Escolar Documentos
Profissional Documentos
Cultura Documentos
ScienceDirect
w w w . i i fi i r . o r g
Article history: A multi-ejector expansion pack, intended as a substitute for a standard high-pressure
Received 30 January 2015 electronic expansion valve (HPV), was designed, manufactured and experimentally
Received in revised form investigated. Four different ejector cartridges were sized to enable a discrete opening
11 May 2015 characteristic with a binary profile for a parallel-compression R744 system. The system is
Accepted 30 May 2015 rated for 70 kW at a 35 C gas cooler outlet temperature and a 3 C evaporation tem-
Available online 9 June 2015 perature. High values of ejector efficiency, exceeding 0.3 over a broad operation range, were
recorded for all four of the cartridges tested under vapour compression conditions. The
Keywords: applicability of the multi-ejector pack as a main flashing device was verified experimen-
Multi-ejector tally. Similar profiles of the discharge pressure control error were recorded for both
Expansion work recovery alternative options: expansion purely in the HPV vs. HPV-assisted expansion in the multi-
R744 ejector pack.
Discharge pressure control © 2015 Elsevier Ltd and IIR. All rights reserved.
the flash gas from the liquid separator. This design elevates
2. Design procedure the suction pressure in the medium-temperature evaporators
much higher than a conventional R744 booster system, where
2.1. Vapour compression unit design and controlling all of the compressors are connected to the exits of the
strategy evaporators. The ejectors are applied to maintain a required
pressure difference between the liquid separator and the
The multi-ejector expansion work recovery system (Fig. 1) liquid receiver for proper feeding of individual cabinets.
substitutes for a single high-pressure valve (HPV) used in At low and moderate ambient temperatures, the optimum
conventional booster systems to reduce high pressures below high side pressure is low, i.e., a subcritical mode of the R744
a certain level (typically 40 105 Pa) before metering refrig- system is selected. In this case, the pressure lift capability of
erant to the individual cabinets/cold room evaporators (LTE the ejectors is reduced because less work can be recovered
and MTE). A series of vapour ejectors are assembled in parallel from the condensate expansion. Therefore, the number of
(from VEJ1 to VEJ4). The geometry of each ejector can be compressors connected to the liquid receiver increases. This
optimized for different operating conditions governed by reduces the entrainment ratio of the ejectors, which supports
variable ambient temperatures. Every ejector is individually the ejectors in operation to maintain the necessary pressure
controlled by a shut-off valve at the inlet to the motive nozzle lift.
and a check valve at the inlet to the suction nozzle. Thus, by Proper oil management can be performed both on the
controlling the number of ejectors in operation and main- discharge side (before the gas cooler) and on the suction side
taining the high side pressure level according to ambient (inside the liquid separator) by the pressure lift invoked by the
temperature or load requirements, system operation at the ejectors.
maximized overall COP should be possible. Additionally, an
auxiliary liquid ejector (LEJ) compresses the remaining liquid
not vaporized in the evaporators, while benefitting from the 2.2. Boundary conditions for the multi-ejector pack
advantages of wet evaporators (optimum use of the effective
heat transfer area, higher values of the heat transfer coeffi- To determine the operational envelope for a sample multi-
cient, simpler and cost-effective metering valves, etc.). ejector pack, a mathematical model of the R744 refrigeration
The medium-temperature compressors (MT) are either installation for a typical supermarket was created. A calcula-
connected to the liquid receiver (LR) or to the liquid separator tion worksheet supplied with the REFPROP 9.1 library for the
(LS) downstream from the ejectors. MT2 and MT3 can work in R744 thermal and transport properties was used and a series
alternative modes whereas the frequency-controlled MT1 and of system simulations was carried out by a non-linear equa-
MT4 are devoted to a specific operation mode, i.e., MT1 pumps tion solver. The mass and energy balances for the components
out the return gas from the evaporators while MT4 pumps out of the refrigeration installation were formulated,
Fig. 1 e Schematic representation of the novel multi-ejector pack for expansion work recovery in R744 refrigeration units for
supermarkets. Standard components in the booster system are presented in black, and additional components of the
energy recovery system are indicated in red. (For interpretation of the references to colour in this figure legend, the reader is
referred to the web version of this article.)
