Air-Conditioning of the future

Service Manual

Residential A/Cs
CONTENTS
1. DIAGNOSTIC CHART 1

2. The service rules of the R407C(R410a) product 5

3. MAS 8

4. MES 45

5. CES/CED/CEM 65

6. G E S 97

7. G I S 115

8. LIS 127

9. CUS 139

10. BES 157

11. CES I 178

12. CED I & CEM I 197

Please find CAS, CAD, CAM (R or I), CMP, etc.. in separate papers!
Diagnostic Chart(5000Btu/h-12000Btu/h)
1. Self-diagnose the failure
COOLWEX units have self-diagnose function.
Note: for the following series
CES
CED
CEM
2. After energizing, no indicator is lighted and the air conditioner can’t be operated.

After energizing, the air conditioner can’t be operated

Check if AC220V power supply outputs to Indoor PCB.

Yes

Check if AC220V exists at the primary coil of transformer.

Yes No

Indoor PCB is defective


Or current fuse is melt.

Check if AC14.5V exists at the secondary coil of transformer.

No Yes

Take off the secondary plug of transformer, and then check if


Yes
AC14.5V exists at the secondary coil of transformer.

No

The transformer is defective. Indoor PCB is defective

3. Resetting phenomenon often occurs during operation. (That is automatically entering to


the status when power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check
according to the following procedure:

Resetting phenomenon often occurs during operation.

After changing Indoor PCB, check if the failure releases.

No Yes

After changing indoor fan motor, check if the failure releases. Indoor PCB is defective

No
Power supply circuit has problems.

1
4. Failure phenomenon for cooling only type
Failure phenomenon Operation lamp Timer lamp
Indoor fan speed has been out of control for over 1 minute ☆ X
Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On
Over current protection of the compressor occurs 4 times X ☆
EEPROM error On ☆
r Extinguish
☆ Flash at 5Hz
4.1 Operation lamp flashes and Timer lamp off.

Operation lamp flashes and Timer lamp off.

Yes

Change the main control board

4.2 Operation lamp flashes and Timer lamp on.

Is connection to connector good?

yes No
Replace the sensor Repair connector

4.3 Operation lamp off and Timer lamp flashes

Operation lamp off and Timer lamp flashes

After changing the main control board, check if the failure releases.

No Yes
The voltage of power supply is too low (less than 187V)? Indoor PCB is defective

Yes No

Power supply fault Outdoor unit fault (such as the compressor)

4.4 Operation lamp on and Timer lamp flashes


EEPROM error, indoor PCB is defective.

2
5. Failure phenomenon(heat pump)
Failure phenomenon Operation lamp Timer lamp Defrosting lamp
Over current protection of the compressor occurs 4
☆ X ☆
times
Indoor fan speed has been out of control for over 1
X ☆ ☆
minute
No over-zero signal ☆ ☆ ☆
Temp. sensor on indoor evaporator is open circuit or
X X ☆
short circuit
Indoor room temp. sensor is open circuit or short circuit X ☆ X
EEPROM error On ☆ X
r Extinguish
☆ Flash at 5Hz
5.1 Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes.

Operation lamp flashes ,Timer lamp off and Defrosting lamp flashes

After changing the main control board, check if the failure releases.

No Yes
The voltage of power supply is too low (less than 187V)? Indoor PCB is defective

Yes No

Power supply fault Outdoor unit fault (such as the compressor)

5.2 Operation lamp off, Timer lamp flashes and Defrosting lamp flashes.

Is connector connection good?

Yes No

Is voltage being applied to the fan motor?


Repair the connector
Yes No

Fan motor is defective


Indoor PCB is defective

5.3 Operation lamp flashes, Timer lamp flashes and Defrosting lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such
failure occurs, the main control board must have fault.

3
Operation lamp flashes and Timer lamp off.

Yes

Change the main control board

5.4 Operation lamp off ,Timer lamp off and Defrosting lamp flashes.

Is connection to connector good?

yes No

Replace the sensor Repair connector

5.5 Operation lamp off, Timer lamp flashes and Defrosting lamp off

Is connection to connector good?

yes No

Replace the sensor Repair connector

5.6 Operation lamp on, Timer lamp flashes and Defrosting lamp off
EEPROM error, main PCB has fault.

Temporarily turn off the power supply and turn it on again in about 1 minutes

Does the trouble occur again?

Yes

Replace the indoor PCB

4
The service rules of the R407C product
The service rules of the R410A product
1. The service rules of the new refrigerant R407C product
COOLWEX uses the green refrigerant R407C firstly in China.
Its thermal characters are similar to R22, but there is little difference between them.
1.1 The main difference between R407C and R22:

R407C R22
Component HFC32/125/134a HCFC22
The ratio of mix Wt% 23/25/52 100
The saturation liquid density Kg/m3 1136 1191
Specific heat Normal pressure kj/kg.k 0.835 0.622
The saturation liquid kj/kg.k 1.554 1.256
Evaporating pressure kpa 499 498
Condensing pressure kpa 2112 1943
Temperature slippage ℃ 4.3-7.1 0
Heating capacity w 92-97 100
Input power w 106 100
COP 97 100
The consistent with the oil Fat oil Mineral oil

1.2 Service precautions:


1.2.1 Because R407C is a mixture composed of three kinds of matter, when vapor phase and liquid
phase coexist, the component of the vapor phase is different from the liquid phase. When we fill
the refrigerant, we must ensure to fill it in liquid phase, in order to maintain the stability of the
character.
1.2.2 The leakage of the refrigerant is from vapor side or liquid side, and the leakage from vapor side
could make the component change and impact the character seriously. So when the amount of
the leakage is up to 5%, we need discharge all refrigerant in the system, and fill liquid
refrigerant according to amount in nameplate.
1.2.3 Because the lubricant fit for refrigerant R407C is ester refrigerating engine oil (POE) or ether
refrigerating engine oil (PVE). The mineral lubricant fit for refrigerant CFC and HCFC is weak in
consistent with the HFC, and it doesn’t fit for the refrigerant HFC. So when the compressor
using new refrigerant R407C is worn out, to replace it by compressor of CFC or HCFC is
forbidden.
1.2.4 When the connection of the refrigerant pipe is finished, before the system start up we should
vacuum the indoor unit by cut-off valve or discharge the indoor unit air by refrigerant R407C
bottle. Discharged the air in system by outdoor unit refrigerant is forbidden.
1.2.5 Ester oil could adsorb the water in the air. In order to removemoisture in refrigeration system,
avoid capillary jammed by ice and the ester lubricant oil decomposed with water, we use
desiccant in system. Artificial zeolite (molecular sieve R etc.) is the effective water sorbent.
Toavoid absorb refrigerant but only absorbmoisture, we use the molecular sieve whose
aperture is smaller than the molecule of the refrigerant. For R407C we should adopt XH-11
rather than XH-9AK and 4A-NRG.
1.2.6 Because the corrosion of R407C and POE to high molecular material is different from R22 and
mineral oil, the airproof material inside high/low pressure valve and foul-way valve needs to be
changed in refrigeration system, such as R407C, polyurethane rubber etc. The high/low
pressure valve and four-way valve which are fit for R22 couldn’t be used in service.
1.2.7 When there is leakage, filling with other kind of refrigerant is forbidden.
1.2.8 When we need to vacuum the system, we should use the special quick joint, but use the quick
joint of other refrigerant is forbidden lest pollute by mixing refrigerant. The time for vacuuming is

5
about 30 minutes, and vacuity is less than 133Pa.
1.3 Precautions:
1.3.1 Regulations
Being liquefied vapor, R-407C and R-410A are high-pressure vapor, the high-pressure gas regulation is
applicable. Before use it, please refer to high-pressure gas regulation. To prevent the high-pressure
vapor from causing damage, the regulation should be followed.
1.3.2 Usage of vessel
Being high-pressure vapor, R-407C and R-410A are contained in high-pressure vessel. The
safety condition of vessel is good, but if you don’t use it carefully, you may damage the vessel
and cause accident.
1.3.3 Storage
Although R-407C and R-410A are nonflammable, when they are stored with the normal
high-pressure gas, we should place them in the good ventilation area.
In addition, there are safe devices in the high-pressure vessel. Please note that when the
temperature (fusible valve) or pressure (spring safe valve) is up to a certain value, it will eject
vapor.
1.3.4 Ventilation
Because R-407C and R-410A are heavier then air, they will go down. If room is full of the
leakage vapor, the density of oxygen will decrease, and cause people suffocated.
In addition, if you light the fire when there is R-407C in the air, it will produce the toxic gas with
pungent odor and corrosiveness.
1.3.5 Precautions about health
For R-407C, R-410A and normal liquefied high-pressure vapor, please don’t contact with skin
directly, and prevent being splashed into eyes and avoid drinking.
1.3.6 The following are the urgent disposal methods:
Splash into eyes:
Wash eyes with pure water for more than 15 minutes, and don’t knead the eyes or blink.
Please wash eyes with watery boric acid water if the ache gets heavy.
To avoid the accident, please ensure that you wear the protection glasses.
Contact with skin directly
The temperature will decrease rapidly by evaporation if R-407C and R-410A expose to air in
liquid phase. So if the liquid contacts with skin directly, it may cause frostbite. If there are freeze
burns, please go to see the doctor immediately.

2. The service rules of the R410A product


2.1 There are some differences between air conditioner of R410A s and that of R22:
2.1.1 The compressor used is different, it is a new refrigerant compressor (special);
2.1.2 The air conditioner of new refrigerant R410A has a drier, while the A/C of R22 doesn’t have.
2.1.3 There is no difference between the evaporator, condenser and system pipe of new refrigerant
R410A A/C and that of R22 A/C in appearance. The requirement of new refrigerant R410A A/C
for craft is higher, and the amount of moisture and impurity in the system is less than that of A/C
using R22. The resistance to pressure is higher.
2.1.4 The manufacture process is different, the requirement of air conditioner using R410A for craft is
high.
2.2 Refrigerant system:
2.2.1 The high pressure of refrigerant system is 3.0 Mpa, and the low pressure is 1.2 Mpa. (The
value is 1.5 times more than that of R22 under the same condition)
2.2.2 When installing the split type of new refrigerant R410A, all connecting pipes must be special
pipes of R410A. Discharging air must use refrigerant R410A, and couldn’t misuse the
connecting pipe and refrigerant of A/C using R22. Otherwise, it will destroy the stability of A/C.
2.2.3 Because the compressor of refrigerant R410A split type uses POE oil, which can react with
moisture to form water and acid. The water produced by reaction could react further, and if the
6
chain reaction proceeds continually, the water in the system will be more and more. It will cause
the capillary ice blocking; at the same time, acidity of working substance circulated in the
system will be higher and higher (the value of PH is lower and lower), and it may corrode the
components and parts in the system. The phenomenon of copperizing would happen. When
installing A/C, the action should be prompt, and after opening the plug of connecting pipe we
must tighten the nut in 5 minutes. The time of discharging air should be enough. When
installing A/C, the sweat drops into the connecting pipe is forbidden; the infusible impurity
mixed in the system is forbidden. It is better to install the A/C of refrigerant R410A split type in
fine weather, do not do it in rainy day, nor humid weather.
2.2.4 The chlorine ion could react with POE oil to form acid, and the acid corrodes the components
and parts of refrigerant system. So pollute the system with chlorine ion in installation is
forbidden, such as sweat beads and other impurities that contain chlorine ion.
2.2.5 Whatever the reason we must change the drier, if the refrigerant system is exscinded in service,
after we exscind the refrigerant system, we must use something to wrap the fracture lest the
moisture in air enters into the system. The time that refrigerant system expose to air should be
less than 5 minutes.
2.2.6 Must weld the drier into system in 5 minutes in order to isolate the air when changing it.
Otherwise it will influence the performance of the drier.
2.2.7 Must use special pump after service. The lubricant should be the grease. The pump couldn’t be
used to vacuum the A/C of refrigerant R22, otherwise it would cause the contamination of
refrigerant, and influence the performance of A/C. The time of vacuuming must be over 25
minutes, Otherwise the moisture in system will be too high, and affect the stability of A/C.
2.2.8 If need to change the components and parts, must use the special one of R410A in service.
Using the components and parts of R22 is forbidden; otherwise it would affect the stability of
A/C.
The refrigerant R410A should be placed in environment under 30℃. If the refrigerant has been
placed in environment above 30℃, it is necessary to store the refrigerant in the environment below
30℃ for more than 24 hours. Otherwise the component of refrigerant would be changed and it
affects the performance of A/C.

7
CES, CED & CEM

1. Features 66

2. Specification 67

3. Dimensions 73

4. Refrigeration cycle diagram 77

5. Operation limits 78

6. Wiring diagram 79

7. Troubleshooting 86

8. Electronic function 86
1.Features
1.1 Compact design
1.2 High efficiency and quiet operation

66
2.Specification
Model CES-05.R.....................CES-07.R.........................CES-07.RC...................CES-09.R....................CES-09.RC

Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz

Capacity Btu/h 5000 7000 7000 9000 9000

Input W 560 760 760 1000 1000


Cooling
Rated current A 2.6 3.6 3.6 4.5 4.5

EER Btu/w.h 8.6 8.8 8.8 9 9

Capacity Btu/h 7600 10000

Input W 760 980


Heating
Rated current A 3.4 4.4

COP w/w 2.9 3.0

Moisture Removal L/h 0.6 0.8 0.8 1 1

Max. input consumption W 800 1050 1050 1300 1300

Max. current A 3.8 5 5 7 7

Starting current A 16 18 18 25 25

Model KH104VFHC 2P14C235ANA 2P14C235ANA PH170X1C-4DZ2 PH170X1C-4DZ2

Type Rotary Rotary Rotary Rotary Rotary

Brand SHANGHAI SENLIN GD Matsushita GD Matsushita GD Toshiba GD Toshiba

Capacity Btu/h 5700 7500 7500 10000 10000

Input W 590 725 725 970 970


Compressor
Rated current(RLA) A 2.7 3.4 3.4 4.5 4.5

Locked rotor Amp(LRA) A 13 15 15 24 24

Thermal protector BF540-KB MRA98854 MRA98854 UP3QE0591-T61 UP3QE0591-T61(int

Capacitor uF 15 25 25 25 25

Refrigerant oil ml MS-56 270 ATOMOS M60 270 ATOMOS M60 270 SUNISO 350 SUNISO 350

Model RPG13H RPG13H RPG13H RPG13H RPG13H

Brand WELLING WELLING WELLING WELLING WELLING


Indoor fan motor Input W 36.5 36.5 36.5 36.5 36.5

Capacitor uF 1.2µF/450V 1.2µF/450V 1.2µF/450V 1.2µF/450V 1.2µF/450V

Speed(hi/mi/lo) r/min 1020/ 960/ 900 1020/ 960/ 900 1020/ 960/ 900 1100/1020/950 1100/1020/950

Indoor air flow (Hi/Mi/Lo) m3/h 300/270/240 380/350/320 380/350/320 450/420/390 450/420/390

Indoor noise level (Hi/Mi/Lo) dB(A) 32/28/25 32/28/25 32/28/25 33/31/27 33/31/27

Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188 750×250×188


Indoor unit Packing (W*H*D) mm 830X336X280 830X336X280 830X336X280 830X336X280 830X336X280

Net/Gross weight Kg 8/9.5 8.5/10 8.5/10 8.5/10 8.5/10

Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T YDK24-6T

Brand WELLING WELLING WELLING WELLING WELLING


Outdoor fan motor Input W 70 70 70 70 70

Capacitor uF 3 3 3 3 3

Speed r/min 850 850 850 850 850

Outdoor air flow m3/h 1400 1400 1400 1500 1500

Outdoor noise level dB(A) 49 49 49 49 49

Dimension(W*H*D) mm 700×535×235 700×535×235 700×535×235 700×535×235 700×535×235


Outdoor unit Packing (W*H*D) mm 815×580×325 815×580×325 815×580×325 815×580×325 815×580×325

Net/Gross weight Kg 26/29 28/31 27/30 30/33 29/32

Refrigerant type R22 g 480 620 580 650 580

Design pressure MPa 2.6 2.6 2.6 2.6

Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Refrigerant piping Max. refrigerant pipe length m 10 10 10 10 10

Max. difference in level m 5 5 5 5 5

Connection wiring No No No No No

Plug type 10A 10A 10A 10A 10A

Thermostat type Electronic control Electronic control Electronic control Electronic control Electronic control

Operation temp ℃ 17-30 17-30 17-30 17-30 17-30

Ambient temp ℃ 18-45 -7-45 18-45 -7-45 18-45

Application area m2 8-12 10--14 10-14 14-21 14-21

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.

67
Model CES-12.RC CES-12.R CES-18.RC CES-18.R

Power supply Ph-V-Hz 220-240V,50HZ 220-240V,50HZ 220-240V~,50Hz 220-240V~,50Hz

Capacity Btu/h 12000 12000 18000 18000

Input W 1230 1230 18000 18000


Cooling
Rated current A 5.7 5.7 1820 1800

EER Btu/w.h 9.8 9.8 8.5 8.4

Capacity Btu/h 13000 10.0,2.9

Input W 1290 19000


Heating
Rated current A 6 1800

COP w/w 3.0 3.1

Moisture Removal L/h 1.2 1.2 1.5 1.5

Max. input consumption W 1650 1690 2040 2080

Model PH200X2C-8FTC PH225X2C-4FT PH290X2C-4FT1 PH290X2C-4FT1

Capacity Btu/h 11840 13610 17435 17435

Input W 1135 1305 1670 1670

Rated current(RLA) A 5.2 6.1 8.0 8.0


Compressor
Locked rotor Amp(LRA) A 26 41.2 41.2

Thermal protector Internal External Internal Internal

Capacitor uF 25 35 35 35

Refrigerant oil ml 440 430 520 520

Input W 36.5 36.5 53 53

Indoor fan motor Capacitor uF 1.2 1.2 1.5uF/450V 1.5uF/450V

Speed(hi/mi/lo) r/min 1350 1350 1180 1180

Indoor air flow (Hi/Mi/Lo) m3/h 550 550 750/710/650 750/710/650

Indoor noise level (Hi/Mi/Lo) dB(A) 36/33/30 36/33/30 41/38/35 41/38/35

Dimension (W*H*D) mm 750X250X188 750X250X188 906×286×235 906×286×235

Indoor unit Packing (W*H*D) mm 830X336X280 830X336X280 1020X380X328 1020X380X328

Net/Gross weight Kg 8.5/10 8.5/10 13.5/16.5 13.5/16.5

Input W 70 70 96 96
Outdoor fan motor
Capacitor uF 2.5 2.5 2.5µF/450V 2.5µF/450V

Outdoor noise level dB(A) 51 51 53 53

Dimension(W*H*D) mm 780X540X250 780X540X250 780X540X250 780X540X250

Outdoor unit Packing (W*H*D) mm 910X575X335 910X575X335 910X575X335 910X575X335

Net/Gross weight Kg 34/37 36/39 43/47 44/48

Refrigerant type g R22/750 R22/820 1110 1370

Design pressure MPa 2.6 2.6 2.6 2.6

Liquid side/ Vapor side mm(inch) Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7 Ф6.35/Ф12.7

Refrigerant piping Max. refrigerant pipe length m 10 10 15 15

Max. difference in level m 5 5 8 8

Plug type 16A 16A 15 15

Application area m2 18-26 18-26 25-35 25-35

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.

68
Model C ES-21 .R C C E S-21 .R
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 21000 21000
Input W 2300 2300
Cooling
Rated current A 10.5 10.5
EER Btu/w.h 9.1 9.1
Capacity Btu/h 23500
Input W 2400
Heating
Rated current A 11.0
COP w/w 2.9
Moisture Removal L/h 2.0 2.0
Max. input consumption W 2500 2600
Max. current A 11.3 14.5
Starting current A 42 42
Model 2V36S225AUD 2V36S225AUD
Type rotary rotary
Capacity Btu/h 20600 20600
Input W 2010 2010
Compressor Rated current(RLA) A 9。5 9。5
Locked rotor Amp(LRA) A 42 42
Thermal protector INNER INNER
Capacitor uF 50 50
Refrigerant oil ml 680 680
Model RPG25 RPG25
Brand WELLING WELLING
Indoor fan motor Input W 53 53
Capacitor uF 1.5uF/450V 1.5uF/450V
Speed(hi/mi/lo) r/min 1325 1325
Indoor air flow (Hi/Mi/Lo) m3/h 920\760\700 920\760\700
Indoor noise level (Hi/Mi/Lo) dB(A) 41/37/33 41/37/33
Dimension (W*H*D) mm 906×286×235 906×286×235
Indoor unit Packing (W*H*D) mm 1020X380X328 1020X380X328
Net/Gross weight Kg 13.5/16.5 13.5/16.5
Model YDK53-6 YDK53-6
Input W 100 100
Outdoor fan motor
Capacitor uF 2.5μF/450V 2.5μF/450V
Speed r/min 640 640
Outdoor air flow m3/h 2600 2600
Outdoor noise level dB(A) 53 53
Dimension(W*H*D) mm 845×695×335 845×695×335
Outdoor unit Packing (W*H*D) mm 970×770×395 970×770×395
Net/Gross weight Kg 52/57 55/60
Refrigerant type R22 g 1220 1740
Design pressure MPa 2.6 2.6
Liquid side/ Gas side mm(inch) Ф6.35/Ф12.7 Ф6.35/Ф12.7
Refrigerant piping Max. refrigerant pipe length m 15 15
Max. difference in level m 8 8
Thermostat type Electronic control Electronic control
Operation temp ℃ 17-30 17-30
Ambient temp ℃ 10-43 (-5~43)
Application area m2 34-49 34-49

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.

69
Comfort
Model CES-07_R7______________CES-07_R7C____________CES-09_R7_________CES-09_R7C
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 7000 7000 9000 9000
Input W 800 800 1050 1050
Cooling
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h 8.8 8.8 8.6 8.6
Capacity Btu/h 8500 10000
Input W 880 1050
Heating
Rated current A 4 4.6
COP w/w 2.9 2.93
Moisture Removal L/h 0.6 0.6 0.8 0.8
Max. input consumption W 1000 1000 1330 1330
Max. current A 4.4 4.4 6 6
Model PG135X1C-4DZ2 PG135X1C-4DZ2 PG180X1C-4DZ3 PG180X1C-4DZ3
Type Rotary Rotary Rotary Rotary
Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8086/8172 8086/8172 10800 10800
Input W 765/785 765/785 1015 1015
Compressor
Rated current(RLA) A 3.52/3.34 3.52/3.34 4.5 4.5
Locked rotor Amp(LRA) A
Thermal protector UP3SE0591-T71 UP3SE0591-T71 UP3SE0591-T61 UP3SE0591-T61
Capacitor uF 25 25 30 30
Refrigerant oil ml 400 400 400 400
Model RPG13H RPG13H RPG13H RPG13H
Input W 36.5 37.5 38.5 39.5
Indoor fan motor
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1020/960/900 1020/960/900 1100/1020/950 1100/1020/950
Indoor air flow (Hi/Mi/Lo) m3/h 430/400/370 430/400/370 470/440/410 470/440/410
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 35/32/30 36/32/30 36/32/30
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188
Indoor unit Packing (W*H*D) mm 830×336×280 830×336×280 830×336×280 830×336×280
Net/Gross weight Kg 8.5/10.5 8.5/10.5 8.5/10.5 8.5/10.5
Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Outdoor fan
Input W 70 70 70 70
motor Capacitor uF 3 3 3 3
Speed r/min 850 850 850 850
Outdoor air flow m3/h 1600 1600 1900 1600
Outdoor noise level dB(A) 49 49 49 49
Dimension(W*H*D) mm 700X535X235 700X535X235 700X535X235 700X535X235
Outdoor unit Packing (W*H*D) mm 815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg 30/33 29/32 29/32 30/33
Refrigerant type R407C g 740 650 840 770
Design pressure MPa 2.8 2.8 2.8 2.8

Refrigerant Liquid side/ Gas side mm(inch Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refrigerant pipe length m 10 10 10 10
piping
Max. difference in level m 5 5 5 5
Operation temp ℃ 17 30 17 30 17 30 17 30
Ambient temp ℃ -7-45 18-45 -7-45 18-45
Application area m2 10-14 10-14 14-21 14-21

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.

