Você está na página 1de 8

Ind. Eng. Chem. Res.

1993,32, 3029-3036 3029

Modeling and Temperature Regulation of a Thermally Coupled Reactor


System via Internal Model Control Strategy
S. Y. Lee$ C. J. Coronella, A. S. Bhadkamkar, and J. D. Seader*
Department of Chemical and Fuels Engineering, University of Utah, Salt Lake City, Utah 84112

Modeling and temperature control of a two-stage, thermally coupled fluidized-bed reactor system
are addressed in this study. A process model and transfer function are determined by a transient
response technique and the reactor temperatures are controlled by PI controllers with tuning settings
determined by an internal model control (IMC) strategy. Using the IMC tuning method, sufficiently
good control performance was experimentally observed without lengthy on-line tuning. It is shown
that IMC strategy provides a means to directly use process knowledge t o make a control decision.
Although this control method allows for fine tuning by adjusting a single tuning parameter, it is
not easy to determine the optimal value of this tuning parameter, which must be specified by the
user. A novel method is presented to evaluate that parameter in this study. It was selected based
on the magnitude of elements on the off-diagonal of the relative gain array to account for the effect
of thermal coupling on control performance. I t is shown that this method provides stable and fast
control of reactor temperatures. By successfully decoupling the system, a simple method of extending
the IMC tuning technique to multiinput/multioutput systems is obtained.

