Escolar Documentos
Profissional Documentos
Cultura Documentos
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.
• Ratio-based methods, which are preaudit analysis approaches that rely on building energy/cost
densities to quickly evaluate building performance.
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.
Location
Proof
FIGURE 4.2 Basic approach of a typical inverse energy analysis model.
• Inverse methods, which use both steady-state and dynamic modeling approaches and include
variable-base degree-day methods.
Instructor
• Forward methods, which include either steady-state or dynamic modeling approaches and are
Proof
often the bases of detailed energy simulation computer programs.
Instructor
• Total building energy use (i.e., including all end-uses). This total energy use can be expressed in
kWh or MMBtu.
Proof
• Building energy consumption by end-use (i.e., heating, cooling, and lighting).
• Energy demand (in kW).
For the cost ratios, a monetary value (specifically for the energy expenditure or for the overall build-
ing operation) is typically used for the numerator.
For the denominator, several variables can be used depending on the building type and the main goal
intended for the computed ratios. Some of the common variables, used in the denominator of energy
and cost ratios, are:
•
Instructor
Surface area or space volume (such as heating area or conditioned volume in offices )
• Proof
Building users (in collective buildings such as hotels or schools)
• Degree-day [generally with 65°F (18°C) as a base temperature]
• Units of productions (especially for manufacturing facilities or restaurants)
In general, annual or seasonal values are used to obtain the energy or cost ratios. However, daily or
monthly ratios can be considered. The monthly variations of energy ratios are often referred to as build-
ing signatures.
Instructor
4.2.3 Examples of Energy Ratios
Proof
Generally, meaningful energy ratios require careful analysis and screening of the data. For instance,
it is important to consider effects such the climate and building function when estimating energy
ratios. Sources of building energy data are typically difficult to obtain. In the United States, the Energy
Information Administration (EIA) annually provides statistical data about the energy use of vari-
ous building types. In other countries, it is generally very difficult to obtain such data even through
governmental agencies. Table 4.1 provides some energy ratios for selected commercial and institutional
building types in the United States and France.
It should
You are viewing be stressed
a preview. that
Your final energy
book, ratios
as well such
as your as those
digital provided
desk copy, in Table 4.1
will include pristineshould be used
files directly fromonly as
the publishers.
generic indicators of typical energy use for the listed buildings or facilities. Energy ratios specified by
climate zone, type of HVAC system, or building size may be required for an adequate energy screening
or preaudit energy analysis.
c Not available.
Instructor
4.3 Inverse Modeling Methods
Proof
As discussed in the introduction, methods using the inverse modeling approach rely on existing
building performance data to identify a set of building parameters. Inverse modeling methods can
be valuable tools in improving building energy efficiency. In particular, the inverse models can be
used to:
• Help detect malfunctions by identifying time periods or specific systems with abnormally high
energy consumption.
Instructor
• Provide estimates of expected savings from a defined set of energy conservation measures.
• Verify the savings achieved by energy retrofits. Proof
Typically, regression analyses are used to estimate the representative parameters for the building
or its systems (such as building load coefficient or heating system efficiency) using measured data. In
general, steady-state inverse models are based on monthly or daily data and include one or more inde-
pendent variables. Dynamic inverse models are usually developed using hourly or subhourly data to
capture any significant transient effect such as the case where the building has a high thermal mass to
delay cooling or heating loads.
Instructor
Proof
4.3.1 Steady-State Inverse Models
These models generally attempt to identify the relationship between the building energy consumption
and selected weather-dependent parameters such as monthly or daily average outdoor temperatures,
degree-hours, or degree-days. As mentioned earlier, the relationship is identified using statistical
methods (based on linear regression analysis). The main advantages of the steady-state inverse models
are:
• Simplicity: Steady-state inverse models can be developed based on a small dataset such as energy
You are viewingdata obtained
a preview. Yourfrom
final utility
book, asbills.
well as your digital desk copy, will include pristine files directly from the publishers.
• Flexibility: Steady-state inverse models have a wide range of applications. They are particularly
valuable in predicting the heating and cooling energy end-uses for both residential and small
commercial buildings.
