Compliance Approach: Prescriptive (402.1.1 thru 402.1.3) UA Trade-Off (402.1.4) Building Performance (404)
State: Jurisdiction:
Additional Comments:
Additional Comments:
1
Relevant 2006 IECC code section numbers are included in brackets. Code section numbers followed by an asterisk indicate a Tier 2 checklist item.
1 2
KEY High Impact (Tier 1) Medium Impact (Tier 2) Page 1
General building information only required if different than above
Additional Comments:
2
Steel frame equivalent: R-19 in 2x6 or R-19+R-6 in 2x8 or 2x10
3
Up to 15 ft2 of glazed fenestration, including skylights, may be exempted from U-factor and SHGC requirements under the prescriptive approach.
4
If more than ½ the insulation is on the interior, checklist item #IN1 applies (R-6).
1 2
KEY High Impact (Tier 1) Medium Impact (Tier 2) Page 2
Verified Complies
Item Number Insulation Inspection Code Value Value Y N N/A Comments/Notes/Findings
IN1 Wall insulation R-value. Installed per Wood: R-
[402.1.1 manufacturer’s instructions. R-13
402.2.3-4, Mass:
1 5
102.1.1] R-4
Additional Comments:
Additional Comments:
5
Mass equivalent: If more than ½ the insulation is on the exterior, checklist item #FR6 applies (R-4).
6
One side-hinged door up to 24 ft2 can be exempted from the prescriptive door U-factor requirements.
1 2
KEY High Impact (Tier 1) Medium Impact (Tier 2) Page 3