Introduction In recent years, Rivera et al. (1986) introduced a PID


A two-stage, thermally coupled fluidized-bed reactor tuning technique based on an internal model control (IMC)
system has been developed for energy-efficient conversion structure that has received much attention (Chien and
Fruehauf, 1990;Rotstein and Lewin, 1991; Chang and Yu,
of tar-sand bitumen to synthetic crude oil (Oblad et al., 1992). The IMC scheme has a number of advantages over
1987; Coronella and Seader, 1992). In the first reactor, conventional PID tuning methods. For example, it uses
the bitumen is pyrolyzed at 450-550 "C to condensable only one tuning parameter (closed-looptime constant, rC)
crude oil and a light gaseous product. Coke, formed as a that can be adjusted to yield the best compromise between
by-product from the pyrolysis reaction and left behind on performance and robustness (Morari and Zafhiou, 1989).
the sand, flows into the second reactor and is combusted A larger value of the tuning parameter results in more
with air at 550-650 "C. Excess energy generated by the robust control which, in turn, makes the designed con-
combustion reaction is then transferred by liquid-potas- trollers insensitive to model error. Thus, the concept of
sium-containing heat pipes to the first reactor, providing the IMC structure provides a way to include robustness
the energy required by the pyrolysis reaction and the as a design criterion in an explicit manner. In addition,
preheat for bringing the tar-sand feed to operating a simulation study by Chien (1988) showed that the IMC-
temperature. The use of the heat pipes causes significant based tuning method was superior to the Ziegler-Nichols
thermal interaction between the two reactors, with a and Cohen-Coon tuning methods for setpoint responses
relatively large time constant. As a result, precise regu- in dead-time-dominant processes; also, it worked very well
lation of the reactor temperatures becomes a complicated under severe model mismatch conditions. Chien and
control problem (Hsu and Seader, 1989). Fruehauf (1990) also indicated that this tuning technique
Despite many advanced control strategies proposed in minimizes controller interactions and enhances overall
the past 20 years, the majority of controllers used in the process disturbance rejection, resulting in no oscillation
chemical industry are still of the proportional-integral- or overshoot of the closed-loop load response. Therefore,
derivative (PID) type. It is recognized that most of the it appeared that a better temperature control of the tar-
major advanced feedback control algorithms to date can sands processing system might be obtained via the IMC-
be converted into some form of the PID algorithm (Bohl
and McAvoy, 1976; Rivera et al., 1986; McMillan, 1986). based tuning technique.
Although IMC has been studied extensively, most
Also, a well-tuned PID controller can do better than most studies are based on simulation or theoretical analysis;
advanced control algorithms for unmeasured load dis- very little laboratory experimental work has been con-
turbances (McMillan, 1990). Hsu and Seader (1989) ducted. The study reported here presents digital PID
employed various control schemes, including PID control, controllers, tuned by the IMC technique, that are used to
deadbeat algorithm, Dahlin's method, and Kalman's control temperatures of the tar-sands reactor processing
approach (Smith, 1972),to regulate temperatures of a tar- clean sand (not tar sand). Dynamic simulation of the
sands processing system. They found that the PID thermal behavior of the reactor system was also carried
algorithm yielded the best control performance, although out at various levels of complexity to illustrate the effect
it was difficult to determine the optimum tuning settings. of model error on the control performance. Because the
Even though several tuning techniques, such as continuous reactor system is thermally coupled and the temperatures
cycling and reaction curve methods (Seborg et al., 1989), are interrelated, this study provides a better understanding
are widely used to determine controller settings, the best of the application of the IMC tuning technique to systems
settings are normally difficult to obtain, and thus, lengthy involving process interactions.
on-line tuning may be necessary.
Experimental Section
* Author to whom correspondence should be addressed.
+ Current address: at Hoechst Celanese Corp., Corpus Christi, Reactor System. As shown in Figure 1, the laboratory
TX. reactor system consists of two 4-in.-diameter fluidized-
0SSS-5S8~/93/2632-3029$04.00/0 @ 1993 American Chemical Society
3030 Ind. Eng. Chem. Res., Vol. 32, No. 12, 1993
n transmitters, which measured the pressure drops across
the fluidized beds and maximum pressures below the gas
distributors. A four-channel D/A converter (HP E1328A)
was used to provide four independent, isolated channels
of digital-to-analog (D/A) output capacity. Two output
channels sent variable voltage signals to the pressure
transducers for regulating the two solids control valves.
The other two output channels were used to control
temperatures in the two reactors by sending variable DCV
(direct current voltage) signals to single-phase, phase-
angle-fired (SCR) power controllers, which in turn reg-
ulated ACV (alternating current voltage) to the electrical
heaters. All manipulated variables were sent to the process
through a zero-order hold.
A computer code was developed for data acquisition
and execution of control algorithms. Typical procedures
for the process control included acquisition of on-line data,
noise rejection of the pressure-drop data, comparison of
process variables and setpoints, calculation of appropriate
control signals, and transfer of the control signals to the
process. Because the sampling period was taken as only
5 s, much less than the dominant time constants, the digital
control algorithms provided good approximations to
- Air In I
continuous controllers. Therefore, the transfer function
in Laplace transform notation was used in this control
study. Detailed control strategy will be discussed later.
I\
V The control system was evaluated from the point of view
of its ability to handle servo problems. Prior to all test
runs, the reactor system was maintained at "hot" conditions
DP Differential-PressureTransmitter (approximately 20 "C less than the initial temperature
vp Electric-To-PneumaticConverter setpoints) overnight to yield better reproducibility.
LC Level Controller
TC Temperature Controller
Mathematical Model
SCR Power Package A rigorous mathematical model of the fluidized-bed
C-O+J Heating Wire reactor system has been under development (Coronella
@ AC Source and Seader, 1992). Although the model can provide a
detailed description of the reactor system, it is relatively
Figure 1. Laboratory experimental apparatus and instrumentation. complex and, thus, is not considered suitable for on-line
control applications of the type discussed here. Instead,
bed reactors thermally coupled by three potassium- alinear time-invariant model was developed for the control
containing heat pipes. In this work, ambient-temperature study reported here. Since the major purpose of a control
silica sand was continuously fed into the upper fluidized model is to provide a basis for evaluating temperature
bed (i.e., pyrolysis reactor), transported to the lower controller settings, only thermal characteristics of the
fluidized bed (i.e., combustion reactor) by gravity through process are of concern.
a standpipe, and then discharged from the bottom of the The primary mechanisms of heat transfer through the
combustion reactor. Solids retention times (or sand three heat pipes are conductive evaporation and conden-
holdups) in the two reactors were regulated by two solids sation. When the heat pipes are in operation, the lower
control valves employing a digital PID control algorithm end of each heat pipe is heated to a relatively high
in conjunction with a valve linearization method (Hsu temperature, causing liquid potassium to vaporize. The
and Seader, 1989). Both reactors were equipped with vapor then moves at speeds approaching sonic velocity
independent electrical heaters to allow for separate from the lower end to the upper end of the heat pipe,
temperature control of each reactor. In all test runs, where it condenses at a lower temperature, releasing its
temperature in the combustion reactor (T,) was always latent heat of vaporization. The condensed liquid is then
maintained higher than that in the pyrolysis reactor (Tp). returned to the lower end along a wick on the inside pipe
Ambient-temperature compressed air was employed as wall by gravity for reevaporation. Obviously, for the heat
the fluidizing gas. In the work presented here, only clean pipes to function properly, the temperature of the lower
sand was fed to the reactor. Thus, no pyrolysis or section must be high enough to vaporize the liquid
combustion reaction occurred in the beds. potassium. A test was carried out by slowly increasing
Control System. A computer control system, consist- the temperature in the lower combustion reactor. It can
ing of an H P Vectra personal computer and a data be seen in Figure 2 that a time delay is generated by the
acquisition unit, was used for data logging and process heat pipes before energy is transferred to the pyrolysis
control. The system handled communications of control reactor. The heat-transfer rate through the heat pipes
signals and data between the computer and the process increased rapidly only when the temperature in the
via an HPIB (Hewlett-Packard Interface Bus) interface. combustion bed was above 450 "C. Accordingly, initial
Two 16-channel thermocouple relay multiplexers (HP temperatures in the combustion reactor were at least 450
E1347A) were employed to provide basic analog-to-digital "C for all experiments studied here, so that the time-delay
conversion capability for data logging. One of the mul- behavior at low temperatures was irrelevant. This practice
tiplexers was used to measure temperature and the other assured that the thermal coupling effect of the reactor
was used to read output signals from four pressure system could be adequately addressed.
Ind. Eng. Chem. Res., Vol. 32, No. 12, 1993 3031
700 system are given by

