Você está na página 1de 32

ACO H a u s t e c h n i k

Installation
information

(Stamp)

0173.02.59 G
As per 07/2010

ACO Quatrix-K above ground pipes


DIN EN 13564 ACO Quatrix-K installation in the base plate
Contents
Chapter Page(s)

1 Product Identification
1.1 Addresses 3
1.2 EC Conformity declaration 4

2 General Notes
2.1 Field of application of installation, operating and maintenance manual 5
2.2 Use of backflow stops 5
2.3 General notes 5
2.4 Legal aspects 5
2.5 Safety notes 5-6
2.6 Type / Scope of supply 6
2.7 Application scopes / Function 6
2.8 Diagram of emergency seal 7

3 Installation
3.1 Installation site 7
3.2 Gradient 7
3.3 Installation in frost-proof pipes (without shaft system) 8
3.4 Installation in the base plate (with shaft system) 9-10
3.5 Motor fitting 11

4 Description of the Control 11-13

5 Electrical Installation / Works Settings 14-15

6 Commissioning 18

7 Operation 19

8 Servicing 19-20

9 Spare Parts / Accessories 21-22

10 Technical Data - Suggested Installations 23,24

11 Inspection Log Book 25-27

12 Maintenance Contract 28

13 Warranty 29

14 Service Partners 29

15 ACO subsidiaries 30,31

Caution!
This operating manual has to be handed out to the end user and to be kept in a safe place.
Maintenance works have to be recorded in the relevant inspection pages.

Subject to technical alterations


2
ACO Haustechnik
0173.02.59 G

1 Product identification

1.1 Addresses

Name and address of the manufacturer Name and address of the electrician

ACO Passavant GmbH _________________________


Postfach 11 62 _________________________
36267 Philippsthal _________________________
Ulsterstraße 3 _________________________
36269 Philippsthal After-sales service division After-sales service division
Tel. 0 66 20/ 77- 0 Service Tel. ++49 (0) 3 69 65 - 819 - 444 Tel. _____________________ __________________________
Fax 0 66 20/ 77- 52 Service Fax. ++49 (0) 3 69 65 - 819 - 367 Fax ____________________ __________________________

Name and address of the supplier Name and address of the plumber

_________________________ _________________________
_________________________ _________________________
_________________________ _________________________
_________________________ _________________________
After-sales service division After-sales service division
Tel. _____________________ __________________________ Tel. _____________________ __________________________
Fax ____________________ __________________________ Fax ____________________ __________________________

Subject to technical alterations


3
1.2 EC Conformity declaration

We, ACO Passavant GmbH, Ulsterstrasse 3, 36269 Philippsthal

hereby state under our sole responsibility that the designs of the following anti-flood protection systems, put in circulation by us, correspond to
DIN EN 13564-1:2002, Anti-flood Protection Systems for Buildings; as well as to the following EC Directives and DIN Standards:

Product designation:
Anti-flood Protection System Quatrix-K
Use: Anti-flood protection of buildings, for wastewater with and without faeces

Type 3 F Nominal width: Art. no.:


DN 100 620368, 620370
DN 125 620486, 620487
DN 150 620369, 620371

The housing is made of PP material, the cover is made of PA material.

The requirements for gas proofness, watertightness, efficiency, temperature stability, mechanic rigidity and durability are met.

Machinery Directive 89/392/ EEC in the version of 98/68/EEC


Building Products Directive 89/106/EEC in the version of 93/68/EEC
Low Voltage Directive 73/23/EEC in the version of 93/68 EEC
EMC Directive 2004/108/EG

CE Identification Directive System 4; see Directive 89/106/EEC (BPR), Attachment III.2(ii), 3rd option

Harmonised standards applied:


DIN EN 12056-1:2001-01
DIN EN 12056-2:2001-01
DIN EN 13564-2:2002
DIN EN 13564-3:2004
DIN 1986-100:2008-05
DIN EN 1451-1:1999
DIN EN 61000-6-2:2005
DIN EN 55011:2007

Competent documentary agent:


Marco Eulenstein
ACO Haustechnik
Im Gewerbepark 11 c
36457 Stadtlengsfeld

36269 Philippsthal, September 2008

ACO Passavant GmbH

Date, January 2009

R. Sand
General Manager

Subject to technical alterations


4
ACO Haustechnik
0173.02.59 G

2 General notes

2.1 Field of application of installation, operating and Supplements


maintenance manual The operator of the plant must supplement the operating manual
with instructions on existing national regulations for accident preven-
This manual is effective for the AC0 anti-flood protection system tion and environmental protection.
Quatrix-K. Besides the operating manual and the binding regulations for acci-
The manual is used for installation, commissioning, operation, main- dent prevention valid in the user country and at the point of use, the
tenance, repair and decommissioning. The operator must keep the approved expert regulations for safe and professional working have
manual at a safe place. to be observed.
Indications on possible standards, test signs, quality symbols and
trademarks are state-of-the-art at the printing date of this manual. Copyright
Deviations with illustrations, dimensions and weights are possible. ACO Passavant GmbH holds the copyright for these operating
We reserve the right to carry out amendments and improvements instructions. These operating instructions are written for the assem-
without prior notice to keep up with technical progress. bly, operating, maintenance and supervisory staff. They contain regu-
lations and technical drawings whose complete or partial reproduc-
Date of installation, operating and maintenance manual: tion, dissemination or use for competitive purposes, or passing on
06 February 2008 to others, is prohibited unless authorised in advance.

2.2 Use of backflow stops 2.4 Legal aspects

According to DIN 1986-100, para 7.4, drain points below the backflow Home owners and developers have to bear the costs of cellar flooding
level have to be protected against backflow from the sewers by automa- themselves in the event of sewer backflow because the local authorities
tic wastewater lifting plants with backflow loop as per DIN EN 12056-4 cannot be held liable for such damage. Owners are also liable to their
or, under certain conditions, by anti-flood protection systems as per tenants for any damage caused. The relevant standards therefore stipu-
DIN EN 13564-1. late that sanitary installations which are located beneath the backflow
level must be protected by lifting plants (active backflow prevention) or
The following criteria have to be met when fitting an anti-flood protec- by anti-flood protection systems (passive backflow prevention).
tion system: Although it is now possible to take out insurance against such damage,
The wastewater must be capable of draining away along a natural the insurance companies usually turn down any claims if building regula-
slope. tions have not been implemented or have been incorrectly observed.
There must only be a small number of users.
The drainage point(s) cannot be used during a backflow situation. The anti-flood protection system is a safety device and must thus be
Installation must be located in a room with inferior utilisation. permanently kept in operable condition. It must be easily accessible at
any time.