268 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6
Table 1 e The simulated set of boundary conditions for the multi-ejector expansion work recovery pack.
Motive nozzle inlet Suction nozzle inlet Required Total required mass
pressure lift, Pa flow rate expanded through
motive nozzles, kg s1
Pressure, Pa Temperature, C Pressure, Pa Quality LEJ/VEJ, e LEJ VEJs
5 5 5
93.9 10 35 32 10 0/1 6.1 10 0.0109 0.723
72.1 105 25 32 105 0/1 4.9 105 0.0152 0.590
57.3 105 15 32 105 0/1 4.0 105 0.0255 0.484
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6 269
dimensioning parameter, the motive nozzle throat diameter, modification enabled very compact design (crucial for the
was identical for each originalesubstitute pair, while the units dedicated to supermarket applications) and easier inte-
operating hours predicted for the auxiliary liquid ejectors gration of the necessary accompanying automation and con-
(working only periodically in practice) were substantially trolling components. However, this modification prevented
reduced. individual measurements of each particular cartridge during
Modular design of the multi-ejector pack was applied simultaneous operation of the entire pack of parallel ejectors.
(Fig. 2c), where individual ejector cartridges were placed into a Therefore, the ejector performance mapping was carried out
monoblock casing, instead of a set of separate ejectors. This individually for each cartridge in the course of separated runs.
Fig. 2 e Schematics of the multi-ejector test facility, (a) R744 circuit, (b) glycol circuit and (c) multi-ejector pack.
Instrumentation signatures: t e temperature sensor, p e absolute pressure sensor, m e mass flow rate meter.
270 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6
Fig. 3 e Motive nozzle mass flow rate as a function of the motive nozzle inlet conditions for VEJ1 (a), VEJ2 (b), VEJ3 (c), and
VEJ4 (d).
pressure lift influences the motive nozzle mass flow rate. The 4.1.2. Suction nozzle mass flow rate, entrainment ratio, and
registered profiles were clearly dependent on the inlet den- ejector efficiency e vapour compression
sity and inlet pressure, where the highest mass flow rate In contrast to the motive nozzle, the suction nozzle mass flow
values were recorded for the heat recovery operation mode rate is a function of more than two independent parameters.
while the lowest occurred in the vicinity of the switching
point between the subcritical and supercritical operation
modes.
The motive nozzle mass flow rate profiles are expressed as
functions of the following structure,
" 2 #
p 2 pMN;in pMN;in
m_ MN ¼ dth ArMN;in þ BrMN;in þ C
2
þD þE (1)
4 pcr pcr
Therefore, it is not possible to graphically present represen- ejector cartridge may provide an individual performance map
tative performance maps for the suction nozzle mass flow rate of unique features. Thus, by applying common boundary
unless three of the five degrees of freedom are held constant. conditions to a series of parallel ejectors placed in operation,
The same conclusion applies to derivative parameters such as the overall system performance should be maximized
entrainment ratio and ejector efficiency. because it is not possible to optimise individual ejector oper-
A number of the five degrees of freedom reportedly have ations simultaneously.
less significant effect than others and can be neglected. It should be emphasised that the recorded levels of ejector
Namely, moderate superheating of the suction stream also efficiency for the four cartridges outperformed reported
causes a moderate reduction in density when compared to the achievements to date for R744 systems. Namely, Elbel and
saturation conditions. Therefore, it may be presumed that Hrnjak (2008) registered values at or below 0.145, while
within a limited range (from 0 K to 10 K), the influence of Nakagawa et al. (2011a) reached values as high as ca. 0.22.