v
600

500
-
- Combustion Reactor
Ms,pcs % = hpAp(Tr,p - Ts,p) + hh,pAh,p(Th - Ts,p)-
WCs(Ts,p - ‘ s , J - J’a,pCa(Ta,p - T a , J (1)
MS,CCS dTs’c - h A ~ ( T r , c - T8,c)
dt - hh,Ah,c(Te,c - Th) -
W C s ( T s , c - Ts,p) - J’a,cCa(Ta,c - T a , J (2)

Mr,PC !%.?
d t = Qp - h p A p ( T r , p - Ts,p) (3)
0 I I I I
dTr c
0 100 200 300 400 500 600
Mr,cCr dt = Qc - hcAc(Tr,c - TS,J (4)

Time, min Th
Figure 2. Temperature responses for slowly heating the combustion
MhCh dt = hh,Ah,c(Ts,c- Th) - hh,pAh,p(Th - Ts,p) (5)
reactor. The energy balances of eqs 1-5 represent a relatively
W rigorous model (called model l ) , and describe in detail the
temperature response of two beds, two vessel walls, and

V
n w Fp
I
the heat pipes. The model is relatively complex, making
it difficult to incorporate it directly into control algorithms.
Because in this study the IMC tuning method was used
to determine the temperature controller settings and the
controllers tuned by this technique were found to perform
well even under severe model error (Morari and Zafiriou,
1989),a simplified model was sought. Such a model should
allow for easy implementation into a control strategy
without sacrificing control performance.
Energy conservation equations (1)-(5) can be simplified
by neglecting the reactor energy conservation equations,
eqs (3) and (4), and assuming a constant heat input into
the beds. Consequently, a simpler reactor model (called
model 2) is formed from eqs 1,2, and 5, where the first
terms on the right-hand side of eqs 1and 2 are replaced
by Qpand Qc,respectively. In a similar manner, the energy
conservation equation ( 5 ) for the heat pipes can be
simplified by assuming no heat accumulation. Accord-
ingly, a further simplified model (called,model 3) is derived
from model 2, where eq 5 is replaced by the following
equation:

Th = hh,Ah,cTa,c + hh,pAh,pTs,p (6)


h h , k h , c + hh,pAh,p

Figure 3. Schematic representation of the reactor system for


Each of the three models, with appropriate parameter
developing an energy balance. values, was used to simulate transient behavior of the
reactor system; the simplest was adopted for the control
With the above-described evaporation-condensation study.
cycle, heat pipes can rapidly transport a large amount of
heat from the lower section to the upper section with an Transient Response
extremely small temperature gradient (Dunn and Reay, Model parameters were determined by best-fitting
1982). Therefore, it is assumed that the temperature of experimental open-loop step response curves to the model
the three heat pipes is uniform. I t may be assumed that, predictions. To obtain the response curves, step changes
within a specific temperature range, the effective thermal in electric power inputs, Qp and Qc to the system were
conductivity of the heat pipes was greater than that for made to force the reactor temperatures to seek new steady-
an equivalent copper rod. In addition, each fluidized bed state values. An effort was made to reduce the number
can be viewed as a continous stirred tank operated under of adjustable parameters by exploring the relationship
isothermal constant-holdup conditions with respect to sand between effective heat-transfer coefficients in the two
flowing through the reactor system. As a result, the whole reactors. Although there have been many empirical
reactor system can be schematically represented by Figure correlations proposed to estimate fluidized-bed-to-surface
3. Thermal resistances to convective and radiative heat heat-transfer coefficients, most of them are not reliable or
transfer between the inside wall of a reactor and its require knowledge of parameters that are not generally
fluidized bed and between the outer surface of a heat pipe available (Saxena and Ganzha, 1985). Under bubbling
and the surrounding fluidized bed were thought to be the fluidization conditions with silica sands, the maximum
most significant, and thus, equivalent convection is the heat-transfer coefficient between an immersed surface
only heat-transfer mechanism considered here. Accord- (e.g., heat-pipe surface) and a fluidized bed can be
ingly, the dynamic energy balances for the two-reactor estimated by (Zabrodsky et al., 1976)
3032 Ind. Eng. Chem. Res., Vol. 32, No. 12, 1993
600 Table I. Adjustable Model Parameters and Their Best-Fit
Values for the Base Case*
adjustable parameter model 1 model 2 model 3
Combustion Reactor
Qc, kcal/min 15.9 15.5 15.4
hh,&,c, kcal/(min.K) 0.29 0.29 0.28
@ Mr,ckg, 0.95
J
0 C, N 0.25 kcal/(kg.K); Ch N C, c* 0.12 kcal/(kp.K); C
. N 0.24
t kcal/(kg.K); h f h 3.9 kg; Qh = 0 kcal/min; hc hh,c; h p hkp.
800 I 1
350 - -Model 1
Model 2 700
-.- - - - - Model 3
300 I I 1 I I 1 t
v
lime, min
Figure 4. Comparison of three process models with experimental
results.
400
(7) I