70
Model CES-12_R7C____________________________CES-12_R7

Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz

Capacity Btu/h 12000 12000

Input W 1320 1320


Cooling
Rated current A 5.8 5.8

EER Btu/w.h 9.1 9.1

Capacity Btu/h 14000

Input W 1360
Heating
Rated current A 6

COP w/w 3.02

Moisture Removal L/h 1.2 1.2

Max. input consumption W 1800 1800

Max. current A 7.8 7.8

Starting current A

Model 4KS225EBA 4KS225EBA

Type Rotary Rotary

Brand MATSUSHITA-WABAO MATSUSHITA-WABAO

Capacity Btu/h 13000 13000

Input W 1260 1260


Compressor
Rated current(RLA) A 5.7 5.7

Locked rotor Amp(LRA) A 30 30

Thermal protector

Capacitor uF 35 35

Refrigerant oil ml 480 480

Model RPG20D RPG20D

Input W 49.2 49.2


Indoor fan motor
Capacitor uF 1.5 1.5

Speed(hi/mi/lo) r/min 1180/1000/900 1180/1000/900

Indoor air flow (Hi/Mi/Lo) m3/h 620/550/520 620/550/520

Indoor noise level (Hi/Mi/Lo) dB(A) 37/34/31 37/34/31

Dimension (W*H*D) mm 815X280X195 815X280X195


Indoor unit Packing (W*H*D) mm 915X360X275 915X360X275

Net/Gross weight Kg 10.5/13.5 10.5/13.5

Model YDK25-6C YDK25-6C

Input W 85 85
Outdoor fan motor
Capacitor uF 2.5 2.5
Speed r/min 900 900

Outdoor air flow m3/h 1900 1900

Outdoor noise level dB(A) 54 54

Dimension(W*H*D) mm 780X540X250 780X540X250


Outdoor unit Packing (W*H*D) mm 910X575X335 910X575X335

Net/Gross weight Kg 34/38 37/41

Refrigerant type R407C g 830 1150

Design pressure MPa 2.8 2.8

Liquid side/ Gas side mm(inch) Ф6.35/Ф12.7 Ф6.35/Ф12.7


Refrigerant piping Max. refrigerant pipe length m 10 10

Max. difference in level m 5 5

Plug type 16A 16A

Thermostat type Electronic control Electronic control

Operation temp ℃ 17-30 17-30

Ambient temp ℃ 18-45 —7-45

Application area m2 18-26 18-26

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.

71
Comfort
Model CES-07_R7______________CES-07_R7C____________CES-09_R7________CES-09_R7C
Power supply Ph-V-Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz 220-240V~,50Hz
Capacity Btu/h 7000 7000 9000 9000
Input W 800 800 1050 1050
Cooling
Rated current A 3.5 3.5 4.6 4.6
EER Btu/w.h 8.8 8.8 8.6 8.6
Capacity Btu/h 8500 10000
Input W 880 1050
Heating
Rated current A 4 4.6
COP w/w 2.9 2.93
Moisture Removal L/h 0.6 0.6 0.8 0.8
Max. input consumption W 1000 1000 1330 1330
Max. current A 4.4 4.4 6 6
Model PG135X1C-4DZ2 PG135X1C-4DZ2 PG180X1C-4DZ3 PG180X1C-4DZ3
Type Rotary Rotary Rotary Rotary
Brand TOSHIBA TOSHIBA TOSHIBA TOSHIBA
Capacity Btu/h 8086/8172 8086/8172 10800 10800
Input W 765/785 765/785 1015 1015
Compressor
Rated current(RLA) A 3.52/3.34 3.52/3.34 4.5 4.5
Locked rotor Amp(LRA) A
Thermal protector UP3SE0591-T71 UP3SE0591-T71 UP3SE0591-T61 UP3SE0591-T61
Capacitor uF 25 25 30 30
Refrigerant oil ml 400 400 400 400
Model RPG13H RPG13H RPG13H RPG13H
Input W 36.5 37.5 38.5 39.5
Indoor fan motor
Capacitor uF 1.2 1.2 1.2 1.2
Speed(hi/mi/lo) r/min 1020/960/900 1020/960/900 1100/1020/950 1100/1020/950
Indoor air flow (Hi/Mi/Lo) m3/h 430/400/370 430/400/370 470/440/410 470/440/410
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/30 35/32/30 36/32/30 36/32/30
Dimension (W*H*D) mm 750×250×188 750×250×188 750×250×188 750×250×188
Indoor unit Packing (W*H*D) mm 830×336×280 830×336×280 830×336×280 830×336×280
Net/Gross weight Kg 8.5/10.5 8.5/10.5 8.5/10.5 8.5/10.5
Model YDK24-6T YDK24-6T YDK24-6T YDK24-6T
Outdoor fan
Input W 70 70 70 70
motor Capacitor uF 3 3 3 3
Speed r/min 850 850 850 850
Outdoor air flow m3/h 1600 1600 1900 1600
Outdoor noise level dB(A) 49 49 49 49
Dimension(W*H*D) mm 700X535X235 700X535X235 700X535X235 700X535X235
Outdoor unit Packing (W*H*D) mm 815X580X325 815X580X325 815X580X325 815X580X325
Net/Gross weight Kg 30/33 29/32 29/32 30/33
Refrigerant type R407C g 740 650 840 770
Design pressure MPa 2.8 2.8 2.8 2.8

Refrigerant Liquid side/ Gas side mm(inch Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53
Max. refrigerant pipe length m 10 10 10 10
piping
Max. difference in level m 5 5 5 5
Operation temp ℃ 17 30 17 30 17 30 17 30
Ambient temp ℃ -7-45 18-45 -7-45 18-45
Application area m2 10-14 10-14 14-21 14-21

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient condition.

70
3.Dimensions
3.1 Indoor unit
CES-05/07/09_R(7)(C),CES-12_R(7)(C)

3.2 Indoor unit CES-12_R(7)(C)


280

73
3.3 Indoor unit CES-18/21_R(7)(C))

3.4 Outdoor unit CES-05/07/09_R(7)(C),

74
3.5 Outdoor unit CES-12_R(7)(C) & CES-18_R(7)(C)

3.6 Outdoor unit CES-18_R(7)(C)

750
285

590

62
315

290

530 110

75
3.7 Outdoor unit CES-21_R(7)(C)

12.5

76
4.Refrigeration cycle diagram
4.1 Cooling/heating
Indoor unit outdoor unit

Valve

Sensor of room temp

. 4 way valve

Heat exchanger Heat exchanger

Sensor of heat exchanger temp

Compressor

Valve Capillary

4.2 Cooling only


Indoor unit outdoor unit

Valve

Sensor of room temp

Heat exchanger Heat exchanger

Sensor of heat exchanger temp

Compressor

Valve Capillary

77
5.Operation limits
5.1Cooling operation
Outdoor unit air temp.℃ DB
45

40 DRY COOLING

35

30

25

20

10 15 20 25 30 35 40
Indoor air temp. ℃ DB
Note : The chart is the result from the continuous operation under constant air temperature
conditions. However, excludes the initial pull-down stage.

5.2Heating operation
Indoor air temp. ℃ DB

30

25

20

15

10

-5 5 15 25
Outdoor unit air temp.℃ DB
Note : The chart is the result from the continuous operation under constant air
temperature conditions. However, excludes the initial pull-down stage.

78
6.Wiring diagram
6.1 Cooling only
6.1.1 CES-05_R(7)(C) Indoor unit

POWER SUPPLY

INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T

1
2
(
N
)

Y&G
B
L
A
C
K

B
L
A
C
K
O
VR
EE
RL
LA
OY
A
D

R
E
D

R
E
D
B
L
A R
C E
K D
C
O
M
P
R
E
S
S
O
R
C

FM
AO
NT
R
E
D
O
R
R

Y&G
S

Y&G
B
L
U
E

B
L
U
E

COMPRESSOR FAN
CAPACITOR CAPACITOR

79
6.1.2 CES-07_R(7)(C) & CES-09_R(7)(C)

POWER SUPPLY

INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T

1
2
(
N
)

Y&G
B
L
A
C
K

B
L
A
C
K
O
V
ER
R
LL
O
AY
D
E
A

R
E
D

R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C

R
E
D

F
AO
NT
R
E
D
M
O
R
R

Y&G
S

Y&G
B
L
U
E

B
L
U
E

COMPRESSOR FAN
CAPACITOR CAPACITOR

80
6.1.3 CES-12_R(7)(C) Indoor unit (A Type)

POWER SUPPLY

INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T

1
2
(
N
)

Y&G
B
L
A
C
K

B
L
A
C
K
O
VR
E
RE
L
O
AY
D
L
A

R
E
D

R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C

R
E
D

FM
A
NT
R
E
D
O
O
R
R

Y&G
S

Y&G
B
L
U
E

B
L
U
E

COMPRESSOR FAN
CAPACITOR CAPACITOR

81
CAPACITOR
D
E

FAN
R D
E

Y&G
K
C R E
A U
L
L NTR
O B
B

82
A
F O
M
)
N

Y&G
(
2 D
E
R

COMPRESSOR
1

CAPACITOR
K
C
A
L
B D
K E E
C R R U
T A L
6.1.4 CES-12_R(7)(C) (B Type)

I L B
B

INDOOR UNIT
N
U D
A C S
R
O O Y R
O L A
L O
D R
E E S
T R S

Y&G
U V
O E
O R
P
M
O
C
6.1.5 CES-18_R7(C) & CES-21_R7(C)

TRANSFORMER COMPRESSOR RELAY

BLUE
WHITE
BROWN
SWITCH BOARD

CN14
CN9 CN4

CN2
CURRENT DETECTOR
DISPLAY BOARD

CN12

CN1
CN6 CN5

BLACK
WHITE
CN8 CN7 CN10
AMBIENT SENSOR

HEAT EXCHANGER

LOUVER MOTOR

LOUVER MOTOR
SENSOR

INDOOR MOTOR

INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T

1
2
(
N
)

Y&G
B
L
A
C
K

B
L
A
C
K
O
V
E
R
L
O
A
D
R
E
L
A
Y

R
E
D

R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C

R
E
D

F
A
NT
R
E
D
M
O
O
R
R

Y&G
S

Y&G
B
L
U
E

B
L
U
E

COMPRESSOR FAN
CAPACITOR CAPACITOR

83
6.2 Heating/cooling
6.2.1 CES-07_R(7),CES-09_R(7) & CESG-09HRN2,

84
6.2.2 CES-12_R7(B TYPE) & CES-12_R7

85
6.2.3 CES-18_R(7) & CES-21_R(7)

TRANSFORMER COMPRESSOR RELAY

BLUE
WHITE
BROWN
SWITCH BOARD

CN14
CN9 CN4

CN2
CURRENT DETECTOR
DISPLAY BOARD

CN12

CN1

YELLOW
CN6 CN5

GREEN
BLACK
WHITE
CN8 CN7 CN3 CN10
AMBIENT SENSOR

HEAT EXCHANGER

LOUVER MOTOR

LOUVER MOTOR
SENSOR

INDOOR MOTOR

86
7.Troubleshooting
7.1 For all cooling only model
Failure phenomenon Operation lamp Timer lamp

Indoor fan speed has been out of control for over 1 minute ☆ X

Indoor room temp. or evaporator sensor is open circuit or short


☆ On
circuit

Over current protection of the compressor occurs 4 times X ☆

EEPROM error On ☆

No over-zero signal ☆ ☆

r Extinguish
☆ Flash at 5Hz
7.2 For all heat pump model
Failure phenomenon Operation lamp Timer lamp Defrosting lamp

Over current protection of the compressor occurs 4 times ☆ X ☆

Indoor fan speed has been out of control for over 1 minute X ☆ ☆

No over-zero signal ☆ ☆ ☆

Temp. sensor on indoor evaporator is open circuit or short circuit X X ☆

Indoor room temp. sensor is open circuit or short circuit X ☆ X

EEPROM error On ☆ X

r Extinguish
☆ Flash at 5Hz

8 Electronic function
8.1 Electric Control working environment
8.1.1 input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7°C~+43°C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I3sec: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I5MIN: Self-protection amp of compressor, continue five minutes until turns off the compressor.
IFAN: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
IRESTORE: Amp self-protection return value
THDEFROST: High wind, defrosting temperature difference
TMDEFROST: Middle wind, defrosting temperature difference
TLDEFROST: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
87
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature

8.3 Systematic functions


Remote receiving
Testing and forced run
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at heating mode
8.4 Protection
8.4.1 The compressor functions protection with a delay of three minutes.
8.4.2 Sensor protection at open circuit and breaking disconnection
8.4.3 Temperature Fuse break protection
8.4.4 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
8.4.5 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
8.4.6 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark

Current up I< IRESTORE On On On

IRESTORE <I< IFAN On On Off Heating mode

Low speed On On Cooling mode

IFAN <I<I5MIN Off Off After 5 Minutes

I5MIN<I< I3SEC Off Off After 3 Seconds

Current down I5MIN<I< I3SEC Off Off After 3 Seconds

IFAN <I<I5MIN Off Off After 5 Minutes

IRESTORE <I< IFAN On On Off Heating mode

Low speed On On Cooling mode

I< IRESTORE On On On

If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.
88
8.5 Fan-only mode
Fan speed is high/mid/low/ Auto
8.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition Compressor Outdoor fan
Temp. up T> Ts+1 On On
T<Ts+1 Off Off
Temp. down T> Ts On On
T<Ts Off Off

Auto fan at cooling mode:


Condition Indoor fan speed
T=Indoor Temp.-Setting Temp.
Temp. up T<3℃ Low
3℃<T<5℃ Med.
T>5℃ High
Temp. down T> 3℃ High
1℃<T<3℃ Med.
T<1℃ Low

Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )


Condition Compressor Outdoor fan
Temp. Time
Temp. up T> TE6 On On
T< TE6 >5 Minutes Off Off
Temp. down T> TE5 On On
T< TE5 >5 Minutes Off Off

8.7 Dehumidifying mode


8.7.1 The 4-way valve is off in dehumidifying mode
8.7.2 Compressor and Indoor Fan actions in dehumidifying mode
NO Conditions Indoor Fan Compressor and Outdoor Fan
LOW ON 6minutes
1 TA ≥ TS+2
BREEZE OFF 4minutes
LOW ON 5minutes
2 TS ≤TA<TS+2
BREEZE OFF 5minutes
LOW ON 4minutes
3 TA < TS
BREEZE OFF 6minutes
Repeat on and off cycle.

89
8.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan

Room temp. up T> Ts+3 Off Off

T<Ts+3 On On

Room temp. down T< Ts+2 On On

T>Ts+2 Off Off

8.8.4 Indoor Fan actions at heating mode


Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
function prevails.
Anti-cold wind control function at heating mode
Condition Indoor fan speed

T= Indoor exchanger temp.

Indoor exchanger temp. up T<TE1 Off

TE1<T<TE2 Breeze

T>TE2 Setting fan speed

Indoor exchanger temp. down T> TE3 Setting fan speed

TE3<T<TE4 Breeze

T<TE4 Off

8.8.5 Auto wind at heating mode


Condition Indoor fan speed

T=Indoor Temp.-Setting Temp.

Room temp. up T<2℃ High

T>2℃ Med.

Room temp. down T> 0℃ Med.

T<0℃ High

90
8.8.6 Indoor evaporator high-temperature protection at heating mode
Condition Compressor Outdoor fan

T= Indoor exchanger temp.

Indoor exchanger temp. up T<TE8 On On

TE8<T<TE7 On Off

T>TE7 Off Off

Indoor exchanger temp. down T>TE9 Off Off

T<TE9 On On

8.9 Defrosting operation (Available for heating only).


8.9.1 Defrosting condition: Defrosting starts when either of the following ①&②:
① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:

Temp. of evaporator---room temp.

Fan speed is high ≤THDEFROST

Fan speed is mid ≤TMDEFROST

Fan speed is low ≤TLDEFROST

Breeze Meet only if it is Breeze

② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
If the temp. difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
circulation is as following:
→6-minute defrost → 6-minute defrost→6-minute defrost→10-minute defrost→

8.9.3 Ending condition of defrosting


If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 6 or 10 minutes.
B. The compressor current has reached to IDEFROST or above, IDEROST differs in different models.

91
8.9.4 Defrosting Actions:

Defrost 10or 6minutes

45S 25S
Compressor

4-way Valve 23S


40S
Outdoor Fan

Indoor Fan

10S

8.9.7 Turn into heating mode, turn off the heating mode in 7 minutes.

8.10 Automatic operation mode


8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or
fan only according to the temp. difference between room temp. (TA) and set temp. (TS).
TA—TS Operation mode

TA—TS>2℃ Cooling

-1℃≤TA—TS≤+2℃ Fan-only

TA—TS<-1℃ Heating (air-only for cooling only type)

8.10.2 The indoor fan blows automatically in corresponding selected mode.


8.10.3 The motion of indoor fan’s blade should accord with the selected operation mode.

8.11 Forced cooling function


8.11.1 Select forced cooling function with the forced cooling button or the switch.
8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is
set as low, the A/C operates at the DRY mode with a set temp. of 24℃.
8.11.3 All protections of remote control cooling are available at forced cooling operation.
8.12 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
8.13 Timer Function

8.14 Economic Running


8.14.1 The economic running function is available at cooling, heating or auto mode.
8.14.2 Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the fan speed is kept at low speed.
8.14.3 Heating:
92
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Cold air proof function takes precedence over
all).
8.14.4 Auto:
The economic running function operates in accordance with selected running mode by auto mode.
8.15 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before
the power failure when power returns.

93
8.16 Models and Parameters
Model CES-07_RC CES-07_R CES-09_RC CES-09_R CES-12_RC CES-12_R

I3SEC 8.5A 8.5A 10.0A 10.0A 11.0A 11.0A

I5MIN 6.2A 6.2A 7.5A 7.5A 10.0A 10.0A

IFAN 5.2A 5.2A 5.5A 5.5A 8.0A 8.0A

IRESTORE 4.2A 4.2A 4.5A 4.5A 6.0A 6.0A

IDEFROST 3.2A 3.5A 5.5A

TE1 28℃ 28℃ 28℃

TE2 32℃ 32℃ 32℃

TE3 30℃ 30℃ 30℃

TE4 26℃ 26℃ 20℃

TE5 2℃ 2℃ 2℃ 2℃ 3℃ 3℃

TE6 7℃ 7℃ 7℃ 7℃ 8℃ 8℃

TE7 60℃ 60℃ 60℃

TE8 53℃ 53℃ 53℃

TE9 50℃ 50℃ 50℃

ANGLCOOL 200° 200° 200° 200° 200° 200°

ANGLHEAT 0° 0° 0°

ANGLOFF 124° 124° 124° 124° 124° 124°

THDEFROST 16°C 14°C 14°C

TMDEFROST 17°C 15°C 15°C

TLDEFROST 18°C 16°C 16°C

94
Model CES-07_R7C CES-07_R7 CES-09_R7C CES-09_R7

I3SEC 8.5A 8.5A 10.0A 10.0A

I5MIN 6.2A 6.2A 7.5A 7.5A

IFAN 5.2A 5.2A 5.5A 5.5A

IRESTORE 4.2A 4.2A 4.5A 4.5A

IDEFROST 3.2A 3.5A

TE1 28℃ 28℃

TE2 32℃ 32℃

TE3 30℃ 30℃

TE4 26℃ 26℃

TE5 4℃ 4℃ 4℃ 4℃

TE6 10℃ 10℃ 10℃ 10℃

TE7 60℃ 60℃

TE8 53℃ 53℃

TE9 50℃ 50℃

ANGLCOOL 200° 200° 200° 200°

ANGLHEAT 0° 0°

ANGLOFF 124° 124° 124° 124°

THDEFROST 14°C 14°C

TMDEFROST 15°C 15°C

TLDEFROST 16°C 16°C

95
Model CES-12_RC CES-12_R* CES-18_R_C CES-18_R CES-21_RC CES-21_R

(B type) (B type)

CES-12_R7C______CES-12_R7________CES-18_R7C_______CES-18_R7_______CES-21_R7C_____CES-21_R7

I3SEC 14.5A 14.5A 16.0A 16.0A 17.0A 17.0A

I5MIN 13.5A 13.5A 13.0A 13.0A 16.0A 16.0A

IFAN 9.5A 9.5A 11.0A 11.0A 14.0A 14.0A

IRESTORE 8.5A 8.5A 9.5A 9.5A 12A 12A

IDEFROST 6.5A 6.5A 7A

TE1 34℃ 34℃ 34℃

TE2 37℃ 36℃ 36℃

TE3 33℃ 30℃ 30℃

TE4 22℃ 20℃ 20℃

TE5 2℃ 2℃ 3℃ 3℃ 3℃ 3℃

TE6 7℃ 7℃ 10℃ 10℃ 10℃ 10℃

TE7 62℃ 60℃ 64℃

TE8 56℃ 52℃ 56℃

TE9 50℃ 50℃ 50℃

ANGLCOOL 40° 40° 50° 50° 50° 50°

ANGLHEAT 197° 105° 105°

ANGLOFF 100° 100° 0° 0° 0° 0°

THDEFROST 17°C 17°C 20°C

TMDEFROST 18°C 18°C 21°C

TLDEFROST 19°C 19°C 22°C

96
COOLWEX Group USA

SPLIT TYPE, HEAT PUMP AIR CONDITIONERS

Technical & service manual 2005

CES Inverter Type (50Hz) R407C Wall Mounted

[Models]

CES 7 I7

CES 7 I7

CES 12 I7
Contents

1. Features 2

2. Specification 3

3. Dimensions 4

4. Refrigeration cycle diagram 6

5. Operation limits 7

6. Wiring diagram 8

7. Troubleshooting 10

8. Electronic function 11

1
1.Features
1.1 Powerful at cooling/heating, 1.3 times and 1.6 times relatively higher than normal same type of
models.
1.2 Low voltage start-up function, even at 160 V it can normally start.
1.3 Anti-icing function at cooling mode.
1.4 Anti-cold air function at heating mode.
1.5 Auto-defrosting and heating recovering function at heating mode.
1.6 Outdoor whole electric current protection
1.7 Temperature protection of the outdoor compressor top.
1.8 Restart protection for the compressor.
1.9 24 hours on/off mode time setting.
1.10 Error self diagnosis function.
1.11 Protection against over-load or too-low current inputted through alternating current.