2.3 General notes

Safety-conscious working 2.5 Safety notes


These operating instructions contain fundamental information and pre-
cautionary notes. Please read the manual thoroughly prior to installation Prior to installation, the plant (flaps, body, electrical units
of unit, connection to power supply and commissioning. It is imperative etc.) has to be checked for transport damages. A da-
to comply with all other operation instructions referring to components maged unit may not be put into operation. In such a case,
of this plant. The mentioned safety notes, the pertinent national acci- please contact us immediately (refer to chapter 1.1).
dent prevention regulations as well as possible internal working-, opera-
tion and safety regulations of the user have to be observed. The safety If the installation and operating manual is infringed upon, damages to
notes which could lead to danger for people in the case of their non- property, personal injuries or fatal accidents cannot be excluded.
observance as well as in the case of warning of electric voltage, are
marked with the general safety marks. The plant may only be operated, maintained and commissioned by per-
sons who are familiar with the operating manual, the instructions con-
Safety (from: VDMA information sheet 24292) tained therein and the pertinent regulations for job safety and accident
This operation manual contains basic information which must be prevention.
observed during installation, operation and maintenance. Therefore,
this operation manual must be read by the fitter as well as the The ready assembly / electrical installation must be carried out by a
competent personnel / user prior to assembly and commissioning specialist contractor. This company must ensure that relevant DIN and
and must always be available at location of plant. VDE standards and directives (0100, 0113) as well as regulations of
local power supply utilities are observed and adhered to!

Subject to technical alterations


5
The control device must be fitted in such a way that all signals are noti- Prior to working at the control or at the water installations,
ced by the plant user. This ensures that in case of a closed valve, the isolate from mains electrical supply.
appliance drained via the anti-flood protection system is not used. The
manufacturer is not liable for self-inflicted backflow damages. In order to guarantee the operational reliability of the plant, it has to be
maintained as per DIN 1986-3. We recommend to take out a mainte-
nance contract with the plumber of your choice. Please note that during
a backflow or during a period where backflow is likely to occur, no
maintenance works may be carried out.

2.6 Type / Scope of supply

Quatrix-K (type 3F) Quatrix-K (type 3F)


for above ground pipes for installation in the base plate

Art. no. 620368 (DN 100) Art. no. 620370 (DN 100)
Art.-no. 620486 (DN 125) Art.-no. 620487 (DN 125)
Art. no. 620369 (DN 150) Art. no. 620371 (DN 150)

consisting of:
Body Body
+ Cover with sealing and emergency seal + Top section with sealing and cover
+ Six nuts with flat washers + Cover with sealing and emergency seal
+ Valve flap + Six nuts with flat washers
+ Emergency seal flap + Valve flap
+ Electrical kit (motor unit + control device) + Emergency seal flap
+ Electrical kit (motor unit + control device)

2.7 Application scopes / Function

The ACO automatic anti-flood protection system Quatrix-K type 3F cor-


responds to DIN 13564 and is intended for use with wastewater contai-
ning faeces.
The automatic anti-flood protection system is equipped with an automa-
tic valve and an emergency seal which is capable of being operated
manually. In the normal operation condition (fig. 1), both flaps are open.

Fig. 1
If in case of a backflow the sewers rise above permissible pipe filling
height, the pressure sensor sends a signal to the control device. The
control triggers the closing of the valve flap by means of an electric
motor. During backflow period, the connected drainage objects may not
be used. If backflow situation eases up, this is noticed by the control
and the flap is opened automatically. Backflow is signalled by a visual
and an audible signal (fig. 2). In the case of mains failure, an integrated
battery keeps up operational readiness up to 24 hours.
Fig . 2
The emergency seal serves as an additional safety. With the help of this
seal, the second flap can be manually locked (fig. 3). It is of essential
importance that the emergency seal is re-opened after e.g. return from
holidays.

Fig. 3

Subject to technical alterations


6
ACO Haustechnik
0173.02.59 G

2.8 Diagram of the emergency seal

1. Flap - open - 2. Flap - closed -

Click!

Fig. 4.1 Fig. 4.2


1. Flap - open -: 2. Flap - closed -:
Flap open (normal condition), water drains off, the valve closes Flap closed, water cannot drain off.
automatically in the case of backflow.

3 Installation

3.1 Installation site

Correct
Incorrect

Fig. 5 Fig. 6

Drainage objects lying above the backflow level (fig. 5) must not drain For this reason, all drainage objects fitted above the backflow level have
via a backflow safety valve. In this case, wastewater accumulating to be connected behind an anti-flood protection system (fig. 6). In the
above the backflow level could not be drained anymore in case of back- case of backflow, the downpipe fills up to road level at the most, the
flow. Because of the principle of communicating pipes, the wastewater anti-flood protection system prevents the wastewater from drawback in
would escape from the lowest drain points below the backflow level and lower drainage objects and it thus escapes via the manhole covers.
flood the cellar.

3.2 Gradient

The ACO cleaning pipes/anti-flood protection systems are excellently If the pipe gradient is not sufficient, the anti-flood protection system
suited for refurbishment as they only have a minimum proper gradient of must not be fitted with an inclination (counter gradient), as faults may
12 mm. The anti-flood protection systems must be fitted in the pipe occur.
gradient, the proper gradient is a result of the product construction.

CORRECT INCORRECT

Horizontal installation Installation with counter gradient

Subject to technical alterations


7
3.3 Installation in above ground pipes (without shaft system)

1. Fix body in local shaft or freely accessible e. g. at wall.

Caution!
Do not cast body into concrete.

2. Fit body in flow direction and align horizontally. Body may not be
installed tilted - neither to the side nor to the front or to the back Fig. 7
(fig. 8). The individual parts (flap, cover etc.) may not be soiled by
building materials and thus affected in their functioning.
close
open

3. The operating seal flap can be opened and closed manually by tur-
ning the construction period protection of the motor shaft (fig. 8).
Fig. 8

4. Connect pipes to anti-flood protection system as per relevant instal-


lation instructions (plastic, steel, cast iron or stoneware) (fig. 9).

Caution!
Drop in height 12 mm.

Fig. 9

5. If the pipe is laid along a wall, two pipe mountings have to be fitted
around the pipe shortly before and shortly behind the anti-flood pro-
tection system and to be fixed to the wall. For proper operation, the
emergency seal and the operating seal must be open (lever position
“1”)!

