Escolar Documentos
Profissional Documentos
Cultura Documentos
Environmental Engineering
Submitted By:
Submitted To:
Treatment systems are installed for two main reasons: to remove those things that can
cause diseases and to eliminate those that create nuisances. In raw water treatment, the
water is treated by a confirmed series of treatmentsteps or unit processes to produce safe
drinking water. The goals are to remove pollutants that affect water quality and to ensure
thatwater, safe for consumption is delivered to the consumer.The unit processes used to
prepare raw or untreated water for public use and consumption are controlled and
determined by water quality parameters. These parameters are set by federal regulations
and are supported and strengthened by state law.
In this paper, a problem on the quality of the raw groundwater was identified.The
water quality did not meet the drinking water standards and a treatment plant was needed.
A solution for the problem was identified based on the raw water composition and the
drinking water standards and requirements.The quality standardsand requirements chosen
for the drinking water was based on the standards set by the World Health Organization
(WHO).
This paper will give an emphasis on water quality, functionality of each unit processes
within the treatment chain and simple design calculations on water treatment plants. It
will discuss on the selection, theory and operation of the water treatment processes such
as aeration, water softening, coagulation, flocculation, sedimentation, filtration, and
disinfection in water treatment plants. Moreover, calculations in the process and
mechanical designs of this treatment processes were also included in the plant design.
Design a water treatment plant that treats groundwater extracted from a well in an
unconfined aquifer. Based on the water analysis of the groundwater, it was found out that
the water contains undesirable contaminants and the water quality did not meet the
drinking water standard. Design the treatment processes and equipment needed based on
the nature and quality of the groundwater to be treated, the WHO drinking water quality
standard, the desired quality of the finished water and the mode of operation planned.
1
III. Design Input
i. Physical Characteristics
Actual
Parameter
Value
Color 25
Odor negative
Taste normal
Temperature , °C 25
Turbidity , NTU 30
Total Suspended
253.8
Solids , mg/L
Table 1.0: Physical Characteristics of Raw Water
i. Physical Characteristics
Highest Desirable Minimum Permissible
Parameter
Level Level
Color 5 50
Odor Unobjectionable Unobjectionable
Taste Unobjectionable Unobjectionable
Temperature , °C 25 5
Turbidity , NTU 2.5 5
Total Suspended Solids , mg/L 500 1500
Table 1.3: WHO Standard Physical Characteristics
3
Copper, mg/L 1 1.3
Lead, mg/L 0.005 0.01
Mercury, mg/L 0.005 1.0
Selenium, mg/L 0.05 0.01
Sodium, mg/L 200 200
Zinc, mg/L 5.0 5.0
Nitrates, mg/L 10 10
Sulfate, mg/L 250 400
Hydrogen Sulfide, mg/L 0 0
Magnesium, mg/L 25 150
Cyanides, mg/L 0.1 0.05
Table 1.4: WHO Standard Chemical Characteristics
4
IV. Design Analysis
Treatment processes for the treatment plant are identified based on the raw water
composition and the drinking water standards and requirements.
5
B. Process Flow Diagram
LIME-SODA SOFTENING
AERATION
INTAKE
SEDIMENTATION
FLOCCULATION AND
COAGULATION
FILTRATION
DISTRIBUTION
DISINFEFCTION
6
C. Water Treatment Unit Processes
1. INTAKE
i. Theory
The basic function of the intake structure is to withdraw water from the source
over predetermined pool levels and then to discharge this water into the withdrawal
conduit, through which it flows up to the water treatment plant. A pump is used to
lift groundwater from an aquifer where the water is stored. The aquifer has an area
that influences the movement of contaminants in groundwater. Knowing these areas
promotes understanding of the possible location of the contaminants and the
technology needed for treatment. In building an aquifer, the aquifer’s permeability
and porosity of rocks are taken into consideration. Porosity is the ratio between the
volume of soil and the volume of the area or medium they occupy and permeability
is the property of rocks that is an indication of the ability of liquid to flow through
rocks.
ii. Operation
To draw the groundwater from the reservoir, a submerged pump will be used.
