SECTION 1
Medium Voltage Variable Frequency Drives
SECTION 2
Low Voltage Variable Frequency Drives
SECTION 3
Medium Voltage Starters
SECTION 4
http://benshaw.cwfc.com
24/7/365 Service and Support
Field Services
• Installations & commissioning
• On-site repairs
- Scheduled/emergency
• On-site retrofits and upgrades
Factory Services
• Send-in repairs
- Scheduled/emergency
• Send-in retrofits and upgrades
• Quick ship modified — Benshaw Express stock
• Benshaw and 3rd party
Technical Training
• In-class in our training center
• In-class at your facility
• Customized for your business
Maintenance Services
• Thermography
• Service contracts
• Preventive
- Maintenance / agreements
• Power quality
Spare Parts
• 24/7/365 availability
• Emergency delivery
- Courier available
• Replace or repair
Technology Retrofits
• Solid state motor controls and drives
• Electromechanical motor controls
• Orphaned OEM equipment retrofits
Low Voltage Starters
Standard Low Voltage Starter Products
MX3 Controller...........................................................2
MX2 Controller...........................................................4
Open Chassis Solid State Starters............................7
Prepackaged Starters.............................................16
KEYPAD
(INCLUDED)
OPTIONAL
KEYPAD
MX2 BOARD
Standard Features:
• High performance motor control
with multiple starting modes built in
• Jogging 7 and 14% speed
• 3 user configurable digital inputs
Highlights: • 2 fixed inputs for start and
bypass confirm
The new MX control technology from Benshaw provides a powerful,
2
flexible, intelligent low voltage motor control platform. MX2-based • 3 user configurable output relays
and 1 fixed bypass confirm
controls offer multiple, user selectable starting modes, an increased
• User configurable analog I/O
selection of configurable digital and analog I/O’s, comprehensive built-
in metering capabilities, unprecedented onboard protection and an • Programmable burden CT settings
easy to use, intuitive user interface. • Residual ground fault
• Advanced line / motor metering
The new control board terminal configuration—coupled with program-
• DC braking light duty
mable burden CT settings—makes Benshaw’s MX2 technology an
• Power stack thermistor
excellent choice for a wide range of intelligent, soft start motor control
applications. • Data snapshot of each fault
• Power up on start
With more built-in starting modes, more built-in protection features,
• 1000V capable
additional communications capabilities, improved noise immunity, a
• Energy saver
more complete user I/O and CE compliance, Benshaw’s new MX2-
based low voltage motor controls raise the bar for intelligent, low- • Remote keypad ready
cost, soft start motor control. • CE, UL, CUL, NEMA compliance
• Built-in self-testing (BIST)
When you factor in our 24/7 comprehensive technical support,
• ModBus 485 plus expanded
we think you’ll find Benshaw’s MX2-based controls to be an communications capabilities with
excellent value. optional bridges
MISCELLANEOUS MX2
MX3 PROTECTION MX2
MX3 USER I/O MX2
MX3
Voltage Ramp Separate Starting/Running Programmable Digital Inputs
Current Ramp Overload Classes Programmable Digital Outputs
TruTorque™ Ramp Adj. Hot/Cold Ratio User Analog Input
Power Ramp Adj. Cooling Time Programmable User Analog Output
Tach/Speed Control Ramp Intelligent Start Lockout Local/Remote Source Input
Linear Ramp Profiles Adj. OL Lockout Level Power Up Start
Squared and S Ramp Profiles Over/Under Current Protection
Dual Ramps Retained OL When Power Lost METERING MX2
MX3
Kicking Current Imbalance Protection Full Voltage and Current Metering
Voltage Decel IOC (Instantaneous Over Current) True RMS Calculation
TruTorque™ Decel Open/Shorted SCR Detection Factory Menu Calibration
DC Braking Overcurrent/Shear Pin Current Imbalance Meter
Heater/Antiwindmill Undercurrent/Load Loss Ground Fault Meter
Jogging 7-14% Speed Residual Ground Fault Protection Watt Meters
Slow Speed Cyclo™ Operation Zero Seq. Ground Fault Protection KVA Meters
0-40% speed Starts Per Hour VAR Meter
Inside Delta RTD Monitoring Watt Hour Meters
Wye-Delta/Electromechanical Control Motor PTC Line Frequency Meter
Phase Controller Stack OT Switch Power Factor Meter
Current Follower Stack Thermistor Input % OL Meter
ATL Backspin Timer Time Until OL Lockout Release Meter
Time Between Starts Phase Rotation Meter
Phase Rotation & Power and % TruTorque™ Meter
Overvoltage Run Time Meter
Undervoltage Number of Starts Meter
Phase Loss Peak Current of Last Start Meter
UTS/Stall Timer Last Starting Time Meter
Zero Speed Switch Analog Input Meter
PF Trip Real Time Clock
PORT (Power Outage Ride Through) RTD Meters
Keypad Fault Reset
Adj. Auto Fault Reset Timer MISCELLANEOUS MX2
MX3
Adj. No. of Auto Resets Before Lockout LV BIST
Decel After Fault MV BIST
Fault Log LV Powered BIST
Time and Date Stamp
9 Data Snapshots of Each Fault
Event Log (last 99 events)
Fault Classes
Key Advantages:
• Economical at low horsepower
• High duty cycle starting
• Long starting times
• Suitable for jogging applications
• Fan cooled stack
• Energy saver applications
• Integrated motor protection
• Modbus standard / Profibus,
Ethernet, DeviceNet, Ethernet IP
web addressable communication
protocols are available via optional
communication bridges
• 1.25 service factor
Highlights: • Integrated metering and diagnostics
The RC Series Solid State Starter combines the high performance • Multiple starting ramps for various
MX2 or MX3 control with the rugged, continuous duty, fan cooled RC applications
stack.