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.
900000
BLC V
× VB × DDH × I
EH = 24 × (4.1)
ηH desk copy, will include pristine files directly from the publishers.
You are viewing a preview. Your final book, as well as your digital
where
EH is the annual building heating energy consumption (in kWh).
BLCV is the building loss coefficient based on the building volume (in kW/m3 °C).
Then, ANAGRAM proceeds to calculate the monthly heating energy use using the following
expression:
BLC V
E H,m = 24 × × VB × I × [DDH,m − (18 − Tb ) × 30] (4.2)
ηH
Instructor
where
Proof
EH,m is the monthly building heating energy use (in kWh).
DDH,m is the heating degree-days (based on 18°C).
Tb is the building balance temperature. Tb is defined as the outdoor temperature for which the build-
ing does not need any heating.
Instructor
BLCV, I, VB, ηH have the same definition as in Eq. (4.1).
Proof
30 is the number of days in a month (which corresponds to the number of days included in the GDF
utility bills).
Thus, a linear regression is carried out to correlate the monthly building energy use to the monthly
degree-days (based on 18°C using only heating season data). This regression analysis provides an esti-
mation of the building balance temperature Tb and the ratio of BLCV/ηH and is the average seasonal
energy efficiency of the heating system. Example 4.1 illustrates how the ANAGRAM approach is used to
analyze monthly building energy use.
Instructor
Proof
Example 4.1
Illustration of the Anagram Method
Using the ANAGRAM approach, analyze the heating energy use data for a building having a
heated volume of 15,000 m3. Monthly energy consumption and degree-day data are provided
Instructor
below for two years, 0 and 1.
Proof Monthly Degree Monthly Consumption Monthly Consumption
Days (MWh) Year 0 (MWh) Year 1
September (S) 115 0 0
October (O) 235 80 20
November (N) 375 200 80
May (My) 185 60 10
March (M) 465 260 110
June (Ju)
You are viewing a preview. 105 as your digital desk copy,
Your final book, as well 0 will include pristine files
0 directly from the publishers.
January (J) 580 340 150
February (F) 535 310 135
December (D) 485 280 120
April (A) 310 140 50
400
350
Monthly consumption (MWh) year 0
Monthly consumption (MWh) year 1 300
250
Instructor 200
Proof 150
100
50
Instructor 0
Proof 700 600 500 400 300
Monthly Degree Days
200 100 0
For year 0, the regression line intersects the x-axis at degree-days DDH.,m = 120oC-days. Thus,
the balance temperature Tb can be estimated as follows: [DDH,m – (18 – Tb) × 30] = 0. Therefore, for
year 0, the balance temperature is:
Tb = 18 – 120/30 = 14°C
Instructor
Using the slope of the regression line (which is 570 kWh/oC-days), the ratio BLCV/ηH can be
estimated using the fact that: Proof
570 kWh/oC-days = 24 * BLCV/ηH * VB,
BLCV/ηH = 1. 58 W/m3°C
A similar analysis can be carried out for year 1. It is found that between year 0 and 1, the bal-
Instructor
ance temperature has decreased from 14°C to 13.5°C, and the ratio BLCV/ηH is reduced from 1.58
Proof
W/m3°C to 0.70 W/m3°C. It is most likely that this reduction in both Tb and BLCV/ηH is attributed
to improvement in the energy efficiency of the building envelope.
BLC
E H/C = 24 × × DDH/C (Tb, H/C ) + E base, H/C (4.3)
η H /C
Traceable User Identifier: e9cf122e85c3db39818b6157256f5d5a - 192.168.80.254 - 08/10/2016 06:29:53
4-8 Energy Audit of Building Systems: An Engineering Approach, Second Edition
You are viewing a preview. Your final book, as well as your digital
Fuel deskDay
Use Per copy,
vs. will
HDD include pristine files directly from the publishers.