The pump will be selected base from the criteria of the desired input flow rate. As
the water is pump up, it flows through a pipe where it will go tanks for treatment
processes. In short, groundwater is pumped to an intake pipe from the groundwater
source and pumps carry the water through a transmission conduit to the treatment
processes and distribution system.
2. AERATION
i. Theory
Water aeration is the process of increasing the oxygen saturation of the water.
Aeration treatment consists of passing large amounts of air through water and then
venting the air outside. The air causes the dissolved gases or volatile compounds to
release from the water. The air and the contaminants released from the water are
vented.
7
Organic Consuming Substances in Raw Water
Many organic and inorganic substances, and micro-organisms are present in raw
water from surface or ground sources. Most of these substances are unstable, produce
taste, color, odor, and turbidity, which are objectionable to water consumers. These
substances may be converted into stable ones when oxygen is available. When
dissolved oxygen is generated in raw water (effluent) during aeration, it oxidizes
several compounds including iron, manganese, ammonium and organic substances.
Similarly, gases such as carbon dioxide, carbon monoxide, hydrogen sulphide and
hydrocarbons, which may be trapped in the raw water, are desorbed. During the
design stage of a gas transfer component, the levels of oxidation and desorption are
estimated.
Organic Compounds
Organic substances often found in water sources have elements including carbon,
hydrogen, oxygen and nitrogen. When oxygen is present, the organic substance is
broken down according to the reaction,
C5 H 7 O2 N 7O2 3H 2 O 5CO2 NO3 H
Ammonium compound is formed as an intermediary and is further broken down into
nitrites and nitrates, with the help of the bacteria, nitrosomonas and nitrobacter.
NH 4 2O2 H 2O 2H NO3
In this reaction, 3.5 g of oxygen is consumed per gram of ammonium compound.
Inorganic substances
Oxidation of iron
4Mn 2 2O2 8H 2 O 4MnO2 4H 2 O 8H
In this reaction 0.29 g of oxygen is consumed per gram of manganese. This is double
the oxygen demand for oxidation of iron II Oxide. Reactions (1) to (4) indicate that
hydrogen ions are produced in excess.
8
ii. Operation
The air pump delivers air into the tank and a pocket of compressed air forms in
roughly the top third of the tank. As water enters the tank through the pipe, it hits a
baffle and sprays down through the pocket of compressed air. The water is further
aerated inside the tank before it leaves by way of the long tube which picks it up at
the bottom of the tank and sends it out through the other pipe.
3. SOFTENING
i. Theory
Lime-Soda Softening
Raising the pH of a water by addition of alkalinity will convert bicarbonates into
carbonates and CaCO3 formation and precipitation will ensue. Also, Mg(OH)2 will
be formed and precipitate. Slaked lime or lime Ca(OH)2, which is hydrated calcium
oxide (CaO), is usually the least expensive source of alkalinity. Calcium oxide is also
known as quicklime. Sodium hydroxide, NaOH, can also be used for alkalinity
depending on economics and other factors such as availability and ease of handling.
When insufficient bicarbonate concentrations exist, sodium carbonate (Na2CO3),
known as soda ash, is added to supply both alkalinity and carbonate ions. The
stoichiometry of the reactions is straightforward. The reactions involved in the lime-
soda process are given below.
Any carbon dioxide present in the raw water consumes lime according to reaction
(1). As lime is added, the pH rises and HCO3- is converted to CO32- and the reactions
in (2) and (3a) occur. As more lime is added, the concentration of OH- ions becomes
significant and reactions (3b) and (5) proceed. Reaction (6) applies only when soda is
added because some of the Ca2+ and Mg2+ ions are associated with noncarbonated
ions. Soda ash is more expensive than lime.
9
Adding the above two reactions, the net lime requirement for magnesium carbonate
hardness is
Hardness concentration,
Degree of Hardness
mg/L as CaCO3
Moderately Hard 60-120
Hard 120-180
Very hard 180 and over
Table 1.8: Qualitative Hardness of Water
10
pH above 10.5 must be achieved in order to precipitate Mg(OH)2. The actual amount
of excess alkalinity required is dependent on the buffering capacity of water. Carbon
dioxide can be added to neutralize the excess lime in the treated water and lower the
pH to the desired value as shown by the following reactions.
