ - Switch RTD Switch 2/26/2004 5:34:32 PM Tank 1 Temp 09 74 °F Off Off
Position Sensor Position
TC

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com


APM Series

Performance Specifications Process Inputs SENSOR BREAK


Specifications apply to operation at 25°C. INPUTS All relays and alarm status LEDs go to alarm state.
Field selectable: ±20 mA DC and ±10 VDC Analog output may go to pre-programmed state.
General Display will flash.
ACCURACY
DISPLAY ±0.05% of calibrated span ±1 count, Relays
0.56”(14.2 mm) red LEDs. Four digits (-1999 to 9999).
square root: 10-100% F.S. RATING
DISPLAY INTENSITY LOW-FLOW CUTOFF 2 SPDT (form C); rated 3 amps @ 30 VDC or 3 amps
Eight user-selectable intensity levels. @ 250 VAC resistive load; 1/14 HP @ 125/250 VAC for
0 to 9999 (0 disables cutoff function).
inductive loads.
FRONT PANEL DECIMAL POINT
NEMA 4X, IP65. Panel gasket provided.
Up to three decimal places: d.ddd, dd.dd, ddd.d,or DEADBAND
dddd. 0-100% of full scale, user selectable.
PROGRAMMING METHODS
Four front panel push buttons, PC and MeterView
CALIBRATION HIGH OR LOW ALARM
software, or cloning with Copy feature. User may program any alarm for high or low.
Internal or external signal or with PC.
NOISE FILTER CALIBRATION RANGE RELAY OPERATION
Programmable between 2 - 199 (0 will disable filter). 1. Automatic (non-latching).
User Programmable over entire range of meter.
2. Latching.
DISPLAY UPDATE RATE INPUT IMPEDANCE 3. Pump alternation control.
1.8-2.5/sec for TC input or 3.7-5/sec for process/RTD.
Voltage range: greater than 1M ohms.
Current range: 50-100 ohms. RELAY RESET
OVERRANGE AND UNDERRANGE User selectable via front panel buttons or PC.
Display flashes 9999 (over) or -1999 (under).
INPUT OVERLOAD 1. Automatic reset only (non-latching).
MAX/MIN DISPLAY Protected by automatically resettable fuse. 2. Automatic + manual reset any time (non-latching).
Stored until reset by user or meter is turned off. 3. Manual reset only, at any time (latching).
TEMPERATURE DRIFT 4. Manual reset only after alarm condition has cleared
NON-VOLATILE MEMORY ±50 PPM/°C. (latching).
All programmed settings are stored in nonvolatile
TRANSMITTER SUPPLY Automatic reset: Resets when input passes reset point.
memory for a minimum of ten years if power is lost.
Isolated, one or two transmitter supplies (optional) Manual reset: Front panel ACK button.
POWER P1 (-1 option): 24 VDC ±10% @ 200mA max.
P1/P2 (-2 option) TIME DELAY
APM Series

AC: 85-265 VAC, 50/60 Hz, 20 VA.