However, eq 7 is seldom used directly to calculate a heat- 300 - ' 1 I I 1


transfer coefficient because the maximum heat-transfer 0 200 400 600 800 1000
coefficient is normally difficult to realize (Zabrodsky et
al., 1976) due to,for example, the disturbance caused to Time, min
the local fluidization condition when immersing a tube in Figure 5. Justification of model 3 with subsequent step increases
the bed. Thus, the proportionality constant, 35.8, might in electric power to the reactor system.
not be appropriate. In this study, the sand-particle density
and particle diameter in the two reactors are the same. major drawback of the step-response technique is that it
Thus, the heat-transfer coefficient is mainly affected by assumes the system to be time-invariant. In reality, the
air thermal conductivity, which, at near-atmospheric two-reactor system is subjected to variations in parameters.
pressure, is proportional to the absolute temperature raised For instance, the heat-transfer coefficient is a function of
to an exponent of 0.84. By substituting this temperature temperature and should not be a constant as temperature
effect into eq 7 and recognizing that gas and particle changes with time. Nevertheless, time-invariant param-
temperatures are equal in fluidized beds, the following eters were assumed and found by fitting data using the
useful relationship is derived: maximum-likelihood method. The calculated parameter
values are summarized in Table I, where only those
associated with the combustion reactor are presented. The
corresponding values in the pyrolysis reactor can be
estimated by eqs 8 and 9. The calculated heat input is
Surface area of heat pipes immersed in a fluidized sand only about 87% of the electric power to the system,
bed, vessel wall heat-transfer area, and the mass of the implying a 13% heat loss, despite the heavy insulation
reactor vessel are each assumed to be proportional to sand used. Nevertheless, Figure 4 shows that all three models
holdup, i.e., give reasonably satisfactory results, with model 1fitting
-=-=-=-
Ah,p Mr,~ M s , ~
the data most closely, and model 3 fitting the data least
closely, as might be expected.
A~ Ah,c Mr,c M a , ~ The data points in Figure 5 characterize the response
where sand mass holdups and can be determined of the two-reactor system to two step increases in heat
by the setpoints of bed-level controllers. For a base case, input, i.e., a step increase in electric power to the
the feed rate of silica sand is about 2.5 kg/h and the combustion reactor at 100 min followed by an electric-
fluidizing air velocities are 45 and 90 scfh (standard cubic power increase to the pyrolysis reactor at approximately
feet per hour) for pyrolysis and combustion reactors, 550 min. The solid lines in Figure 5 were calculated by
respectively. The sand holdups in the two laboratory model 3. As can be seen, although heat transfer in the
reactors are approximately 1.8 and 3.6 kg. heat pipes is limited to the upward direction from the
In a typical experiment, electric power to the combustion combustion bed to the pyrolysis bed, an increase in electric
reactor was suddenly increased by about 18 kcal/min after power to the pyrolysis reactor not only increases the
the system reached a steady state (Ts,c= 470 "C),at a time temperature in the pyrolysis reactor but also increases
arbitrarily called zero. Reactor temperatures responded the temperature in the combustion reactor. This is
rapidly to the small amount of additional heat input and possible because a higher temperature in the pyrolysis
then slowly moved to another steady state, as shown in reactor lowers the rate of energy transfer from the
Figure 4 (closed circles and squares). The process dead combustion reactor, resulting in an increase in the com-
time was observed to be only about 1min. Compared to bustion-reactor temperature. Because the models devel-
the process time constant, the dead time is unimportant oped in this study are independent of the direction of heat
and can be neglected. Therefore, digital PID control transfer in the heat pipes, the significance of this test was
algorithms without any dead-time compensation were used to evaluate the validity of the proposed models. It was
throughout this study. found that model 3, the simplest of the three models
Various adjustable parameters were used, depending developed above, could, with appropriate adjustable
on the model selected, to fit the experimental data. The parameter values, predict satisfactorily the dominant static
Ind. Eng. Chem. Res., Vol. 32, No. 12,1993 3033
and dynamic behavior of the system. As a result, model largely relies on the accuracy of a process model and, thus,
3 was chosen for the control study reported next. is very sensitive to the mismatch between the model and
the real process (Skogestad and Morari, 1988). This
Control Strategy feature seriously limits its application because an exact
process model is normally difficult to obtain. Other
Transfer Function. In this study, individual power multivariable control schemes based on IMC have been
input to a reactor is the manipulated variable to control proposed (Garcia and Morari, 1985; Morari and Zdiriou,
the reactor temperature (i.e., controlled variable). By 1989),but are difficult to apply to the system of this study.
combining eq 6 with eqs 1 and 2 to eliminate Th, model Alternatively, the velocity form of the PID control
3 can be converted to the following mathematical forms: algorithm, with settings determined by the IMC tuning
technique, was adopted. It was anticipated that, with this
control strategy, the requirements of an exact process
model and complicated decoupling design could be avoid-
ed, providing a simple control strategy for MIMO control.
a2 % = b2,T0,,+ b2,T0,,+ 8,’
The detailed procedure and the justification are as follows:
1. Two separate digital PID controllers are used for the
temperature control. The relative gain array (RGA) of
where ai and bij are functions of process variables and the system in eq 16 is
model parameters, e.&, bll = (hh,Ah,p)’/(hh,dh,p + hh,dh,c)
-h h , d h , , - WC,- Fa,pCa.The process variables and model
parameters are dependent upon operating conditions.
RGA = [0*56
0.44 0.56
‘*.“I
Laplace transforms of eqs 10 and 11are taken and solved Based on this RGA, it is determined that TB,,and Ta,,
simultaneously, resulting in the following process transfer should be paired with Qp and Qe,respectively.
function: 2. The changes in reactor temperatures resulting from
heat transfer through the heat pipes are not controllable
T(s) = Gp(s) M(s) (12) and, thus, are regarded as load disturbances. Accordingly,
where the thermal coupling effect (Le., off-diagonal elements in
the RGA) is treated as an unmeasured disturbance in
developing the control algorithm.
3. By neglecting the off-diagonal elements in eq 15, the
transfer function becomes a second-order-lag-plus-first-