2OH + CO2 → CO32- + H2O (7)
CO32- + H2O + CO2 →2HCO3- (8)
An alternate to remove the Ca2+ resulting from excess lime is to add Na2CO3. The
Na2CO3 is added along with the lime to the water entering the basin. Where
precipitation of CaCO3 and Mg(OH)2 will occur. The excess OH- in the effluent from
the basin is neutralized by addition of acid to achieve the pH desired for a stable
water. This approach requires only a single basin for hardness removal in contrast
with split recarbonation processes.
ii. Operation
Split-Flow Treatment
A split-treatment process softens raw water pumped from a nearby wall field.
Lime, soda ash and carbon dioxide are the principal chemicals used in the softening
process. Chemical softening occurs in Upflow solids contact basins, followed by the
pH adjustment and filtration using dual media gravity filters. Stabilizing chemicals
and filtration aids may also be added to the water. Following filtration, water is
chlorinated, fluorinated and stored in the plant clear well prior to pumping into the
City’s distribution systems.
In a split treatment process a portion of the water is treated for hardness removal
and recombined with a bypassed stream. The combined flow may be further treated
for calcium reduction. Also magnesium reduction in the water can be controlled in a
split treatment process. Chemical costs are also reduced in split treatment process.
The bypassed flow can be treated with coagulation agents as required for removal of
suspended solids in the settling basin.
A split treatment is normally applied to a water with a low amount of non-
carbonate hardness and magnesium hardness reduction is desired. In a split treatment
process all lime based on the total flow is added to the stream entering the first stage
to cause reactions. There is normally a large excess of lime in the first basin and
magnesium concentration below 0.2 meq/L down to practically zero can be attained
in the settled effluent from this stage. Recarbonation of the effluent from the first
11
stage is sufficient alkalinity and carbon dioxide in the bypassed flow to react with the
excess lime. There will be no precipitation of magnesium after the first stage because
the pH will be lowered below solubility product values for Mg(OH)2 precipitation.
Mixing the treated and bypassed streams result in more carbonate formation and
subsequent precipitation of calcium carbonate. If further reduction of noncarbonnate
hardness is required the influent to the second stage can be supplemented with
Na2CO3 to reduce the noncarbonate Ca2+ according to reaction (6). Another settling
basin is required to settle the precipitate formed by these reactions. Finally, CO2 is
added to cause reaction (8) to bring the pH to the desired final value.
The final desired magnesium concentration dictates the fraction of flow that is
bypassed in a split treatment process. Water heater fouling problems are avoided
when magnesium concentrations are 40 mg/L as CaCO3 (0.8 meq/L) or lower.
Because no magnesium is removed in the second stage,
where x is bypassed fraction of influent flow, Q, while [Mg]0, [Mg]1, [Mg]t are the
influent, first stage, and final magnesium concentrations, respectively. The
maximum fraction that can be bypassed occurs when [Mg]t = 0.
Recycling a portion off the sludge from the clarifier promotes reaction and
settling in the process. Does higher than stoichiometric requirements may be required
to achieve desired results.
Carbon dioxide can be supplied in bulk containers or generated by burning a
hydrocarbon such as gas or oil or burning oil or coke. Polyphosphates are synthetic
phosphate compounds that sequester hardness ions, keeping them in solution.
Polyphosphates compounds that are often added to treated waters to prevent deposit
build-up on pipes.
12
4. COAGULATION
i. Theory
Water treatment methods are generallyclassified into three categories:
mechanical,chemical and biological treatments.Chemical treatment is generally
applied to carryout mechanical treatment more efficiently and one type of this is
coagulation.
Alum or aluminum sulphate is selected as the coagulant used. Aluminum is
purchased as either dry or liquid alum, Al2(SO4)3·14H2O. Liquid alum is sold as
approximately 48.8% alum and the rest are water to avoid problems with
crystallization.
Each mole of alum uses 6 moles of alkalinity and produces 6 moles of CO 2. The
reaction shifts the carbonate equilibrium and decreases the pH. As long as sufficient
alkalinity is present and CO2(g) is allowed to evolve, the pH is not drastically reduced
and is generally not an operational problem. When sufficient alkalinity is not present
to neutralize the sulfuric acid production, the pH may be greatly reduced:
Al2 SO4 3 14H 2O 2 Al OH 3 8H 2O 3H 2 SO4
ii. Operation
Mixing is a very important operation associated with coagulation and
flocculation process. This operation hastens the settling process of particles in water.