superheating on the ejector performance will be barely Approximately the same maximum level, 0.22, was recorded
measurable. For the purpose of presentation, if the influence by Lucas and Koehler (2012), while Xu et al. (2012) managed to
of the suction/outlet conditions becomes expressed solely by reach efficiencies as high as 0.282. The highest efficiency
the pressure ratio, i.e., the ratio of the ejector outlet pressure values in the R744 ejector cycle were reported by Banasiak
to the suction pressure, then individual quasi-maps for ejector et al. (2012), specifically up to 0.308, while the highest ever
suction performance may be generated either explicitly for reported efficiency values, namely up to 0.42, were published
the suction nozzle mass flow rate or for any derivatives, e.g., by Bilir Sag et al. (2015) for the R134a ejector system. In the
ejector efficiency (Fig. 5). current research, the highest measured efficiency for VEJ1 was
The registered profiles, particularly the high-resolution 0.330, 0.368 for VEJ2, 0.362 for VEJ3, and 0.336 for VEJ4,
efficiency map for VEJ1, prove effective vapour compression respectively.
over a broad range of operating conditions. According to the The vapour compression performance of each ejector
data presented in Fig. 5, the region where the ejector efficiency cartridge is expressed by functions of the following structure,
is equal to at least 0.3 may be found from ca. 70 105 Pa to ca. !2
m_ SN pDIF;out pDIF;out
95 105 Pa and from ca. 25 C to ca. 35 C for the motive nozzle ¼ K1 þ K2 þ K3 (2)
m_ MN pSN;in pSN;in
inlet conditions (right side), which constitutes a substantial
part of the operational area. At the same time, clear depen-
dence between the maximum performance pressure ratio and with parameters K1…K3 defined as follows:
the motive nozzle inlet conditions are observed (left side). All
of the points characterized by ejector efficiency greater than " 2 #
pMN;in pMN;in
or equal to 0.3 recorded at the inlet pressure higher than Ki ¼ ki;1 r2MN;in þ ki;2 rMN;in þ ki;3 þ ki;4
pcr pcr
90 105 Pa were reached with a substantial pressure ratio, (3)
ranging from 1.22 to 1.31. Conversely, points with an ejector pSN;in
ki;5 þ ki;6
efficiency greater than or equal to 0.3 recorded at inlet pres- pcr
sures lower than 75 105 Pa were reached with a much lower
pressure ratio that ranged between 1.15 and 1.18. Thus, the where coefficients ki,1…ki,6 are adjusted individually for a
recorded profiles suggest that to utilize a given ejector geom- particular cartridge. The values from the increased-resolution
etry in the optimum way, one should adjust the floating area investigated for VEJ1are shown in Table 3.
pressure ratio (or pressure lift) according to the heat sink Because the registered entrainment ratio of VEJ1varied
conditions in the gas cooler. It should be noted that each greatly from 0 to ca. 0.6, the relative expressions of the
Fig. 5 e Ejector efficiency as defined by Elbel and Hrnjak (2008) as a function of the motive nozzle inlet conditions and
pressure ratios for VEJ1. The average measurement uncertainties for ejector efficiency are ±0.008.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6 273
approximation errors were discarded. Because the relative da Silva et al. (2012), Cecchinato et al. (2012) and Sharma et al.
values were approaching infinity for an entrainment ratio (2014).
close to 0, giving a false indication of substantial inaccuracy, Because optimization of the controlling algorithms ex-
the absolute errors were calculated instead. It was verified ceeds the scope of the paper, a simplified procedure was
that for 358 test points of the 400 points analysed for VEJ1, the applied to regulate the discharge pressure. The requested
absolute error was less than ±0.02, while for 397 points, the configuration of ejectors in use at any given time was
absolute error was less than ±0.04. dependent on the opening degree of the accompanying HPV
working in parallel. Each time the registered opening degree of
4.1.3. Suction nozzle mass flow rate, entrainment ratio, and the HPV rose to the 'step-up' level, the next point of higher
ejector efficiency e liquid compression capacity on the multi-ejector opening characteristics was
Although the number of points investigated was limited, it is applied by switching on/off the appropriate solenoid valves.