107 Acoma (2006–2007)
Monthly Daily Gas Consumption (MMBtu/day) 1.2
1.0
y = 0.0252x + 0.0833
R2 = 0.9423
0.8
0.6
Instructor
0.4
Proof
0.2
All months
Linear (all months)
0
Instructor
0 5 10 15 20 25 30 35 40 45
Proof Daily Heating Degree-Days fn (Tb best)
FIGURE 4.4 Analysis of gas consumption as a function of monthly heating degree-days. (Kalinic, 2009.)
where
EH/C represents the annual building energy use during heating or cooling season.
BLC is the building loss coefficient.
ηH/C is the average seasonal energy efficiency of the heating or the cooling system. Instructor
Tb, H/C is the building balance temperature for heating or cooling energy use. Proof
DDH is the heating or cooling degree-days (based on the balance temperature). Chapter 6 discusses
in more detail how variable base degree-days are defined. For heating, for instance, the heating
degree-days are estimated as follows: DDH(Tb) = Σj[Tb−To,j]+ with To,j the outdoor air tempera-
ture at day j.
E base, H/C is the base-load for building energy use. It represents nonheating or noncooling energy
use.
Instructor
Through regression analysis, the balance temperature and the building load coefficient can be deter-
Proof
mined (assuming the heating or cooling system efficiency is known). With these two parameters deter-
mined, the PRISM tool can be used to establish an energy use model for the building and to determine
any energy savings attributed to measures that affect one of the three parameters, balance temperature,
building load coefficient, or heating/cooling system efficiency. Figure 4.4 illustrates the PRISM method
for the analysis of natural gas usage as a function of the heating degree-day for a residential building.
One variation of the PRISM approach represented by Eq. (4.3) is to use the average outdoor temperature
instead of the variable-base degree-day. This method is described in Chapter 6.
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.
4.3.2 Dynamic Models
Steady-state inverse models are only suitable for predicting long-term building energy use. Therefore,
energy use data is collected for a relatively long time period (at least one season or one year) to carry out
the regression analysis. On the other hand, dynamic inverse models can be used to predict short-term
Traceable User Identifier: e9cf122e85c3db39818b6157256f5d5a - 192.168.80.254 - 08/10/2016 06:29:53
Energy Analysis Tools 4-9
Variable-base degree-day methods generally provide good predictions of the fuel use for buildings
dominated by transmission loads (i.e., low-rise buildings). However, they are not recommended for
Instructor
buildings dominated by internal loads or with involved HVAC system operation strategies.
Proof
4.4.3 Bin Methods
Another energy analysis method that uses the forward approach but is based on steady-state modeling of
building energy systems is the bin method (Knebel et al., 1983). The bin method is similar to the variable-
base degree-day method but relies on bin weather data to estimate total building heating or cooling energy
Instructor
consumption. In the United States, a number of HVAC engineers use the bin method to perform a variety of
Proof
energy analyses. Moreover, computer energy simulation tools based on the bin methods have been developed
(DOE, 2010). The simulation tools based on the bin method are typically appropriate for residential or small
commercial buildings.
In the classical bin method, only the outdoor temperatures are grouped into bins of equal size, typi-
cally 5°F (2.8°C) bins. The number of hours of occurrence is determined for each bin. For other weather
variables, only average values coincident to each temperature bin are determined. The resulting weather
data from the classical bin method is often referred to as one-dimensional bin weather data. Table 4.2
illustrates one-dimensional weather data obtained for Atlanta, Georgia. In addition to the outdoor dry-
Instructor
Table 4.2 Proof
Classical (or One-Dimensional) Bin Weather Data
for Atlanta, Georgia
Average of Outdoor
Dry-Bulb Number of Hours of Average Coincident
Temperature Bin (oF) Occurrence Humidity Ratio (lb/lb)
15 1 0.0020
20 42 0.0020
25 154 0.0020
Instructor30 291 0.0025
Proof 35
40
354
641
0.0031
0.0038
45 623 0.0044
50 665 0.0053
55 741 0.0065
60 882 0.0083
65 905 0.0100
70 1225 0.0128
75 1000 0.0133
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.
80 672 0.0137
85 421 0.0143
90 133 0.0156
95 19 0.0170
Instructor
bulb temperature bins, Table 4.3 provides the average values for coincident humidity ratio. The current
Proof
version of ASEAM software uses one-dimensional bin weather data.