Mixing must be in such amount of power that is enough to promote contact of
coagulants with the particles and form microflocs but not to tear the macroflocs
formed in flocculation process.
Flash mixing coagulants and other chemicals is necessary because of the minute
amounts of solutions added to the relatively large amount of raw water treated.
Because a rapid chemical reaction starts the instant the alum or other coagulant is
blended with raw water, there must be instant diffusion of the coagulant solution or
many particles will be missed, resulting in an overall higher turbidity or excessive
use of coagulant.
13
Mixing equipment: In-line Mechanical Mixer or In-line Blender
5. FLOCCULATION
i. Theory
Flocculation is a process where a solute comes out of solution in the form of floc
or flakes. The action differs from precipitation in that the solute coming out of
solution does so at a concentration generally below its solubility limit in the liquid.
In colloid chemistry, flocculation refers to the process by which fine particulates are
caused to clump together into floc. The floc may then float to the top of the liquid,
settle to the bottom of the liquid, or can be readily filtered from the liquid. According
to the IUPAC definition, flocculation is a “process of contact and adhesion whereby
the particles of dispersion form larger-size clusters”. Flocculation is synonymous
with agglomeration and coagulation. For emulsions, flocculation describes clustering
of individual dispersed droplets together, whereby the individual droplets do not lose
their identity. Flocculation is thus the initial step leading to further aging of the
emulsion (droplet coalescence and the ultimate separation of the phases).
Flocculation and sedimentation are widely employed in the purification of drinking
water as well as sewage treatment, storm water treatment and treatment of other
industrial wastewater streams.
Microscale Flocculation
The type of flocculation used is microscale flocculation since the water extracted
is groundwater. In this type, the flocculation of small particles (particle size less than
0.1 µm in diameter) is caused by diffusion. The rate of flocculation is relative to the
rate at which the particles diffuse. Thus, the primary mechanism of aggregation is
14
through Brownian motion. This aggregation is called Microscale flocculation or
perikinetic flocculation. After a period of seconds, the microflocs range in size from
1 to about 100 µm in diameter.
Differential Settling
Because the floc particles are of different size, they settle at different rates.
Differences in the settling velocities cause the particles to collide and flocculate.
Chemical Sequence
The addition of multiple chemicals to improve flocculation is common practice.
The order of addition is important to achieve optimum results at minimum cost.
Typically, the addition of a polymer after the addition of hydrolyzing metal salts is
most effective. Ideally, the polymer addition should be made 5 to 10 minutes after
the addition of the hydrolyzing metal salt. This allows for the formation of pinpoint
floc that is then “bridged” by polymer. In conventional water treatment plant design
this is rarely possible because of space limitations.
ii. Operation
Flocculation is the most critical factor that affects particle removal efficiency. It
speeds slow-settling particles and chemical precipitants. This is accomplished by a
slow mixing process, designed to bring particles into contact so that they collide,
stick and agglomerate to size that readily settles. How fast and well the particles
agglomerate depends on the velocity gradient. Too much mixing shears the floc
particles, breaking them down into smaller units. The velocity gradient must be
strictly controlled. Enough mixing to bring the floc into contact must occur, without
breaking apart the forming floc, until maximum floc formation occurs and
sedimentation can begin. Gentle agitation for about one-half hour, using redwood
paddles mounted horizontally on motor-drive shafts, is common. The paddles rotates
slowly, providing gentle agitation that encourages floc growth. Floc formation
depends on how much particulate is present, how much volume it occupies, and the
basin velocity gradient.
15
6. SEDIMENTATION
i. Theory
The performance of a sedimentation basin for a given raw-water quality can be
understood with the help of particle settling theories. Particle suspensions are
separated into four classifications based on their concentration and morphology.
