Escolar Documentos
Profissional Documentos
Cultura Documentos
Modeling and temperature control of a two-stage, thermally coupled fluidized-bed reactor system
are addressed in this study. A process model and transfer function are determined by a transient
response technique and the reactor temperatures are controlled by PI controllers with tuning settings
determined by an internal model control (IMC) strategy. Using the IMC tuning method, sufficiently
good control performance was experimentally observed without lengthy on-line tuning. It is shown
that IMC strategy provides a means to directly use process knowledge t o make a control decision.
Although this control method allows for fine tuning by adjusting a single tuning parameter, it is
not easy to determine the optimal value of this tuning parameter, which must be specified by the
user. A novel method is presented to evaluate that parameter in this study. It was selected based
on the magnitude of elements on the off-diagonal of the relative gain array to account for the effect
of thermal coupling on control performance. I t is shown that this method provides stable and fast
control of reactor temperatures. By successfully decoupling the system, a simple method of extending
the IMC tuning technique to multiinput/multioutput systems is obtained.
v
600
500
-
- Combustion Reactor
Ms,pcs % = hpAp(Tr,p - Ts,p) + hh,pAh,p(Th - Ts,p)-
WCs(Ts,p - ‘ s , J - J’a,pCa(Ta,p - T a , J (1)
MS,CCS dTs’c - h A ~ ( T r , c - T8,c)
dt - hh,Ah,c(Te,c - Th) -
W C s ( T s , c - Ts,p) - J’a,cCa(Ta,c - T a , J (2)
Mr,PC !%.?
d t = Qp - h p A p ( T r , p - Ts,p) (3)
0 I I I I
dTr c
0 100 200 300 400 500 600
Mr,cCr dt = Qc - hcAc(Tr,c - TS,J (4)
Time, min Th
Figure 2. Temperature responses for slowly heating the combustion
MhCh dt = hh,Ah,c(Ts,c- Th) - hh,pAh,p(Th - Ts,p) (5)
reactor. The energy balances of eqs 1-5 represent a relatively
W rigorous model (called model l ) , and describe in detail the
temperature response of two beds, two vessel walls, and
V
n w Fp
I
the heat pipes. The model is relatively complex, making
it difficult to incorporate it directly into control algorithms.
Because in this study the IMC tuning method was used
to determine the temperature controller settings and the
controllers tuned by this technique were found to perform
well even under severe model error (Morari and Zafiriou,
1989),a simplified model was sought. Such a model should
allow for easy implementation into a control strategy
without sacrificing control performance.
Energy conservation equations (1)-(5) can be simplified
by neglecting the reactor energy conservation equations,
eqs (3) and (4), and assuming a constant heat input into
the beds. Consequently, a simpler reactor model (called
model 2) is formed from eqs 1,2, and 5, where the first
terms on the right-hand side of eqs 1and 2 are replaced
by Qpand Qc,respectively. In a similar manner, the energy
conservation equation ( 5 ) for the heat pipes can be
simplified by assuming no heat accumulation. Accord-
ingly, a further simplified model (called,model 3) is derived
from model 2, where eq 5 is replaced by the following
equation:
[ ]
order lead model:
kp(Bps+ 1)
T2S2 + 2TfS + 1
G,(s) = (17)
k,(Bs + 1)
7’s’ + +
2TfS 1
The constants k,, k,, B,, Bp, T , and f are defined here by
comparison with the elements on the main diagonal in eq
16. This decoupling, of course, causes serious modeling
where A = a m s 2 - (azb11+ alb22)s + bllbzz - b12b-21. T(s) errors. However, a major advantage of the IMC tuning
and M(s) are perturbation variables, which represent technique is that it can perform well despite serious model
controlled variables and manipulated variables, respec- mismatch conditions. Therefore, satisfactory control
tively. The transfer function is typical of a multiinput/ performance might be achieved despite this simplification.
multioutput system (MIMO), Le., a reactor temperature 4. The transfer function of the digital PID controllers
can be affected by both heat inputs (Q, and 8,) to the is based on the followingform, which includes an “optimal”
system. If ai and bij are assumed to be constants and the roll-off element (Morari and Zafiriou, 1989).