The MX2 or MX3 series control provides users with a powerful group of
programming parameters, designed for flexibility in industrial applica-
tions. The MX2 and MX3 both provide simple setup and commission-
ing via the Quick Start Menu.
The RC power section is a rugged non-bypassed section. It is an eco-
nomical solution at low horse-power. In addition, the fan cooled stack
provides high duty cycle and high inertia starting and energy saver
operation.
Standard Features:
• NEMA 12, redundant, combination/
circuit breaker
• Shunt trip on main circuit breaker
• 500% – 30 seconds rated solid state
starter, UL certified and listed
• 1800 PIV rated SCRs, UL certified
and listed
• 125% continuous duty rated solid
state starter, UL certified and listed
• Selector switch for selecting solid
state or full voltage operation
mounted inside enclosure
• Full HP rated bypass contactor
with a 1.15 service factor, wired for
normal bypass operation and full
voltage start and run operation, with
normally open auxiliary contact
• Separately mounted “SPE” series
overload relay wired for full voltage
start and run operation
Highlights: • 110 volt control power transformer
with primary and secondary fuses
RX2E starters provide solid state reduced voltage starting for normal
operation and full voltage emergency backup starting with complete • Door mounted start and
stop push-buttons
electronic motor protection at the flip of a switch. This unique redun-
• Door mounted keypad
dant design is the ideal solution for critical applications where down-
time is extremely disruptive to production operations and cannot be • Door mounted run indicating light
tolerated. Benshaw’s MX solid state controls provide precise digital • Door mounted local-off remote
switch
starting and stopping, motor protection, metering, diagnostics and
communications. • Door mounted overload reset
• Benshaw soft start and emergency
Units are stocked with MX2 technology, but are available with MX3 bypass control board with customer
technology. connections
• Auxiliary relay with (2) Form C run
contacts
• Benshaw MX2 programmable motor
controller with soft start, soft stop
and motor protection capabilities
• RS485 ModBus communications
• Analog I/O
• Available with MX3 technology
3. Select a voltage
4. Select an enclosure
=
5. Select a circuit breaker (or none)
mx2pb 150 4 4 CB ST
240 V
Dimensions (in.)
Weight
Model Number A HP V (lbs.)
H W D
MX2PC-010-2-4-NC-** 27 10 240 24 16 15 110
MX2PC-015-2-4-NC-** 40 15 240 24 16 15 110
MX2PC-020-2-4-NC-** 52 20 240 24 16 15 110
MX2PC-025-2-4-NC-** 65 25 240 24 16 15 110
MX2PC-030-2-4-NC-** 77 30 240 24 16 15 110
MX2PC-040-2-4-NC-** 96 40 240 30 16 16 140
MX2PC-050-2-4-NC-** 124 50 240 30 16 16 140
** Insert option code. See page 4-23 for a list of available options. ST = No options / OP = Options included
• Available for next day shipment.
480 V
Dimensions (in.)
Weight
Model Number A HP V (lbs.)