Type I particles are discrete and do not interfere with one another during settling
because the concentration is low and they do not flocculate. Type II suspensions
consist of particles that can adhere to each other if they bump into each other. At
concentrations higher than Type I and II suspensions, hindered, or Type III, settling
occurs. At much higher concentrations than are found in Type III settling, Type IV
settling or compression settling occurs where the suspension begins to consolidate
slowly.
In this process, Type III settling occurs because when the particles are dispersed
in a solution they go down the lower regions of the sedimentation basin. Hindered
settling typically occurs in this region and it is here where the concentration of
suspended particles is highest.
The solids flux in a sedimentation basin or solids thickener is defined in the
expression
JT J s Ju
where JT = total solids flux toward the bottom of the basin, kg/m2.h
Js = solids flux due to particle settling by gravity, kg/m2.h
Ju = solids flux due to fluid flow from the underflow, kg/m2.h
The solids flux values due to particle settling is determined by multiplying the
concentrations of particles by their respective initial settling velocities as
J s vs C
16
Surface Influent,
Area, A Qr Ci
Underflow,
Qu, Cu
17
Table 1.8 shows the settling velocity and solids flux values.
The solids flux due to the fluid flow to the underdrain, Js, is defined by
Qu C
Ju vu C
A
where Qu = flow rate leaving the bottom of basin/thickener, m3/h
A = cross-sectional area of basin, m2
vu = bulk downward fluid velocity, m/h
The total flux at a suspended solids concentration C
J T vs vu C
The limiting flux is the point at which the mass flow of solids entering the thickener
is equal to the mass flow of solids leaving the thickener.
The downward velocity of the bulk fluid may be determined using the relationship
JL
vu
Cu
where vu = downward velocity of bulk fluid, m/h
JL = limiting solids flux, kg/m2.h
Cu = concentration of solids in underflow, kg/m3
Estimation of the flow rate through the underdrain can be done using the solid mass
balance analysis expression
Qi Ci Qi Qu Ce Qu Cu
18
ii. Operation
Water flows horizontally through the sedimentation basin, then rises vertically to
overflow the discharge channel weir at the tank surface. While the water slowly rises,
the floc settles in the opposite direction and is expelled mechanically by continuous-
action sludge removal machinery. The process does not remove all the floc so
particles lighter than the overflow rate flow out with the effluent, and are removed by
filtration. The sedimentation basin sludge is disposed of by passing it to a lagoon,
thickening and holding, or directing it to the sanitary sewer.
7. FILTRATION
i. Theory
Filtration is a process where water flows through a permeable layer, either a
membrane, filter paper, a sieve, a porous medium or such. In water treatment,
granular filtration is a process where water flows through granular material (often
sand) while suspended solids (sand, clay, iron and aluminum flocs) are retained,
substances are biochemically decomposed and pathogenic microorganisms (bacteria,
viruses, protozoa) are removed.
The suspended solids slowly fill the pores, resulting in an increase in hydraulic
resistance. The suspended solids are removed by periodically cleaning the filter beds.
This prevents the resistance from becoming too high or the breakthrough of
suspended solids. Filters are also used for chemical and biological reactions. This is
mainly of importance for the treatment of groundwater where the oxidation of iron,
manganese, and ammonium and, in case of poor gas stripping, methane takes place.
The removal of pathogenic microorganisms is of importance for surface water
treatment, and the efficiency is approximately 90 to 99%. The removal of pathogenic
microorganisms occurs by decay and retention on the grains.
19
the filter bed must be cleaned by backwashing. During backwashing the filter bed is
expanded, and the accumulated suspended solids are removed. The backwash water
is drained through a central trough to a waste receptacle. The backwash frequency is
repeated every few days.