2
2. Specification

Model Item CES 7 I7 CES 9 I7 CES 12 I7

Power source 220-240V~ 50Hz 220-240V~ 50Hz 220-240V~ 50Hz

Capacity BTU/H 7000(2700~9000) 9000(2730~10600) 12000(3070~13300)

Input W 780(250~1200) 1000(270~1470) 1320(310~1710)


Cooling
Running current A 4.8(1.35~6.2) 4.5(1.2~6.6) 5.8(1.60~7.60)

EER BTU/W.H 9.0, 2.6 9.0, 2.6 9.1, 2.6

Capacity BTU/H 9000(2700~11000) 12000(2730~14000) 15000(3070~17060)

Heating Input W 1010(250~1300) 1250(270~1800) 1560(300~2380)

Running current A 4.4(1.35~6.7) 5.5(1.45~9.3) 6.8(1.6~10.6)

Max. input consumption W 2100 2300 2600

Model BG130X1C-20FZ BG130X1C-20FZ BG130X1C-20FZ

Type Rotary Inverter Rotary Inverter Rotary Inverter

Compressor Brand MIDEA TOSHIBA MIDEA TOSHIBA MIDEA TOSHIBA

Refrigerant oil ml 370 370 370

Refrigerant oil type R407C R407C R407C

Refrigerant R407C g 800 800 1150

Design pressure MPa 2.6 2.6 2.6

Indoor fan Input W RPG13H 36 RPG13H 36 RPG13C 50

motor Capacitor uF 1.2uF/≥450VAC 1.2uF/≥450VAC 1.5uF/≥450VAC

Speed level 3 3 3

Hi speed( rpm) 1100 1100 1060

Mid speed( rpm) 1000 1000 900

Low speed( rpm) 800 800 800

High fan m3/h 500 520 560


Air flow
Middle fan m3/h 430 430 460
(indoor)
Low fan m3/h 330 330 380

Noise level 36/32/26 36/32/26


dB(A) 35/32/26
(indoor)

Outdoor fan Input W YDK23-6G 63 YDK23-6G 63 YDK23-6G 63

motor Capacitor uF 2.5uF/≥450VAC 2.5uF/≥450VAC 2.5uF/≥450VAC

Noise High dB(A) ≤51 ≤51 ≤53

(outdoor)

dimension(W*H*D) 750*250*188 750*250*188 815*280*195

Indoor unit Packing (W*H*D) 830*336*280 830*336*280 915*360*275

Net weight kg 8.5 8.5 11

dimension(W*H*D) 780*520*240 780*520*240 780*520*240

Outdoor unit Packing (W*H*D) 910*575*335 910*575*335 910*575*335

Net weight kg 37 37 40

★1 The noise date is base on anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient

condition.

3
3. Dimensions
3.1 Indoor Unit

CES 7 I7, CES 9 I7

3.2 Indoor Unit

CES 12 I7

4
3.3 Outdoor Unit

CES 7 I7, CES 9 I7, CES 12 I7

5
4. Refrigeration Cycle Diagram

Indoor unit outdoor unit

Valve

Sensor of room temp Heat exchanger

. 4 way valve

Sensor

Heat exchanger Sensor of temp

Sensor of heat exchanger temp

. Sensor of heat exchanger temp

Compressor

Valve Capillary

6
5. Operation Limits

5.1 Cooling operation


Outdoor unit air temp.℃
60

50

40

30

20

10

10 17 25 30 35 40
Indoor air temp. ℃
Note :the chart is the result from the continuous operation under constant air temperature
conditions. however, excludes the initial pull-down stage.
5.2 Heating operation
Indoor air temp. ℃

30

20

10

-5

-15

-15 -5 5 15 25 30
Outdoor unit air temp.℃
Note :the chart is the result from the continuous operation under constant air
temperature conditions. however, excludes the initial pull-down stage.

7
6. Wiring Diagram
6.1 Indoor unit(CES 7 I7, CES 9 I7)

6.2 Indoor unit(CES 12 I7)

8
6.3 Outdoor unit (CES 7 I7 / CES 9 I7 / CES 12 I7)

S
L N

9
7.Troubleshooting
7.1 Indoor Unit Error Display Function
LED4 operation LED2 defrosting LED1 timer LED4 auto
LED2 LED1 LED3 LED4
LED STATUS
defrost Timer Auto operation

X X O ☆ Mold protection

O X X ☆ Compressor top protection against temperature

X O X ☆ Open or short circuit of outdoor temperature sensor

X O O ☆ Over load or too low voltage protection

Room temperature or evaporator temperature sensor open


O O O ☆
or short circuit of

O O ☆ ☆ Fan speed beyond control

☆ X O ☆ Zero-crossing examination error

☆ O X ☆ Temperature fuse protection

X X ☆ ☆ EEPROM data error

☆ O X ☆ Types doesn't match

☆ ☆ ☆ ☆ Indoor / outdoor units communication protection

O (on) X (off) ☆ (flash)

7.2.Outdoor Unit Error Self-diagnosis Display


Outdoor Unit Error: if L4 flashes at 1Hz.
Outdoor unit works: L4 on
Outdoor unit Stand by: if L4 flashes at 0.5Hz

10
8 .Electronic Function
8.1 General Protection
8.1.1 Temperature Protection of Compressor Top
8.1.2 3 minutes Delayed Starting Protection of the Compressor
8.1.3 Voltage Protection
8.1.4 The frequency Up-Down speed at which the compressor starts, operates and shuts off will be
subject to the following principles (outdoor chip):

HZ

1HZ/S
92Hz 2HZ/S

57Hz 1HZ/S

1HZ/S

6HZ/S

time
50 Sec
2 min

8.1.5 Frequency Converter Mold Protection (outdoor chip):


The Frequency Converter Mold itself has a protection function against current, voltage and
temperature, if there are 4 times of above mentioned protection functioning within 1 hour (when
the compressor's consecutive operation lasts more than 10 minutes, the fore-mentioned 4
counts will be cleared), the whole machine will shut off and the mold protection gives an alarm.
8.2 Fan-only Mode Function Requirement
8.2.1 The compressor, 4 way valve and outdoor fan are off at Fan-only mode.
8.2.2 Temperature setting function is cancelled, the set temperature can not be displayed, nor
adjusted.
8.2.3 The rotational speed of indoor fan can be optionally chosen by remote control as
High/Mid/Low/Auto.
8.2.4 The indoor fan vanes at Fan-only mode perform the same as those at cooling mode.

11
8.2.5 Performance at Auto mode at Fan-only status is the same as that at Auto mode at cooling status,
provided that the set temperature is 24°c.

°C

27.5 High

27.0

25.5 Mid

25.0

Low

8.3 Cooling Mode Function Requirement


8.3.1 At cooling mode the 4 way valve is off.
8.3.2 Anti-icing Control for Indoor Evaporator
When the temperature of indoor heat exchanger drops to ≤ 4°c, the frequency will reduce one
step down (including F0) and last for 1 minute every time until the temperature is kept between 4
- 7°c. If the temperature rises to ≥ 7°c, the limitation then will be removed.
When the temperature of indoor heat exchanger drops to < 0°c, shut off the compressor and it
will resume when the temperature rises up to > 5°c.
8.3.3 Outdoor Unit Current Control When Cooling:

Shut off the compressor


(10.2A) 8.0 A

frequency down

(8.8A) 6.8 A
frequency unchanged
(7.4A) 5.4 A

resume to normal

Note: The frequency down at the diagram is in accordance with the present frequency dropping
down, to determine every 2 seconds whether the frequency is keeping going down or is
recovering.

12
8.3.4 Indoor fan operates in accordance with the following principles:
8.3.4.1 When indoor fan is in operation, it can be remote controlled to High/Mid/Low/Auto modes.
8.3.4.2 The fan speed at Auto mode in cooling status is subject to the following:

°C room temperature - set temperature

+4.0 High

+3.0

+1.5 Mid

+1.0

Low

8.3.5 Indoor fan vanes at cooling mode will swing in accordance with the following:
When just plugged in for cooling, the vanes will open to the standard angle 50°.
The vane angle can be set by remote control at any angle between 50° and 105° (every setting
can adjust 6°) or set swinging (swinging angle will be 25°).
8.4 Dehumidifying Mode Requirements
8.4.1 At dehumidifying mode, the 4 way valve is shut off
8.4.2 At dehumidifying mode, the indoor fan is fixed in Breeze status and not adjustable.
8.4.3 At dehumidifying mode, the compressor operates in accordance with the following principles:

Room temperature - set temperature

2.5 F3

2.0

1.5 F2

1.0

0.5 F1

0.0
F1

8.4.4 Too-low room temperature protection


During dehumidifying, when room temperature drops down < 10°c, the compressor will shut off,
and when the room temperature rises up than 12°c, the compressor resumes operation.
8.4.5 At dehumidifying mode, the anti-icing function of indoor heat exchanger applies.
13
8.4.6 At dehumidifying mode, the power voltage and outdoor temperature limitation to the highest
frequency when compressor starts and operates is the same as that at cooling mode.
8.5 Heating Mode Function Requirement
8.5.1 At heating mode, the 4 way valve is on, during defrosting operation, it is off.
8.5.2 Outdoor fan usually turns on or off in accordance with the action of compressor, except for
defrosting and ending of the defrost.
8.5.3 Indoor fan action:
Anti-cold air control

Temperature of heat exchanger

37°c
Set rotational speed
34°c
33°c
breeze
18°c
fan off

8.5.4 Indoor fan can be set by remote control to any mode like High/Mid/Low/Auto, however anti-cold
air function comes first.
Auto fan

Room temperature - set temperature

-0.5
Low
-1.0
-1.5 Mid

-2.0
High

14
8.5.5 Outdoor Unit current control when heating
Note:

Compressor off The frequency in the table


(11.5A) 10.0A goes down in accordance
with the present frequency,
frequency down
determine every 2 seconds
whether it keeps going
(10.5A) 8.8A
frequency unchanged down or it is recovering.
(9.2A) 7.4A

8.5.6 Indoor evaporator protection against high temperature


When the temperature of indoor heat exchanger is higher than 53°c, the frequency will reduce one
step and last for 20 seconds every time until the temperature drops down lower than 53°c. If the
temperature drops down < 48°c, the limitation then will be removed (the frequency will not going
down further when reaching 35Hz).
When the temperature of indoor heat exchanger is higher than 63°c, shut off the compressor.
8.5.7 Indoor fan vanes at heating mode will swing in accordance with the following:
When just plugged in for heating, the vanes will open to the standard angle 220°.
The vane angle can be set by remote control at any angle between 0° and 220° (every setting can
adjust 6°) or set swinging (swinging angle will be 25°).
8.5.8 Defrosting operation
8.5.8.1 Defrosting precondition:
Defrosting starts when meeting one of the three conditions:
① The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively Ti1 for more than 3 minutes.
Model Ti1:

CES 9 I : -4°c

CES 12 I : -6°c

CES 9 I7 : -9°c

CES 9 I7 : -9°c

15
② The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
80 minutes, and the temperature remains consecutively Ti2 for more than 3 minutes.
Model Ti2:

CES 9 I : -2°c

CES 12 I : -4°c

CES 9 I7 : -7°c

CES 9 I7 : -7°c
③ The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
120 minutes, and the temperature remains consecutively Ti3 for more than 3 minutes.
Model Ti3:

CES 9 I : -0°c

CES 12 I : -2°c

CES 9 I7 : -5°c

CES 9 I7 : -5°c
Note: The time period starts to count when outdoor heat exchanger temperature is lower than
3°c, the defrosting operation starts when the exchanger temperature remains lower than the
starting temperatures which are Ti3, Ti2, Ti1.
8.5.8.2 Conditions of defrost ending
Defrosting ends when meeting any of the following three conditions and it turns to normal
heating operation.
① When the temperature of outdoor heat exchanger rises up to 12°c.
② When the temperature of outdoor heat exchanger rises up to 8°c and this continues for more
than 80 seconds.
③ When defrosting action continues for 10 minutes.
8.5.8.3 Defrosting Action

Max 10 mins
30 sec.
ON 10 sec. ON 30 sec
Compressor OFF
ON ON
4 way valve OFF
ON ON
Outdoor fan OFF
ON ON
Indoor fan OFF

The indoor fan operates in anti-cold air mode when it recovers

16
8.5.9 Set Function Test
When it is detected that the outdoor temperature is between 5 - 9°c and room temperature is
between 18 - 22°c, provided that the heating operation remains consecutively more than 30
minutes, the compressor's highest operational frequency is FMAX=F8=96HZ. If any of the above
conditions is not met, it will quit from set frequency operation.
8.6 Auto Mode Function
Using remote control to choose auto mode, under which the set temperature can be adjusted in a
range of 17 - 30°c.
8.6.1 When entering auto mode, the A/C will choose cooling, heating or fan only according to the
difference between room temperature (TA) and set temperature (TS).
TA - TS Operation status

TA -TS > 1°c Cooling

-1°c ≤TA - TS≤+1°c Fan only

TA - TS < -1°c Heating

8.6.2 At auto mode, the indoor fan will choose auto fan in corresponding mode.
8.6.3 At auto mode, the vane action of indoor fan is the same as that of chosen mode.
8.6.4 Once a mode is chose, it will take 5 minutes after shutting off the compressor to re-choose
another mode according to the difference between room temperature and set temperature, or
you can re-choose mode when set temperature is changed.
8.7 Forced Operation Function
8.7.1 Forced operation is controlled by the switch on switch board and divided into forced cooling and
forced auto. Remote control doesn't work at forced operation control.
8.7.2 At forced operation status, all protection functions in general protection fore-mentioned apply.
8.7.3 At forced cooling mode, the compressor operates at a fixed frequency of F2=42HZ, indoor fan is
Breeze, anti-icing control and general current control of cooling outdoor unit work; forced
operation will transfer to auto mode whose set temperature is 24°c automatically after 30
minutes.
8.7.4 At forced auto mode, the remote control controls in a set temperature of 24°c.
8.8 Timer Function Requirement
8.8.1 The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes.
8.8.2 Timer on function: first turn off the A/C, the A/C will be automatically on at the set time.
8.8.3 Timer off function: first turn on the A/C, the A/C will be automatically off at the set time.
8.8.4 Timer on/off function( on time is earlier than off time): first turn off the A/C, it will be automatically
on at set time, and later be off at the set time.
8.8.5 Timer off/on function( off time is earlier than on time): first turn on the A/C, it will be automatically
off at set time, and later be on at the set time.
8.8.6 Timer function execution is applicable upon one operation only.
8.8.7 Timer error is less than 1 min/h.

17
INVERTER COMFORT - Multiple

1. Product features 198

2. Specification 199

3. Dimensions 203

4. Refrigeration cycle diagram 204

5. Operation limits 205

6. Capacity table 206

7. Wiring diagram 208

8. Electric control functions 210

197
1. Product Features
Both indoor units can be operated either simultaneously or separately through the utilization of the advanced
converter technique and microcomputer control.
The flowing volume of refrigerant is adjustable through the electronic expansion valve.
High Cooling and Heating capacity is facilitated through the famous-brand frequency converter compressor.
Indoor noise is minimized through the optimization of the air flow system design, a four-folded evaporator and a
big diameter Cross Flow Fan.
The system is operable under low-voltage.
Effective and prompt defrosting correlates into no cold feelings.
High heating effects under extremely low temperatures.
The systems purging function improves the quality of the air in the room.
Wireless remote controlled function:
---A Manual Switch can operate the air conditioner when the remote controller is misplaced and the batteries are
exhausted.
---Horizontal and vertical louvers can swing automatically and the customized setting flows the air as desired.
---Grounding's have been connected and are safe to use.
---Compressor protection function enabled.

Indoor unit:
1) 4-Bend heat exchanger.
2) Trapeziform innergroove copper.
3) Hydrophilic Aluminum Fin.
4) Two-direction air vane technology.
5) Sleep mode.
6) Anti-rust cabinet.
7) Easy-cleaned panel.
8) Self-diagnosis auto-protection function.

198
2. Specification
Model CED 9-9 I7
Indoor unit 7000Btu/h 9000Btu/h 12000Btu/h
Power supply Ph-V-Hz 1Ph, 220-240V~, 50Hz
Capacity Btu/h single: 7000-12000; Twin:16000-24000
Input W single: 1000W-1350W; Twin:2570W-2900W
Cooling Rated current A single: 4.8A-6.7A; Twin:11.7A-13.8A
EER Btu/w.h single: 7.0-8.9; Twin:6.2-8.3
Capacity Btu/h single: 10000-14000; Twin:24000-27000
Input W single: 1300W-1650W; Twin:2100W-2800W
Heating Rated current A single: 6.3A-8.0A; Twin:11.0A-13.5A
COP Btu/w.h single: 7.7-8.5; Twin:11.4-9.6
Moisture Removal L/h 0.7 0.9 1.2
Max. input consumption W single: 1800W; Twin:3200W
Max. current A single: 13A; Twin:20A
Starting current A 10
Model BG240X2CS-20KU
Type Rotary inverter
Brand GD Toshiba
Capacity Btu/h 18000
Compress Input W 1690
or Rated current(RLA) A 11.6
Locked rotor Amp(LRA) A 60
Thermal protector Internal
Capacitor uF 85UF/250V
Refrigerant oil ml RB68AF/α68TF/T-68 750 ml
Model RPG13H RPG13H RPG13C
Brand Welling Welling Matsushita
Indoor
Input W 36 36 50
fan motor
Capacitor uF 1.2uF/≥450VAC 1.2uF/≥450VAC 1.5uF/≥450VAC
Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800
Indoor Number of rows 2 2 2
coil Tube pitch(a)x row pitch(b) mm 21×13.37 21×13.37 21×13.37
Fin spacing mm 1.5 1.5 1.3
Hydrophilic Hydrophilic Hydrophilic
Fin type (code)
aluminium aluminium aluminium

φ7, innergroove
Tube outside dia.and type mm φ7, innergroove
φ7, innergroove tube
tube tube
Coil length x height x width mm 578×252×27.34 578×252×27.34 635×315×27.34

199
Number of circuits 2 2 2
Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26
Dimension (W*H*D) mm 750*250*188 750*250*188 815*280*195
Indoor
Packing (W*H*D) mm 830*336*280 830*336*280 915*360*275
unit
Net/Gross weight kg 8.5/11 8.5/11 11/14
Model YDK53-6M
Brand Welling
Outdoor
Input W 148
fan motor
Capacitor uF 3.0
Speed r/min 775
Number of rows 1.5
Tube pitch(a)x row pitch(b) mm 25.4×22
Fin spacing mm 1.7
Outdoor
Fin type (code) Hydrophilic aluminium
coil
Tube outside dia.and type mm φ9.53 innergroove trube
Coil length x height x width mm 776×660×22
Number of circuits 2
Outdoor air flow m3/h 2500
Outdoor noise level dB(A) 60
Dimension(W*H*D) mm 845X695X335
Outdoor
Packing (W*H*D) mm 975X772X405
unit
Net/Gross weight kg 71/74
Refrigerant type R407C g 2200
Design pressure(Hi/Lo) MPa 2.8/1.2
Liquid side/ Gas side mm Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7
Refrigera
Max. refrigerant pipe length m 10 10 10
nt piping
Max. difference in level m 5 5 5
Connection wiring No
Plug type No
Controller Remote
Operation temp ℃ 17~30
Ambient temp ℃ 18~43(cooling); -15~24(heating)
Application area m2 14-18 18-24 20-30

Notes: 1. Nominal cooling capacities are based on the following conditions:


Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 8m(horizontal)
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 8m(horizontal)
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.

200
Model CAM 9-9-9 I7
Indoor unit 7000Btu/h 9000Btu/h 12000Btu/h
Power supply Ph-V-Hz 1Ph, 220-240V~, 50Hz
Capacity Btu/h single: 7000-12000; Twin:16000-24000; Three:24000
Input W single: 1000W-1350W; Twin:2570W-2900W; Three:2900W
Cooling Rated current A single: 4.8A-6.7A; Twin:11.1A-13.8A; Three: 13.8A
EER Btu/w.h single: 7.0-8.9; Twin: 6.2-8.3; Three: 8.3
Capacity Btu/h single: 10000-14000; Twin: 24000-27000; Three: 27000
Input W single: 1300W-1650W; Twin: 2100W-2800W; Three: 2800W
Heating Rated current A single: 6.3A-8.0A; Twin: 11.0A-13.5A; Three: 13.5A
COP Btu/w.h single: 7.7-8.5; Twin: 11.4-9.6; Three: 9.6
Moisture Removal L/h 0.7 0.9 1.2
Max. input consumption W 3200
Max. current A 20
Starting current A 10
Model BG240X2CS-20KU
Type Rotary inverter
Brand GD Toshiba
Capacity Btu/h 18000
Compress Input W 1690
or Rated current(RLA) A 11.6
Locked rotor Amp(LRA) A 60
Thermal protector Internal
Capacitor uF 85UF/250V
Refrigerant oil ml RB68AF/α68TF/T-68 750 ml
Model RPG13H RPG13H RPG13C
Brand Welling Welling Matsushita
Indoor
Input W 36 36 50
fan motor
Capacitor uF 1.2uF/≥450VAC 1.2uF/≥450VAC 1.5uF/≥450VAC
Speed(hi/mi/lo) r/min 1050/950/750 1100/1000/800 1060/900/800
Indoor Number of rows 2 2 2
coil Tube pitch(a)x row pitch(b) mm 21×13.37 21×13.37 21×13.37
Fin spacing mm 1.5 1.5 1.3
Hydrophilic Hydrophilic Hydr0philiC
Fin type (code)
aluminium aluminium aluminium

201
Tube outside dia.and type mm φ7, innergroove tube φ7, innergroove tube
φ7, innergroove tube
Coil length x height x width mm 578×252×27.34 578×252×27.34 635×315×27.34
Number of circuits 2 2 2
Indoor air flow (Hi/Mi/Lo) m3/h 500/410/320 520/430/330 560/460/380
Indoor noise level (Hi/Mi/Lo) dB(A) 35/32/26 36/32/26 36/32/26
Dimension (W*H*D) mm 750*250*188 750*250*188 815*280*195
Indoor
Packing (W*H*D) mm 830*336*280 830*336*280 915*360*275
unit
Net/Gross weight Kg 8.5/11 8.5/11 11/14
Model YDK53-6M
Brand Welling
Outdoor
Input W 148
fan motor
Capacitor uF 3.0
Speed r/min 775
Number of rows 1.5
Tube pitch(a)x row pitch(b) mm 25.4×22
Fin spacing mm 1.7
Outdoor
Fin type (code) Hydrophilic aluminium
coil
Tube outside dia.and type mm φ9.53 innergroove trube
Coil length x height x width mm 776×660×22
Number of circuits 2
Outdoor air flow m3/h 2500
Outdoor noise level dB(A) 60
Dimension(W*H*D) mm 845X695X335
Outdoor
Packing (W*H*D) mm 975X772X405
unit
Net/Gross weight Kg 72/76
Refrigerant type R407C g 2400
Design pressure(Hi/Lo) MPa 2.8/1.2
Liquid side/ Gas side mm Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7
Refrigera
Max. refrigerant pipe length m 10 10 10
nt piping
Max. difference in level m 5 5 5
Connection wiring No
Plug type No
Controller Remote
Operation temp ℃ 17~30
Ambient temp ℃ 18~43(cooling); -15~24(heating)
Application area m2 14-18 18-24 20-30
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB; Equivalent ref. Piping: 8m(horizontal)
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB; Equivalent ref. Piping: 8m(horizontal)

202
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.

3 Dimensions
1. Indoor unit 7/9K

2. Indoor Unit 12K

3. Outdoor unit

203
4 Refrigeration Cycle Diagram
Refrigeration circuit drawing of inverter trinary type

indoor unit outdoor unit

heat filter
inverter compressor
exchanger
high-pressure
switch 1
filter
oil separator
discharge
sensor

up part

capillary low-pressure
switch 2
capillary
heat
2
exchanger
down part
filter capillary
3
filter
condenser

4-way low-pressure oil tank


valve

heat
exchanger

filter

Refrigeration circuit drawing of inverter binary type

outdoor unit

inverter compressor

high-pressure
switch 1
oil separator
discharge
sensor

up part

capillary low-pressure
switch 2
capillary
heat
2
exchanger
down part
filter capillary
3
filter
condenser

4-way low-pressure oil tank


valve

heat
exchanger

filter

204
5 Operation Limits
5.1 Cooling operation
Outdoor unit air temp.℃
60

50

40

30

20

10

10 17 25 30 35 40
Indoor air temp. ℃
Note :the chart is the result from the continuous operation under constant air temperature
conditions. however, excludes the initial pull-down stage.
5.2 Heating operation
Indoor air temp. ℃

30

20

10

-5

-15

-15 -5 5 15 25 30
Outdoor unit air temp.℃
Note :the chart is the result from the continuous operation under constant air

205
temperature conditions. however, excludes the initial pull-down stage.