parameter values given in Table I are used, eq 15becomes
G,(s) e [ 295s 37
33
+ 30
133s2+ 48s + 1 133s’ + 48s 1
148s + 35
133s2+ 48s + 1 133s’ + 48s + 1
+
] (16)
By following the straightforward two-step IMC controller
design procedure (Rivera et al., 1986), the digital PID
controller settings can be calculated from the process
Based on this example, the process transfer function is model, Le., eq (17), via
second-order lag with time constant T 2 12 min and
damping coefficient of 2 (overdamped system). Due to
the relatively large time constant and the significant
thermal coupling effect, precise temperature regulation 5. Controller tuning settings can be calculated from eq
of the process becomes difficult. 19, provided that the value of T , is known. This so-called
Controller Design. The presence of process interac- closed-loop time constant is the only tuning parameter,
tions generally leads to a degradation of the control system specified by the user, which determines the closed-loop
performance. The classic approach to MIMO control speed of response. A smaller T , gives a faster return to the
problems is to incorporate decouplers into the control temperature setpoint while a larger T, results in slower
system. However, the success of the decoupler design response. Although a larger T, sacrifices performance, it
3034 Ind. Eng. Chem. Res., Vol. 32, No. 12, 1993
Process Test
Time, min
Control performance was evaluated on the basis of Figure 7. Temperature responses to the setpoint changes of PI
transient responses of the two reactor temperatures to controllers that are tuned by IMC strategy with = 6 min for a sand
setpoint changes. Temperatures in the pyrolysis (T,) and holdup in the combustion reactor of 3.6 kg.
combustion (T,) reactors were controlled according to the
following sequence over a 6-h period: caused by noisy temperature signals). To avoid this
problem, the derivative control action was nullified by
1. Tp= 475 "C, T,= 500 "C setting 7 d to zero. Subsequently, significant improvement
in control performance was achieved by using the PI
2. Tp= 475 "C, T,= 550 "C controllers, as shown in Figure 7. Thus, PI controllers
were used in all of the subsequent tests.
3. Tp= 525 "C, T,= 550 "C As observed in Figure 7, sufficiently good controller
settings were obtained through the IMC tuning method
4. Tp= 575 "C, T,= 600 "C without lengthy on-line tuning. At least, the settings
obtained here can be used as the initial values for an on-
The control objectivewas to force the reactor temperatures line tuning operation. However, the settings may not be
to track their setpoints quickly and smoothly. optimal values, which is indicated by the relatively long
For IMC-based controllers, the choice of a closed-loop settling time. This imperfection is likely due to the
time constant, T,, has a strong influence on the control inaccurate system transfer function, which results from
results. Chien and Fruehauf (1990) suggested T, values the process/model mismatch. There are two dominant
between the open-loop dominant time constant and the sources of model error. The first, due to the inherent
process dead time. On the other hand, Morari and Zafiriou assumptions in model 1 (e.g., constant heat capacities,
(1989) indicated that T, should be selected at least greater ambient heat loss) is relatively small, as can be seen in
than one-tenth of the process time constant T . For our Figure 4. However, the error resulting from neglecting
study purposes, the tuning prameter, r,, was selected to the thermal coupling between the two beds is significant,
be one-half of the process time constant (i.e., -6 min). and dominates the model mismatch. The different types
Then, PID controller settings were calculated by eq 19. of model error may require a design procedure not provided
The resulting PID control with the calculated settings is for in the IMC tuning method.
shown in Figure 6, where the reactor temperatures According to eq 19,the IMC tuning method incorporates
fluctuate and cannot reach steady-state values within the the tuning parameter, r,, into the controller design, which
test period. Small, but vigorous, temperature fluctuations in turn decreases the controller proportional constants.
(Le., within *3 "C) were observed during the test run, As a result, the control system is sluggish but relatively
caused by one or more of a number of possible causes (e.g., insensitive to model error. In principle, this feature should
oscillatory sand holdups, derivative-dominated control improve control performance when an exact process model
Ind. Eng. Chem. Res., Vol. 32,No. 12, 1993 3035
625 I 1
600
575
550
525
500
475
A
cc_ _ _ _ _ _ _ _ 1 -Tc setpoint 475
- Tcsetpoint
_ _ _ - _ Tp
_ setpoint
I I
0 20 40 60 80 100 120 140 160 180 200