[ ]
order lead model:

kp(Bps+ 1)
T2S2 + 2TfS + 1
G,(s) = (17)
k,(Bs + 1)
7’s’ + +
2TfS 1
The constants k,, k,, B,, Bp, T , and f are defined here by
comparison with the elements on the main diagonal in eq
16. This decoupling, of course, causes serious modeling
where A = a m s 2 - (azb11+ alb22)s + bllbzz - b12b-21. T(s) errors. However, a major advantage of the IMC tuning
and M(s) are perturbation variables, which represent technique is that it can perform well despite serious model
controlled variables and manipulated variables, respec- mismatch conditions. Therefore, satisfactory control
tively. The transfer function is typical of a multiinput/ performance might be achieved despite this simplification.
multioutput system (MIMO), Le., a reactor temperature 4. The transfer function of the digital PID controllers
can be affected by both heat inputs (Q, and 8,) to the is based on the followingform, which includes an “optimal”
system. If ai and bij are assumed to be constants and the roll-off element (Morari and Zafiriou, 1989).
parameter values given in Table I are used, eq 15becomes

G,(s) e [ 295s 37

33
+ 30
133s2+ 48s + 1 133s’ + 48s 1
148s + 35
133s2+ 48s + 1 133s’ + 48s + 1
+
] (16)
By following the straightforward two-step IMC controller
design procedure (Rivera et al., 1986), the digital PID
controller settings can be calculated from the process
Based on this example, the process transfer function is model, Le., eq (17), via
second-order lag with time constant T 2 12 min and
damping coefficient of 2 (overdamped system). Due to
the relatively large time constant and the significant
thermal coupling effect, precise temperature regulation 5. Controller tuning settings can be calculated from eq
of the process becomes difficult. 19, provided that the value of T , is known. This so-called
Controller Design. The presence of process interac- closed-loop time constant is the only tuning parameter,
tions generally leads to a degradation of the control system specified by the user, which determines the closed-loop
performance. The classic approach to MIMO control speed of response. A smaller T , gives a faster return to the
problems is to incorporate decouplers into the control temperature setpoint while a larger T, results in slower
system. However, the success of the decoupler design response. Although a larger T, sacrifices performance, it
3034 Ind. Eng. Chem. Res., Vol. 32, No. 12, 1993