6 Capacity Table
6.1 Capacity table of Inverter Comfort Binary type
Indoor units can be combined by
7000Btu/h+9000 Btu/h;
7000Btu/h+12000 Btu/h
9000Btu/h+9000 Btu/h
9000Btu/h+12000 Btu/h
12000Btu/h+12000 Btu/h
Cooling
Indoor unit a (W) Indoor unit b (W)

7000Btu/h 2800
9000Btu/h 3000
12000Btu/h 3400
7000Btu/h+7000 Btu/h 2300 2300
7000Btu/h+9000 Btu/h 2500 2500
7000Btu/h+12000 Btu/h 2200 2800
9000Btu/h+9000 Btu/h 2500 2500
9000Btu/h+12000 Btu/h 2400 3200
12000Btu/h+12000 Btu/h 3200 3200
Heating
Indoor unit a (W) Indoor unit b (W)

7000Btu/h 3400
9000Btu/h 3600
12000Btu/h 4000
7000Btu/h+7000 Btu/h 2800 2800
7000Btu/h+9000 Btu/h 3000 3000
7000Btu/h+12000 Btu/h 2600 3400
9000Btu/h+9000 Btu/h 3000 3000
9000Btu/h+12000 Btu/h 3000 3900
12000Btu/h+12000 Btu/h 3900 3900

6.2 Capacity table of Inverter Comfort Trinary type


Indoor units can be combined by
7000Btu/h*2+9000 Btu/h;
7000Btu/h*2+12000 Btu/h
7000Btu/h*3
9000Btu/h*2+7000 Btu/h
9000Btu/h*2+12000 Btu/h
9000Btu/h*3
12000Btu/h*2+7000 Btu/h

206
12000Btu/h*2+9000 Btu/h
7000Btu/h+9000Btu/h+12000 Btu/h
Cooling
Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)

7000Btu/h 2800
9000Btu/h 3000
12000Btu/h 3400
7000Btu/h+7000 Btu/h 2300 2300
7000Btu/h+9000 Btu/h 2500 2500
7000Btu/h+12000 Btu/h 2200 2800
9000Btu/h+9000 Btu/h 2500 2500
9000Btu/h+12000 Btu/h 2400 3200
12000Btu/h+12000 Btu/h 3200 3200
7000Btu/h*2+9000 Btu/h 2200 2200 2200
7000Btu/h*2+12000 Btu/h 2000 2000 2600
7000Btu/h*3 2200 2200 2200
9000Btu/h*2+7000 Btu/h 2200 2200 2200
9000Btu/h*2+12000 Btu/h 2100 2100 2600
9000Btu/h*3 2200 2200 2200
12000Btu/h*2+7000 Btu/h 2000 2400 2400
12000Btu/h*2+9000 Btu/h 2000 2400 2400
Heating
Indoor unit a (W) Indoor unit b (W) Indoor unit c (W)
7000Btu/h 3400
9000Btu/h 3600
12000Btu/h 4000
7000Btu/h+7000 Btu/h 2800 2800
7000Btu/h+9000 Btu/h 3000 3000
7000Btu/h+12000 Btu/h 2600 3400
9000Btu/h+9000 Btu/h 3000 3000
9000Btu/h+12000 Btu/h 3000 3900
12000Btu/h+12000 Btu/h 3900 3900
7000Btu/h*2+9000 Btu/h 2600 2600 2600
7000Btu/h*2+12000 Btu/h 2300 2300 3200
7000Btu/h*3 2400 2400 2400
9000Btu/h*2+7000 Btu/h 2700 2700 2700
9000Btu/h*2+12000 Btu/h 2500 2500 3200
9000Btu/h*3 2700 2700 2700
12000Btu/h*2+7000 Btu/h 2400 3200 3200
12000Btu/h*2+9000 Btu/h 2400 3200 3200

207
7. Wiring Diagram
7.1 Indoor unit 7/9K

7.2 Indoor unit 12K

208
7.3 Outdoor unit CED 9-9 I7

Outdoor unit CEM 9-9-9 I7

209
8. Electric Control Functions
8.1 Control system
The control system adopts modular design, that is, all indoor units communicate with outdoor units, ref. to the
following figures for the control structure between indoor units and outdoor units. In the structure, the indoor control
board receives the information from users (for exam. set temp., fan speed etc.) and environment (ex, indoor coil
temp., indoor temp. etc.) ,and organize it to control the action of relevant parts, then transmits the signals to outdoor
control board through the following communication circuit. Outdoor control board can deal with the information
from indoor unit and figure out the best running mode, then transfer the instruction to indoor units to carry out it.
Indoor unit receive the user’s remote control signals.
Indoor unit Outdoor unit
T2B
T1、T2、Ts T3、 T4、T3
Fan Speed Pressure switch
Pressure switch

4-way valve
Fan Fan motor
通讯 Co Compressor
Swing motor mote control EXV

1、 T1 Indoor ambient temp.


2、 T2 Indoor evaporator middle part temp

210
3、 T2B Indoor evaporator outlet temp.
4、 Ts Indoor setting temp.
5、 T3 Outdoor heat-exchanger outlet temp.
6、 T4 Outdoor ambient temp.

8.2 Protection function


8.2.1 AC Volt Protection
a. Over-voltage protection
z When AC voltage ≤ 260V for 30 seconds, Outdoor Unit resumes operation.
z When AC voltage ≥ 270V for 30 seconds, Outdoor Unit stops operation and alarms.
Note: Voltage sampling precision is ±3%.
b. Lack-voltage protection

Volt(V)
Volt increase (Resume)

198
190 MAX=78Hz 190
180
172 MAX=70Hz 172
167
Stop

Volt decrease (Limited Frequency)

8.2.2 AC Amp Protection


The outdoor control board checks the compressor current and do over-current protection.
If the compressor current is over the scheduled value, the system will stop and all indoor units will display
malfunction code.
Note: 1. In order to prevent protection due to too big LRA when compressor starts, the outdoor control board begins
to check the compressor current after 10 seconds.
2. If current protection happens, the compressor will stop and restart 3 minutes later.

8.2.3 High-pressure Protection and Low-pressure Protection

211
The High-pressure switch and Low-pressure switch are installed at suction pipe and discharge pipe separately. And
users can select to install. Normally, the high-pressure switch is cut down when higher than 425Psi (3.3Mpa Cut
down, 2.4Mpa Resume). While the low-pressure switch is cut down when lower than 7Psi (0.05Mpa
On, 0.15Mpa Resume).
Under high-pressure protection or low-pressure protection, the compressor will stop and restart 3
minutes later.

8.2.4 Outdoor Unit communication protection


8.2.4.1 Communication protection between indoor unit and outdoor system chip
If the outdoor unit can’t receive the indoor signal for 30 seconds, then the indoor units are judged as no starting and
there is no alarm signal. If the indoor units send signal to system chip for 2 minutes and no feedback signal is
received, then judge as communication malfunction.
8.2.4.2 Communication protection between outdoor system chip and inverter chip
If can’t receive signal or receive wrong signal for over 2 minutes, Indoor/Outdoor Unit stops operation. When the
signal is right, Indoor/Outdoor Unit restarts.

8.2.5 Outdoor condenser high temperature protection


Under cooling mode, if T3〉65℃ for 3 minutes, the compressor will stop. When T3〈52℃, the protection
is not valid.
When protection is released, the compressor restarts 3 minutes later.

8.2.6 Temperature Sensor short/open protection


When the outdoor condenser pipe temperature T3, outdoor ambient temperature T4, indoor evaporator outlet
temperature T2B are checked out of range 0.05~4.95V, it think temperature sensor short/open
protection. The compressor, four-way valve and outdoor fan motor will stop and send malfunction
signal to indoor units.
When the volt is resumed to the range 0.05~4.95V, then resume signal to indoor units and control
on-off of the compressor, four-way valve and outdoor fan motor by indoor size.

8.2.7 Outdoor low temperature protection


If the outdoor temperature is lower than -15℃ for 1hour, the compressor and fan motor will stop. And
any operation is not valid.
If the outdoor temperature is higher than -12℃ for 10 minutes and the compressor stops operation
for 1h, or the outdoor temperature is higher than 5℃ for 10 minutes, then restart and enter into the
prior operation mode.
If any indoor unit sends out this protection request, the outdoor unit will stop compressor until all
indoor units have not this protection request.

8.2.8 Compressor pre-heating function


When the outdoor temperature is lower than 3℃ and the compressor stops operation for more than 3
hours, or the outdoor temperature is lower than 3℃ and the power is just put on, the compressor
enters into pre-heating condition.

8.3 Display function

212
8.3.1 Checking function
The indoor and outdoor operation condition can be examined by check button.
Normal display Operation mode Capacity request Number of indoor units ambient temp.

Outdoor pipe temp. Compressor current No.1 PMV opening No.2 PMV opening

No.3 PMV opening


8.3.2 Explanation of display function
1. “--”: Standing-by
2. When the compressor is in operation, the compressor operation frequency will be displayed on
the digital pipe.
3. “dF”: Defrosting
4. Under standing-by, display“--” when pre-heating and display “11.” When pre-heating after
turning on the AC.
5. Under malfunction protection:

Display contents Malfunction or Protection


E 0 EEPROM Parameter Malfunction
E1 No.1 Indoor unit Evaporator outlet temp. sensor malfunction
E2 No.2 Indoor unit Evaporator outlet temp. sensor malfunction
E3 No.3 Indoor unit Evaporator outlet temp. sensor malfunction
E4 Outdoor temp. sensor malfunction
E5 Compressor volt protection
E6 Obligate
E 7 Outdoor inverter communication malfunction
P 0 Top temp. protection
P1 High-pressure protection
P2 Low-pressure protection
P3 Compressor current protection
P4 Module protection
P5 Outdoor low-temperature protection
P6 Condenser high-temperature protection
P 7 Obligate

213
214
COOLWEX Group USA.

SPLIT TYPE, HEAT PUMP AIR CONDITIONERS

Technical & service manual 2005

CAS (50Hz) R410a Wall Mounted

[Models]

CAS 7 R10 C

CAS 7 R10

CAS 9 R10 C

CAS 9 R10

CAS 12 R10 C

CAS 12 R10
Contents

1. Features………………………………………………………………….. 2

2. Specification………………………………………………………..……..3

3. Dimensions…………………………………………………………..……4

4. Refrigeration cycle diagram……………………………………………..7

5. Pressure table…………….……………………………………….………8

6. Capacity table………………………………………………………….…11

7. Wiring diagram…………………………………………………..……….16

8. Electronic function………………………………………….………….…21

9. Troubleshooting……………………………………………………….….29

10. Characteristic of temp. sensor………………………………………….32

1
1.Features
1.1 Compact design
1.2 High efficiency and quiet operation
1.3 A class energy level

2
2.Specification
Model CAS 07 R10 C CAS 7 R10 CAS 9 R10 C CAS 9 R10 CAS 12 R10 C CAS 12 R10
Factory Model CE-KF20GW/N1Y-H CE-KFR20GW/N1Y-H CE-KF26GW/N1Y-H CE-KFR26GW/N1Y-H CE-KF36GW/N1Y-H CE-KFR36GW/N1
Y-H
Power supply Ph-V-Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~, 50Hz 1, 220-240V~,
50Hz
Capacity Btu/h 7000 7000 9000 9000 12000 12000
Input W 640 640 820 820 1120 1120
Cooling
Rated current A 2.8 2.8 3.6 3.6 5.0 5.0
Btu/w.h,
EER 11,3.2 11,3.2 11,3.2 11,3.2 11,3.2 11,3.2
w/w
Capacity Btu/h 8500 11000 —— 15000
Input W 690 890 —— 1180
Heating
Rated current A 3.0 3.9 —— 5.3
COP W/W 3.6 3.6 —— 3.6
Moisture Removal L/h 0.7 0.7 1.0 1.0 1.2 1.2
Max. input consumption W 850 1000 1000 1200 1550 1550
Max. current A 3.8 4.5 4.5 5.3 10 10
Starting current A 30 30
Model PA82X1C-4DZ2 PA82X1C-4DZ2 PA108X1C-4FT PA108X1C-4FT PA145X2C-4FT PA145X2C-4FT
Type Rotary Rotary Rotary Rotary rotary rotary
Capacity Btu/h 6680 6680 8870 8870 12000 12000
Input W 675 675 890 890 1200 1200
Compressor Rated current(RLA) A 3.11 3.11 4.07 4.07 5.6 5.6
Locked rotor Amp(LRA) A 15.0 15.0 21.7 21.7 29.9 29.9
Thermal protector UP3QE0591-T71 UP3QE0591-T71 UP3QE0591-T61 UP3QE0591-T61 UP3RE0591-T56 UP3RE0591-T56
Capacitor uF 25 25 25 25 35 35
Refrigerant oil ml 350 350 330 330 480 480
Model RPG13H RPG13H RPG13H RPG13H RPG20D RPG20D
Input W 36.5 36.5 36.5 36.5 51.5 51.5
Indoor fan motor
Capacitor uF 1.2 1.2 1.2 1.2 1.5 1.5
Speed(hi/mi/lo) r/min 1050/9200/820 1050/9200/820 1200/950/850 1200/950/850 1250/1000/800 1250/1000/800
Number of rows 2 2 2 2 2 2
Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydr0philiC Hydr0philiC
Indoor coil aluminium aluminium
Tube outside dia.and type mm φ7, innergroove tube φ7, innergroove φ7, innergroove φ7, innergroove φ7, innergroove φ7, innergroove
tube tube tube tube tube
Number of circuits 2 2 2 2 2 2
Indoor air flow (Hi/Mi/Lo) m3/h 450/400/350 450/400/350 500/460/410 500/460/410 680/520/420 680/520/420
Indoor noise level (Hi/Mi/Lo) dB(A) 34/32/30 34/32/30 36/34/32 36/34/32 39/33/28 39/33/28
Dimension (W*H*D) mm 750*250*205 750*250*205 750*250*205 750*250*205 815*280*215 815*280*215
Indoor unit Packing (W*H*D) mm 830X285X335 830X285X335 830X285X335 830X285X335 915X290X360 915X290X360
Net/Gross weight Kg 8/10 8/10 8/10 8/10 10/12 10/12
Model YDK24-6T YDK24-6T YDK24-6F YDK24-6F YDK36-6 YDK36-6
Input W 56 56 56 56 68 68
Outdoor fan motor
Capacitor uF 2.5 2.5 2.5 2.5 2.5 2.5
Speed r/min 800 800 800 800 900 900
Number of rows 2 2 2 2 2 2
Fin type (code) Unhydrophilic aluminium Hydrophilic aluminium Unhydrophilic Hydrophilic aluminium Unhydrophilic Hydrophilic
aluminium aluminium aluminium
Outdoor coil Tube outside dia.and type mm Ф7,innergroove tube Ф7,innergroove tube Ф7,innergroove tube Ф7,innergroove tube Ф9.53,innergroove Ф9.53,innergroove
tube tube
Coil length x height x width mm 750x508x26.74 750x508x26.74 810x508x26.74 810x508x26.74 680x550x44 680x550x44
Number of circuits 2 2 2 2 2 2
Outdoor air flow m3/h 1500 1500 1800 1800 1900 1900
Outdoor noise level dB(A) 49 49 50 50 52 52
Dimension(W*H*D) mm 700X535X235 700X535X235 780X540X250 780X540X250 760X590X285 760X590X285
Outdoor unit Packing (W*H*D) mm 815X580X325 815X580X325 910X575X335 910X575X335 890X655X360 890X655X360
Net/Gross weight Kg 31/34 32/35 36/39 37/40 41/45 41.5/45.5
Refrigerant type R410A g 800 820 900 920 1160 1170
Design pressure MPa 4.2 4.2 4.2 4.2 4.2 4.2
Liquid side/ Gas side mm(inch) Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф9.53 Ф6.35/Ф12.7 Ф6.35/Ф12.7
Refrigerant piping Max. refrigerant pipe length m 10 10 10 10 10 10
Max. difference in level m 5 5 5 5 5 5
Connection wiring No No No No No No
Plug type 16A 16A 16A 16A 16A 16A
Thermostat type Electrolic control Electrolic control Electrolic control Electrolic control Electrolic control Electrolic control
Operation temp ℃ 17-30 17-30 17-30 17-30 17-30 17-30
Ambient temp ℃ 18~-45 -7 -~ 45 18~-45 -7 -~ 45 18~-45 -7 -~ 45

Application area m2 10-14 10-14 14-21 14-21 18-26 18-26

★1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient

condition.

3
3.Dimensions
3.1 Indoor unit
CAS 7 R10 C, CAS 7 R10, CAS 9 R10 C, CAS 9 R10

3.2 Indoor unit


CAS 12 R10 C, CAS 12 R10

4
3.4 Outdoor unit
CAS 7 R10 C, CAS 7 R10

3.5 Outdoor unit


CAS 9 R10 C, CAS 9 R10

5
3.6 Outdoor unit
CAS 12 R10 C, CAS 12 R10
750
285

590
62
315

290

530 110

6
4.Refrigeration cycle diagram

7
5. Pressure table
Note:
*The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.
*D: Dry bulb temp.
*W: Wet bulb temp.
5.1 CAS 12 R10 C
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

21ºC D Pressure
6.2 6.8 7.2 8.0 8.5 9.5
15ºC W ( kg/cm2 )

24ºC D Pressure
6.3 6.5 7.5 8.0 8.7 9.5
17ºC W ( kg/cm2 )

27ºC D Pressure
6.1 6.9 7.7 8.2 9.1 10.0
19ºC W ( kg/cm2 )

32ºC D Pressure 7.0 7.3 7.8 8.3 9.2 10.1


23ºC W ( kg/cm2 )

5.2 CAS 12 R10


Cooling mode Outdoor temperature (Dry bulb temp)
Indoor
Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions

21ºC D Pressure
6.2 6.8 7.2 8.0 8.5 9.5
15ºC W ( kg/cm2 )

24ºC D Pressure
6.3 6.5 7.5 8.0 8.7 9.5
17ºC W ( kg/cm2 )

27ºC D Pressure
6.1 6.9 7.7 8.2 9.1 10.0
19ºC W ( kg/cm2 )

32ºC D Pressure 7.0 7.3 7.8 8.3 9.2 10.1


23ºC W ( kg/cm2 )

Heating mode OUTDOOR CONDITIONS


12ºC D 7ºC D 0ºC D -4ºC D -7ºC D -15ºC D
Indoor Conditions Pressure
11ºC W 6ºC W -1ºC W -6ºC W -9ºC W -xºC W
Pressure
15ºC 24.0 23.0 21.5 21.0 20..5 /
( kg/cm2 )
Pressure
18ºC 24.6 23.5 23.0 22.6 20.8 /
( kg/cm2 )
Pressure
20ºC 25.0 23.8 24.0 23.0 21.0 /
( kg/cm2 )
Pressure
22ºC 25.3 24.6 24.5 23.8 21.7 /
( kg/cm2 )

8
5.3 CAS 12 R10 C
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

21ºC D Pressure
7.8 8.1 8.4 9.0 9.3 10.0
15ºC W ( kg/cm2 )

24ºC D Pressure
7.9 8.2 8.7 9.0 9.5 10.1
17ºC W ( kg/cm2 )

27ºC D Pressure
8.0 8.5 9.2 9.9 10.2 10.8
19ºC W ( kg/cm2 )

32ºC D Pressure 8.8 9.1 9.2 10.0 10.5 11.2


23ºC W ( kg/cm2 )

5.4 CAS 12 R10


Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC

21ºC D Pressure
7.8 8.1 8.4 9.0 9.3 10.0
15ºC W ( kg/cm2 )

24ºC D Pressure
7.9 8.2 8.7 9.0 9.5 10.1
17ºC W ( kg/cm2 )

27ºC D Pressure
8.0 8.5 9.2 9.9 10.2 10.8
19ºC W ( kg/cm2 )

32ºC D Pressure 8.8 9.1 9.2 10.0 10.5 11.2


23ºC W ( kg/cm2 )

Heating mode OUTDOOR CONDITIONS


12ºC D 7ºC D 0ºC D -4ºC D -7ºC D -15ºC D
Indoor Conditions Pressure
11ºC W 6ºC W -1ºC W -6ºC W -9ºC W -xºC W
Pressure
15ºC 26.5 25.0 22.0 21.5 20.5 /
( kg/cm2 )
Pressure
18ºC 27.0 26.0 23.5 22.5 20.8 /
( kg/cm2 )
Pressure
20ºC 27.5 26.5 25.0 23.0 21.0 /
( kg/cm2 )
Pressure
22ºC 28.5 27.0 25.5 23.9 21.5 /
( kg/cm2 )

9
5.5 CAS 12 R10 C
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D Pressure
8.4 8.5 8.8 8.9 9.4 9.9
15ºC W ( kg/cm2 )

24ºC D Pressure
8.6 8.8 9.2 9.4 10.0 10.4
17ºC W ( kg/cm2 )

27ºC D Pressure
8.8 9.2 9.4 9.8 10.3 10.9
19ºC W ( kg/cm2 )

32ºC D Pressure 9.2 9.6 9.9 10.4 10.8 11.2


2
23ºC W ( kg/cm )

5.6 CAS 12 R10


Cooling mode Outdoor temperature (Dry bulb temp)
Indoor Conditions Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
21ºC D Pressure
8.4 8.5 8.8 8.9 9.4 9.9
15ºC W ( kg/cm2 )

24ºC D Pressure
8.6 8.8 9.2 9.4 10.0 10.4
17ºC W ( kg/cm2 )

27ºC D Pressure
8.8 9.2 9.4 9.8 10.3 10.9
19ºC W ( kg/cm2 )

32ºC D Pressure 9.2 9.6 9.9 10.4 10.8 11.2


23ºC W ( kg/cm2 )

Heating mode OUTDOOR CONDITIONS


12ºC D 7ºC D 0ºC D -4ºC D -7ºC D -15ºC D
Indoor Conditions Pressure
11ºC W 6ºC W -1ºC W -6ºC W -9ºC W -xºC W
Pressure
15ºC 27.4 25.9 22.2 21.4 20.0 /
( kg/cm2 )
Pressure
18ºC 29.8 27.2 23.8 22.0 21.1 /
( kg/cm2 )
Pressure
20ºC 30.2 29.1 24.2 23.6 22.1 /
( kg/cm2 )
Pressure
22ºC 32.4 30.1 25.4 24.0 22.7 /
( kg/cm2 )

10
6. Capacity table
6.1 CAS 7 R10 C
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.06 1.95 1.75 1.51 1.58 1.41
21ºC D
Sensitive capacity kW 1.52 1.37 1.39 1.32 1.19 1.07
15ºC W
Input kW. 0.53 0.58 0.62 0.63 0.78 0.80
Total capacity kW 2.14 2.05 1.96 1.72 1.73 1.52
24ºC D
Sensitive capacity kW 1.61 1.46 1.45 1.54 1.23 1.15
17ºC W
Input kW. 0.60 0.60 0.66 0.65 0.78 0.83
Total capacity kW 2.31 2.24 2.10 1.90 1.73 1.67
27ºC D
Sensitive capacity kW 1.78 1.65 1.42 1.43 1.26 1.28
19ºC W
Input kW. 0.55 0.63 0.64 0.70 0.79 0.84
Total capacity kW 2.33 2.33 2.31 2.38 2.15 2.07
32ºC D
Sensitive capacity kW 1.83 1.67 1.65 1.64 1.57 1.53
23ºC W
Input kW. 0.53 0.65 0.69 0.73 0.83 0.88

