Você está na página 1de 1

Project Number Project Name

0509 Process Water Scrubber Cooling

1 Exchanger Side HOT COLD


2 Fluid Entering - Name Process Water Starch Wash Water
3 Flow gpm 300 212
4 Density lb/gal 8.40 8.33
5 Condensible Vapor lb/hr
6 Non-Condensible Vapor lb/hr
7 Liquid lb/hr 151,200 105,840
8 Total Fluid Entering lb/hr 151,200 105,840
9 Fluid Vaporized or Condensed lb/hr 0 0
11 Viscosity In/Out cP 400.0 350.0 1.00 1.00
12 Specific Heat BTU/lb/oF 0.98 1.00
13 Latent Heat BTU/lb 1000 1000
14 Thermal Conductivity BTU/lb/ F/ft
o 0.33 0.33
15 Temperature In o
F/oC 150.0 / 65.6 85.0 / 29.4
16 Temperature Out o
F/ C
o
125.0 / 51.7 120.0 / 48.9
17 Operating Pressure - In * *
18 Velocity ft/sec * *
19 Pressure Drop Allowed psi * *
20 Pressure Drop Calc. psi * *
21 Heat Exchanged (kBTU/hr) 3704 -3704 L.M.T.D. 34.8 o
F 19.3 o
C
22 Overall U BTU/hr/oF/ft2 Service 750 Clean 900
23 Design Pressure psig 150 150
24 Test Pressure psig 225 225
25 Design Temperature o
F/oC 250 / 121 250 / 121
26 Plate Information Total No. 29 Surface 171.717 ft 2
Material 316 SS
Passes 1 Gaskets EPDM - FDA
Note Area calculated based on service heat exchanger coefficient.

379847254.xls Page 1