The accuracy of the classical bin method is adequate only for buildings dominated by sensible heat
loads and with no significant thermal mass effects. However, the classical bin method may not provide
accurate energy predictions for buildings with high latent heat loads as reported by Harriman et al.
(1999) and Cohen and Kosar (2000). To improve the accuracy of the bin method especially for buildings
with significant latent loads, two-dimensional weather data bins were introduced by ASHRAE (1997).
The two-dimensional (also referred to as joint-frequency) weather data bins are generated based on
bins obtained for two variables (such as the dry-bulb temperature and humidity ratio) as presented in
Table 4.3 using a partial dataset for Atlanta, Georgia. Instructor
Proof
The two-dimensional weather bin data can be created using hourly data such as TMY-2 files. A num-
ber of software are available to create these bins including the ASHRAE Weather Data Viewer developed
by Colliver et al. (1998).
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.
Climate data
Load calculation
Building data
Physical
Internal
Envelope
Infiltration Peak heating and cooling loads
Schedules
Energy
Proof
requirements
Economic data
Economic factors
Economic
Instructor Project life
First cost
analysis
Proof Maintenance cost
existing measured energy data (utility bills, for instance). A basic calibration procedure is discussed in
detail in Chapter 16.
Although energy simulation programs are generally capable of modeling most of the building energy
Instructor
systems, they are often not sufficiently flexible and have inherent limitations. To select the appropriate
Proof
energy simulation program, it is important that the user be aware of the capabilities of each simulation
available. Some of the well-known simulation programs are briefly presented below:
• DOE-2 (version DOE-2.1). DOE-2 was developed at the Lawrence Berkeley National Laboratory
(LBNL) by the U.S. Department of Energy and is widely used because of its comprehensiveness. It
can predict hourly, daily, monthly, or annual building energy use. DOE-2 is often used to simulate
complex buildings. Figure 4.6 illustrates a typical zoning scheme used to model the office build-
ing of the case study in Chapter 1 with DOE-2. Typically, significant efforts are required to cre-
ate DOE-2 input files using a programming language called the Building Description Language
Instructor
(BDL). Several tools are currently available to facilitate the process of developing DOE-2 input
Proof
files. Among energy engineers and professionals, DOE-2 has become a standard building energy
simulation tool in the United States and several other countries using interfaces such eQUEST and
VisualDOE. Figure 4.7 shows a 3-D rendering of a residential building modeled using eQUEST.
• BLAST (building loads analysis and systems thermodynamics). This program enables the user
to predict the energy use of the whole building under design conditions or for long-term peri-
ods. The heating/cooling load calculations implemented in BLAST are based on a heat balance
approach (instead of the transfer function technique adopted by DOE-2). Therefore, BLAST can
be used to analyze systems such as radiant heating or cooling panels that cannot be adequately
You are viewingmodeled
a preview.
byYour final book, as well as your digital desk copy, will include pristine files directly from the publishers.
DOE-2.
• EnergyPlus. This builds on the features and capabilities of both DOE-2 and BLAST. EnergyPlus
uses new integrated solution techniques to correct one of the deficiencies of both BLAST and
DOE-2: the inaccurate prediction of space temperature variations. Accurate prediction of space
temperatures is crucial to properly analyze energy-efficient systems. For instance, HVAC system
Traceable User Identifier: e9cf122e85c3db39818b6157256f5d5a - 192.168.80.254 - 08/10/2016 06:29:53
Energy Analysis Tools 4-13
1 PW
1 PE
1 CW 1 CE
1 PSW 1 PSE
Instructor
Proof
2 PW
3 EE
3W
RW
RE
2 CW 3C RC
3S RS
2 PS
Proof
TW
TC Pent
TE
TS
FIGURE 4.6 Space zoning used to model an office building using DOE-2.
Instructor
(a)
Proof
Instructor
Proof
(b)
FIGURE 4.7 Three-dimensional models for a residential building (a) CAD rendering and (b) eQUEST
rendering.
Instructor
Proof
Instructor
Proof
You are viewing a preview. Your final book, as well as your digital desk copy, will include pristine files directly from the publishers.