The emergency seal serves as additional safety. The second flap


can be locked manually with the help of it.
It must be observed that the emergency seal is re-opened, e. g.
Fig. 10
following vacation (fig. 10).

For detailed function of the emergency seal, refer to chapter 2.8,


fig. 4.

Subject to technical alterations


8
ACO Haustechnik
0173.02.59 G

3.4 Installation in the base plate (with shaft system)

1. Apply granular sub-grade course (e. g. sand) to ground.


Fit body in flow direction and align horizontally. Body may not be
installed tilted - neither to the side nor to the front or to the back
(fig. 11).

2. The individual parts (flap, cover etc.) may not be soiled by building
materials and thus affected in their functioning (fig. 8).
Fig. 11

3. Connect pipes to anti-flood protection system as per relevant instal-


lation instructions (plastic, steel, cast iron or stoneware) (fig. 12).
Caution!
Drop in height 12 mm

Fig. 12

4. Continue granular sub-grade course (e. g. sand) above pipe upper


edge (fig. 13).

Fig. 13

5. In case of need:
Fit sealing flange (art. no. 620382) against pressurised water to
intermediate section. In order to keep excess or shortage at a
minimum, the sealing flange can be fitted stepwise to the various
grooves (for height-adjustability of flange, refer to drawing on page
19).

Fig. 14

Subject to technical alterations


9
6. In case of need:
Fit extension piece (art. no. 620381) to body. Lip seal of body must
seat properly. In order to achieve a minimum coverage of the WU
concrete (impervious to water), the sealing flange (art. no. 620382)
can be fitted stepwise to the various grooves (fig. 15).

Fig. 15

7. For the control line and the supply line, a blank cable pipe DN 40
has to be fitted to top section (core bit diameter: 50 mm). Das The
blank cable duct has to be laid with a gradient to the backflow safe-
ty valve. Possible angles have to be carried out with elbows (elbows
<= 45°).
Fit top section to body and align to final height of finished floor level
as well as to tile pattern (fig. 16).

Fig. 16

8. Continue setting up the floor structure (fig. 17).

Fig. 17

9. Prior to laying of tiles, insert reversing plate


Insert O-ring in upper groove
Grease O-ring before inserting the reversing plate (fig. 18)
Reversing plate upper side: plastic cover (fig. 19)
Reversing plate underside: suitable for tile layer (see point 10)
Fill joint of top section and floor covering with permanently
elastic mass
The emergency seal for QUATRIX-K must be open to operate properly
(lever position 1). Fig. 18

10. In case of need:


Reversing plate (ABS) must be free of grease and very dry. Apply
tile adhesive which is suitable for plastic to reversing plate undersi-
de and fit floor tiles into cover. Tiles with a thickness up to 10 mm
can be used. The max. possible filling height (tile adhesive suitable
for plastic + tiles) is 15 mm (fig. 20).

Fig. 19

Fig. 20

Subject to technical alterations


10
ACO Haustechnik
0173.02.59 G

3.5 Motor fitting

1. Before motor is fitted, ensure that the valve flap is 90% open (manu- close
ally open flap completely one time, close with 3 turns to the right). open
For this, turn construction period protective cover (left for opening,
right for closing).

Fig. 21

2. Remove construction period protective cover for motor shaft. Insert


motor and bolt. In case of need, re-adjust position of motor shaft
with protective cover.

Fig. 22

3. Bolt the black pressure hose to the anti-flood protection system by


means of the rapid coupling piece (fig. 24).

Caution
Between automatic anti-flood protection system and control, the con-
trol hose must be laid ascending for the complete length, as otherwise
condensed water may affect its function. Fig. 23
Keep locking cap for maintenance/functional test.

4 Description of the control

Connection must be carried out by a specialist


contractor; VDE regulations (0100,0113) have
to be adhered to

The control is a separate component and is connected to the anti-flood


protection system via a connecting cable (fig. 24).
Dimensions of control box (W x H x D) 120 mm x 160 mm x 80 mm.

Schematic illustration of individual parts (fig. 25).


Fig. 24

Caution!
Correct intended use:
The switchgear may only be installed in dry and frostproof rooms.

Storage

Das The control must be stored at a frostproof place. Prior to


Fig. 25
commissioning, the control must be connected to the
power supply for 8 hours.

Subject to technical alterations


11
1. Displays and push-buttons (fig. 26)
The control is equipped with a display consisting of four light-emit-
ting diodes, an operation unit (two push-buttons) as well as an audi-
ble signal transmitter. The function of the light-emitting diodes and
push-buttons is explained in the following:

1.1 Green light-emitting diode:


Power status
The light-emitting diode indicates respective power status. In the
case of mains operation, the diode lights constantly. This is the nor-
mal condition. In the case of lapse of mains voltage, the control
automatically switches over to battery operation. This is signalled
by flashing of the diode.

1.2 Red upper light-emitting diode:


Backflow detection
Continuous lighting of the light-emitting diode signals backflow. If
there is no backflow, the light-emitting diode is off. Fig. 26

1.3 Yellow light-emitting diode: 1.5 System reset button


Valve status By pressing the push-button once, the audio alarm is cancelled in
The light-emitting diode signals the valve status. If the diode lights case of a fault. By pressing the push-button twice, the system is
continuously, the valve is closed. A flashing light indicates that valve reset (the vave is opened and moves to initial position).
is moving. Normally, however, this light-emitting diode is off.
1.6 Test button
1.4 Red lower light-emitting diode: By pressing the push-button once, the valve is closed. Pressing
Fault diagnosis twice re-opens the valve.
If the ACO QUATRIX-K anti-flood protection system has a motor
fault, the diode indicates this condition by lighting continuously. In 1.7 Audible signal transmitter
case of battery fault, the diode is flashing. The control is equipped with an audible signal transmitter. If the
valve is closed, an audible signal sounds (continuous tone). In the
case of faults (motor/battery), an intermittent tone sounds. By
pressing the system reset button once, the audible signal is swit-
ched off.