H W D
MX2PC-020-4-4-NC-** 27 20 480 24 16 15 110
MX2PC-030-4-4-NC-** 40 30 480 24 16 15 110
MX2PC-040-4-4-NC-** 52 40 480 24 16 15 110
MX2PC-050-4-4-NC-** 65 50 480 24 16 15 110
MX2PC-060-4-4-NC-** 77 60 480 24 16 15 110
MX2PC-075-4-4-NC-** 96 75 480 30 16 16 140
MX2PC-100-4-4-NC-** 124 100 480 30 16 16 140
** Insert option code. See page 4-23 for a list of available options. ST = No options / OP = Options included
##
Built-to-order: Available for next day shipment.
240 V
Std. Heavy Dimensions (in.)
Duty 1 Duty 2 Weight
Model Number V (lbs.)
HP HP H W D
MX2PB-015-2-4-NC-** 15 15 240 24 16 15 110
MX2PB-020-2-4-NC-** 20/25 20 240 24 16 15 110
MX2PB-030-2-4-NC-** 30/40 30/40 240 36 16 15 150
MX2PB-050-2-4-NC-** 50 50 240 36 20 15 150
MX2PB-075-2-4-NC-** 60/75 60/75 240 48 20 15 180
MX2PB-100-2-4-NC-** 100 – 240 48 20 15 180
MX2PB-150-2-4-NC-** 150 100 240 48 20 15 180
MX2PB-200-2-4-NC-** 200 150 240 78 30 20 350
** Insert option code. See page 4-23 for a list of available options. ST = No options / OP = Options included
1
Standard duty = 350% current for 30 seconds, 1.15 S.F.
2
Heavy duty = 500% current for 30 seconds, 1.25 S.F.
##
Built-to-order: Available for next day shipment.
480 V
Std. Heavy Dimensions (in.)
Model Number Duty 1 Duty 2 Weight
V (lbs.)
HP HP H W D
MX2PB-030-4-4-NC-**2 30 30 480 24 16 15 110
MX2PB-050-4-4-NC-**2 50 40 480 24 16 15 110
MX2PB-075-4-4-NC-**2 75 75 480 36 16 15 150
MX2PB-100-4-4-NC-**2 100 – 480 36 20 15 150
MX2PB-150-4-4-NC-**2 150 150 480 48 20 15 180
MX2PB-200-4-4-NC-**2 200 – 480 48 20 15 180
MX2PB-300-4-4-NC-**2 300 200 480 48 20 15 180
MX2PB-400-4-4-NC-**2 400 300 480 78 30 20 350
** Insert option code. See page 4-23 for a list of available options. ST = No options / OP = Options included
1
Standard duty = 350% current for 30 seconds, 1.15 S.F.
2
Heavy duty = 500% current for 30 seconds, 1.25 S.F.
• Available for next day shipment, or modified for next day shipment.
Web stocked
240 V
Std. Heavy Dimensions (in.)
Duty 1 Duty 2 Weight
Model Number V (lbs.)
HP HP H W D
MX2PB-020-2-4-CB-** 20/25 20 240 36 16 15 175
MX2PB-030-2-4-CB-** 30/40 30/40 240 42 20 15 200
MX2PB-050-2-4-CB-** 50 – 240 48 24 15 220
MX2PB-075-2-4-CB-** 60/75 60/75 240 48 24 15 220
MX2PB-100-2-4-CB-** 100 – 240 48 24 15 220
MX2PB-150-2-4-CB-** 150 100 240 48 24 15 220
MX2PB-200-2-4-CB-** 200 150 240 78 30 24 400
** Insert option code. See page 3-29 for a list of available options. ST = No options / OP = Options included
1
Standard duty = 350% current for 30 seconds, 1.15 S.F.
2
Heavy duty = 500% current for 30 seconds, 1.25 S.F.
##
Built-to-order: Available for next day shipment.
480 V
Std. Heavy Dimensions (in.)
Model Number Duty 1 Duty 2 Weight
V (lbs.)
HP HP H W D
MX2PB-050-4-4-CB-** 2
50 40 480 36 16 15 175
MX2PB-075-4-4-CB-**2 75 75 480 42 20 15 200
MX2PB-100-4-4-CB-**2 100 – 480 48 24 15 220
MX2PB-150-4-4-CB-**2 150 150 480 48 30 15 220
MX2PB-200-4-4-CB-**2 200 – 480 48 30 15 220
MX2PB-300-4-4-CB-**2 300 200 480 48 30 15 220
MX2PB-400-4-4-CB-**2 400 300 480 78 30 24 400
** Insert option code. See page 4-23 for a list of available options. ST = No options / OP = Options included
1
Standard duty = 350% current for 30 seconds, 1.15 S.F.
2
Heavy duty = 500% current for 30 seconds, 1.25 S.F.
• Available for next day shipment, or modified for next day shipment.
Web stocked