possible to measure the influence of pressure ratio on the Accordingly, every time the HPV opening degree sank to the
ejector's performance (see Fig. 6). Namely, the higher the 'step-down' level, the closest point of lower capacity for the
motive nozzle inlet pressure, the higher the optimum pres- multi-ejector block was selected. Thus, the applied controlling
sure ratio. Nevertheless, the overall efficiency of the liquid algorithm required neither additional sensor(s) nor advanced
compression level is much lower (ca. three times) than the logic.
efficiency of the vapour compression performed with the The recorded system performance for the HPV-assisted
same cartridges. This indicates that the ejectors optimised for operation of the multi-ejector block was compared to the
vapour compression perform relatively ineffectively during standard HPV operation. Two test cases were run, one veri-
liquid pumping. Therefore, the ejectors in the liquid return fying the system reaction for a quick jump in the load profile
section should be individually sized. (Fig. 7), and the other verifying the system response to a rapid
change in ambient conditions (Fig. 8). Identical values of
4.2. Test runs with the multi-ejector block as the main proportional gain and integration time for the HPV controller
expansion device were used for both expansion modes. The key system settings
for the test conditions are shown in Table 4 (test run A).
After the ejector cartridges were verified individually, a series The system's response to a shock increment in the load
of test runs for the entire multi-ejector block was performed to profile was relatively similar for both operation modes. The
prove its suitability as the primary component for regulating same profiles of the heat source temperature (Fig. 7a) resulted
the discharge pressure in the system under the superheat in profiles of discharge pressure control errors of comparable
conditions at the evaporator outlet(s), which is a standard magnitudes and trends (Fig. 7c), though slightly different in
regulation strategy for evaporators in classic R744 cycles, e.g., shape. Unlike in the pure HPV mode, the discrete feature of
Fig. 6 e Ejector efficiency as defined by Elbel and Hrnjak (2008) as a function of the motive nozzle inlet conditions and
pressure ratios for LEJ1 (diamonds) and LEJ2 (triangles). The average measurement uncertainties for ejector efficiency are
±0.002 for both cartridges.
274 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6
Fig. 7 e System's response to a rapid change in load for the Fig. 8 e System's response to a rapid change in ambient
HPV operation mode (red profiles) and HPV-assisted multi- conditions for the HPV operation mode (red profiles) and
ejector operation mode (green profiles). Evaporator inlet HPV-assisted multi-ejector operation mode (green
temperature in the glycol circuit (a), opening degree of HPV profiles). Gas cooler outlet temperature (a), opening degree
and indication of the ejector cartridges in use (b), and of HPV and indication of the ejector cartridges in use (b),
deviation between the actual value and set-point value for and deviation between the actual value and set-point value
the discharge pressure (c). (For interpretation of the for the discharge pressure (c). (For interpretation of the
references to colour in this figure legend, the reader is references to colour in this figure legend, the reader is
referred to the web version of this article.) referred to the web version of this article.)
the multi-ejector opening characteristics invoked a fluctua- performance will be enhanced by the effects of the expansion
tion of the control discrepancy, which increased its integrated work recovery. The percentage of the mass flow rate
values. The standard deviation of the discrepancy over the expanded through the multi-ejector block registered during
recorded test periods was 1.20 105 Pa compared to these tests was high and varied between 84% and 96%.