1.8 Display matrix


The following table shows the various possible control displays:

Diode (1) Diode (2) Diode (3) Diode (4) Audible Control condition Measures
green red yellow red signal

- - - - - Control off: Connect control to power supply


no backflow monitoring
on - - - - Automatic operation -
(mains operation)
blinks - - - - Automatic operation Connect control to power supply
(battey operation)
on on on - on Mains operation; backflow: Wait for termination of backflow
valve closed
on on on on interval Mains operation; backflow: Close manual seal until
motor fault at the same time termination of backflow
on - on - on Operational test in mains operation: Stop operational test by pres-
valve closed sing push-button (6)
on - - blinks interval Battery fault See below (point 1)
slowly

Subject to technical alterations


12
ACO Haustechnik
0173.02.59 G

2. Battery
2.1. Behaviour in case of battery fault 3.4 Battery warning
Establish mains connection and wait. Battery faults always occur With every run of the flap, the battery is checked. In case of a low bat-
with insufficient charging condition of the battery or with a dama- tery capacity, a warning signal is given (LED 4 flashes slowly). In this
ged battery fuse. case, the buzzer is not switched on. If this signal appears, the battery
should be exchanged promptly for safety reasons.
2.2 Motor fault in mains / battery operation
Check motor fuse and supply or connecting cable for damages. If Caution!
required, start initialisation by double-pressing button (5). Check Even in the case of mains operation, function of the control is guaran-
motor spindle by de-assembling the housing cover (spindle break). teed only with a fully functional battery. The control must not be opera-
In this case, contact fitter / specialist contractor. ted without battery!

The control is equipped with a battery which ensures operation for 3.5 Decommissioning
at least 24 hours in case of a mains failure. After 24 hours, an In battery operation, the device can be switched off manually. For this,
empty battery has again attained 90 % of its capacity. both buttons must be pressed at the same time for approx. 5 seconds.
As an acknowledgement, all LEDs light up, then the control is switched
Caution! off. The battery hence remains loaded.
Batteries are subject to a natural ageing. In this case, the battery has to If the appliance is separated from the mains, it switches to battery ope-
be exchanged (original type from manufacturer). ration until same is unloaded and appliance switches off completely.
The manufacturer recommends to exchange the battery prophylactically
after 5 years.

A battery exchange may only be carried out by


an electrician. Prior to opening the housing,
isolate from mains electrical supply.

3. Fuses
3.1 Fuses
A microfuse is fitted to the circuit board to protect the micro-elec-
tronics of the control effectively against connection faults and occu-
ring faults.

Battery fuse
Fuse 1 protects the control against reverse polarity of the battery. If the
fuse responds, cabling has to be checked and a new fuse has to be
inserted.

3.2 Fuse values


Fuse Value Behaviour
Battery fuse 2.5 A slow-blowing

The anti-flood protection system does not have any mains fuse in the
form of a safety fuse. One fuse is integrated in the primary circuit of
the mains transformer in the form of a thermal switch. In case of an
electronics defect, this switch opens after a short period when reaching
a temperature of 120°C. In this happens, the control is seriously dama-
ged. It must be handed on to the fitter / specialist contractor for repair.

3.3 Automatic self-test


Every 4 weeks, the control carries out a self-test. The motor is started
and stopped for some seconds to avoid the seizing of the drive. The
battery is checked at the same time and a fault signal is given, where
applicable.

Subject to technical alterations


13
ACO Haustechnik
0173.02.59 G

5 Electrical installation / Works settings

Connection must be carried out by a specia-


list contractor; VDE regulations (0100,0113)
must be adhered to

1. Fit the control at the intended location. The control housing has to be
fixed with 2 bolts. In accordance with VDE regulation 0100, the control
is splash water and dripping water proof (IP 56) (fig. 27).

Caution!
The control device must be fitted in such a way that all signals are noti-
ced by the plant user. This ensures that in case of a closed valve the
appliance drained via the anti-flood protection system is not used. The
manufacturer is not liable for self-inflicted backflow damages.

Prior to working at the control or at the


water installation, isolate from mains elec-
trical supply!
Fig. 27

2. Cabling

2.1 Mains connection:


When supplied, the mains connection (safety plug, 230 V, fuse min.
B 10) is already connected to the control unit (fig. 28.1).

2.2 Control hose:


By means of the rapid connector, the control hose must be connec-
ted to the cover of the anti-flood protection system and the control
box (fig. 28.2).
Caution!
Fig. 28.1 Fig. 28.2
Between automatic anti-flood protection system and control, the control
hose must be laid ascending for the complete length, as otherwise con-
densed water may affect its function.

2.3 Supply cable:


The motor supply cable is connected to the motor at the works.
This supply cable must be connected to the control box by means
of the electric push-fit connection. The electrical push-fit connec-
tion corresonds to protection grade IP 67 (fig. 28.3).
Important!
The cables and hose screw-joints, firmly bolted at the works, may not be
disconnected. This would affect flood-protection.
Fig. 28.3

2.4 Fault transmitter contacts


As a standard feature, the control is equipped with a potential-free
output with which further audible or visual signals can be connected
optionally.
The contact acts as two-way contact.

Subject to technical alterations


14
ACO Haustechnik
0173.02.59 G

2.5 Battery connection: The fault transmitter contact closes in case


The battery is already connected. If a battery exchange is required, this Batt. Cable Terminal strip of a fault signal. During configuration of the
contacts care has to be taken that a max.
may only be carried out by an electrician. The battery has two connec- (+) red battery (+) current of 500 mA is not exceeded. In addi-
tions which may not be mixed up! (-) black battery (-) tion, only pure Ohm resistive loads may be
connected. Signalling devices, PCs, tele-
phones and alarm devices can be connected
2.6 Extension set: to the contacts.
If the supplied cables and hoses are too short (standard length
5 m), the cable extension set (10 m), art. no. 620438, can be
ordered. However, a total length of 15 m should not be excee-
ded as otherwise functionality can no longer be guaranteed.

2.7 Switch-on process: Prior to wor-


The ACO QUATRIX-K automatic anti-flood protection system must king at the
be carried over in a definite condition by the control unit. This control or at
is achieved by the switch-on process (insert mains connection). the water connection,
An initialisation is always carried out (fig. 29) isolate from mains elec-
 when the control is switched on from a currentless condition trical supply!
 by double-pressing the system reset button.

Initialisation is done in such a way that the valve is completely


closed at first and then re-opened. When reaching the open posi-
tion, initialisation is finished and control passes into automatic
Fig. 29
operation (green diode lights).

2.9 Resetting the control


Isolate from mains electrical supply. By pressing the system
reset button and the control button at the same time for 5
seconds, the control appliance is reset to works settings, i. e.
is carried over in the currentless condition.

If both buttons are operated at the same time for 5 seconds, all
light-emitting diodes flash simultaneously before the appliance swit-
ches off.

Subject to technical alterations


15
6 Commissioning

1. Commissioning
Commissioning can be compared to the switching on process. If the
green diode lights up after initialisation was completed, commissio-
ning is completed (fig. 30).