DC: 90-265 VDC, 20 W. P1: 24 VDC ±10% @ 200mA. 0 to 199 seconds, on and off delays; programmable.
Option: 12-36 VDC or 12-24 VAC. P2: 24 VDC ±10% @ 40mA. FAIL-SAFE OPERATION
REQUIRED FUSE Programmable, independent for each relay. Relay coils
Temperature Inputs are energized in normal condition. In case of alarm or
UL Recognized, 5A max, slow blow INPUTS
(up to six meters may share one fuse). power failure, relays will go to de-energized state.
Factory calibrated, field selectable: type J, K, T, or E
NORMAL MODE REJECTION thermocouples and 100 ohm. platinum RTD (0.00385 AUTO INITIALIZATION
64 dB at 50/60 Hz. or 0.00392 curve). When power is applied to the meter, relays will reflect
the state of the input to the meter.
ISOLATION RESOLUTION
Input or output to power line: 4kV. 1°; type T, 1° or 0.1°. Isolated 4-20mA Output
Input or output to P1 or P2: 500V. ACCURACY OUTPUT RANGE
Input to output: 500V. Type Temperature Range Accuracy 1.00 to 23.00mA typical. Scalable for 0.00 to 23.99mA.
P1 to P2: 500V. J -58 to 1382°F (-50 to 750°C) ±2°F (±1°C) Factory calibrated for 4-20 mA.
ENVIRONMENTAL K -58 to 2300°F (-50 to 1260°C) ±2°F (±1°C) ACCURACY
Operating range: 0 to 65°C (32 to 149°F). T -292 to 700°F (-180 to 371°C) ±2°F (±1°C) ±0.1% F.S. ±0.004 mA.
Storage range: -40 to 85°C (-40 to 185°F). E -58 to 1578°F (-50 to 870°C) ±2°F (±1°C)
Relative humidity: 0 to 90% non-condensing. RTD -328 to 1382°F (-200 to 750°C) ±1°F (±1°C) TEMPERATURE DRIFT
50 PPM/°C from 0 to 65°C ambient.
CONNECTIONS COLD JUNCTION REFERENCE
Automatic. Note: Analog output drift is separate from input drift.
Power & Signal: removable screw terminal blocks
accept 12 to 26 AWG. Serial: RJ11 header, standard TEMPERATURE DRIFT OUTPUT LOOP RESISTANCE
on all meters. ±2°C maximum; 0 to 65°C ambient temperature. Power Supply Minimum Maximum
24 VDC 10 ohms 700 ohms
ENCLOSURE OFFSET ADJUSTMENT 35 VDC (external) 100 ohms 1200 ohms
1/8 DIN, high impact plastic, 94V-0, color; gray. Programmable to ±19.9°. This allows the user to apply
an offset value to the temperature being displayed. OUTPUT MAXIMUM LOAD
WEIGHT Rload (max) = (Vsupply - 10V) / 0.020A
8 oz (227 g) (no options). INPUT IMPEDANCE
Greater than 100k ohms. EXTERNAL POWER RANGE
WARRANTY 10-35 VDC.
3 years parts and labor.

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com


Digital Panel Meters

Ordering Information
Panel Meters
Please select models from the table below.

Power: 85-265V AC Power: 12-36V DC 24V DC Dual 24V DC Two 4-20mA Modbus
Model No. or 90-265V DC or 12-24V AC Supply Supplies Relays Output Interface
APM765-6R0-00 • •
APM765-6R0-10 • • •
APM765-6R2-00 • • •
APM765-6R2-10 • • • •
APM765-6R3-00 • • •
APM765-6R3-10 • • • •
APM765-6R3-20 • • • •
APM765-7R0-00 • •
APM765-7R2-00 • • •
APM765-7R3-00 • • •

Accessories Field Enclosures


APMA2801
NEMA 4X plastic enclosure, holds one APM765 meter Low-Cost Plastic NEMA 4X Enclosure
APMA6845 The APMA2801 is a low-

APM Series®
Pipe-mount kit (2-inch pipe) for use with APMA2801. cost, compact, plastic
APMA7232 NEMA 4X enclosure that
RS-232 serial adapter, APMA7420 included will house one meter.
APMA7420
Standard modular cable, 7ft. (2.1m).
Pipe Mount Kit
The APMA6845 kit mounts a panel meter inside an
APMA7422 APMA2801 NEMA 4X enclosure to a 2-inch pipe.
RS-422/485 serial adapter, APM7420 included
APMA7503-1, APMA7503-2, APMA7503-3 Mounting Plate Hole Pattern
MeterView software with 1 meter license (-1 model),
10 meter license (-2), or 100 meter license (-3).
4.10"
(104mm)

8.20"
(208mm)

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com


APM Series

Application #1: Solution


Pump down with high alarm Model APM765-6R2-10 panel meter
Problem: Need to excite a 2-wire, 4-20mA continuous level sensor, and
provide two relay outputs. One relay for pump down and one relay for high
alarm with automatic or manual reset.

2-Wire Level Transmitter

+ P+ (24V DC) To pump motor


*R1
- mA + starter circuit

COM
1234 *R2 To high alarm
audible/visual circuit
R2 Energized Relay 2 P-
High Alarm

AC (85-265V AC) *Relay contacts shown


R1 Energized Relay 1 DC (90-265V DC) in de-energized or
High Level Trip "shelf" state.
"Pump On"