0.75 105 Pa for the pure HPV mode. However, the stepwise-
occurring control gaps invoked by stepping up/down were 4.3. Investigation of the feasible COP improvement for
not large (less than 2 105 Pa at their peaks) and were alle- parallel operation of ejectors
viated over time by the opening/closing HPV compensating for
a too large or too small overall opening of the multi-ejector The main goal of this phase of the study was to investigate the
block. Additionally, the magnitude and frequency of the effects of parallel ejectors operation on the overall multi-
resulting oscillations in control error can be influenced by ejector pack efficiency as well as to verify the expected
settings of the regulator parameters, so further optimization improvement of the overall COP due to the use of expansion
of the controlling algorithm is possible. work recovery. The authors of the paper were aware of the fact
The system's response to a shock increment in the ambient
conditions again proved to be similar in terms of magnitude
and trend for the control error profile in both controlling Table 4 e Test settings for the system's response
modes (Fig. 8c) despite different profiles of the HPV opening verification runs.
degree (Fig. 8b). The standard deviation of the control error
Test run A B
over the recorded period was 1.11 105 Pa for the HPV mode
R744 circuit
and 0.96 105 Pa for the HPV-assisted mode.
Evaporation temperature, C 5 8
In general, a relatively flat shape of the COP curve Evaporator outlet superheat, K 10 10
(expressed as a function of the discharge pressure) shall pre- Gas cooler outlet temperature (after 2nd stage), C 25 30
vent significant penalty in the integrated value of the system Liquid separator pressure, 105 Pa 34.0 35.0
energy performance caused by an aggregated control gap Glycol circuit
resulting from the discrete opening characteristics of the Evaporator inlet temperature, C 15 12
Evaporator circuit mass flow rate, kg s1 0.81 0.85
multi-ejector block. Furthermore, the overall system
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6 275
that the latter effect measured at the test facility designed The recorded system performance proved to be dependent
specifically for mapping the multi-ejector pack performance on a number of various parameters. Contrary to the expected
would not be entirely representative for the complete super- performance, the largest COP and exergy efficiency improve-
market installations where additional sections of the low- ments, equal to 9.8% and 13.1%, respectively, were registered
temperature compressors/evaporators are typically installed. for only partial use of the multi-ejector pack where almost
Moreover, typical medium-temperature sections consist of a 50% of the total refrigerant flow was expanded in HPV. This
much larger number of base-load/parallel compressors where fact may be attributed to both the decreasing efficiency of the
only one, two units are equipped with inverter for precise multi-ejector pack and the intensified irreversibilities in the
capacity adjustment. This entails entirely different regulation compressors section. The overall performance of the com-
approach, i.e., much more refrigeration load is transferred to pressors, expressed by the ratio of the total isentropic power
the heat sink by the compressors run at constant frequency. to the total electric power measured, reaches its peak for the
Nevertheless, in order to identify the effects of stepwise multi-ejector pack operated with VEJ3 and degrades along
shifting from the high-pressure-valve to the multi-ejector with the rising load transferred to the parallel compressor
expansion mode, an example test series was carried out for section. This suggests the correct usage of the multi-ejector
subcritical operating conditions (Table 4, test run B). block that could maximize not only the effects of expansion
Due to the fact the use of liquid ejectors would enforce work recovery but also the overall system performance shall
transient behaviour of the system (alternating phases of take into account individual characteristics of the system
accumulating and discharging the low-temperature conden- components.
sate in/from the liquid receiver) this test series was also con-
ducted under the superheat conditions at the evaporator
outlet. Thus, the obtained results excluded the potential ef- 5. Conclusions
fects of evaporation at elevated temperature.
The list of investigated parameters comprised ejector effi- The proposed concept of replacing a standard high-pressure
ciency (determined for the entire multi-ejector pack) as well expansion valve with a block of properly designed parallel
as COP and exergy efficiency of the refrigeration system, ejectors for maintaining the discharge pressure in R744
where the latter was defined as a ratio of the exergy rate parallel-compression systems was successfully verified under
increment in evaporator to the overall electric power con- laboratory conditions. It was proven that the refrigeration
sumption by compressors. The individual power consumption system upgraded with the multi-ejector block fully retains its
for each compressor was determined by three separate dynamic operational characteristics, and precise discharge
MG16G102 VTL Refrigeration Drives by Danfoss with the pressure adaptations according to the variable load and
measurement accuracy equal to 1% of the read value. The ambient conditions are possible, even with the use of a
resulting average measurement uncertainties of COP and simplified controlling strategy.