6.2 CAS 7 R10


SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.04 1.94 1.70 1.61 1.53 1.41
21ºC D
Sensitive capacity kW 1.52 1.41 1.39 1.32 1.19 1.07
15ºC W
Input kW. 0.53 0.58 0.60 0.67 0.73 0.80
Total capacity kW 2.14 2.05 1.93 1.81 1.73 1.51
24ºC D
Sensitive capacity kW 1.61 1.46 1.45 1.54 1.23 1.15
17ºC W
Input kW. 0.54 0.60 0.62 0.70 0.74 0.82
Total capacity kW 2.31 2.24 2.05 1.95 1.70 1.65
27ºC D
Sensitive capacity kW 1.78 1.65 1.54 1.43 1.26 1.28
19ºC W
Input kW. 0.57 0.62 0.64 0.71 0.75 0.83
Total capacity kW 2.33 2.36 2.31 2.25 2.15 2.03
32ºC D
Sensitive capacity kW 1.83 1.67 1.65 1.64 1.57 1.52
23ºC W
Input kW. 0.58 0.64 0.66 0.73 0.80 0.86

11
WINTER OUTDOOR CONDITIONS
Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D
Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
Capacity kW 3.01 2.73 2.47 1.76 1.65 1.58
15ºC
Input kW. 0.76 0.66 0.60 0.58 0.50 0.45
Capacity kW 2.86 2.64 2.34 1.69 1.53 1.41
18ºC
Input kW. 0.78 0.67 0.62 0.59 0.62 0.47
Capacity kW 2.77 2.49 2.28 1.62 1.59 1.33
20ºC
Input kW. 0.81 0.69 0.64 0.59 0.53 0.48
Capacity kW 2.61 2.43 2.13 1.58 1.26 1.17
22ºC
Input kW. 0.83 0.68 0.65 0.60 0.56 0.51

6.3 CAS 9 R10 C


SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.42 2.37 2.23 2.03 1.87 1.75
21ºC D
Sensitive capacity kW 1.72 1.69 1.65 1.53 1.43 1.36
15ºC W
Input kW. 0.72 0.75 0.80 0.84 0.89 0.96
Total capacity kW 0.65 2.55 2.45 2.24 2.11 1.98
24ºC D
Sensitive capacity kW 1.83 1.73 1.70 1.63 1.63 1.57
17ºC W
Input kW. 0.70 0.76 0.84 0.88 0.92 1.01
Total capacity kW 2.89 2.80 2.66 2.46 2.25 2.03
27ºC D
Sensitive capacity kW 1.95 1.91 1.83 1.78 1.66 1.63
19ºC W
Input kW. 0.65 0.78 0.82 0.91 0.95 1.02
Total capacity kW 3.01 2.98 2.92 2.83 2.69 2.45
32ºC D
Sensitive capacity kW 2.05 1.88 1.96 1.87 1.87 1.85
23ºC W
Input kW. 0.64 0.80 0.88 0.98 1.03 1.10

12
6.4 CAS 9 R10
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.42 2.41 2.24 2.03 1.87 1.75
21ºC D
Sensitive capacity kW 1.72 1.69 1.65 1.53 1.43 1.36
15ºC W
Input kW. 0.72 0.75 0.80 0.84 0.89 0.97
Total capacity kW 0.65 2.55 2.45 2.24 2.11 1.98
24ºC D
Sensitive capacity kW 1.83 1.73 1.70 1.63 1.63 1.57
17ºC W
Input kW. 0.68 0.76 0.81 0.88 0.93 1.02
Total capacity kW 2.89 2.80 2.63 2.45 2.23 2.05
27ºC D
Sensitive capacity kW 1.99 1.95 1.81 1.78 1.66 1.63
19ºC W
Input kW. 0.65 0.78 0.82 0.92 0.96 1.03
Total capacity kW 3.03 2.98 2.92 2.83 2.69 2.46
32ºC D
Sensitive capacity kW 2.05 1.88 1.96 1.87 1.87 1.85
23ºC W
Input kW. 0.65 0.80 0.86 0.95 0.99 1.08

WINTER OUTDOOR CONDITIONS


Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D
Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
Capacity kW 3.75 3.38 3.02 1.97 1.59 1.52
15ºC
Input kW. 0.97 0.84 0.73 0.65 0.62 0.63
Capacity kW 3.52 3.26 2.94 1.84 1.60 1.49
18ºC
Input kW. 0.98 0.86 0.78 0.70 0.65 0.68
Capacity kW 3.45 3.22 2.85 1.82 1.56 1.50
20ºC
Input kW. 1.02 0.89 0.80 0.74 0.68 0.67
Capacity kW 3.18 3.13 2.72 1.73 1.58 1.42
22ºC
Input kW. 1.06 0.93 0.82 0.77 0.71 0.65

13
6.5 CAS 12 R10 C
SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 3304 3198 3921 2856 2787 2684
21ºC D
Sensitive capacity kW 2607 2497 2411 2304 2242 2111
15ºC W
Input kW. 907 1006 1096 1184 1259 1457
Total capacity kW 3683 3511 3339 3166 3066 2960
24ºC D
Sensitive capacity kW 2938 2790 2745 2580 2470 2359
17ºC W
Input kW. 926 1035 1127 1230 1278 1380
Total capacity kW 3896 3718 3646 3387 3235 3232
27ºC D
Sensitive capacity kW 3076 2938 2856 2690 2580 2470
19ºC W
Input kW. 943 1058 1120 1265 1322 1437
Total capacity kW 4199 4009 3850 3614 3541 3370
32ºC D
Sensitive capacity kW 3098 2990 2900 2745 2607 2552
23ºC W
Input kW. 977 1090 1190 1310 1368 1495

6.6 CAS 12 R10


SUMMER OUTDOOR TEMPERATURE DRY
Indoor
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 3276 3187 3105 2821 2746 2621
21ºC D
Sensitive capacity kW 2567 2457 2413 2287 2210 2087
15ºC W
Input kW. 890 1010 1082 1188 1243 1337
Total capacity kW 3663 3503 3315 3148 3076 2932
24ºC D
Sensitive capacity kW 2918 2766 2725 2557 2453 2334
17ºC W
Input kW. 915 1033 1121 1228 1278 1367
Total capacity kW 3860 3700 3626 3371 3215 3125
27ºC D
Sensitive capacity kW 3039 2913 2832 2645 2567 2419
19ºC W
Input kW. 944 1048 1120 1253 1312 1426
Total capacity kW 4215 4100 3845 3601 3501 3313
32ºC D
Sensitive capacity kW 3120 2939 2891 2715 2589 2503
23ºC W
Input kW. 969 1088 1189 1302 1349 1455

14
WINTER OUTDOOR CONDITIONS
Indoor 12ºC D 7ºC D 4ºC D 0ºC D -4ºC D -7ºC D
Conditions 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
Capacity kW 4446 4264 4132 3838 3335 305
15ºC
Input kW. 1141 1106 1059 1035 895 812
Capacity kW 4380 4248 3954 3761 3258 2948
18ºC
Input kW. 1188 1153 1142 1082 953 918
Capacity kW 4261 4153 3877 3683 3189 2871
20ºC
Input kW. 1224 1180 1129 1082 976 941
Capacity kW 4106 3989 3761 3567 3045 2876
22ºC
Input kW. 1259 1212 1153 1106 1000 836

15
7. Schematic diagram and wiring diagram
7.1 Schematic diagram
1 2 3 4 5 6 7 8

R18 10K +5V


D1 IN4007*4 IC1 7812 +12V-a IC3 7805 +5V +5V ZERO
1 3 1 3 R19 150
CN1 Vin Vout Vin Vout +5V
D2

GND
D13

GND
R16 12K REC1
4 A A Q2 R20 1K IN4148 +12V-a CN4
E1 C1 E2 C3 E3 C4 REC
3 D3 REC
R15R17 9014 V
2 B 104 104 104 D11 1N4148 C9 R215.1K 3
D4 D12 1N4148 12K12K C10 C11 GND FANSP_FEEDBACK 2
1 104
2

2
B E7 1
RECEIVER_V C12
TRANS
2200uF/25V 1000uF/16V 470uF/16V 102 104 103 FAN_BACK
D D
IC10 7812 +12V-b 10uF/16V
D16 IN4007*4 1 3
Vin Vout COM1 COM2 COM3
GND

C D17 E10 C23 E11 C24 +5V +5V +5V


R41 R42 R43
D D18 104 104 2K 2K 2K
R41 R41 R41
2

D19
2200uF/25V 1000uF/16V 10K 10K 10K
GNDB
+5V
R4 12K Q8 Q9 Q10

+5V
C5 1
3
104 RST 9012 9012 9012
2
C26 IC4
C25
IC5 KIA7042 104 1 42 X1 R7 X1 DIS1
104 VSS0 X1 +5V C2
+5V 1M WT4021BG
2 41 X2 IC2
+12V VDD0 X2
4M R1 R2 104
JR8 FAN_IN 3 40 RST 8 1 +12V-a CN9
FAN_IN P25 RESET RST 10K 10K VCC A0
10K 7 2 LOAD_HEAT N
R5 6
WC A1
3
Only For Heat Pump 1
1K HEAT BUZ BUZ 4
P26 XT1
39 SCL SCL A2 D21
5 4 HEAT_N
SDA SDA GND RY2
BUZ1 JR9 STEP_I1 5 38
BUZ ' STEP_I1 P00 XT2 RELAY-SPST
BUZZER1 10K 24C04
+5V STEP_I2 6 37 IN4148
C STEP_I2 P01 Vpp/IC C
N

a
e
d

b
com1
com2
h
g
f
STEP_I3 7 36 SCL Q3
R38 STEP_I3 P02 P24 SCL R27
IC8 9014
10K STEP_I4 8 35 SDA 7 13
STEP_I4 P03 P23 SDA GND Q7 2K
C24 R44 330
SW_TEST 104
R39 COMP 9 34 COM1 14 12
C22 COMP P04 P22 COM1 Vcc Q6
5.1K 104 JR1 R45 330
10 33 COM2 11
VSS1 P21 COM2 Q5
+12V-a CN10
10K R46 330
HEAT 11 32 9 10 LOAD_HEAT L
P05 VDD1 +5V +5V MR Q4 LED6 1
SW1
R47 330 自动 D22
SEG1 12 31 COM3 8 6 HEAT_L
SEG1 P50 P20 COM3 SEG3 CP Q3 LED7 IN4148 RY3
R48 330 化霜 RELAY-SPST
SEG2 13 30 FAN_OUT FAN_OUT C16 5
SEG2 P51 P33 102 Q2
R49 330 LED8
SEG3 14 29 FANSP FANSP_FEEDBACK 2 4 定时
SEG3 P52 P32 SEG4 Dsb Q1 FUSE2
LED9 Q5
R54 330 R33
SEG4 15 28 ZERO C17 1 3 运行灯 9014
SEG4 P53 P31 ZERO 102 Dsa Q0 HEAT 10A
R55 330 2K
16 27 REC REC 74HC164
+5V AVDD P30 +5V SW2 CN16
17 26 VALVE VALVE +12V-b 1
CN2 +5V AVREF P11

FRESH
R59 R60 +12V-a CN13
2 T1_room T1 18
AN10 P10
25 FRESH FRESH 2
10K 10K JR4 10K LOAD_FAN OUT
D5 1
1 IN4148 T2_I.pipe T2 19
AN11 AVSS
24
JR5 10K R62 IC9 R63 D23
+5V R61 Q12 RY4 2
T1_room
B R10 2K Current CURRENT 20 AN12 AN15
23
2K
1K 5.1K
RELAY-SPST B
JR2 10K 9014
T1_room IN4148
AUTO_SELECT AUTO_SELECT 21 22 SW SW_TEST Q11
D6 E4 C6 AN13 AN14 JR3 10K +12V-a PC817 +12V-b L1
R8 UPD789166 9014 GNDB Q6
8.1K/1% IN4148 10uF/16V 104 IC7 R34 9014
FAN_OUT
1 16 2K
STEP_I1 IN1 OUT1 1
CN3 +5V
2 15
STEP_I2 IN2 OUT2 2 CN12
2
D7 3 14
STEP_I3 IN3 OUT3 3
1 IN4148 +12V-a
4 13 LOAD_VALVE
T2_I.pipe STEP_I4 IN4 OUT4 4
R11 2K C20
T2_I.pipe 5 12 D24
FAN_IN IN5 OUT5 FAN_IN ' 5 333
RY5
D8 E5 C7
6 11 +12V-a SWING RELAY-SPST
R9 +5V BUZ IN6 OUT6 BUZ ' IN4148
8.1K/1% IN4148 10uF/16V 104
7 10 R36
COMP IN7 OUT7 COMP ' 51/1W
Q7
JR6 R35
8 9 9014
10K VSS VDD VALVE
2K
R23 2K C19 UJN2003 L1
104 FUSE1
AUTO_SELECT
+5V
CN6 3.15A/250V
JR7 C13 +12V-a
1 +12V-a LOAD_COMP
D9 10K 104 R25 51/1W C15 L1 C21
1N4148 CN15
A 2 333 A
E9 C23 1 RY6 333
R12 2K R14 ? ZR1
3 T2 T1 470uF/25V COMP
Current 10D471K 0.1uF/275VAC
1.4K/1% L2 Z1 R28 R29 2
CT1 BT131 D15 t COMP ' R37
D10 4 C14 12V 11K/2W 11K/2W TRANS_IN
C8 R13 TR1 N 51/1W
1N4148 0057h
104 E6 16K R6 1.2uF/450V L(POWER_IN PORT)
5 IC6 PC817 IN4007 PTC
G

10uF/16V 1K/1% CN14 CN11


FAN_IN +12V-a 82RM
1 1
2K R24 R26
FAN_IN ' N N
1K

1 2 3 4 5 6 7 8

16
7.2 Wiring diagram
7.2.1 Cooling only

7.2.1.1 CAS 7 R10 C, CAS 9 R10 C

INDOOR UNIT
O
U
T
D
O
O
R
U
N
I
T

1
2
(
N
)

Y&G
B
L
A
C
K

B
L
A
C
K
O
V
E
RE
L
O
A
D
R
L
A
Y

R
E
D

R
E
D
B
L
A
C
K
C
O
M
P
R
E
S
S
O
R
C

R
E
D

F
A
NT
R
E
D
M
O
O
R
R

Y&G
S

Y&G
B
L
U
E

B
L
U
E

COMPRESSOR FAN
CAPACITOR CAPACITOR

17
7.2.1.2 CAS 12 R10 C

18
7.2.2 Heating/cooling
7.2.2.1 CAS 7 R10, CAS 9 R10

19
7.2.2.2 CAS 12 R1

20
8 Electronic function
8.1 Electric Control working environment
8.1.1 input voltage: 175~253V
8.1.2 Input power frequency:50Hz
8.1.3 Ambient temperature: -7°C~+43°C
8.1.4 Indoor fan normal working amp is less than 1A,
8.1.5 Outdoor fan. Normal working amp is less than 1.5A
8.1.6 Four-way valve normal working amp is less than 1A.
8.1.7 Swing motor: DC12V.
8.1.8 Compressor: single-phase power supply. Its normal working amp is less than 15A
8.2 Proper symbols and their meanings:
TA: Indoor ambient temperature
TE: Indoor evaporator temperature
TS: Setting temperature through the remote controller
I3sec: Self-protection amp of compressor, continue three seconds until turns off the compressor.
I5MIN: Self-protection amp of compressor, continue five minutes until turns off the compressor.
IFAN: Self-protection amp of outdoor fan/indoor fans when they change from higher wind to lower wind.
IRESTORE: Amp self-protection return value
THDEFROST: High wind, defrosting temperature difference
TMDEFROST: Middle wind, defrosting temperature difference
TLDEFROST: Low wind, defrosting temperature difference
TE1: Anti-cold wind, from Fan Off to Breeze temperature
TE2: Anti-cold wind, from Breeze to Setting Fan Speed temperature
TE3: Anti-cold wind, from Setting Fan Speed to Breeze temperature
TE4: Anti-cold wind, from Breeze to Fan Off temperature
TE5: Evaporator low temperature protection entering temperature
TE6: Evaporator low temperature protection restoring temperature
TE7: Evaporator high temperature protection, compressor off temperature
TE8: Evaporator high temperature protection, fan off temperature
TE9: Evaporator high temperature protection, restoring temperature

8.3 Functions
Remote receiving
Testing and forced running
Position set for indoor unit wind vane
LED displaying and alarm
On or off Timer
Protection for the compressor
Current protection
High temperature protection of indoor heat exchanger at heating mode
Auto defrosting and heating recovery at heating mode
Anti cold air at heating mode
Anti frozen at cooling mode

21
8.4 Protection
8.4.1 3 minutes delay at restart for compressor.
8.4.2 Sensor protection at open circuit and breaking disconnection
8.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t returns to
normal operation automatically.
8.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t returns to normal operation automatically.
8.4.5 The current protection of the compressor
Condition Indoor fan Compressor Outdoor fan Remark

Current up I< IRESTORE On On On

IRESTORE <I< IFAN On On Off Heating mode

Low speed On On Cooling mode

IFAN <I<I5MIN Off Off After 5 Minutes

I5MIN<I< I3SEC Off Off After 3 Seconds

Current down I5MIN<I< I3SEC Off Off After 3 Seconds

IFAN <I<I5MIN Off Off After 5 Minutes

IRESTORE <I< IFAN On On Off Heating mode

Low speed On On Cooling mode

I< IRESTORE On On On

If compressor turns off for continuously 4 times due to current protection in 5 minutes from
Compressor On, the unit stops and LED displays failure information and can’t returns to normal
operation automatically.

8.5 Fan-only mode


Fan speed is high/mid/low/ Auto
8.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:
Condition Compressor Outdoor fan
T=Indoor Temp.
Ts=Setting Temp.
Room temp. up T> Ts+1 On On
T<Ts+1 Off Off
Room temp. down T> Ts On On
T<Ts Off Off
Auto fan at cooling mode:
Condition Indoor fan speed
T=Indoor Temp.-Setting Temp.
Room temp. up T<4℃ Low
4℃<T<5℃ Med.
T>5℃ High
Room temp. down T> 4℃ High
1℃<T<4℃ Med.
T<1℃ Low
22
Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Condition Compressor Outdoor fan
Temp. Time
Evaporator Temp. up T> TE6 On On
T< TE6 >5 Minutes Off Off
Evaporator Temp. down T> TE5 On On
T< TE5 >5 Minutes Off Off

8.7 Dehumidifying mode


8.7.1 The 4-way valve is off in dehumidifying mode
8.7.2 Compressor and Indoor Fan actions in dehumidifying mode
NO Conditions Indoor Fan Compressor and Outdoor Fan
LOW ON 6minutes
1 TA ≥ TS+2
BREEZE OFF 4minutes
LOW ON 5minutes
2 TS ≤TA<TS+2
BREEZE OFF 5minutes
LOW ON 4minutes
3 TA < TS
BREEZE OFF 6minutes
Repeat on and off cycle.

23
8.7.3 Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 13℃.
8.7.4 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that
of cooling mode.
8.7.5 At dehumidifying mode, the action of fans of indoor is the same as that of air-only mode.
8.8 Heating mode
8.8.1 Generally, the 4-way valve is open in heating mode, but it is closed in defrosting mode. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
8.8.2 Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
8.8.3 Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan

Room temp. up T> Ts+3 Off Off

T<Ts+3 On On

Room temp. down T< Ts+2 On On

T>Ts+2 Off Off

8.8.4 Indoor Fan actions at heating mode


Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
function prevails.
Anti-cold wind control function at heating mode
Condition Indoor fan speed

T= Indoor exchanger temp.

Indoor exchanger temp. up T<TE1 Off

TE1<T<TE2 Breeze

T>TE2 Setting fan speed

Indoor exchanger temp. down T> TE3 Setting fan speed

TE3<T<TE4 Breeze

T<TE4 Off

8.8.5 Auto wind at heating mode


Condition Indoor fan speed

T=Indoor Temp.-Setting Temp.

Room temp. up T<2℃ High

T>2℃ Med.

Room temp. down T> 0℃ Med.

T<0℃ High

24
8.8.6 Indoor evaporator high-temperature protection at heating mode
Condition Compressor Outdoor fan

T= Indoor exchanger temp.

Indoor exchanger temp. up T<TE8 On On

TE8<T<TE7 On Off

T>TE7 Off Off

Indoor exchanger temp. down T>TE9 Off Off

T<TE9 On On

8.8.7. The louver opens to Standard Angle ANGLHEAT when power is on for the first time
8.9 Defrosting operation (Available for heating only).
8.9.1 Defrosting condition: Defrosting starts when either of the following ①&②:
① A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:

Temp. of evaporator---room temp.

Fan speed is high ≤THDEFROST

Fan speed is mid ≤TMDEFROST

Fan speed is low ≤TLDEFROST

Breeze Meet only if it is Breeze

② Calculate from the end of latest defrost, evaporator high temp. protection only closes outdoor fan
with the compressor still running. Add up to 90 minutes.
8.9.2 Defrosting time
If the temp. difference condition ① is satisfied for less than 40 minutes, this can be regarded as
severe frosting. The defrosting time is 10 minutes.
If the temp. difference condition ② is satisfied for more than 40 minutes, the defrosting time is 6
minutes.
If the temp. difference condition ① is satisfied out of 40 minutes, generally the defrosting time is 6
minutes, after three continuous 6-minute defrost, the fourth should be 10 minutes defrost. The
circulation is as following:
→7.5-minute defrost → 7.5-minute defrost→7.5-minute defrost→10-minute defrost→

8.9.3 Ending condition of defrosting


If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minutes.
B. The compressor current has reached to IDEFROST or above, IDEROST differs in different models.

25
8.9.4 Defrosting Actions:

Defrost 10or 6minutes

45S 25S
Compressor

4-way Valve 23S


40S
Outdoor Fan

Indoor Fan

10S

8.10 Automatic operation mode


8.10.1 The air conditioner automatically selects one of the following operation modes: cooling, heating or
fan only according to the temp. difference between room temp. (TA) and set temp. (TS).
TA—TS Operation mode

TA—TS>2℃ Cooling

-1℃≤TA-TS≤+2℃ Fan-only

TA-TS<-1℃ Heating (air-only for cooling only type)

8.10.2 The indoor fan blows automatically in corresponding selected mode.


8.10.3 The motion of indoor fan’s blade should accord with the selected operation mode.
8.10.4 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot
start for 15 minutes, reselect the operation mode according to the room temp. and set temp., or
reselect when the set temp. varies.

8.11 Forced cooling function


8.11.1 Select forced cooling function with the forced cooling button or the switch.
8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is
set as low, the A/C operates at the DRY mode with a set temp. of 24℃.
8.11.3 All protections of remote control cooling are available at forced cooling operation.
8.12 Forced Auto function
Select forced auto function with the forced auto button or the switch.
In forced auto status the A/C operates at remote control mode with a set temp. of 24℃.
8.13 Timer Function

8.14 Economic Running


8.14.1 The economic running function is available at cooling, heating or auto mode.
8.14.2 Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a
26
constant and the fan speed is kept at low speed.
8.14.3 Heating:
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the air circulation is kept at low speed (Cold air proof function takes precedence over
all).
8.14.4 Auto:
The economic running function operates in accordance with selected running mode by auto mode.
8.15 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings before
the power failure when power returns.