Fig. 30

2. Operational check
Control, operating seal flap and emergency seal flap have to be
checked for tightness and function.

2.1 Mechanical check (fig. 31)


 Operate the test button, let operating seal open and close (refer
to arrowhead in fig. 30).
 Switch box: yellow diode flashes during closing and opening
process
 Switch box: yellow diode lights if operating seal is closed

 Opening and closing the emergency seal (page 7, para 2.8). Fig. 31

2.2. Operational check backflow detection

 Close emergency seal (page 7, para 2.8).

Fig. 32

 Remove black pressure hose from hose coupling at cover and insert
locking cap (fig. 33). Tighen spigot nut.

Fig. 33

 Immerge pressure hose into water app. 150 mm (vial or similar) and
fix.
 Switch box:
 red diode lights in the case of a backflow detection.
 Operating seal flap closes automatically with a 3 second delay,
 yellow diode flashes during closing process
 yellow diode lights if operting seal flap is closed
 Warning signal (continuous tone) sounds (can be switched off
by pressing the release button once). Fig. 34

If backflow detection was carried out properly and all flap are closed,
tightness test can be continued.
Caution!
Pressure hose remains furthermore in water bottle!

Subject to technical alterations


16
ACO Haustechnik
0173.02.59 G

2.3 Tightness test

 Remove locking bolt from test connection and insert test funnel.

Fig. 35

 Fill with clear water up to upper edge of test pipe (100 mm).

Fig. 36

Observe water level for 10 minutes. If filling level drops, replenish with
clear water until a water level of 100 mm is again reached. Note down
re-plenished water quantity.

Fig. 37

If less than 500 cm3 water must be replenished within 10 minutes, the
tightness test is passed.
Remove test funnel, re-insert test screws, open emergency seal.

Fig. 38

If more than 500 cm3 water have to be replenished within 10 minutes,


the flap seals and flaps have to be checked again and to be renewed, if
applicable.
Then, carry out another tightness test.

Fig. 39

 Take pressure hose out of water.


 Switch box:
 The red diode goes out.
 After a 30 seconds delay, the operating seal flap opens automati-
cally.
 The yellow diode flashes during the opening process.
 The yellow diode goes out as soon as the operating seal flap is
completely open.

Fig. 40

Subject to technical alterations


17
 Shake pressure hose several times and connect airtightly to hose
coupling at cover.

Fig. 41

 Remove test pipe and insert test screw.

Fig. 42

 Open the emergency seal.

Fig. 43

 The Quatrix-K is again ready for operation.

Subject to technical alterations


18
ACO Haustechnik
0173.02.59 G

7 Operation

1. Caution!
After initial connection and depending on loading condition of bat-
tery, entire operational capability is reached only after 24 hours of
mains operation.

2. Behaviour in the case of battery fault


Establish mains connection and wait. Battery faults always occur
with insufficient charging condition of the battery or with a damaged
battery fuse.

3. Behaviour in the case of motor fault


Check motor fuse and supply or connecting cable for damages. If
required, start initialisation by double-pressing button (5). Check
motor spindle by de-assembling the housing cover (spindle break).
In this case, contact fitter / specialist contractor.

8 Servicing
Caution!
No warranty claims accepted in the case of insufficient servicing!
The anti-flood protection system must be visually checked once a
month by the operator or an authorised person. For this, the valve flap
is opened and closed by pressing the test button. In addition, the emer-
gency seal lever is closed and re-opened several times manually.

At the end, both flaps must be open.

The anti-flood protection system must be serviced at least twice a year


by a specialist contractor. During servicing, no wastewater must be fed
to the anti-flood protection system.

Following actions have to be carried out:

Caution!
Close valve and emergency seal before cover is removed.
Valve flap: press test button once.
Emergency seal flap: position 3 (para 2.8 on page 7).

Fig. 44

Loosen six cap nuts and remove cover care- fully.


Remove valve flap and emergency seal flap.

Fig. 45

Subject to technical alterations


19
Check and clean cover seal and backflow flap seal and exchange, if
required. Rinse body.

Fig. 46

Re-insert valve flap and emergency seal flap in body; observe seating of
seals. Aligh lever for emergency seal vertivally so that lever can slide in
guide (detail “X”).

Fig. 47
X

Refit cover onto body. Tighten cap nuts screw joints in mentioned order
(tightening torque 5 - 8 Nm). 4
2
6

3
1
5

Fig. 48

After servicing is finished, press the test button and the valve flap re-
opens. Then, the control has to be initialised anew. For this, isolate from
mains electrical supply and follow the instructions under para 2.9 (reset-
ting of control).

Then, carry out operational check as per para 6.2.

Subject to technical alterations


20
ACO Haustechnik
0173.02.59 G

9 Spare parts / Accessories

Product Illustration Art. no.

ACO control device 620376


for automatic anti-flood protection system
Quatrix-K type 3F. DN 100/DN 150.

Extension kit (10 m) 620438


consisting of pressure hose, supply cable and
plug

ACO drive motor with 5 metres supply line 620377


for automatic anti-flood protection system
Quatrix-K type 3F. DN 100/DN 150.

ACO valve flap with insertion element for auto- 620374


matic anti-flood protection system
Quatrix-K type 3F. DN 100/DN 150.

ACO emergency seal flap with insertion element 620375


for automatic anti-flood protection system
Quatrix-K type 3F. DN 100/DN 150.

ACO extension element with lip seal, suitable 620381


for automatic anti-flood protection system
Quatrix-K type 3F with shaft system.
Height: 100 mm

ACO sealing flange, suitable for automatic anti- 620382


flood protection system Quatrix-K type 3F with
shaft system.

ACO top section, suitable for automatic anti- 620383


flood protection system Quatrix-K type 3F with
shaft system.

ACO cover reversing plate, surface-watertight,


suitable for automatic anti-flood protection 620384
system Quatrix-K type 3F with shaft system.

ACO test pipe, suitable for automatic anti-flood


protection system Quatrix-K type 3F with shaft 6010.00.15
system.

ACO Alarm Module NA-1.2 self-loading for 0150.26.73


assembly outside the Ex-area, with audible and
visual fault signal, with potential-free contact

Sealing for housing cover 620454


Triplex-K/Quatrix-K

Subject to technical alterations


21
Extension elements for recessed installation
If an anti-flood protection system must be installed recessed to a large
extent because of structural conditions, the shaft systems of the ACO
anti-flood protection systems can be retrofitted without problems with
optionally available extension pieces for recessed installation. In case of
need, max. 2 extension elements can be put together with just a few
turns.