exergy efficiency were equal to ±0.08 and ±0.004, respectively. Based on the high values of ejector efficiency recorded
In general, according to the results presented in Table 5, (broad areas of efficiency higher than 0.3 for the four vapour-
the overall multi-ejector efficiency degraded gradually compression cartridges), the overall energy performance of
together with the increasing mass flow rate expanded. Such supermarket refrigeration systems can be potentially
performance implies intensified flow irreversibilities in the improved when utilising the multi-ejector block as a main
pack, most likely due to the augmented friction on the man- flashing device, given the expansion work recovery invoked
ifold's walls (increased velocity) and because of the imperfect and consequent transfer of the load from the base-load
mixing of individual streams flowing out of the ejector car- compressors group to the parallel compressors group does
tridges and interspersed in the manifold volume. Neverthe- not deteriorate the overall efficiency of the compressor pack.
less, the registered values remained relatively high (above 0.2) The initial tests aimed at the estimation of the feasible COP
even for almost entire flow expanded in the pack. improvement, performed at the laboratory test facility that
Table 5 e The measured energy/exergy effects of stepwise shifting into the multi-ejector expansion mode.
P
Expansion HPV m_ MN a m_ SN a Ejector COP Exergy Pis
Pel (CD1400H) Pis
Pel (CD1000H) Pis
Pel (CD380H) P Pis
mode opening kg s1 kg s1 efficiencya efficiency Pel
degree
No-ejector 18.9% 0.000 0.000 e 2.409 0.112 0.679 e 0.577 0.651
VEJ1 18.8% 0.035 0.009 0.325 2.536 0.121 0.674 0.715 e 0.690
VEJ2 16.5% 0.071 0.017 0.318 2.576 0.120 0.680 0.712 e 0.690
VEJ1þVEJ2 15.7% 0.100 0.022 0.289 2.574 0.121 0.683 0.701 e 0.687
VEJ3 12.5% 0.127 0.023 0.242 2.646 0.127 0.686 0.706 e 0.697
VEJ1þVEJ3 12.4% 0.155 0.027 0.231 2.630 0.124 0.689 0.695 e 0.686
VEJ2þVEJ3 8.6% 0.194 0.033 0.239 2.612 0.122 0.692 0.681 e 0.682
VEJ1þVEJ2þVEJ3 2.7% 0.224 0.036 0.228 2.610 0.121 0.693 0.675 e 0.681
a
Measured for the overall multi-ejector pack.
276 i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 5 7 ( 2 0 1 5 ) 2 6 5 e2 7 6
was scaled down in refrigeration capacity and system Da Silva, A., Filho, E.P.B., Antunes, A.H.P., 2012. Comparison of a
complexity as well as required non-typical regulation tech- R744 cascade refrigeration system with R404A and R22
niques, yielded the results that only partly can be considered conventional systems for supermarkets. Appl. Therm. Eng. 41,
30e35.
representative for the real applications. Therefore, to verify
Elbel, S., Hrnjak, P., 2008. Experimental validation of a prototype
the performance of the multi-ejector pack in industrial envi- ejector designed to reduce throttling losses encountered in
ronment, two independent field test campaigns are planned transcritical R744 system operation. Int. J. Refrigeration 31,
for the integrated multi-ejector-equipped R744 installations 411e422.
covering the needs of the supermarket facilities (heating, Elbel, S., 2011. Historical and present developments of ejector
cooling, chilling and air conditioning) where detailed, year- refrigeration systems with emphasis on transcritical carbon
round COP recordings will be gathered for the two alterna- dioxide air-conditioning applications. Int. J. Refrigeration 34,
1545e1561.
tive flashing modes (pure HPV vs. HPV-assisted multi-ejector)
Girotto, S., 2012. Efficiency Improvement in Commercial
to estimate actual feasible COP gains. The wet-evaporator Refrigeration for Warmer Climates with CO2. Proceedings
controlling strategy, potentially providing the benefits of from the ATMOsphere Europe 2012, 5e7.11.2012, Brussels.
elevation of the requested evaporation temperature and the Hafner, A., Fo € rsterling, S., Banasiak, K., 2014a. Multi-ejector
enhanced heat transfer mechanism, will also be a part of the concept for R-744 supermarket refrigeration. Int. J.
testing procedure. Refrigeration 43, 1e13.