can tolerate greater modeling errors and minimize control- 625


loop interactions. Thus, with a proper choice of ?, the
1
PID controllers can satisfy performance requirements, but
still allow some modeling errors as well as process
interactions. Thus, even though the thermal coupling
effect is not explicitly considered in developing the control
algorithm (see procedure 21, the effect is indeed taken
into account by adjusting the controller tuning settings.
6. The RGA is employed here to help determine the
proper value of 7,. When the model error and process
interactions are significant, which is indicated by large - Tc setpoint
off-diagonal elements in the RGA, the value of 7, should
475
J- -W ... .... . .
...__.
Tp setpoint
be increased to enhance the controller robustness. Thus, I I

depending on the magnitude of RGA, a proper 7, value


might be chosen.
7. The parameters of the process model are automat- Time, rnin
ically adjusted based on operating conditions to account
for the nonlinear and time-variant nature of the reactor Figure 6. Temperature responses to the setpoint changes of PID
controllers that are tuned by IMC strategy with T~ = 6 min.
system. The idea is very similar topredetermined adaptive
controllers, where the adaptation rule is determined as
part of the control system design. One example is the
electric power (Le., V / R )to the reactor system, which is
regulated by SCR power controllers. At low output voltage
(ACV),a small change in DCV signal to the SCR produces v
only a modest change in the electric power while the same
DCV change will produce a relatively large change in the
power in the high-voltage range. Thus, the process gain,
in this case the ratio of a change in the electric power to
a change in the DCV signal, increases rapidly as the ACV
increases to its maximum value (i.e., 110 V). Since their - T,setpoint
relationship is reasonably well understood, it is possible 475 - - - -- - - - -- .
..___.
Tp setpoint
to compensate for this change in process gain in a 450 '
predetermined manner. +

0 20 40 60 80 100 120 140 160 180 200

Process Test
Time, min
Control performance was evaluated on the basis of Figure 7. Temperature responses to the setpoint changes of PI
transient responses of the two reactor temperatures to controllers that are tuned by IMC strategy with = 6 min for a sand
setpoint changes. Temperatures in the pyrolysis (T,) and holdup in the combustion reactor of 3.6 kg.
combustion (T,) reactors were controlled according to the
following sequence over a 6-h period: caused by noisy temperature signals). To avoid this
problem, the derivative control action was nullified by
1. Tp= 475 "C, T,= 500 "C setting 7 d to zero. Subsequently, significant improvement
in control performance was achieved by using the PI
2. Tp= 475 "C, T,= 550 "C controllers, as shown in Figure 7. Thus, PI controllers
were used in all of the subsequent tests.
3. Tp= 525 "C, T,= 550 "C As observed in Figure 7, sufficiently good controller
settings were obtained through the IMC tuning method
4. Tp= 575 "C, T,= 600 "C without lengthy on-line tuning. At least, the settings
obtained here can be used as the initial values for an on-
The control objectivewas to force the reactor temperatures line tuning operation. However, the settings may not be
to track their setpoints quickly and smoothly. optimal values, which is indicated by the relatively long
For IMC-based controllers, the choice of a closed-loop settling time. This imperfection is likely due to the
time constant, T,, has a strong influence on the control inaccurate system transfer function, which results from
results. Chien and Fruehauf (1990) suggested T, values the process/model mismatch. There are two dominant
between the open-loop dominant time constant and the sources of model error. The first, due to the inherent
process dead time. On the other hand, Morari and Zafiriou assumptions in model 1 (e.g., constant heat capacities,
(1989) indicated that T, should be selected at least greater ambient heat loss) is relatively small, as can be seen in
than one-tenth of the process time constant T . For our Figure 4. However, the error resulting from neglecting
study purposes, the tuning prameter, r,, was selected to the thermal coupling between the two beds is significant,
be one-half of the process time constant (i.e., -6 min). and dominates the model mismatch. The different types
Then, PID controller settings were calculated by eq 19. of model error may require a design procedure not provided
The resulting PID control with the calculated settings is for in the IMC tuning method.
shown in Figure 6, where the reactor temperatures According to eq 19,the IMC tuning method incorporates
fluctuate and cannot reach steady-state values within the the tuning parameter, r,, into the controller design, which
test period. Small, but vigorous, temperature fluctuations in turn decreases the controller proportional constants.
(Le., within *3 "C) were observed during the test run, As a result, the control system is sluggish but relatively
caused by one or more of a number of possible causes (e.g., insensitive to model error. In principle, this feature should
oscillatory sand holdups, derivative-dominated control improve control performance when an exact process model
Ind. Eng. Chem. Res., Vol. 32,No. 12, 1993 3035
625 I 1
600

575

550

525

500

475
A
cc_ _ _ _ _ _ _ _ 1 -Tc setpoint 475
- Tcsetpoint
_ _ _ - _ Tp
_ setpoint
I I
0 20 40 60 80 100 120 140 160 180 200