Fig. 45

Sealing flange for pressurised water


If the base plate must be protected against pressurised water, the shaft
system can be equipped optionally with a sealing flange. This flange reli-
ably protects the cellar against moisture from the ground. Chief attrac-
tion: The flange is stepwise height-adjustable and thus makes perfect
adaptation to local base plate level possible.

Fig. 46

Adaptation to tile pattern and floor level


The top section for load class K3 is continuously height-adjustable and
inclinable. The position of the cover can thus be adapted to floor height
and tile pattern. A specially adjusted locking system in addition prevents
small children from removing the cover.

Fig. 47

Multi option cover for customer-specific requirements


Both sides of the cover can be used ad libitum. The massive side is a
plastic cover. If, however, the cover is to form an optical unity with the
locally fitted tiles, the cover can be turned over and the tiles can be fitted.

Fig. 48

Subject to technical alterations


22
ACO Haustechnik
0173.02.59 G

10 Technical data / Suggested installations

10.1 Technical data

Quatrix-K for installation in above ground pipe

405

12

205
DN
DN
H1

250
400
L

Art. no. DN ∅ (mm) L (mm) H1 (mm)

620368 100 110 460 79


620486 125 125 469 86
620369 150 160 504 104

Quatrix-K with shaft system for installation in the base plate


30

20

Hmax. 512
Hmin. 460
20
H2
12
DN
H1

DN
6

360 x 300

Art. no. DN ∅ (mm) L (mm) H1 (mm) H2 (mm)

620370 100 110 460 79 217


620487 125 125 469 86 210
620371 150 160 504 104 192

Subject to technical alterations


23
10.2 Suggested installations

Quatrix-K for installation in above ground pipe

Control

Control line

ACO automatic anti-flood protection


system QUATRIX-K, DN 150
Tiles for above ground pipes

Base plate

Ground

Quatrix-K with shaft system for installation in the base plate

Control

Mains connection

Tiles
Control line
Tile adhesive
Empty conduit DN 40, to be
Screed laid at a gradient to anti-flood
protection system (angles have
Thermal insulation
to be carried out with 2 elbows
Excess or 45°)
shortage
min. 40 mm ACO sealing flange
460 - 510

Floor above ground


(concrete impervious to
water = WU)
(thickness as per
specification)
ACO automatic anti-flood protection
system Quatrix-K, DN 150 with tele-
scopically adjustable top section and
cover plate K3

Granular sub-grade course


(e. g. sand)

Ground

Subject to technical alterations


24
ACO Haustechnik
0173.02.59 G

11 Inspection log book

Date Works carried out Carried out by:

Subject to technical alterations


25
ACO Haustechnik
0173.02.59 G

Date Works carried out Carried out by:

Subject to technical alterations


26
ACO Haustechnik
0173.02.59 G

Date Works carried out Carried out by:

Subject to technical alterations


27
12 Maintenance contract

A maintenance contract covering regular maintenance is closed between the following undersigned parties.

Ordering party: Consignee:

Beginning of contract:

Product description:

Scope of supply: According to DIN EN 13564, anti-flood protection systems should be serviced twice a year by specialist per-
sonnel. During such servicing, all fittings have to be cleaned, moveability of backflow insert has to be checked
and defective parts, if any, must be exchanged (at extra charge and working time).

Dates: Appointment is suggested by consignee. If in a special case, the consignee cannot keep this maintenance
date agreed upon, this does not result in any right to claim by the ordering party. However, the ordering party
must be informed about this deadline shift by the consignee.

Contract duration: This maintenance contract is closed for an indefinite time. It is prolonged by each one year if it not terminated
in writing three months prior to year’s end.

Duties of the ordering party: For proper maintenance, the ordering party ensures accessibility of product and will not accept any delay in
carrying out the works.

Costs: For each half-yearly maintenance, the consignee charges an amount of ______ (plus VAT).
Invoice is issued after maintenance works were carried out. Spare parts possible required are charged extra.

Ordering party: Consignee:

(Date / Stamp / Signature / Town) (Date / Signature / Town)

Subject to technical alterations


28
ACO Haustechnik
0173.02.59 G

13 Excerpt from the Sales Terms and Delivery Conditions ACO Passavant GmbH

1. General
2. Price and payment
3. Time of delivery, delivery delays
4. Dispatch, transfer of risk, acceptance
5. Retention of title
6. Warranty

Supplier shall be liable for property damage and deficiency in title with immediately.
any further claims excluded, with the reservation of paragraph 7 and 3. Repair and/or replacement costs to be borne by Supplier – as far as
irrespective of sections 478, 479 German Civil Code as specified the objection is justified – shall include costs for the replaced part inclu-
hereinafter: ding inland shipping costs as well as reasonable costs for removal and
installation, and furthermore, if reasonably demandable in the individual
1. Any and all of those parts included in the delivery, that after delivery case, costs for possible provision of its fitters and assistants.
turn out to be unusable or not irrelevantly impaired in their serviceability,
the cause of which lies prior to passage of risk, shall be repaired or 4. In particular, no warranty shall be granted in the following cases:
supplied again at no cost for Purchaser. Supplier may choose between Unsuitable or improper use, faulty assembly and/or putting into opera-
repair and substitute delivery. Purchaser shall be entitled to reduction of tion by Purchaser or any third party, natural wear and tear, faulty or
the purchase price or withdrawal from contract after the second unsuc- negligent usage, improper maintenance1, unsuitable operating means,
cessful attempt of repair or replacement or should repair or replace- defective construction works, unsuitable construction ground, chemical,
ment be unacceptable. For the rest, Supplier shall be liable for damages electrochemical or electrical impacts – as far as such impacts are not
only in the scope of the following section 7. Supplier shall be informed due to Supplier's intention or negligence.
immediately of detected defects. Irrespective of the statutory mer-
chants' requirement of examination and requirement to give notice of 5. Supplier shall not be responsible for consequences resulting from
defects, written notice of evident defects shall be given to Supplier not Purchaser's or any third Party's improper repairs. This provision shall
later than 14 days upon delivery, otherwise the warranty shall cease. apply also to alterations made to the object of delivery without Supp-
Replaced parts shall become Supplier's property. lier's prior consent.