27
8.16 Models and Parameters

Model CAS_7_R7_C_______CAS_7_R7________CAS 9 R7 C CAS 9 R7 CAS_12_R7_C CAS_12_R7

I3SEC 7.5A 7.5A 10.0A 10.0A 12.0A 12.0A

I5MIN 6.2A 6.2A 7.5A 7.5A 8.5A 8.5A

IFAN 5.2A 5.2A 5.5A 5.5A 7.5A 7.5A

IRESTORE 4.2A 4.2A 4.5A 4.5A 6.5A 6.5A

IDEFROST 3.2A 3.5A 5.0A

TE1 28℃ 28℃ 34℃

TE2 32℃ 32℃ 37℃

TE3 30℃ 30℃ 33℃

TE4 26℃ 26℃ 22℃

TE5 4℃ 4℃ 4℃ 4℃ 3℃ 3℃

TE6 10℃ 10℃ 10℃ 10℃ 10℃ 10℃

TE7 60℃ 60℃ 63℃

TE8 53℃ 53℃ 53℃

TE9 50℃ 50℃ 50℃

ANGLCOOL 200° 200° 200° 200° 155° 155°

ANGLHEAT 0° 0° 10°

ANGLOFF 124° 124° 124° 124° 124° 124°

THDEFROST 17°C 17°C 20°C

TMDEFROST 18°C 18°C 23°C

TLDEFROST 19°C 19°C 26°C

28
9.Troubleshooting

9.1 Display board

Infrared Signal
1 2 3 4 5 6
Receiver

1: AUTO indicator

2: TIMER indicator

3: PRE.-DEF. Indicator

4: OPERATION indicator

5: SLEEP indicator

9.2 For all heat pump model


Failure phenomenon Operation lamp Timer lamp

Indoor fan speed has been out of control for over 1 minute ☆ X

Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On

Over current protection of the compressor occurs 4 times X ☆

EEROM error On ☆

No over-zero signal ☆ ☆

r Extinguish
☆ Flash at 5Hz

29

9.3 Diagnostic Chart
9.3.1 After energizing, no indicator is lighted and the air conditioner can’t be operated.

After energizing, the air conditioner can’t be operated

Check if AC220V power supply outputs to Indoor PCB.

Yes

Check if AC220V exists at the primary coil of transformer.

Yes No

Indoor PCB is defective

Check if AC14.5V exists at the secondary coil of transformer.

No Yes

Take off the secondary plug of transformer, and then check if


Yes
AC14.5V exists at the secondary coil of transformer.

No

The transformer is defective. Indoor PCB is defective

9.3.2 Resetting phenomenon often occurs during operation. (That is automatically entering to the status when
power is on.)
The reason is that the instantaneous voltage of main chip is less than 4.5V. Check according to the following procedure:

Resetting phenomenon often occurs during operation.

Yes

After changing Indoor PCB, check if the failure releases.

No Yes

After changing indoor fan motor, check if the failure releases. Indoor PCB is defective

No
Power supply circuit has problems.

30
9.3.3 Failure phenomenon
Failure phenomenon Operation lamp Timer lamp

Indoor fan speed has been out of control for over 1 minute ☆ X

Indoor room temp. or evaporator sensor is open circuit or short circuit ☆ On

Over current protection of the compressor occurs 4 times X ☆

EEROM error On ☆

No over-zero signal ☆ ☆

r Extinguish
☆ Flash at 5Hz
9.3.3.1 Operation lamp flashes and Timer lamp off.

Is connector connection good?

Yes No

Is voltage being applied to the fan motor? Repair the connector

Yes No

Fan motor is defective Indoor PCB is defective

9.3.3.2 Operation lamp flashes and Timer lamp on.

Is connection to connector good?

No
Yes

Replace the sensor Repair connector

9.3.3.3 Operation lamp off and Timer lamp flashes

Operation lamp off and Timer lamp flashes

After changing the main control board, check if the failure releases.

Yes
No Yes
The voltage of power supply is too low (less than 187V)? Indoor PCB is defective

Yes No

Power supply fault Outdoor unit fault (such as the compressor)

9.3.3.4 Operation lamp on and Timer lamp flashes


EEROM error, indoor PCB is defective.
9.3.3.5 Operation lamp flashes, Timer lamp flashes .
This is alarm signal when the main chip can’t detect over-zero signal. When such failure occurs, the main
control board must have fault.
31
10. Characteristic of temp. sensor
Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ

-10 62.2756 17 14.6181 44 4.3874

-9 58.7079 18 13.918 45 4.2126

-8 56.3694 19 13.2631 46 4.0459

-7 52.2438 20 12.6431 47 3.8867

-6 49.3161 21 12.0561 48 3.7348

-5 46.5725 22 11.5 49 3.5896

-4 44 23 10.9731 50 3.451

-3 41.5878 24 10.4736 51 3.3185

-2 39.8239 25 10 52 3.1918

-1 37.1988 26 9.5507 53 3.0707

0 35.2024 27 9.1245 54 2.959

1 33.3269 28 8.7198 55 2.8442

2 31.5635 29 8.3357 56 2.7382

3 29.9058 30 7.9708 57 2.6368

4 28.3459 31 7.6241 58 2.5397

5 26.8778 32 7.2946 59 2.4468

6 25.4954 33 6.9814 60 2.3577

7 24.1932 34 6.6835 61 2.2725

8 22.5662 35 6.4002 62 2.1907

9 21.8094 36 6.1306 63 2.1124

10 20.7184 37 5.8736 64 2.0373

11 19.6891 38 5.6296 65 1.9653

12 18.7177 39 5.3969 66 1.8963

13 17.8005 40 5.1752 67 1.830

14 16.9341 41 4.9639 68 1.7665

15 16.1156 42 4.7625 69 1.7055

16 15.3418 43 4.5705 70 1.6469

32
COOLWEX Group USA

SPLIT TYPE, HEAT PUMP AIR CONDITIONERS

Technical & service manual 2005

CAS DC Inverter (50Hz) R410a DC INVERTER Wall Mounted

[Models]

CAS 7 I10

CAS 9 I10

CAS 12 I10
Contents

1. Features…………………………………………………………………… 2

2. Specification………………………………………………………..………3

3. Dimensions…………………………………………………………………4

4. Refrigeration cycle diagram………………………………………………6

5. Pressure table…………….……………………………………….………7

6. Capacity table………………………………………………………….….9

7. Operation Limits………………………………………………………….11

8. PCB diagram……………………………………………………………..12

9. Wiring diagram…………………………………………………..……….14

10. Electronic function………………………………………….……………16

11. Troubleshooting……………………………………………………….…23

12. Characteristic of temp. sensor…………………………………………29

1
1.Features
1.1 Powerful at cooling/heating.
1.2 Low voltage start-up function.
1.3 Anti-icing function at cooling mode.
1.4 Anti-cold air function at heating mode.
1.5 Auto-defrosting.
1.6 Outdoor electric current protection
1.7 Temperature protection of the outdoor compressor top.
1.8 Restart protection for the compressor.
1.9 Error self diagnosis function.
1.10 Protection against over-load or too-low current inputted through alternating current.

2
2.Specification
M odel CAS 7 I10 CAS 9 I10 CAS 12 I10
F a c to r y M o d e l C E - K F R 2 6 G W /B P 2 N 1 Y C E - K F R 2 6 G W /B P 2 N 1 Y C E - K F R 3 5 G W /B P 2 N 1 Y
P o w e r s u p p ly P h -V -H z 1 , 2 2 0 -2 4 0 V ~ , 5 0 H z 1 , 2 2 0 -2 4 0 V ~ , 5 0 H z 1 , 2 2 0 -2 4 0 V ~ , 5 0 H z
C a p a c ity B tu /h 7 0 0 0 (1 5 5 0 -9 6 6 0 ) 9 0 0 0 (2 0 5 0 -1 1 2 6 0 ) 1 2 0 0 0 (2 3 5 0 -1 4 5 0 0 )
In p u t W 6 1 5 (2 0 0 -1 1 5 0 ) 7 6 0 (2 5 0 -1 3 5 0 ) 1 0 7 0 (2 7 0 -1 7 5 0 )
C o o lin g
R a te d c u r r e n t A 2 .6 7 ( 1 .3 - 6 .5 ) 3 .3 ( 1 .5 - 7 .0 ) 4 .8 ( 1 .5 ~ 8 .5 )
EER B tu /w .h ,W /W 1 1 .5 , 3 .4 1 1 .5 , 3 .4 1 1 .3 , 3 .3
C a p a c ity B tu /h 9 0 0 0 (2 2 0 0 -1 2 5 0 0 ) 1 0 0 0 0 (2 4 0 0 -1 3 8 0 0 ) 1 4 0 0 0 (2 8 0 0 -2 0 5 0 0 )
In p u t W 7 1 0 (2 2 0 -1 4 0 0 ) 7 8 0 (2 4 0 -1 5 5 0 ) 1 1 2 0 (2 6 0 -2 0 5 0 )
H e a tin g
R a te d c u r r e n t A 3 .1 ( 1 .3 - 7 .3 ) 3 .4 ( 1 .4 - 7 .5 ) 5 .1 ( 1 .5 - 1 0 .0 )
COP W /W 3 .5 3 .7 3 .7
M o is tu r e R e m o v a l L /h 1 .0 1 .0 1 .2
M a x . in p u t c o n s u m p tio n W 2000 2100 2550
M a x. c u rre n t A 9 .5 1 0 .0 12
S ta r tin g c u r r e n t A 14 15 18
M odel 5CS090XC B 5CS090XCB 5C S102XFB
Type S c r o ll S c r o ll S c r o ll
B ra n d N a tio n a l N a tio n a l N a tio n a l
C a p a c ity B tu /h 10510 10510 11840
In p u t W 1000 1000 1150
C o m p re s s o r
R a te d c u r r e n t( R L A ) A 4 .4 4 .4 5 .2
L o c k e d r o to r A m p ( L R A ) A 40 40 50
T h e r m a l p r o te c to r C S -7 L N 1 1 5 C S -7 L N 1 1 5 C S -7 L N 1 1 5
C a p a c ito r uF No No No
R e fr ig e r a n t o il ml 360 360 360
M odel R PG 13H RPG 13H R PG 20D
B ra n d W e llin g W e llin g W e llin g
In d o o r fa n m o to r In p u t W 3 6 .5 3 6 .5 5 1 .5
C a p a c ito r uF 1 .2 1 .2 1 .5
S p e e d ( h i/m i/lo ) r /m in 1 3 0 0 /1 0 0 0 /8 5 0 1 3 0 0 /1 0 0 0 /8 5 0 1 3 0 0 /1 0 0 0 /9 0 0
a .N u m b e r o f r o w s 2 2 2
b .T u b e p itc h ( a ) x r o w p itc h ( b ) mm 2 1 x 1 3 .3 7 2 1 x 1 3 .3 7 2 1 x 1 3 .3 7
c .F in s p a c in g mm 1 .3 1 .3 1 .3
In d o o r c o il d .F in ty p e ( c o d e ) H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m
e .T u b e o u ts id e d ia .a n d ty p e mm φ 7 IN N E G R O O V E T U B E φ 7 IN N E G R O O V E T U B E φ 7 ,in n e r g r o o v e tu b e
f.C o il le n g th x h e ig h t x w id th mm 5 7 8 X 2 5 2 X 2 6 .7 4 5 7 8 X 2 5 2 X 2 6 .7 4 6 3 5 X 3 1 5 X 2 7 .3 4
g .N u m b e r o f c ir c u its 2 2 2
In d o o r a ir flo w ( H i/M i/L o ) m 3 /h 5 7 0 /4 8 0 /3 5 0 5 7 0 /4 8 0 /3 5 0 7 0 0 /5 2 0 /4 2 0
In d o o r n o is e le v e l ( H i/M i/L o ) d B (A ) 4 2 /3 5 /3 0 4 2 /3 5 /3 0 4 2 /3 5 /3 0
D im e n s io n ( W * H * D ) mm 750×250×205 750×250×205 815×280×215
In d o o r u n it P a c k in g (W *H *D ) mm 830×335×285 830×335×285 915×360×290
N e t/G r o s s w e ig h t Kg 8 .0 /1 0 .0 8 .0 /1 0 .0 1 0 .0 /1 2 .0
M odel Y D K 2 4 -6 F Y D K 2 4 -6 F Y D K 3 6 -6
B ra n d W e llin g W e llin g W e llin g
O u td o o r fa n m o to r In p u t W 56 56 68
C a p a c ito r uF 2 .5 2 .5 2 .5
Speed r /m in 800 800 900
a .N u m b e r o f r o w s 2 2 2
b .T u b e p itc h ( a ) x r o w p itc h ( b ) mm 2 5 .4 x 2 2 2 5 .4 x 2 2 2 5 .4 x 2 2
c .F in s p a c in g mm 1 .4 1 .4 1 .5
O u td o o r c o il d .F in ty p e ( c o d e ) H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m H y d r o p h ilic a lu m in iu m
e .T u b e o u ts id e d ia .a n d ty p e mm φ 9 .5 3 ,in n e r g r o o v e tu b e φ 9 .5 3 ,in n e r g r o o v e tu b e Ф 9 .5 3 ,in n e r g r o o v e tu b e
f.C o il le n g th x h e ig h t x w id th mm 6 8 0 x5 5 0 x4 4 6 8 0 x5 5 0 x4 4 6 8 0 x5 5 0 x4 4
g .N u m b e r o f c ir c u its 2 2 2
O u td o o r a ir flo w m 3 /h 1900 1900 1900
O u td o o r n o is e le v e l d B (A ) 52 55 55
D im e n s io n ( W * H * D ) mm 760X590X285 760X590X285 760X590X285
O u td o o r u n it P a c k in g ( W * H * D ) mm 890X655X360 890X655X360 890X655X360
N e t/G r o s s w e ig h t Kg 4 2 /4 5 4 2 /4 5 4 2 /4 5
R e fr ig e r a n t ty p e R 4 1 0 A g 1000 1000 1140
D e s ig n p r e s s u r e MPa 4 .2 4 .2 4 .2
L iq u id s id e / G a s s id e m m ( in c h ) Ф 6 .3 5 /Ф 9 .5 3 Ф 6 .3 5 /Ф 9 .5 3 Ф 6 .3 5 /Ф 1 2 .7
R e fr ig e r a n t p ip in g M a x . r e fr ig e r a n t p ip e le n g th m 10 10 10
M a x . d iffe r e n c e in le v e l m 5 5 5
C o n n e c tio n w ir in g No No No
P lu g ty p e 16A 16A 16A
T h e r m o s ta t ty p e E le c tr o lic c o n tr o l E le c tr o lic c o n tr o l E le c tr o lic c o n tr o l
O p e r a tio n te m p ℃ 17 30 17 30 17 30
A m b ie n t te m p ℃ -1 5 ? 45 -1 5 ? 45 -1 5 ? 43
A p p lic a tio n a r e a m2 1 4 -1 8 1 8 -2 4 2 0 -3 0
Q ty ’p e r 2 0 ’ /4 0 ’ /4 0 'H Q set 9 3 /2 0 9 /2 4 9 9 3 /2 0 9 /2 4 9 9 2 /1 9 5 /2 2 8
T O S H IB A R o ta r y T O S H IB A R o ta r y T O S H IB A R o ta r y
R e m a r k ( a lte r n a te c o m p r e s s o r )
D A 8 9 X 1 C -2 3 F Z D A 8 9 X 1 C -2 3 F Z D A 1 0 8 X 1 C -2 0 F Z

★1 The noise date is base on hemi-anechoic chamber, during actual operation, these values are normally somewhat different as a result of ambient

condition.

3
3.Dimensions
3.1 Indoor unit
CAS 7 I10, CAS 9 I10

3.2 Indoor unit


CAS 12 I10

4
3.4 Outdoor unit

CAS 7 I10, CAS 9 I10, CAS 12 I10

750
285

590
62
315

290

530 110

5
4.Refrigeration cycle diagram

6
5. Pressure table
Note:
*The pressure data is from 3 way valve, the pressure data are pressure above atmosphere.
*D: Dry bulb temp.
*W: Wet bulb temp.
5.1 CAS 9 I10
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor
Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions

21ºC D Pressure
8.7 8.7 8.9 9.0 10.0 10.6
15ºC W ( kg/cm2 )

24ºC D Pressure
9.0 8.9 8.9 9.0 10.5 11.0
17ºC W ( kg/cm2 )

27ºC D Pressure
9.0 9.0 9.0 9.6 11.0 11.5
19ºC W ( kg/cm2 )

32ºC D Pressure 9.2 9.2 9.1 10.1 12.0 12.5


23ºC W ( kg/cm2 )

Heating mode OUTDOOR CONDITIONS


12ºC D 7ºC D 0ºC D -4ºC D -7ºC D -15ºC D
Indoor Conditions Pressure
11ºC W 6ºC W -1ºC W -6ºC W -9ºC W -xºC W
Pressure
15ºC 32.0 34.0 33.5 31.0 28.0 27.0
( kg/cm2 )
Pressure
18ºC 34.5 34.0 35.0 32.5 29.0 27.5
( kg/cm2 )
Pressure
20ºC 36.5 35.5 36.0 33.5 30.0 28.5
( kg/cm2 )
Pressure
22ºC 37.5 37.0 36.5 35.0 31.5 29.0
( kg/cm2 )

7
5.2 CAS 12 I10
Cooling mode Outdoor temperature (Dry bulb temp)
Indoor
Pressure 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions

21ºC D Pressure
6.4 6.6 6.8 7.2 7.6 8.1
15ºC W ( kg/cm2 )

24ºC D Pressure
6.6 6.9 7.0 7.6 8.2 8.7
17ºC W ( kg/cm2 )

27ºC D Pressure
6.9 7.0 7.3 7.6 8.6 9.2
19ºC W ( kg/cm2 )

32ºC D Pressure 6.9 7.4 7.6 8.1 9.4 9.8


23ºC W ( kg/cm2 )

Heating mode OUTDOOR CONDITIONS


12ºC D 7ºC D 0ºC D -4ºC D -7ºC D -15ºC D
Indoor Conditions Pressure
11ºC W 6ºC W -1ºC W -6ºC W -9ºC W -xºC W
Pressure
15ºC 32.5 31.5 31.0 29.0 28.0 25.5
( kg/cm2 )
Pressure
18ºC 34.0 33.0 31.0 30.5 28.5 26.0
( kg/cm2 )
Pressure
20ºC 33.0 34.0 33.5 30.0 29.0 27.5
( kg/cm2 )
Pressure
22ºC 36.0 35..0 34.5 30.0 29.0 28.0
( kg/cm2 )

8
6. Capacity table

6.1 CAS 9 I10


COOLING OUTDOOR TEMPERATURE DRY
Indoor
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 2.87 3.00 2.60 2.34 1.98 1.70 1.53
21ºC D
Sensitive capacity kW 1.84 1.91 2.03 1.99 1.65 1.46 1.32
15ºC W
Input kW. 0.701 0.72 0.80 0.86 0.89 0.98 1.16
Total capacity kW 2.98 3.15 2.85 2.45 2.30 1.95 1.74
24ºC D
Sensitive capacity kW 1.84 2.01 2.23 2.11 1.93 1.72 1.50
17ºC W
Input kW. 0.72 0.73 0.82 0.90 0.92 1.01 1.17
Total capacity kW 3.13 3.20 2.98 2.58 2.60 2.34 2.03
27ºC D
Sensitive capacity kW 2.04 2.15 2.30 1.96 2.23 2.09 1.73
19ºC W
Input kW. 0.75 0.78 0.85 0.76 0.96 1.04 1.19
Total capacity kW 3.29 3.33 3.12 3.05 2.80 2.62 2.32
32ºC D
Sensitive capacity kW 2.17 2.15 2.43 2.56 2.38 2.33 2.05
23ºC W
Input kW. 0.78 0.80 0.86 1.00 1.01 1.08 1.23

HEATING OUTDOOR CONDITIONS


-15ºC D
Indoor 24ºC D 12ºC D 7ºC D 4ºC D 0ºC D -5ºC D -7ºC D
-16ºC
Conditions 18ºC W 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
W
Capacity kW 3.5 4.11 4.10 3.80 3.49 3.12 3.01 1.72
15ºC
Input kW. 0.958 1.53 1.57 1.56 1.51 1.39 1.37 1.30
Capacity kW 3.45 4.10 4.05 3.70 3.48 3.11 2.99 1.70
18ºC
Input kW. 0.96 1.55 1.58 1.60 1.52 1.40 1.38 1.32
Capacity kW 3.44 4.05 2.87 3.69 3.47 3.00 2.86 1.69
20ºC
Input kW. 0.965 1.60 0.79 1.63 1.54 1.42 1.40 1.35
Capacity kW 3.435 4.00 3.932 3.65 3.47 2.97 2.81 1.68
22ºC
Input kW. 0.98 1.65 1.64 1.67 1.58 1.45 1.43 1.38
Capacity kW 3.4 3.95 3.85 3.60 3.43 2.89 2.79 1.67
27ºC
Input kW. 0.99 1.69 1.69 1.70 1.61 1.50 1.48 1.40

9
6.2 CAS 12 I10
COOLING OUTDOOR TEMPERATURE DRY
Indoor
21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Conditions
Total capacity kW 3.187 3.48 3.30 3.01 2.81 2.38 2.16
21ºC D
Sensitive capacity kW 2.23 2.40 2.38 2.28 2.25 2.10 1.90
15ºC W
Input kW. 0.924 1.08 1.18 1.30 1.39 1.45 1.59
Total capacity kW 3.579 3.76 3.65 3.43 2.98 2.70 2.44
24ºC D
Sensitive capacity kW 2.505 2.61 2.66 2.61 2.41 2.35 2.20
17ºC W
Input kW. 0.957 1.10 1.19 1.33 1.41 1.49 1.61
Total capacity kW 3.879 4.09 3.90 3.50 3.19 2.99 2.79
27ºC D
Sensitive capacity kW 2.792 2.86 2.89 2.80 2.58 2.60 2.45
19ºC W
Input kW. 0.979 1.11 1.20 1.07 1.45 1.51 1.60
Total capacity kW 4.087 4.32 4.02 3.80 3.62 3.40 3.28
32ºC D
Sensitive capacity kW 3.168 3.80 3.01 3.07 3.11 2.96 2.89
23ºC W
Input kW. 0.989 1.12 1.25 1.40 1.48 1.55 1.68

HEATING OUTDOOR CONDITIONS


-15ºC D
Indoor 24ºC D 12ºC D 7ºC D 4ºC D 0ºC D -5ºC D -7ºC D
-16ºC
Conditions 18ºC W 11ºC W 6ºC W 3ºC W -1ºC W -6ºC W -8ºC W
W
Capacity kW 4.875 6.15 5.72 5.13 4.52 4.21 3.75 3.41
15ºC
Input kW. 1.568 2.07 2.20 2.09 2.01 1.99 1.80 1.76
Capacity kW 4.801 6.09 5.58 5.02 4.39 4.10 3.59 3.27
18ºC
Input kW. 1.6 2.18 2.39 2.20 2.16 2.09 1.83 1.81
Capacity kW 4.684 5.89 4.03 4.90 4.21 3.89 3.37 3.11
20ºC
Input kW. 1.658 2.21 1.11 2.35 2.27 2.15 1.99 1.92
Capacity kW 4.521 5.58 5.39 4.71 4.10 3.70 3.17 2.99
22ºC
Input kW. 1.729 2.28 2.45 2.41 2.40 2.25 2.11 2.00
Capacity kW 4.387 5.37 4.99 4.48 3.90 3.49 3.01 2.71
27ºC
Input kW. 1.804 2.39 2.61 2.55 2.51 2.38 2.27 2.13

10
7. Operation Limits

7.1 Cooling mode


Indoor temperature: 17℃~32℃
Outdoor temperature: 0℃~50℃
2.2 Heating mode
Indoor temperature: 17℃~27℃
Outdoor temperature: -15℃~34℃
2.3 Dry mode
Indoor temperature: 10℃~32℃
Outdoor temperature: 0℃~50℃

11
8 PCB diagram
8.1 Display board
1 2 3 4 5 6

+5
R7
221
D Q4 D
R8
9012
+5 102
104
IC1
1 14 C1
Dsa Vcc
2 13
Dsb Q7
3 12
Q0 Q6
LED1 LED2 LED3
4 11 DISP2
Q1 Q5
5 10
Q2 Q4
6 9
Q3 MR

R17 221
R15 221
R16 391

R9 221
7 8
GND CP

R11 391
R12 391
R13 391
R14 391
74HC164

CN1 8LED
C 7 C
6 CLK DEF R
5 DATA
4 +5 TIME Y
FROM INDOOR PCB DIGI +5
3 +5V AUTO G
2 REMOTE
1 GND E2 C3 C6 R6
47u/16V 221
104 102
Q1
9012