Rapid sand filters are present in nearly every water treatment plant. Surface water
treatment uses the filters after floc formation and removal to get rid of the remaining
flocs and pathogens and to decompose ammonium. In groundwater treatment, the
filters are usually placed after aeration to remove iron flocs, manganese and
ammonium. With softening, filters are often placed after pellet reactors to remove the
‘carry-over’.
ii. Operation
Some particles are removed by simple mechanical screening because the particle
is larger than the smallest opening through which the water flows. This is the
dominant mechanism for slow sand filters. Straining causes a cake to form at the
surface of the filter. This improves the efficiency of particle removal but also
increases the head loss. In depth-filtration, particles smaller than the openings
between the granular material are removed by a variety of mechanisms including
sedimentation, flocculation, interception, and impaction. The pore spaces between
the grains of granular material are small, and the water velocity through the
interstices is small. If the mass and diameter of the particles is large enough, it will
settle through the short distance from the water to the particle. Because the
streamlines of water flowing through the interstices bend as the water passes around
the granular material, particles are brought into contact with one another. This
mixing causes them to flocculate and grow larger in size. The larger particles may
then be captured by straining. Bending streamlines also cause smaller particles to
pass near enough to the grains of filter material to be intercepted. In some cases, the
particles have sufficient mass that they cannot follow the alteration in flow path with
the streamlines, and their trajectory causes them to impact on the granular material of
the filter. As the particles in the water come in contact with the granular filter
material, the surface forces must be favorable for them to attach. They must
sufficiently destabilized so that the electrostatic repulsive forces are minimized and
the short range van der Waals forces result in a net attractive force.
20
8. DISINFECTION
i. Theory
Chlorination
In water, chlorine reacts with various substances or impurities present (organic
materials, sulfides, ferrous iron, and nitrites, for example). The presence of these
materials creates a chlorine demand, a measure of the amount of chlorine needed to
eliminate these impurities by combining with them. That amount of chlorine cannot
disinfect; it is already chemically depleted.
Chlorine also combines readily with ammonia or other nitrogen compounds,
forming chlorine compounds. These chlorine compounds have some disinfectant
properties, and are called the combined available chlorine residual. Chlorine in this
form acts as a disinfectant. The chemically unchanged chlorine remaining in the
water after combined residual is formed is free available chlorine residual. Free
chlorine is much more effective than combined chlorine in disinfection.
For successful chlorination, several factors must be addressed: concentration of
free chlorine, contact time, temperature, pH, and turbidity. How effectively chlorine
disinfects is directly related to contact time with the water, as well as the free
available chlorine concentration. Lower chlorine concentrations require increased
contact times. Lower pH levels also aid disinfection effectiveness. Chlorine
disinfects more quickly at higher temperatures. Turbidity affects chlorine's
effectiveness as well, as it does any disinfectant. Chlorine must contact organisms to
kill them. High turbidity levels provide shelter for microorganisms, preventing
efficient contact.
Chemistry of Chlorination
Chlorine is added to the water supply in two ways. It is most often added as a gas,
Cl2(g). However, it also can be added as a salt, such as sodium hypochlorite (NaOCl)
or bleach. Chlorine gas dissolves in water following Henry's Law. Once dissolved, the
following reaction occurs forming hypochlorous acid (HOCl):
HOCl OCl- + H+
21
Hypochlorous acid and hypochlorite ion compose what is called the free chlorine
residual. These free chlorine compounds can react with many organic and inorganic
compounds to form chlorinated compounds. Reactions between ammonia and
chlorine form chloramines, which is mainly monochloramine (NH2Cl), although some
dichloramine (NHCl2) and trichloramine (NCl3) also can form. Many drinking water
utilities use monochloramine as a disinfectant. If excess free chlorine exits once all
ammonia nitrogen has been converted to monochloramine, chloramine species are
oxidized through what is termed the breakpoint reactions. The overall reactions of
free chlorine and nitrogen can be represented by two simplified reactions as follows:
Monochloramine Formation Reaction. This reaction occurs rapidly when ammonia
nitrogen is combined with free chlorine up to a molar ratio of 1:1.
Ozonation
Ozone (O3) used as disinfectant leaves no taste and odor in the treated water, is
actually more effective than chlorine against some viruses and cysts, and is
unaffected by pH or ammonia levels in the water. Ozone is a gas at normal
temperatures and pressures, and disinfects by breaking up molecules in water. When
ozone reacts with organic materials and inorganic compounds in water, an oxygen
(instead of a chlorine) atom is added, resulting in an environmentally acceptable
compound. Ozone's instability, however, means that it cannot be stored and must be
produced on site, generating higher costs than chlorine disinfection.
Giardia Cysts
The cyst stage is the stage that is responsible for the spread of the organism.