2. Upon consultation with Supplier, Purchaser shall grant Supplier suffi- 6. The claims as fixed under section 6 – except of those resulting from
cient time and opportunity for performing repairs and replacements con- section 478, 479, 438 subsection 1 no. 2, 634a subsection 1 no. 2
sidered necessary by Supplier, otherwise Supplier shall be released German Civil Code – shall expire by limitation one year after delivery.
from liability for consequential damages. Purchaser shall be entitled to
repair the defect himself or to having the defect repaired by any third
party and to demand reimbursement of incurred costs from Supplier
only in urgent cases of risk of improper operational safety and/or for
preventing unreasonably large damage or should Supplier be in default
with the elimination of defect. In such cases, Supplier shall be informed

1 In order to guarantee proper operation of the anti-flood protection system, all chapter „Inspection and Maintenance“. As maintenance works have to be carried
anti-flood protection systems should be serviced every 6 months. If no servicing out by properly qualified technician twice a year, the closing of a maintenance
is carried out as per DIN EN 13564-1 regulations, the warranty claim expires. contract covering the complete drainage plant is strongly recommended.
For detailed information on DIN EN 13564-1 regulations, please refer to the

7. Liability of supplier for compensation


8. Excluding a redemption
9. Use of software
10. Applicable law, jurisdiction

For complete Sales Terms and Delivery Conditions of ACO Passavant


GmbH, please refer to:
www.aco-haustechnik.de/unternehmen

14 Service partners

For more details on our service partners, please refer to:


www.aco-haustechnik.de/servicepartner

Subject to technical alterations


29
15 ACO subsidiaries

Germany Bulgaria France


ACO Passavant GmbH ACO Building Elements LTD ACO Produits Polymères S.A.
Ulsterstraße 3 119, "Iliyanci" BLVD. "Le quai à bois", B.P. 85
36269 Philippsthal BG- 1220 Sofia F - 27940 Notre Dame de l'Isle
Telephone 0049 6620 / 77 - 0 Tel. / Fax 00359/28 31 00 57 Telephone 0033/2 3251 3055
Telefax 0049 6620 / 77 - 52 Tel. / Fax 00359/28 32 40 53 Telefax 0033/2 3251 5082
E-mail info.ph@aco-online.de E-mail office@aco.bg E-mail contact@aco.tm.fr
Internet: www.aco-haustechnik.de Internet www.aco.bg Internet www.acofrance.com

Greece
Albania Czech Republic ACO Domikes Lyseis Poiotitas A.E.
ACO Elemente Ndërtimi shpk ACO Industries k.s. 13 Lavriou Avenue
Rr. Durrësit, Kulla e Pazarit Nr. 2 Havlickova 260 153 51 Kantza Pallini
AL - Tiranë CZ - 582 22 Pribyslav GR - Athens
Telephone 00355 / 4 222 849 Telephone 00420/569 491 202 Telephone 0030/210 604 2557
Telefax 00355 / 4 224 247 Telefax 00420/569 482 529 Telefax 0030/210 604 2581
E-mail info@acoalbania.com
Internet: www.acoalbania.com ACO Stavební prvky spol. s.r.o. Hungary
Havlickova 260 ACO Magyarország Bt.
CZ - 582 22 Pribyslav Jászberényi út 38-72

Austria Telephone 00420 / 569 491 234 A épület II. emelet


ACO Passavant GmbH Telefax 00420 / 569 482 533 H - 1106 Budapest
Gewerbestraße 14-20 E-mail aco@aco.cz Telephone 0036/1 260 98 82
A-2500 Baden Internet www.aco.cz Telefax 0036/1 260 70 52
Telephone +43 2252 22420 0 E-mail acohu@aco.hu
Telefax +43 2252 22420 30 ACO Passavant Internet www.aco.hu
E-mail info@aco-passavant.at Concrete Seperators s.r.o.
Internet www.aco-passavant.at Hybesova 549 Italy
CZ - 391 81 Veseli nad Luznici ACO Passavant S.p.A.
Telephone 00420/381 582 924 Via Lazio, 2
Belgium Telefax 00420/381 582 925 I - 40060 Osteria Grande (Bologna)
ACO Passavant NV / SA E-mail passavant@aco.cz Italy
Preenakker 6 Telephone 0039/051 946007
1785 Merchtem Denmark Telefax 0039/051 946054
Telephone + 32/52 38 17 70 ACO Plastmo A/S E-mail aco@aco.it
Telefax + 32/52 38 17 71 P.O. Box 259 / Thorsvej 9 Internet www.aco.it
E-mail aco@aco.be DK - 4100 Ringsted
Internet www.aco.be Telephone 0045/576 666 66 Latvia
Telefax 0045/576 666 67 ACO Plastmo Baltic SIA
E-mail aco-plastmo@aco-plastmo.dk Liliju 20, Marupes pag.
Bosnia Herzegowina Internet www.plastmo.dk LV-2167
ACO d.o.o. Telephone 00371/737 7927
Ismeta Alajbegovica Serbe br. 12 Estonia Telefax 00371/782 8430
BiH - 71000 Sarajevo ACO Plastmo A/S Branch office E-mail info@aco-plastmo.lv
Telephone +387 (0) 33 768 910 Laki tn 14A-603 Internet www.plastmo.lv
Telefax +387 (0) 33 768 911 EST - 10621 Tallinn
E-mail aco@aco.ba Telephone + 372 / 6 88 94 39
Internet www.aco.ba Telefax + 372 / 6 88 94 39
E-mail rp@aco.ee
Internet www.aco.ee

Croatia Finland Lithuania


ACO Gradevinski elementi d.o.o. ACO Plastmo Oy ACO PLASTMO A/S
Radnicka cesta 177 Lemminkäisenkatu 46 Lukiskiu 5
HR-10000 Zagreb FIN - 20520 Turku LT-01108 Vilnius
Telephone 00385/1 2700 140 Telephone 00358/225 345 34 Telephone 00370/521 248 98
Telefax 00385/1 2700 141 Telefax 00358/225 344 04 Telefax 00370/521 509 64
E-mail aco@aco.hr E-mail plastmo@plastmo.fi E-mail aco@aco-plastmo.lt
Internet www.aco.hr Internet www.aco-drain.com Internet www.aco.lt

Netherlands Slovakia Ukraine


ACO B.V. ACO Stavebné prvky s. r.o. ACO Building Elements Ltd.
Edisonstraat 36, Stará Vajnorská 37 18/14, Vikentiya Khvoyki str.
NL-7006 RD Doetinchem SK - 83104 Bratislava Business-Center Ost West Express
Telephone +31(0)314-36 82 80 Telephone 00421 / 244 453 651 office 227
Telefax +31(0314-36 82 90 Telefax 00421 / 249 224 145 UA-Kiev, 04080
E-mail info@aco.nl E-mail aco@aco.sk Telephone 00380/442 306 037
Internet www.aco.nl Internet www.aco.sk Telefax 00380/442 306 037
E-mail info@aco.com.ua
Internet www.aco.com.ua
Norway Slovenia