Time, min Time, min


Figure 8. Temperature responses to the setpoint changes of PI Figure 10. Temperature responses to the setpoint changes of PI
controllers that are tuned by IMC strategy with T~ = 40 min. controllers that are tuned by IMC strategy with rC= 6 min for a sand
holdup in the combustion reactor of 7.2 kg.
pled. In principle, when T~ decreases below some value,
the control system will become unstable, and then control
robustness becomes an important issue. However, in this
study, this unstable situation was never observed, even
with a relatively small T~ value. I t is believed that the
electric heaters of the reactor system have a finite
maximum heat duty, which essentially prevents the process
from becoming unstable. As a result, the consideration of
control robustness by the IMC tuning technique becomes
-Tc setpoint irrelevant.
.___
Tp _ .
setpoint
The control test of Figure 7 was repeated using the same
# , I I PI controllers and settings but increasing the sand holdup
0 20 40 60 80 100 120 140 160 180 200 in the combustion reactor from 3.6 to 7.2 kg to investigate
the effect of changing operating conditions on controller
settings. Figure 10 shows the closed-loop control result
Time, rnin for T~ = 6 min. By carefully comparing Figure 10 and
Figure 9. Temperature responses to the setpoint changes of PI Figure 7,for the same T ~it,was found that, with the same
controllers that are tuned by IMC strategy with T~ = 0.5 min. controller settings, control performance is less satisfactory
for the case of largersand holdup in the combustion reactor.
is not available. However, the process studied here is To achieve the same control performance, the T~ value
strongly influenced by thermal interaction, and the should be decreased. This finding suggests that the value
sluggish control action cannot quickly counteract the of T~ should be adjusted with changing operating condi-
temperature disturbances caused by the interaction. tions. Because most chemical processes are nonlinear in
Consequently, good control performance cannot be nature, adjusting controller settings to cope with changing
achieved. IMC theory suggests that T~ should increase operating conditions is a common practice for a better
with increasing model error. Because the transfer function process control. However, most conventional tuning
developed here has a relatively large model error resulting techniques (Seborg et al., 1989) require more than one
from the neglect of the thermal coupling effect, a large T~ tuning parameter, which makes tuning very difficult.
value should be usedaccording to the IMC controlstrategy. On the basis of the formula to calculate the RGA, it is
Obviously, this guideline is not valid for the study reported known that the thermal interaction increases with in-
here. Instead, to quickly respond to thermal disturbances, creasing surface area of heat pipes immersed in sand. Thus,
a small TCshould be used. Thus, depending on the sources the less satisfactory control performance with increasing
of model error, different control strategies or T~ values sand holdup might be due to an increasing thermal
should be adopted. coupling effect. It has been concluded that a small T~
An advantage of the IMC tuning method is that control value should be used when the thermal coupling effect is
performance or robustness can be achieved simply by large. In other words, depending on the significance of
adjusting the sole tuning parameter, T ~ .The effect of T~ the thermal interaction, the T~ value should be adjusted
on IMC-based control was studied with the reactor system accordingly. IMC theory does not reveal a method for
using PI controllers, with results given in Figures 8 and determining a value for T ~ .However, because the IMC
9 for T~ = 40 and 0.5 min, respectively. IMC theory predicts tuning method uses only one tuning parameter, it generally
that a larger T~ increases control robustness but sacrifices can yield a straightforward relationship between the
control performance. As expected, in Figure 8 the control parameter and the nature of the process. For instance, in
performance becomes worse with increasing T ~ and , a this study, the magnitude of off-diagonal elements in the
smaller T~ gives the much better control result in Figure RGA, which is proportional to the thermal interaction,
9. The optimal T~ values obtained here are less than the was used to help determine a value for T ~ .A simple tuning
recommended values (Chien and Fruehauf, 1990; Morari guideline was developed on the basis of the above studies;
and Zafiriou, 1989). The recommended T~ values do not i.e., the value of T~ should decrease with increasing
work well because this system, which is inherently highly magnitude of off-diagonal elements in the RGA. With
coupled, as seen in the RGA, has essentially been decou- this approach, satisfactory control performance was ob-
3036 Ind. Eng. Chem. Res., Vol. 32, No. 12, 1993