Pump Down

Reset Relay 1 & 2


"Pump Off" Reset
R1 & R2
APM Series

De-energized

APM Configuration & Relay Operation Timing Diagrams


Set-up Example
Input: 4-20mA R2 Set

Dec. Point: As needed (d.ddd, dd.dd, ddd.d, or dddd) R1 Set


Relay 1 Action: Automatic reset
Relay 1 Setpoint: As needed (e.g.; 16mA) R1 & R2
Reset
Relay 1 Reset: As needed (e.g.; 8mA)
Relay 2 Action: Auto-manual reset
t
Relay 2 Setpoint: As needed (e.g.; 18mA) De-energized
Relay 2 Reset: As needed or same as relay 1 R2
De-energized Energized
Failsafe Operation: None
R1
Time Delay: None Energized
LED 2
Display Scale 1: 4mA = 0% (or as needed) ACK
Display Scale 2: 20mA = 100% (or as needed) Pressed

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com


Digital Panel Meters

Application #2: Solution


Pump down w/duplex pump control Model APM765-6R2-10 panel meter
Problem: Need to excite a 2-wire, 4-20mA continuous level sensor, and provide For extra high/low alarm relays with built-in silence circuit (manual
two relay outputs for duplex pump control with alternation. Both pumps must reset and acknowledge), use additional APM765-6R2-00 and wire in
be turned on if one can’t handle the duty. series with 4-20mA loop.

2-Wire Level Transmitter

+ P+ (24V DC) To pump 1 motor


*R1
- mA + starter circuit

COM
1234 *R2 To pump 2 motor
R1 & R2 starter circuit
High Level Trip Energized Relay 2 P-
"Both Pumps On"
R1 or R2 AC (85-265V AC) *Relay contacts shown
Energized Relay 1 DC (90-265V DC)
High Level Trip in de-energized or
"One" Pump On "shelf" state.
Pump Pump
Down Down
with with
Alternation 2 Pumps

Reset Relay 1 & 2


Both Pumps Off Reset
R1 & R2
De-energized

APM Series®
APM Configuration & Relay Operation Timing Diagrams
Set-up Example Input
Input: 4-20mA R2 Set

Dec. Point: As needed (d.ddd, dd.dd, ddd.d, or dddd) R1 Set

Relay 1 Action: Alternate


Relay 1 Setpoint: As needed (e.g.; 16mA) R1 & R2
Reset
Relay 1 Reset: As needed (e.g.; 8mA)
Relay 2 Action: Alternate
t
Relay 2 Setpoint: Above relay 1 (e.g.; 18mA)
Relay 2 Reset: Same as relay 1 De-energized
Failsafe Operation: None Pump 1
Time Delay: None Energized

De-energized
Display Scale 1: 4mA = 0% (or as needed)
Pump 2
Display Scale 2: 20mA = 100% (or as needed) Energized

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com


APM Series

Application #3: Solution


Pump Up with overfill alarm Model APM765-6R2-10 panel meter
Problem: Need to excite a 2-wire, 4-20mA continuous level sensor, and
provide two relay outputs. One relay is for pump control (filling) and the
other relay is for high alarm (overfill) with automatic or manual reset.

2-Wire Level Transmitter

+ P+ (24V DC) To pump


*R1
- mA + motor

1234
starter circuit

High Alarm Relay 2 Energized COM To high alarm


(overfill) *R2
audible/visual
Reset Relay 1 De-energized Relay 2
P- circuit
"Pump Off" Relay 2 De-energized

AC (85-265V AC) *Relay contacts shown


Pump Up Relay 1
Low Level DC (90-265V DC) in de-energized or
Trip Relay 1 Energized "shelf" state.
"Pump On"
APM Series

APM Configuration & Relay Operation Timing Diagrams


Set-up Example
Input: 4-20mA R2 Set
Dec. Point: As needed (d.ddd, dd.dd, ddd.d, or dddd) R1 & R2
Reset
Relay 1 Action: Automatic
Relay 1 Setpoint: As needed (e.g.; 6mA)
R1 Set
Relay 1 Reset: As needed (e.g.; 16mA)
Relay 2 Action: Auto manual
t
Relay 2 Setpoint: As needed (e.g.; 18mA) De-energized

Relay 2 Reset: As needed (e.g.; 16mA) R1


Energized De-energized
Failsafe Operation: None
R2
Time Delay: None Energized
LED 2
Display Scale 1: 4mA = 0% (or as needed) ACK
Display Scale 2: 20mA = 100% (or as needed)

Tel: 248-295-0880 Fax: 248-624-9234 e-mail: sales@acromag.com www.acromag.com