CONSTRUCTION FUNDAMENTALS
Presenter:
Colin Lee
Principal Engineer Asset Management
Energex
Email: colinlee@energex.com.au
765 kV Horizontal
(Vee Insulators)
Level II Applicable to overhead lines where collapse of the line would cause
negligible danger to life and property and alternative
arrangements can be provided if loss of support services occurs.
Level III Applicable to overhead lines where collapse of the line would cause
unacceptable danger to life or significant economic loss to the
community and sever vital post disaster services.
θ/2 θ/2
θ
FT = PZ x D x Wd + 2 TX sin
2
θ
F1 = PW x OD x Wd + 2 TX sin
2
= 1747.7 N
Fwφ = Pwφ x OD x d1
= 5220 N
⎛ d + d3 + d4 ⎞ Fwφ
Tip Load = F1 + F2,3, 4 ⎜⎜ 2 ⎟⎟ +
⎝ d 1 ⎠ 2
API Residential 2016 Program
⎛ d + d3 + d4 ⎞ Fwφ
Tip Load = F1 + F2,3, 4 ⎜⎜ 2 ⎟⎟ +
⎝ d 1 ⎠ 2
⎛ 15 + 13.5 + 12 ⎞ 5220
= 1747.7 + 4817.7 ⎜ ⎟ +
⎝ 17 .4 ⎠ 2
= 15.6 kN
θ
F1 = PW x OD x Wd + 2 TX sin
2
= 3627.5 N
Fwφ = Pwφ x OD x d1
= 9048 N
⎛ d + d3 + d4 ⎞ Fwφ
Tip Load = F1 + F2,3, 4 ⎜⎜ 2 ⎟⎟ +
⎝ d 1 ⎠ 2
API Residential 2016 Program
⎛ d + d3 + d4 ⎞ Fwφ
UltimateTip Load = F1 + F2,3, 4 ⎜⎜ 2 ⎟⎟ +
⎝ d 1 ⎠ 2
⎛ 15 + 13.5 + 12 ⎞ 9048
= 3627.5 + 8686.3 ⎜ ⎟ +
⎝ 17 .4 ⎠ 2
= 28.37 kN
To select pole:
(1) Take into account component strength factor, eg 0.72 for
preserved wood pole, 1.0 for steel pole
(2) Ultimate strength for pole is 39 kN for wood pole and 30 kN for
steel pole
Bushfire/Reliability Initiatives
• Ground Fault Neutraliser
• Petersen coil in transformer
neutral
• Virtually eliminates fault
current
• Jemena has installed one in
Victoria
• PBST recommendation in
Victoria
Bushfire/Reliability Initiatives
• Sparkless Fuses (FaultTamer
and Boric Acid fuses)
• FuseSaver Device (Kaon)
• Installed downstream of
MDO fuse
• Operates before fuse
• Reclose time around 9
seconds
Bushfire/Reliability Initiatives
• S&C IntelliRupter
• Unique pulse closing
scheme
• Addresses conductor burn
down
• Do not need to revise
protection settings at
substation