Subject to technical alterations


30
ACO Haustechnik
0173.02.59 G

Internet www.aco.com.ua
Norway Slovenia
Plastmo A/S ACO gradbeni elementi,
Eternittveien 30 zastopanje, d.o.o. United Kingdom
N - 3470 Slemmestad Obrtnika ul. 9 ACO Technologies plc
Telephone 00 47/66 98 74 50 SI-3240 Smarje pri Jelsah Hitchin Road
Telefax 00 47/66 98 74 51 UK - Shefford, Beds. SG17 5TE
E-mail plastmo@plastmo.no Telephone 00386/381 718 80 Telephone 0044/1462 816666
Internet www.plastmo.no Telefax 00386/381 718 82 Telefax 0044/1462 815895
E-mail aco.doo@siol.net E-mail technologies@aco.co.uk
Poland Internet www.aco.si Internet www.aco.co.uk
ACO Elementy Budowlane Sp. z o.o.
ul. Fabryczna 5, Lajski Spain / South America Australia / New Zealand
PL - 05 119 Legionowo ACO Productos Polímeros, S.A. ACO Polycrete Pty Ltd
Telephone 0048/22 767 05 00 Polígono Industrial Puigtió 134 - 140 Old Bathurst Road
Telefax 0048/22 767 05 13 Apartado de Correos 84 EMU Plains
E-mail info@aco.pl E - 17412 Maçanet de la Selva NSW 2750
Internet www.aco.pl Telephone 0034/972 859 300 Telephone 0061/2 47 47 40 00
Telefax 0034/972 859 436 Telefax 0061/2 47 47 40 60
E-mail aco@aco.es E-mail sales@acoaus.com.au
Internet www.aco.es Internet www.acoaus.com.au

China
ACO Trading (Shanghai) Co., Ltd.

Portugal Sweden Shanghai office (headquarter)


Lusitana ACO ACO Plastmo AB Room 407 Jin Zhong Building
Elementos de Construção, Lda. Division ACO Drain Civil Works No. 680 Zhao Jia Bang Road
Av. Afonso Henriques, 1196, sala 1104 - 1106 Laxfiskevägen 8 200031 Shanghai
P - 4450-012 Matosinhos SE - 433 38 Partille The People´s Republic of China
Telephone 00351/22 938 2615 Telephone 0046/31 340 02 40 Telephone 0086 / 216 415 352 1
Telefax 00351/22 938 0189 Telefax 0046/31 340 02 49 Telefax 0086 / 216 415 802 2
E-mail rrebelo@aco.pt E-mail info@acodrain.se E-mail info@aco-online.cn
Internet www.aco.pt
Division ACO TTM Building Drainage Beijing office (branch)
Box 709 Room 918, China International Science and
Slöjdargatan Technology Convention Center
SE - 391 27 Kalmar No. 12 Yumin Road, Chaoyang District
Telephone 0046/480 417 750 100029 Beijing
Telefax 0046/480 417 759 The People's Republic of China

Telephone 0086 / 108 225 032 1


Telefax 0086 / 108 225 032 0
Romania
ACO SRL Canada
Sos. Bucuresti-Urziceni nr. 31, ACO Systems Ltd .
ROM-077010 Afumati, jud.Ilfov 6045 Kestrel Road (PO Box 77280)
Telephone 0040/213 513 053 RPO Courtney Park, Mississauga, ON L5T 1Y8
Telefax 0040/213 513 055 Telephone 001/905 564 873 3 Switzerland
E-mail aco@aco.ro Telefax 001/905 564 923 3 ACO Passavant AG
Internet www.aco.ro E-mail dfilip@aco-online.com Industrie Kleinzaun
Postfach 197
Russia Sales Office Eastern Canada CH-8754 Netstal
ACO Ltd. ACO Polymer Products, Inc. Telephone 0041/ 55 645 53 00
2-nd Kotlyakovsky per., vladenie 18 29 Parkhaven Crescent Telefax 0041/ 55 645 53 12
RUS - 115201 Moscow St. Marys, Ontario E-mail aco@aco.ch
Telephone 007/495 323 430 4 Canada N4X 1E7 Internet www.aco.ch
Telefax 007/495 323 443 4
Telephone 001/519 284 3075
Telefax 001/519 284 2141 Turkey
Serbia & Montenegro E-mail kconquergood@aco-online.com ACO Yapi Malzemeleri Sanayi
ACO gradjevinski elementi d.o.o. ve Ticaret Ltd. Sti
Mala pruga 39a Sales Office Western Canada Koresehitleri CAD. No 11/ 1
11080 Beograd, Zemun ACO Polymer Products, Inc. 34394 Zincirlikuyu
Telephone 00381/11 3777 791 10 Citadel Estates Heights, NW TR - Istanbul
Telefax 00381/11 3777 794 Calgary, AB T3G 5E4 Telephone 0090/212 347 52 54
E-mail office@aco.co.yu Canada Fax 0090/212 347 52 57
Internet www.aco.co.yu E-mail info@acoturkiye.com
Telephone 001/403 698 120 8 Internet www.acoturkiye.com
Telefax 001/403 698 120 8
E-mail jlow@aco-online.com

USA U.A.E.
ACO Polymer Products, Inc. India ACO Systems FZE
12080 Ravenna Road, P.O. Box 245 ACO Systems and Solutions Pvt. Ltd. JAFZA / L.O.B. 17 # 101
USA - Chardon, Ohio 44024 Unit No:19/2, 1st Floor, Fathima Towers, P.O. Box: 18672
Telephone 001/440 285 7000 No.19, Rhenius Street, Langford Town, UAE - Dubai
Telefax 001/440 285 7005 Bangalore – 560025 Telephone 00971/4 88 737 13
E-mail info@acousa.com Telephone 0091 / 8022485487 / 22485488 Telefax 00971/4 88 737 14
Internet http://www.acousa.com/ Telefax 0091 / 8022485491 Internet www.acosystems.ae
E-mail acoindia@acosystems.in
Internet: www.acosystems.in

Subject to technical alterations


31
0173.02.59 G
As per: 07/2010
Origin: German manual

HT 511L  As per: 07/2010  LTC - Subject no. 0173.02.59 G


Origin: German manual  Subject to technical alterations!

ACO Passavant GmbH


Im Gewerbepark 11c
36457 Stadtlengsfeld
Tel. ++49 (0) 36965 819–0
Fax ++49 (0) 36965 819–361
www.aco-haustechnik.de

The ACO Group. A strong family you can build on.

Você também pode gostar