tained regardless of operating conditions. It is believed ~i = integral constant of a PID controller
that, by carefully studying the nature of processes, the 7f = parameter of optimal roll-off element in eq 17
IMC tuning procedure used in this study can be applied {= damping coefficient
to many chemical processes, providing a simple way to Subscripts
tune PID controllers not only for SISO (single-input/single-
output) but also for MIMO systems. a = air
c = combustion reactor
h = heat pipe
Conclusions o = ambient conditions
Precise temperature control of a coupled two-reactor p = pyrolysis reactor
system is difficult because of a relatively large thermal r = reactor vessel
interaction and the nonlinear nature of the process. To s = silica sand
control the reactor temperatures precisely,controllers must
account for the thermal coupling effect and the effect of Literature Cited
changing operating conditions on the controller design. Bohl, A. H.; McAvoy,T.J.Linear Feedbackvs. Time Optimal Control,
This study shows that the IMC strategy provides a means 11. The Regulator Problem. Znd. Eng. Chem. Process Des. Deu.
to directly use process knowledge and a process model to 1976,15,30-33.
make a control decision. However, the major drawback Chang, J. W.; Yu, C. C. Failure Conditions for Inverse-Based
of the IMC tuning technique is that it is difficult to Multivariable Controllers: Internal Model Control Structure.
Chem. Eng. Sci. 1992,47,2047-2056.
determine the optimal value of its only tuning parameter, Chien, I. L. IMC-PID ControllerDesign-An Extension. ZFACSymp.
T~ Even though some typical 7,values have been suggested Adaptive Control Chem. Proc. 1988,147-151.
before, this study shows those recommended values might Chien, I. L.; Fruehauf, P. S. Consider IMC Tuning to Improve
not be appropriate for the process investigated here. Controller Performance. Chem. Eng. Prog. 1990,October, 33-41.
Instead, the relative gain array was used in this study to Coronella, C. J.; Seader, J. D. Combustion of Coked Sand in a Two-
Stage Fluidized Bed System. Fuel 1992,71, 143-150.
help determine the proper Tcvalue,which provides a simple Dunn, P.; Reay, D. A. Heat Pipes; Pergamon Press Ltd.: Elmsford,
approach to extend the IMC strategy to multiinput/ N Y , 1982.
multioutput systems. Garcia, C. E.; Morari, M. Internal Model Control. 2. Procedure for
Multivariable Systems. Znd. Eng. Chem. Process Des. Deu. 1985,
Acknowledgment 24,472-484.
Hsu,J. C. L.; Seader, J. D. Digital Control of a Coupled Fluidized-
The authors are grateful to the US. Department of Bed Thermal Processing System for Tar Sands. Fuel. Process.
Energy/Morgantown Energy Technology Center for fi- Technol. 1989,21,1-17.
nancial support under Contract DE-FC21-89MC26268for McMillan, G. K. Advanced Control Algorithms: Beware of False
Prophecies. In Tech 1986,33,55-57.
the research work presented in this paper. McMillan,G. K.Tuning and Control Loop Performance;Instrument
Society of America: Research Triangle Park, NC, 1990.
Nomenclature Morari, M.; Zafhiou, E. Robust Process Control; Prentice-Hall:
Englewood Cliffs, NJ, 1989.
A = surface area of heat pipe immersed in fluidized bed Oblad, A. G.; Bunger, J. M.; Hanson, F. V.; Miller, J. D.; Ritzma, H.
C = heat capacity R.; Seader, J. D. Tar Sand Research and Development at the
d, = particle diameter University of Utah. Annu. Rev. Energy 1987,12,283-356.
F = fluidizing air flow rate Rivera, D. E.; Morari, M.; Skogestad, S. Internal Model Control. 4.
h = effective convective heat-transfer coefficient PID Controller Design. Znd. Eng. Chem. Process Des. Deu. 1986,
25, 252-265.
K, = proportional constant of a PID controller Rotatein, G. E.; Lewin, D. R. Simple PI and PID Tuning for Open-
k = process steady gain Loop Unstable Systems. Znd. Eng. Chem. Res. 1991,30,1864-
k, = gas thermal conductivity 1869.
M = mass of sand holdup in a bed, reactor vessel, or heat pipe Saxena, S.G.;Ganzha, V. L. Dependence of Heat-Transfer Coefficient
Q = heat-transfer rate or heat input rate for Immersed Surfaces in a Gas-Fluidized Bed on Pressure. Powder
8' = Q + FcaTa,~ Technol. 1985,44, 115.
R = electric resistance Seborg, D. E.; Edgar, T. F.; Mellichamp, D. A. Process Dynamics
s = Laplace transform variable and Control; John Wiley & Sons: New York, N Y , 1989.
T = temperature Skogestad, S.;Morari, M. LV-Control of a High-Purity Distillation
t = time Column. Chem. Eng. Sci. 1988,43, 33-48.
Smith, C. L. Digital Computer Process Control;Intexb Educational
V = voltage Publisher: San Francisco, CA, 1972.
W = sand feed rate Zabrodsky, S. S.;Antonishin, N.V.; Parnas, A.L. On Fluidized Bed-
To-Surface Heat Transfer. Can. J. Chem. Eng. 1976,54,52.
Greek S y m b o l s
/3 = time constant of a first-order lead system Received for reuiew April 19,1993
pp = particle density Accepted August 31, 1993.
7 = process time constant
T~ = closed-loop time constant @ Abstract published in Advance A C S Abstracts, October 15,
7 d = derivative constant of a PID controller 1993.

Você também pode gostar