Hafner, A., Scho € nenberger, J., Banasiak, K., Girotto, S., 2014b. R744
Ejector Supported Parallel Vapour Compression System,
Refrigeration Science and Technology, 3rd IIR International
references Conference on Sustainability and the Cold Chain, pp. 134e141.
Liu, F., Li, Y., Groll, E.A., 2012a. Performance enhancement of CO2
air conditioner with a controllable ejector. Int. J. Refrigeration
35, 1604e1616.
Banasiak, K., Hafner, A., 2011. 1D computational model of a two- Liu, F., Groll, E.A., Li, D., 2012b. Investigation on performance of
phase R744 ejector for expansion work recovery. Int. J. Therm. variable geometry ejectors for CO2 refrigeration cycles. Energy
Sci. 50, 2235e2247. 45, 829e839.
Banasiak, K., Hafner, A., Andresen, T., 2012. Experimental and Lucas, C., Koehler, J., 2012. Experimental investigation of the COP
numerical investigation of the influence of the two-phase improvement of a refrigeration cycle by use of an ejector. Int.
ejector geometry on the performance of the R744 heat pump. J. Refrigeration 35, 1595e1603.
Int. J. Refrigeration 35, 1617e1625. Nakagawa, M., Marasigan, A.R., Matsukawa, T., 2011a.
Banasiak, K., Hafner, A., 2013. Mathematical modelling of Experimental analysis on the effect of internal heat exchanger
supersonic two-phase R744 flows through converging- in transcritical CO2 refrigeration cycle with two-phase ejector.
diverging nozzles: the effects of phase transition models. Int. J. Refrigeration 34, 1577e1586.
Appl. Therm. Eng. 51, 635e643. Nakagawa, M., Marasigan, A.R., Matsukawa, T., Kurashina, A.,
Bilir Sag, N., Ersoy, H.K., Hepbasli, A., Halkaci, H.S., 2015. 2011b. Experimental investigation on the effect of mixing
Energetic and exergetic comparison of basic and ejector length on the performance of two-phase ejector for CO2
expander refrigeration systems operating under the same refrigeration cycle with and without heat exchanger. Int. J.
external conditions and cooling capacities. Energy Convers. Refrigeration 34, 1604e1613.
Manag. 90, 184e194. Sharma, V., Fricke, B., Bansal, P., 2014. Comparative analysis of
Bou Lawz Ksayer, E., 2007. Etude et conception de systemes a various CO2 configurations in supermarket refrigeration
efficacite energetique amelioree fonctionnant au CO2 comme systems. Int. J. Refrigeration 46, 86e99.
fluide frigorigene. PhD dissertation, Paris. Sokolov, M., Hershgal, D., 1990. Enhanced ejector refrigeration
Cecchinato, L., Corradi, M., Minetto, S., 2012. Energy performance cycles powered by low grade heat. Part 2 design procedures.
of supermarket refrigeration and air conditioning integrated Int. J. Refrigeration 13, 357e363.
systems working with natural refrigerants. Appl. Therm. Eng. Xu, X.X., Chen, G.M., Tang, L.M., Zhu, Z.J., 2012. Experimental
48, 378e391. investigation on performance of transcritical CO2 heat pump
Chen, X., Omer, S., Worall, M., Riffat, S., 2013. Recent system with ejector under optimum high-side pressure.
developments in ejector refrigeration technologies. Renew. Energy 44, 870e877.
Sustain. Energy Rev. 19, 629e651.