R5
102
+5
Q2
R1 102 9013 R10
151
R4 221 REC1
dig.1 g f a b

B DISP1 E4 B
C5
+5 d dp e c dig.2 10u/16V
R3 221 104

Q3
R2 102 9012

A A

Size FCSM No. DWG No. Rev


B

Scale Sheet
0 of 0

1 2 3 4 5 6

8.2 Indoor main PCB


1 2 3 4 5 6 7 8

CN1
1 CN10 IC4 CN3
R2 51/1W C2 FUSE1
L 1 16
1 STEP1 IN1 OUT1 1
2 L
333/250VAC E2 3.15A/250V 2
ZR1 2 15
470uF/25V 2 STEP2 IN2 OUT2 3
3 T2 T1 C5
14D681K 4
L1 DZ1 R4 R5 333/250VAC 3 14
TR1 D5 CN9 STEP3 IN3 OUT3 5
4 C25 12V 11K/2W 11K/2W
BT131 N
1.2(1.5)uF/450V 1 4 13
N STEP4 IN4 OUT4
5 IN4007 +12V
G

D D
2 5 12
FAN_IN +5V BUZZ IN5 OUT5
PTC1 B1
2K R1 R3 6 11 R8
t

INDOORFAN' 82RM INDOORFAN IN6 OUT6 INDOORFAN'


561 1 CN2 102
IC1 PC817 ISO+12V
7 10
TRANS_IN CHUCHEN IN7 OUT7
2
8 9
VSS VDD IC5 PC817 R9
IN4007*4 IC2 7812 +12V IC3 7805 +5V C7 IC/ULN2003 R7 Q1
D1 1 3 1 3 104 102 512 9014
Vin Vout Vin Vout
GND

GND

D2 E1 C3 E3 C4 E4 C6 CORTROL CIRCUIT +12V R6


A 104 104 104 202 ISOGND
D4
1000uF/25V
2

D3 IC8 ISO+12V
1 42 R10 X1
2200uF/25V 470uF/16V E7 C10 VSS0 X1
B 100uF/16V 105
2

2
1

223 2 41
CN5 D6 IN4007*4 IC12 7812 ISO+12V VDD0 X2
1 3 2.5M CN6 CN12
4 Vin Vout +5V 3 40
14.5VAC 350mA D7 INDOORFAN P25 RESET RST
GND

3 +5V
2 E5 C8 E6 C9 4 39 R11 10K
14.5VAC 200mA D9 BUZZ P26 XT1 IC9
1 104 104
5 38 R12 10K 2
TRANS_OUT D8 1000uF/25V STEP1 P00 XT2 3
2

RST C11
1
6 37 E8 104
2200uF/25V STEP2 P01 Vpp/IC
C ISOGND 7042 C
7 36 47uF/16V R13 103
STEP3 P02 P24 LED_C +5V

POWER CIRCUIT STEP4


8
P03 P23
35
CLK
9 34
CHUCHEN P04 P22 RXD +5V
10 33
VSS1 P21 TXD
11 32 R14 R15 R16
P05 VDD1
12 31 103 103 103
SELECT3 P50 P20 DIGI_C
IC6 PC817 +5V
4 13 30
R18 SELECT1 P51 P33 FAN_BACK CN7
C14 5.1K R23 +5V 14 29 LED_C 7
C16 3 512 C15 SELECT2 P52 P32 ZERO
D10 CLK 6
103 103 15 28 DATA 5
IN4007 471/250V SW_KEY P53 P31 DATA
IC10 PC851 R24 DIGI_C 4
681 RXD
16 27 +5V 3
+5V AVDD P30 REMOTE
REMOTE 2
R17 R22 17 26 R30 101 1
AVREF P11 SDA C18
2K/2W 123 3 102
18 25 2
Q2 9014 T1_room AN10 P10 SCL DISPLAY
1
R20 R21 CN4
19 24
R26202 T2_pipe AN11 AVSS
11K/2W 11K/2W TXD
DZ2 C13 R19 20 23
B AN12 AN15 B
24V 100K D11 CN10
E9 L1 E10 100uF/16V
CN9 21 22
473 100uF/35V N R25 AN13 AN14
1 2
2 IN4007 512 UPD789166
+5V
C19 104

+5V R28 R29 IC11 24C04


R40 512 103 103 8 1
CN8 VCC A0
ZERO 7 2
WC A1
1 Q3 6 3
SCL SCL A2
R37 123 5 4
S COMMUNICATE CIRCUIT A 9014
C23
SDA SDA GND

D13 1N4148 R38R39 223


D14 1N4148 123 123 C22
B 223

+5V CN11 +5V CN14 +5V


+5V +5V +5V +5V
2 2
D15
R31 R32 R33 1 1
IN4148 CN13 R35
103 T2_pipe T1_room
103 103 103 R34512 3 R27 202 R42 202
SELECT1 SELECT2 SELECT3 FAN_BACK 2 SW_KEY T2_pipe T1_room
C20 1 C24
E16 C17 E11
103 FAN_BACK SW1 C21 R36 R41
J2 J3 J1 104 47uF/16V 223 47uF/16V
A 8061 8061 223 A
+12V

1 2 3 4 5 6 7 8

12
8.3 Outdoor main PCB
1 2 3 4 5 6

+5V
R49 +5V D3
10K
REST
C35 C41 C10
224 101 10uf/16v D2
SW1 +5V
3
2
1

D D
RESET
GND
VDD

D1
D8 AC-IN VOLTAGE SAMPLE
LED +5V W-
1
W+
4007 D7 2
R3 5.1K V-
CURRENT SAMPLE 3
IC1 R6 V+
S1 CT2 +5V 4
7042 R1 U-
390 C5 0057W 4007 5
U+
C6 6
POWER RLY

+12V +12V +12V 47UF/16v


4-WAY RLY

Q1 R2 R4 C7 7
FAN RLY

9013 16K 1k 16K 223 47uf 8


+12V
9
+5V D9 D10 D11 CURRENT TEST ALRAM
10
ADMC328 U1
R9 R13 C1 R7 CN5
R12
2K Q2 Q3 Q4 2K 102 5.1K
12K
9013 9013 9013 POS0 1 28 POS1
PIO6/CLKOUT PIO7
C9
R11 R5 TXD 2 27 POS2
R10 2K PIO5/RFS1 PIO8/AUX0
220uf/25v 1K IC3 74HC04
2K RXD 3 26 1 14
PIO4 AL 1A VCC +5V 6*100
3 2 U-
2A 1Y R55
DISPLAY 4 25 5 4 U+
C PIO3 AH 3A 2Y R54 C
9 6 V-
4A 3Y R53
4-WAY 5 24 11 8 V+
PIO2 BL 5A 4Y R52
13 10 W+
6A 5Y R51
OUT FAN 6 23 7 12 W-
PIO1 BH GND 6Y R50
C31 7 22
PIO0 CL
8 21 +15V
Y2 CLKIN CH
20PF
10M +5V
ALRAM C30 9 20 REST
XTAL RSET R47 R58
+5V
20PF 10 19 2K 560
R8 VDD GND
R30 C29 U8
10k C20 C21 C28 11 18 POS2
103 PWMTRIP ICONST 330
103 101 C8 C38
104 101 R44 5.1K 12 17 T_OUTSIDE 472
ISENSE VAUX2
+15V
CURRENT SAMPLE 13 16 T_PIPE
V2 XAUX1 +5V
VOLTAGE SAMPLE 14 15 T_YJ R46 R57
V1 XAUX0 2K 560
+15V
U7
J4 +5V POS1
B 2 D4 B
C37
1 472
CN11 C27 U4
W R42 220K R43 1 14
+15V
3 R41 OUT2 OUT3
V 2.2uF +15V 2 13 +5V
J3 +5V
2
U R40 220K R38 C26 R39 10K 3
OUT1 OUT4
12
1 V+ GND R45 R56
47K 2.2uF 100K C34 4 11
2 220K 2K 560
472 +15V 5
IN1- IN4+
10
1 IN1+ IN4- U2
6 9
IN2+ IN3+ POS0
7 8
+5V IN2- IN3-
CN3 C36
J2 +12V R29 C25 D5 LM139
T_OUTSIDE R37 472
4
2 2k
3 2.2uf 10K +15V
1 C3 R35 C24 R36
2
1 47K 2.2uF 100K C33
+15V R18 47uF 472
T_PIPE D6
2k
C2
J1 C23
CN4 47uF R34
2 R15 T_YJ
2 R16 2.2uF 10K
1 5.1k R32 C22 R33
1 R14
A 4.3k R17 47K 2.2uF 100K C32 C4 A
C17 C18
5.1k C19 472 103
224 104 4.3k 104 Title

Size Number Revision


B
Date: 2-Feb-2004 Sheet of
File: G:\ 我的文档项\ 目R312\CE-KFR26(35)GW-BP2N1Y-OUTDOOR.DDB
Drawn By:
1 2 3 4 5 6

13
9 Wiring diagram
9.1 CAS 7 I10, CAS 9 I10 indoor unit

INDOOR FAN MOTO R


LOUVER MOTOR

B
L
U
E
3 3 5
Y /G
B
R
O
W
N

CN3
CN9 CN1 CN13 ROOM TEMP. SENSOR
POWER SUPPLY

W
H
I
T
E
B
L
A
C
K

CN14 2
CN11

R
E
D
CN10
CN2 INDOOR PCB 2
RED CN4 P IPE T EMP. SENS OR
Y
E
L
L
O
W

CN8 CN6 7

JX1 CN5 CN12 CN7


L N S
Y/G DISPLAY BOARD
2 2
4 2
AUTO RESTART
N S MICRO SWITCH (CHOICE)
L
PLASMA
OUTDOOR UNIT TRANSFORMER

9.2 CAS 7 I10, CAS 9 I10 outdoor unit

HE AT EXC HANGER
SENSO R
OLP TEMP. SENSOR 2
2
Y/G 2
COMPRES SOR Y/G
AM BI ENT S EN S OR
RED
BLACK
RED
BLUE

BLUE
R ED 4- WAY OUTDOOR
YELLO W

3 FILTER
FAN
BLACK

4
RED
BLUE

RED

W V U N P
BL ACK

CN 16
BL UE

10
CN1 CN1
CN8
CN2 CN21 P-1
BLUE

CN19 CN20 Y/G


CN3
MOD ULE
WHITE

2
O
UM
T
DA
O NB
O
R

CN13 CN12
CN2 3
I

CN4 3 TE RM I NA L
P
C

Y ELLOW

RLY1 4
WHITE
~ + +
B LACK

RED CN5
~
S
N

-
R ECTIFI ER
~ -
RECTIFIER
~ CT2
CN17 CN18
RED
L

CN6 CN 11 CN1 4 CN15

RE ACTOR2 CAPACI TOR


RED RED RED

REAC TOR1 LN S
ORANG E OR ANGE

BLUE INDOOR UNIT

14
9.3 CAS 12 I10 indoor unit

INDOOR FAN MOTOR LOUVER MOTOR

B
L
U
E
3
Y/G 3 5
B
R
O
W
N

CN9 CN1 CN13 CN3 R OOM TEMP. SENSOR


POWER S UPPLY

W
H
I
T
E
CN14
B
L
A
C
K

2
CN11

R
E
D
CN10 INDOOR PCB
CN2 CN 4 2
RED P IPE TEMP. SENSOR
Y
E
L
L
O
W

CN8 CN6 7

JX1 CN5
CN12 CN 7
L N S
Y/ G DISPLAY BOARD
4 2 2 2

AUTO RESTART
(CHOICE)
L N S MICRO SWITCH
PLASMA
OUTDOOR UNIT TRANSFORMER

9.4 CAS 12 I10 outdoor unit

HE AT EXC HANGER
SENSO R
OLP TEMP. SENSOR 2
2
Y/G 2
COMPRES SOR Y/G
AM BI ENT S EN S OR
RED
BLACK
RED
BLUE

BLUE
R ED 4- WAY OUTDOOR
YELLO W

3 FILTER
FAN
BLACK

4
RED
BLUE

RED

W V U N P
BL ACK

CN 16
BL UE

10
CN1 CN1
CN8
CN2 CN21 P-1
BLUE

CN19 CN20 Y/G


CN3
MOD ULE
WHITE

2
O
U
TM
D
O NB
O
R

CN13 CN12
CN2 3
AP
IC

CN4 3 TE RM I NA L
Y ELLOW

RLY1 4
WHITE
~ + +
B LACK

RED CN5
~
S
N

-
R ECTIFI ER
~ -
RECTIFIER
~ CT2
CN17 CN18
RED
L

CN6 CN 11 CN1 4 CN15

RE ACTOR2 CAPACI TOR


RED RED RED

REAC TOR1 LN S
ORANG E OR ANGE

BLUE INDOOR UNIT

Power supply Input Rated Amp


Model Power Cord Size
(Switch/Fuse )

9000Btu/h 25A 1 .5mm


2

2 20 -2 40 V~ 5 0Hz
12 000Btu /h 25A 1.5 mm2

15
10 Electronic function
10.1 Electric Control working environment.
10.1.1 Input voltage: 175~253V.
10.1.2 Input power frequency:50Hz.
10.1.3 Indoor fan normal working amp is less than 1A.
10.1.4 Outdoor fan. Normal working amp is less than 1.5A.
10.1.5 Four-way valve normal working amp is less than 1A.
10.1.6 Swing motor: DC12V.

10.2 Display board

1 2 3 4 5 6
10.2.1 AUTO indicator
This indicator illuminates when the air conditioner is in AUTO operation.
10.2.2 TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
10.2.3 PRE.-DEF. Indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm air
control feature is activated in heating mode.
10.2.4 TEMPERATURE indicator
Usually it displays the temperature settings. When change the setting temperature, this indicator begins
to flash, and stops 20 seconds later.
It displays the room temperature when the air conditioner is in FAN only operation.
When the unit stops operation, it returns to original factory settings.
Displays the malfunction code or protection code.
10.2.5 OPERATION indicator
This indicator flashes after power is on and illuminates when the unit is in operation.
10.2.6 FREQUENCY indicator
This indicator appears only when the compressor is in operation and indicates the current operating
frequency.

16
10.3 Protection
10.3.1. 3 minutes delay at restart for compressor.
10.3.2. Temperature protection of compressor top, compressor stops when the temp. of top of compressor is
more than 115℃, compressor runs when the temp. of top of compressor is less than 100℃.
10.3.3. Voltage protection, unit stop when the voltage is more than 260V and less than 175V.
10.3.4. Inverter module Protection , Inverter module Protection itself has a protection function against current,
voltage and temperature.
10.3.5. Sensor protection at open circuit and breaking disconnection
10.3.6. Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High Fan+300RPM)or
too low(lower than 400RPM), the unit stops and LED displays failure information and can’t return to
normal operation automatically.
10.3.7. Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops and LED
displays failure information and can’t return to normal operation automatically.

10.4 Fan-only mode


Fan speed is high/mid/low/ Auto
10.5. Cooling mode
10.5.1 The 4-way valve is closed at cooling mode.
10.5.2 The action of the compressor and the outdoor fan:
Condition Compressor Outdoor fan
T=Indoor Temp.
Ts=Setting Temp.
Room temp. up T> Ts+1 On On
T<Ts+1 Off Off
Room temp. down T> Ts On On
T<Ts Off Off
10.5.3 Auto fan at cooling mode:
Condition Indoor fan speed
T=Indoor Temp.-Setting Temp.
Room temp. up T<1.5℃ Low
1.5℃<T<4℃ Mid.
T>4℃ High
Room temp. down T> 3℃ High
1℃<T<3℃ Mid.
T<1℃ Low

10.5.4 Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )


Evaporator Temp. Compressor

0℃<T< 4℃ Decrease frequency of compressor


T< 0℃ Off

17
10.5.5 Current protection
Model Current Compressor

Current up CAS 12 I10 I>12 A Off

10.5A<I<12A Decrease frequency of compressor


I< 10.5A On

Current down CAS 9 I10 I>11.5 A Off

8.5A<I<11.5A Decrease frequency of compressor


I< 8.5A On

11.5.6 Rated capacity test


Set mode to cooling mode
Set temp. to 17°C
Set fan speed to high speed
Push turbo button 5 times in 10 seconds.
Using special remoter controller
After 5 hours, cancel rated capacity test
Turbo function
Increasing frequency of compressor
After operating 30 minutes, return automatically to the mode and temp. previously selected.

10.6. Dehumidifying mode


10.6.1. The 4-way valve is off
10.6.2. the indoor fan is fixed in breeze speed
10.6.3. Compressor run in low frequency
10.6.4. Low room temperature protection:
When room temperature decreases to below 10℃, compressor and outdoor fan will stop(indoor fan
is Breeze). Dehumidifying operation will be resumed when room temperature restores to over 12℃.
10.6.5. At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as that of
cooling mode.

10.7. Heating mode


10.7.1. Generally, the 4-way valve is open at heating mode, but it is closed at defrosting. 4-way valve must
delay 2 minutes compared with compressor if the compressor changed into non-heating mode or
turned off. 4-way valve doesn't delay in dehumidifying mode.
10.7.2. Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode, except
for the defrosting mode or the end of defrost.
10.7.3. Action of compressor and outdoor fan motor at heating mode: compressor must run for 7 minutes
after starting and then judge temperature. Meanwhile other protections are still valid.
Condition Compressor Outdoor fan

Room temp. up T> Ts+3 Off Off

T<Ts+3 On On

Room temp. down T< Ts+2 On On

T>Ts+2 Off Off

10.7.4. Indoor Fan actions at heating mode


Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold wind
18
function prevails.
Anti-cold wind control function at heating mode
Condition Indoor fan speed

T= Indoor exchanger temp.

Indoor exchanger temp. up T<34℃ Off

34℃<T<37℃ Breeze

37℃<T<44℃ Low speed

T>44℃ Setting fan speed

Indoor exchanger temp. down T> 38℃ Setting fan speed

33℃<T<38℃ Low sped

18℃<T<33℃ Breeze

T<18℃ Off

10.7.5. Auto wind at heating mode


Condition Indoor fan speed

T=Indoor Temp.-Setting Temp.

Room temp. up T<1.5℃ High

1.5℃<T<2.5℃ Med.

T>2.5℃ Low

Room temp. down T<1.0℃ High

1.0℃<T<2.0℃ Med.

T>2.0℃ Low

10.7.6 Indoor evaporator high-temperature protection at heating mode


Condition Compressor

T= Indoor exchanger temp.

T<48℃ On

53℃<T<63℃ Decrease frequency of compressor


T>63℃ Off

10.7.7 The current protection


Model Current Compressor

Current up CAS 12 I10 I>14.0 A Off

12.0.A<I<14.0A Decrease frequency of compressor


I< 12.0A On

CAS 9 I10 I>12.0 A Off

10.0A<I<12.0A Decrease frequency of compressor


I< 8.5A On

Current down CAS 12 I10 I>14.0 A Off

10.5A<I<14.0A Decrease frequency of compressor

I< 10.5A On

CAS 9 I10 I>12.0 A Off

8.5A<I<12.0A Decrease frequency of compressor

I< 8.5A On

19
10.8. Defrosting operation (Available for heating only).
10.8.1 Defrosting condition:
10.8.1.1 When outdoor temp. is more than 0℃,
Defrosting starts when meeting one of the following conditions,
a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
b. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
80 minutes, and the temperature remains consecutively -4°c for more than 3 minutes
10.8.1.2 When outdoor temp. is less than 0℃,
Defrosting starts when meeting one of the following conditions,
a. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
b. The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
40 minutes, and the temperature remains consecutively -6°c for more than 3 minutes,
c. The temperature of indoor unit pipe decreases 5°c than before

10.8.1.3 The temperature of outdoor heat exchanger remains consecutively lower than 3°c for more than
120 minutes, and the temperature remains consecutively -2°c for more than 3 minutes

10.8.2 Ending condition of defrosting


If one of following conditions is satisfied, end the defrost and turn into heating mode:
a. The defrost time has reached to 10 minutes.
b. When the temperature of outdoor heat exchanger rises up to 8°C and this continues for more
than 80 seconds.
c. When the temperature of outdoor heat exchanger rises up to 12°C

10.8.3 Defrosting Actions:


max. 10 minutes
60s
ON 10s 30s
Com. OFF
ON ON
4 way valve OFF
ON ON
Outdoor fan OFF
ON ON
Indoor fan OFF
breeze

20
10.8.4 Rated capacity test
Set mode to cooling mode
Set temp. to 30 °C
Set fan speed to high speed
Push turbo button 5 times in 10 seconds.
Using special remoter controller
After 5 hours, cancel rated capacity test

10.9 Outdoor low temperature protection (optional)


Factory standard unit has not this function.
Unit stops when outdoor temp. is low than -15°C and lasting time more than 60 minutes, and unit runs
again when outdoor temp. more than -12°C.

10.10. Automatic operation mode


The air conditioner automatically selects one of the following operation modes: cooling, heating or fan
only according to the temp. difference between room temp. (TA) and set temp. (TS).
TA—TS Operation mode

TA—TS>2℃ Cooling

-1℃≤TA-TS≤+2℃ Fan-only

TA-TS<-1℃ Heating (air-only for cooling only type)

10.11. Manual switch


10.11.1 Mode changes when push this button .
Cooing modeÆ Auto modeÆUnit offÆ Cooing mode

10.11.2. At Cooing mode, after 30 minutes cooling operation whose fan speed is set as low, the A/C operates
with a setting temp. of 24℃.
10.11.3. At auto mode, the A/C operates with a set temp. of 24℃
10.12. Timer Function
10.12.1. The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes.
10.12.2. Timer on: first turn off the A/C, the A/C will be automatically on at the set time.
10.12.3. Timer off: first turn on the A/C, the A/C will be automatically off at the set time
10.12.4. Timer on/off function( on time is earlier than off time): first turn off the A/C, it will be automatically on
at set time, and later be off at the set time, then unit turns on at set time.
10.12.5. Timer off/on function( off time is earlier than on time): first turn on the A/C, it will be automatically off
at set time, and later be on at the set time, then unit turns off at set time.

10.13. Sleep mode


10.13.1 It is available at cooling, heating or auto mode.
10.13.2 Cooling:
The set temperature rise 1℃ per hour. Two hours later, the set temperature will maintain as a
constant and the fan speed is kept at low speed.
10.13.3 Heating:
The set temperature decrease 1℃ per hour. Two hours later, the set temperature will maintain as a
21
constant and the air circulation is kept at low speed (Cold air proof function takes precedence over
all).
10.13.4 Auto:
The Sleep Mode running function operates in accordance with selected running mode
by auto mode.
10.13.5 After 7 hours, unit cancels this modes automatically.
10.14 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings
before the power failure when power returns.
8.15 Plasma
Plasma turns on when the indoor fan runs.
Plasma turns off automatically when front panel is opened.

22
11.Troubleshooting
11.1 Indoor Unit Error Display
Display LED STATUS

E0 EEPROM error

E1 Indoor / outdoor units communication protection

E2 Zero-crossing examination error

E3 Fan speed beyond control

E4

E5 Open or short circuit of outdoor temperature sensor

E6 Room temperature or evaporator temperature sensor open or short circuit of

P0 Module protection

P1 Over load or too low voltage protection

P2 Compressor top protection against temperature

P3 Outdoor low temp. protection

P4 Inverter compressor error


Note: E4: Reserved function
11.1.1
Display LED STATUS

E0 EEPROM error

Temporarily turn off the power supply and turn it on again in about 1 minutes

Does the trouble occur again?

Yes

Check indoor model responding to right outdoor model

Replace the indoor PCB

23
11.1.2
Display LED STATUS

E1 Indoor / outdoor units communication protection

Is the LED in outdoor main PCB light?

Yes

No
1. check the signal wire between, is it
connected good.
2. replace the PCB of indoor unit ,is the
unit ok?
3. replace the PCB of power supply
board ,is the unit ok?
4

Is the +5 voltage in outdoor main board?


