Você está na página 1de 1

4.

2 LIGHT LOSS TO BE RECOVERED L+W


5.1.3 CEILING CAVITY RATIO = 5hCC LW
LBO = 100 %
5(0) 12+ 21
LLD = 84 % =
12(21)
LDD = 97.16 %
=0m
RSDD = 97 % RSDD = ?
By interpolation:
LDD =e -At^b
-(0.068)(0.25)^(0.62)
=e RCR RSDD
= 0.9716 2 0.98
2.166715 x
LDT = Luminaire Distribution Type
3 0.98
%EDD = @ 3 months cleaning frequency; clean
-At^b
%EDD = 100(1-e )
RSDD = x = 0.98
%EDD = 100( 1- e -(0.068)(0.25)^(0.62) )
%EDD = 2.8379 %
5.2 EFFECTIVE CEILING CAVITY REFLECTANCES ( pcc )
CCR = 0, pw = 50 %, pcc = 80 %
5. CALCULATIONS
5.3 EFFECTIVE FLOOR CAVITY REFLECTANCES ( pfc )
5.1 CAVITY RATIOS
FCR = 3 m, pf = 30 %, pw = 50 %
5.1.1 ROOM CAVITY RATIO = 5h RC LLW
+W

5(2.5) 8+ 20.688
= 8(20.688)
By interpolation:
= 2.166715 m
FCR pfc
1.3 26
5.1.2 FLOOR CAVITY RATIO = 5hFC LLW
+W
1.300029 x
5(1.5) 8 + 20.688
= 1.4 26
8(20.688)
= 1.300029 m
pfc = x = 26
OCTOBER 7, 2015 REVISION 1
SHEET CONTENT: OWNER: DRAWN BY:
CHECKED BY:
ALVAIRA, JOHN LESTER M.
ELECTRICAL SYSTEM DESIGN OF A ILLUMINATION COMPUTATION DARREN B. ACE ENGR. DINDO T. ANI 241
PROPOSED BUILDING (THIRD FLOOR) ADDRESS: DESIGNED BY: 386
(MALL) OPEN FOODCOURT DATE:
BATANGAS CITY ESCALONA, ABEGAIL T. SEPTEMBER 15, 2015
ZARASPE, RONUALDO F.