Outdoor main PCB: CN5 between No7(Blue) and
No8(Yellow)
Main chip(ADMCF328): between No10 and No19 No

Yes

Check the PC817,PC851 (indoor PCB and Outdoor main PCB)


Inverter module defective.
Rectifier defective

Is PC817 or PC851 normal?

Yes

If PC817 or PC851 are defective, change indoor PCB or outdoor power PCB .

24
11.1.3
Display LED STATUS

E2 Zero-crossing examination error

Is power supply right?

Yes

Is connector connection good?

Yes

Indoor PCB is defective

11.1.4
Display LED STATUS

E3 Fan speed beyond control

Is connector connection good?


No

Yes

Is voltage being applied to the fan motor? No

(rang 90v-160v between mid pin and N on CN2 Repair the connector

Yes

Indoor PCB is defective


Indoor fan motor is defective

11.1.5
Display LED STATUS

E5 Open or short circuit of outdoor temperature sensor

Is connection to connector good?


yes No

Replace the sensor Repair connector


25
11.1.6
Display LED STATUS

E6 Room temperature or evaporator temperature sensor open or short circuit of

Is connection to connector good?


yes No

Replace the sensor Repair connector

11.1.7
Display LED STATUS

P0 Module protection

Is connection to connector good?


yes No

Is the wires to compressor right


Repair connector

Yes
Check the outdoor inverter module.

Is it breakdown between P-N,P-U,P-V;N-W,N-U,N-V


At inverter module

No Yes

Check compressor
Inverter module is defective

26
11.1.8
Display LED STATUS

P1 Over load or too low voltage protection

Is the power supply right?

Yes

Check the outdoor power board

Replace the outdoor power board

11.1.9
Display LED STATUS

P2 Compressor top protection against temperature

Off: 120c; On: 105c

Does compressor operate?


No
No
Yes
Is protector normal?
Is refrigerant circulation volume normal?

No Replace protector
Yes
Gas charging

Check the outdoor main PCB.

Is abnormality the same after gas charging

No

Check refrigerant system (such as clogging of capillary, etc)

27
11.1.10
Display LED STATUS

P3 Outdoor low temp. protection


This is optional, factory standard unit has not this function.
Unit stops when outdoor temp. is low than -15°C and lasting time more than 60 minutes, and unit runs
again when outdoor temp. more than -12°C.

Is the outdoor temp. low than -15°C?

No

Is the outdoor temp sensor right according to the table in clause 12

Yes

Replace the outdoor main board

11.1.11
Display LED STATUS

P4 Inverter compressor error

Are the U,V,W connected to compressor and inverter module right?

Yes

Are the connectors CN6 and CN 11 right?

Yes

Is there +15 voltage between CN6

No
Yes

Replace inverter module


Replace outdoor main PCB

If the problem comes to again, check wingding resistance of inverter compressor, is it 0.64 ohm?

No

Replace inverter compressor

28
12. Characteristic of temp. sensor
Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ Temp.℃ Resistance KΩ

-10 62.2756 17 14.6181 44 4.3874

-9 58.7079 18 13.918 45 4.2126

-8 56.3694 19 13.2631 46 4.0459

-7 52.2438 20 12.6431 47 3.8867

-6 49.3161 21 12.0561 48 3.7348

-5 46.5725 22 11.5 49 3.5896

-4 44 23 10.9731 50 3.451

-3 41.5878 24 10.4736 51 3.3185

-2 39.8239 25 10 52 3.1918

-1 37.1988 26 9.5507 53 3.0707

0 35.2024 27 9.1245 54 2.959

1 33.3269 28 8.7198 55 2.8442

2 31.5635 29 8.3357 56 2.7382

3 29.9058 30 7.9708 57 2.6368

4 28.3459 31 7.6241 58 2.5397

5 26.8778 32 7.2946 59 2.4468

6 25.4954 33 6.9814 60 2.3577

7 24.1932 34 6.6835 61 2.2725

8 22.5662 35 6.4002 62 2.1907

9 21.8094 36 6.1306 63 2.1124

10 20.7184 37 5.8736 64 2.0373

11 19.6891 38 5.6296 65 1.9653

12 18.7177 39 5.3969 66 1.8963

13 17.8005 40 5.1752 67 1.830

14 16.9341 41 4.9639 68 1.7665

15 16.1156 42 4.7625 69 1.7055

16 15.3418 43 4.5705 70 1.6469

29
COOLWEX Group USA

Technical & service manual 2005

Mobile Series

[Models]

Electronic Control

CMP 9 R7 (C)*

CMP 10 R7 (C)*

CMP 12 R7 (C)*

CMP 14 R7 (C)*

Remote Control

CMP 9 R7 (C)

CMP 10 R7 (C)

CMP 12 R7 (C)

CMP 14 R7 (C)
Contents

1. Features 2

2. Specification 3

3. Wiring diagram 6

4. Trouble shooting 8

5. Electronic function 11

1
1.Features
There is one exhaust pipe, which makes the A/C easier to use.
With water pump
The products have multiple uses: dehumidifying and cloth drying.
There is no need for special installation; they can be moved around for simple and
convenient use.
The heating system uses PTC electrical heater and will not be affected by ambient
temperature, which saves energy.
They are suitable for zone cooling and heating.
2.Specification

Model CMP 9 R7* CMP 9 R7 C* C CMP 9 R7 CMP 9 R7 C

Power supply Ph-V-Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz

Capacity Btu/h 9000 9000 9000 9000

Input W 1050 1050 1050 1050


Cooling
Rated current A 4.7 4.7 4.7 4.7

EER Btu/w.h 8.6 8.6 8.6 8.6

Capacity W 1600 1600


Heating Input W 1600 1600

Rated current A 7.0 7.0

Moisture Removal L/h 2.3 2.3 2.3 2.3

Max. input consumption W 1250 1250 2200 2200

Starting current A 23.7 23.7 23.7 23.7

Plug type CE-502 CE-502 CE-502 CE-502

Thermostat type Electronic control Electronic control Electronic control Electronic control

Model PG150X1C-4DZ2 PG150X1C-4DZ2 PG150X1C-4DZ2 PG150X1C-4DZ2

Type Rotary Rotary Rotary Rotary

Brand GD Toshiba GD Toshiba GD Toshiba GD Toshiba

Capacity Btu/h 8870 8870 8870 8870

Input W 860 860 860 860


Compressor
Rated current(RLA) A 3.8 3.8 3.8 3.8

Locked rotor Amp(LRA) A 22 22 22 22

Thermal protector UP3QE0591-T61 UP3QE0591-T61 UP3QE0591-T61 UP3QE0591-T61

Capacitor uF 25uF/ 370-450V 25uF/ 370-450V 25uF/ 370-450V 25uF/ 370-450V

Refrigerant oil ml 400 400 400 400

Refrigerant type g R407C/500 R407C/500 R407C/500 R407C/500

Design pressure MPa 2.6 2.6 2.6 2.6

Model YSK80-4M YSK80-4M YSK80-4M YSK80-4M

Input W 157/131/112 157/131/112 157/131/112 157/131/112


Fan motor
Capacitor uF 6uF/ 450V 6uF/ 450V 6uF/ 450V 6uF/ 450V

Speed(hi/mi/lo) r/min 1110/990/880 1110/990/880 1110/990/880 1110/990/880

Indoor air flow (Hi/Mi/Lo) m3/h 280/230/180 280/230/180 280/230/180 280/230/180

Noise level (Hi/Mi/Lo) dB(A) 54 54 54 54

Number of rows 2 2 2 2

Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator
Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Number of circuits 2 2 2 2

Number of rows 2 2 2 2

Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 517x294x13.37 517x294x13.37 517x294x13.37 517x294x13.37

Number of circuits 2 2 2 2

Dimension (W*H*D) mm 480×400×840 480×400×840 480×400×840 480×400×840

Packing (W*H*D) mm 460×887x667 460×887x667 460×887x667 460×887x667

Net/Gross weight Kg 34/44 33/43 34/44 33/43

Operation temp ℃ 17-30 17-30 17-30 17-30

Ambient temp ℃ 10-35 10-35 35 35

Application area m2 14-20 14-20 14-20 14-20

1
Model CMP 10 R7* CMP 10 R7 C* CMP 10 R7 CMP 10 R7 C

Power supply Ph-V-Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz

Capacity Btu/h 10000 10000 10000 10000

Input W 1100 1100 1100 1100


Cooling
Rated current A 4.9 4.9 4.9 4.9

EER Btu/w.h 9.1 9.1 9.1 9.1

Capacity W 1600 1600


Heating Input W 1600 1600

Rated current A 7.0 7.0

Moisture Removal L/h 2.3 2.3 2.3 2.3

Max. input consumption W 1250 1250 2200 2200

Starting current A 23.7 23.7 23.7 23.7

Plug type CE-502 CE-502 CE-502 CE-502

Thermostat type Electronic control Electronic control Electronic control Electronic control

Model PG150X1C-4DZ2 PG150X1C-4DZ2 PG150X1C-4DZ2 PG150X1C-4DZ2

Type Rotary Rotary Rotary Rotary

Brand GD Toshiba GD Toshiba GD Toshiba GD Toshiba

Capacity Btu/h 8870 8870 8870 8870

Input W 860 860 860 860


Compressor
Rated current(RLA) A 3.8 3.8 3.8 3.8

Locked rotor Amp(LRA) A 22 22 22 22

Thermal protector UP3QE0591-T61 UP3QE0591-T61 UP3QE0591-T61 UP3QE0591-T61

Capacitor uF 25uF/ 370-450V 25uF/ 370-450V 25uF/ 370-450V 25uF/ 370-450V

Refrigerant oil ml 400 400 400 400

Refrigerant type g R407C/500 R407C/500 R407C/500 R407C/500

Design pressure MPa 2.6 2.6 2.6 2.6

Model YSK80-4M YSK80-4M YSK80-4M YSK80-4M

Input W 157/131/112 157/131/112 157/131/112 157/131/112


Fan motor
Capacitor uF 6uF/ 450V 6uF/ 450V 6uF/ 450V 6uF/ 450V

Speed(hi/mi/lo) r/min 1110/990/880 1110/990/880 1110/990/880 1110/990/880

Indoor air flow (Hi/Mi/Lo) m3/h 280/230/180 280/230/180 280/230/180 280/230/180

Noise level (Hi/Mi/Lo) dB(A) 54 54 54 54

Number of rows 2 2 2 2

Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 335x294x26.74 335x294x26.74 335x294x26.74 335x294x26.74

Number of circuits 2 2 2 2

Number of rows 2 2 2 2

Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 517x294x13.37 517x294x13.37 517x294x13.37 517x294x13.37

Number of circuits 2 2 2 2

Dimension (W*H*D) mm 480×400×840 480×400×840 480×400×840 480×400×840

Packing (W*H*D) mm 460×887x667 460×887x667 460×887x667 460×887x667

Net/Gross weight Kg 34/44 33/43 34/44 33/43

Operation temp ℃ 17-30 17-30 17-30 17-30

Ambient temp ℃ 10-35 10-35 35 35

Application area m2 14-20 14-20 14-20 14-20

2
Model CMP 12 R7* CMP 12 R7 C* CMP 12 R7 CMP 12 R7 C

Power supply Ph-V-Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz

Capacity Btu/h 12000 12000 12000 12000

Input W 1330 1330 1330 1330


Cooling
Rated current A 6 6 6 6

EER Btu/w.h 9 9 9 9

Capacity w 1800 1800


Heating Input W 1800 1800

Rated current A 7.8 7.8

Moisture Removal L/h 2.7 2.7 2.7 2.7

Max. input consumption W 1730 1730 1730 1730

Starting current A 23.7 23.7 23.7 23.7

Plug type CE-502 CE-502 CE-502 CE-502

Thermostat type Electronic control Electronic control Electronic control Electronic control

Model PG180X1C-4DZ3 PG180X1C-4DZ3 PG180X1C-4DZ3 PG180X1C-4DZ3

Type Rotary Rotary Rotary Rotary

Brand GD Toshiba GD Toshiba GD Toshiba GD Toshiba

Capacity Btu/h 11000 11000 11000 11000

Input W 1020 1020 1020 1020


Compressor
Rated current(RLA) A 4.5 4.5 4.5 4.5

Locked rotor Amp(LRA) A 25.5 25.5 25.5 25.5

Thermal protector UP3QE0591-T61 UP3QE0591-T61 UP3QE0591-T61 UP3QE0591-T61

Capacitor uF 30uF/ 370-450V 30uF/ 370-450V 30uF/ 370-450V 30uF/ 370-450V

Refrigerant oil ml 400 400 400 400

Refrigerant type g R407C/560 R407C/560 R407C/560 R407C/560

Design pressure MPa 2.6 2.6 2.6 2.6

Model YSK80-4M YSK80-4M YSK80-4M YSK80-4M

Input W 185/157/131 185/157/131 185/157/131 185/157/131


Fan motor
Capacitor uF 6uF/ 450V 6uF/ 450V 6uF/ 450V 6uF/ 450V

Speed(hi/mi/lo) r/min 1230/1110/990 1230/1110/990 1230/1110/990 1230/1110/990

Indoor air flow (Hi/Mi/Lo) m3/h 280/230/180 280/230/180 280/230/180 280/230/180

Noise level (Hi/Mi/Lo) dB(A) 56 56 56 56

Number of rows 2 2 2 2

Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 382x294x13.37 382x294x13.37 382x294x13.37 382x294x13.37

Number of circuits 2 2 2 2

Number of rows 2 2 2 2

.Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 664x294x13.37 664x294x13.37 664x294x13.37 664x294x13.37

Number of circuits 2 2 2 2

Dimension (W*H*D) mm 480×400×840 480×400×840 480×400×840 480×400×840

Packing (W*H*D) mm 460×887x667 460×887x667 460×887x667 460×887x667

Net/Gross weight Kg 35/45 34/44 35/45 34/44

Operation temp ℃ 17-30 17-30 17-30 17-30

Ambient temp ℃ 10-35 10-35 35 35

Application area m2 14-20 14-20 14-20 14-20

3
Model CMP 14 R7* CMP 14 R7 C* CMP 14 R7 CMP 14 R7 C

Power supply Ph-V-Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz 1φ,220-240V,50Hz

Capacity Btu/h 14000 14000 14000 14000

Input W 1550 1550 1550 1550


Cooling
Rated current A 7.0 7.0 7.0 7.0

EER Btu/w.h 9 9 9 9

Capacity w 1800 1800


Heating Input W 1800 1800

Rated current A 7.8 7.8

Moisture Removal L/h 2.7 2.7 2.7 2.7

Max. input consumption W 1730 1730 1730 1730

Starting current A 23.7 23.7 23.7 23.7

Plug type CE-502 CE-502 CE-502 CE-502

Thermostat type Electronic control Electronic control Electronic control Electronic control

Water tank volume L Inner water tank 3L Inner water tank 3L Inner water tank 3L Inner water tank 3L

Brand ULKA, Italy ULKA, Italy ULKA, Italy ULKA, Italy

Input W 16 16 16 16
Water Pump
Water flow 70 70 70 70

Height lift m 4 4 4 4

Model 4PS180EAB 4PS180EAB 4PS180EAB 4PS180EAB

Type Rotary Rotary Rotary Rotary

Brand MATSUSHITA-WANBAO MATSUSHITA-WANBAO MATSUSHITA-WANBAO MATSUSHITA-WANBAO

Capacity Btu/h 10480 10480 10480 10480

Input W 1105 1105 1105 1105


Compressor
Rated current(RLA) A 5.0 5.0 5.0 5.0

Locked rotor Amp(LRA) A 20.2 20.2 20.2 20.2

Thermal protector 7100050 7100050 7100050 7100050

Capacitor uF 25uF/ 370V 25uF/ 370V 25uF/ 370V 25uF/ 370V

Refrigerant oil ml 350 350 350 350

Refrigerant type g R407C/560 R407C/560 R407C/560 R407C/560

Design pressure MPa 2.6 2.6 2.6 2.6

Model YSK80-4M YSK80-4M YSK80-4M YSK80-4M

Input W 185/157/112 185/157/112 185/157/112 185/157/112


Fan motor
Capacitor uF 6uF/ 450V 6uF/ 450V 6uF/ 450V 6uF/ 450V

Speed(hi/mi/lo) r/min 1230/1110/880 1230/1110/880 1230/1110/880 1230/1110/880

Indoor air flow (Hi/Mi/Lo) m3/h 360/290/180 360/290/180 360/290/180 360/290/180

Outdoor air flow (Hi/Mi/Lo) m3/h 680/580/470 680/580/470 680/580/470 680/580/470

Noise level (Hi/Mi/Lo) dB(A) 56/54/50 56/54/50 56/54/50 56/54/50

Number of rows 2 2 2 2

Fin type (code) Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
Evaporator Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 382x294x26.74 382x294x26.74 382x294x26.74 382x294x26.74

Number of circuits 2 2 2 2

Number of rows 2 2 2 2

Fin type (code) Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium Unhydrophilic aluminium
Condenser Tube outside dia.and type mm Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube Ф7x0.25, innergroove tube

Coil length x height x width mm 664x294x13.37 664x294x13.37 664x294x13.37 664x294x13.37

Number of circuits 2 2 2 2

Dimension (W*H*D) mm 480×840×400 480×840×400 480×840×400 480×840×400

Packing (W*H*D) mm 667×887x460 667×887x460 667×887x460 667×887x460

Net/Gross weight Kg 35/45 34/44 35/45 34/44

Operation temp ℃ 17-30 17-30 17-30 17-30

Ambient temp ℃ ≤35 10-35 ≤35 10-35

Application area m2 18-25 18-25 18-25 18-25

Qty’per 20’& 40’HQ Fcl Pieces 86/263 86/263 86/263 86/263

4
3.Wiring diagram
3.1 all only-cooling types (C)

3.2 all heating & cooling types

5
4. Malfunction and troubleshooting

a. No display or no response to remote controller or no response to


button ..

Y
Is there DC5V between pin 3 and pin 7 of main chip

Is CN5 , CN6 and CN7 connector connected good? Check if AC230V exists at the
primary coil of transformer.
Check if 14V exists at the
secondary coil of transformer.
N Y Y
N

Connection loosened. Transformer is


Display board failed. defective.
Control board is defective.

Replace the display


board
b. No fan running.
Is CN5 and CN6 connector connected good?

Y
Y
Is AC230V on fan motor?

Check fan motor and capacitor Is the RY1,RY2,RY3 normal in


Control board

Control board is defective

c. No compressor working.
Is CN5 connector connected good?

Y
Is AC230V on R and S in compressor?

Check compressor and capacitor Is the Relay (RY5) normal in


Control board

Check the 17 leg of main chip ,is the 5V on this leg?

Control board is defective

7
d. No water pump running.
Is CN5 and CN7 connector connected good?

Y
Y
Is AC230V on water pump?

Check fan motor and capacitor Is the RY4 normal in Control board

Control board is defective

e. No PTC working( only for with PTC heater model).


Set temperature at 32℃ and make sure the room temperature is below 30℃.

Is AC230V available on PTC

N
Y

The connection between PTC and Control Is Protector normal?


board is right in relay

Y
PTC is defective
N
Control board or display
board is defective

Connect the connection again.

8
5.Electronic function
5.1 Cooling mode
The air flow speed can be set at high, medium and low.
The temperature can be set from 17℃~-30℃.
The action of the compressor
Condition Compressor
Temp. up T> Ts+1 On
T<Ts+1 Off
Temp. down T> Ts On
T<Ts Off
.
5.2 Heating mode
The air flow speed can be set at high or low;
The temperature can be set from 17℃~-30℃.
The action of the PTC heater:
Condition PTC heater
Temp. up T> Ts+1 Off
T<Ts+1 On
Temp. down T> Ts Off
T<Ts On

5.3 Dehumidifying mode


The fan works at High speed.
The action of the compressor
Condition Compressor
Ta: room temp.
Temp. up Ta> 15℃ On
T<15℃ Off
Temp. down Ta> 13℃ On
T<13℃ Off

5.4 Air blowing mode


The fan can run at high, medium or low speed.

5.5 Timer
5.5.1 Timer On
Push the Timer On button to start the timer;
Time is relative time, from
0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-5.5-6.0-6.5-7.0-7.5-8.0-8.5-9.0-9.5-10-11-12-13-1
4-15-16-17-18-19-20-21-22-23-24-0.0;
5.5.2 Timer Off
Push the Timer On button to start the timer;
Time is relative time, from
0.5-1.0-1.5-2.0-2.5-3.0-3.5-4.0-4.5-5.0-5.5-6.0-6.5-7.0-7.5-8.0-8.5-9.0-9.5-10-11-12-13-1
4-15-16-17-18-19-20-21-22-23-24-0.0;
.

9
5.6 Operation panel
5.6.1 With PTC model
OPERATION PANEL OF THE AIR CONDITIONER(COOLING AND HEATING)
COOL/ DRY /FAN /HEA T IN DIC ATOR
DI GITA L DISPLA Y FAN SPEE D IN DIC ATOR Gr een lamp wi ll l ight w hen the mode is s e lect ed

WATER FU LL IN DICAT OR
Red lamp wil l bli nk when the tank i s ful l
TE MP SET T ING BUT TON
Pr ess y our des ir ed ro om te mpe ratu re
se tting by pr es si ng th e but ton " " ( up)
or butto n " "( dow n)
P OWE R IN DICAT OR

IN FRA RED
SIGNA L R ECEIV ER POWE R BU TTON
Tu rn on/off the u nit

TI MER ON/OFF IND ICATOR MODES BUT TON


Se lect the operation mode
fro m COOL.DRY.FAN.HEAT

FAN SPEED BUTTON


TI MER ON/OFF BU T TON
Select the fan s peed from
Pr ogra m the on/o ff timer func ti on
HIGH.M ED or L OW

5.6.1 Without PTC model


OPERATION PANEL OF T HE AIR CON DITIONER(COOLING ON LY TYPE)
COOL/ DRY /FAN IND ICAT OR
DI GITA L DISPLA Y FAN SPEE D IN DIC ATOR Gr een lamp wi ll l ight w hen the mode is s e lect ed

WATER FU LL IN DICAT OR
Red lamp wil l bli nk when the tank i s ful l
TE MP SET T ING BUT TON
Se lect your desir ed ro om temp eratu re
se tting by pr es si ng th e but ton " " ( up)
or butto n " "( dow n)
P OWE R IN DICAT OR

IN FRA RED
SIGNA L R ECEIV ER POWE R BU TTON
Tu rn on/off the u nit

TI MER ON/OFF IND ICATOR MODES BUT TON


Se lect the operation mode
fro m COOL.DRY.FAN.

FAN SPE ED B UTT ON


TI MER ON/OFF BUTT ON Pres s the butt on to sele ct
Pr ogra m the on/o ff timer func ti on the fan s p eed from
HIGH.M ED or LOW

5.7 Protective function


5.7.1 Alarm on water level
At any mode, when the water level is up to the limit, the LED display ‘P1’, the alarm
lamp flashes at 2 Hz, and the machine enters into air blowing mode.
5.7.2 Low temperature protection for the evaporator
At cooling and dehumidifying modes, if the pipe temperature is lower than 2℃ after
compressor runs for 3 minutes, the compressor will be shut down instantly. When the
pipe temperature goes up to 10℃, the compressor runs again.
5.7.3 High temperature protection
At heating mode, when the temperature at air outlet is more 75℃, the PTC will be turned

10
off; the lamp of heating will flash at 2Hz, when the temperature lowers to 55℃, the PTC
returns to work.
At heating mode, when the temperature at air outlet is more 90℃, the fuse of PTC will be
broken.
.
5.7.4 The delayed protection for compressor
When the power is on for the first time, the compressor starts without waiting for 3
minutes; re-starting the machine after the compressor is stopped needs to wait for 3
minutes.

5.7.5 Sensor defective protection


When the sensor is defective, the unit will display the error.
Pipe temp. sensor error code: E1
Room temp. sensor error code: E2

11