Giardia cysts are elliptically shaped and range in size from 6 to 10 microns. The cyst
stage could be thought of as the equivalent of a "seed" or "spore", the structure of the
cyst makes the organism very resistant to environmental factors and disinfection. The
cyst stage is the "life stage" that will be found in the environment.
22
After entering the host, the stomach acids causes a reaction that causes the cyst to
excyst, i.e., "hatch like and egg." The cyst does not hatch in the stomach, but in the
intestine. The organism quickly subdivide and attach to the lining of the intestine.
This is the second life stage - the trophozoite. The trophozoite stage, Giardia
duodenalis - species that infects humans, is approximately 12 - 15 microns by 6 - 8
microns. The organism has a pointed elongated median body.
Cryptosporidium Oocysts
Cryptosporidium is a microscopic parasite that causes the diarrheal disease
cryptosporidiosis. Both the parasite and the disease are commonly known as
"Crypto." There are many species of Cryptosporidium that infect animals, some of
which also infect humans. The parasite is protected by an outer shell that allows it to
survive outside the body for long periods of time and makes it very tolerant to
chlorine disinfection. While this parasite can be spread in several different ways,
water is the most common way to spread the parasite. Cryptosporidium is a leading
cause of waterborne disease among humans in the United States.
ii. Operation
The formation of oxygen into ozone occurs with the use of energy. This process
is carried out by an electric discharge field as in the CD-type ozone generators
(corona discharge simulation of the lightning), or by ultraviolet radiation as in UV-
type ozone generators (simulation of the ultraviolet rays from the sun). In addition to
these commercial methods, ozone may also be made through electrolytic and
chemical reactions. In general, an ozonation system includes passing dry, clean air
through a high voltage electric discharge, such as corona discharge, which creates
and ozone concentration of approximately 1% or 10,000 mg/L. In treating small
quantities of waste, the UV ozonation is the most common while large-scale systems
use either corona discharge or other bulk ozone-producing methods.
The raw water is then passed through a venturi throat which creates a vacuum
and pulls the ozone gas into the water or the air is then bubbled up through the water
being treated. Since the ozone will react with metals to create insoluble metal
oxides, post filtration is required
23
V. Process Design
1. WATER INTAKE
Sw
h1 h2
hw
r1=8m
r2=30m
ii. Assumptions
1. The aquifer is unconfined.
2. The aquifer has aerial extent.
3. The aquifer is homogeneous, isotropic and of uniform thickness.
4. The water table is horizontal prior to pumping.
5. The aquifer is pumped at a constant discharge rate.
6. The well penetrates the full thickness of the aquifer and thus receives
water from the entire saturated thickness of the aquifer.
24
iii. Design input
r1 = 30 m
r2 = 8 m
h1 = 6.8 m
h2 = 7.24 m
v. Design Calculation
h2 2 h1 2
2
Q
r2
ln
r1
2K
K h2 2 h1 2
r
ln 2
r1
m 3 360s
8.88 10 3 6hr 1day
s 1hr
Design Flow 190m 3 / day
25
2. AERATION
i. Design Input
a. Determination of Average DO
DO ave
(DO i DO f )
3
(8.86 5.49) (8.88 5.65) (8.83 5.53)
DO ave
3
DO ave 3.3 mg
L
DO ave
BOD
P
3.3mg/L
BOD
0.25
BOD 13.2mg/L
26
Pumping Flow Rate
3 1000L
Pumping Flow Rate 32 m
h 1m 3
L
Pumping Flow Rate 32 000
h
Oxygenation Capacity
OC 0.4224 kg
h
O 2 required
hp req
O transfer rate
10.1616 kg
day
hp req
24 hrs
1.5 kg
kg kwh 1 day
1.36hp
hp req 0.28227kw
1kw
hp req 0.3839 hp
27
3. SOFTENING
A. Lime-Soda Softening
i. Design Requirement
Determination of chemical dosages to soften the water to meet the following
finished water criteria using split treatment:
Maximum magnesium hardness = 40 mg/L as CaCO3
Total hardness = 80 to 120 mg/L as CaCO3
i. Design Input
Raw Groundwater Analysis
Constituent mg/L
CO2 5.5
Ca2+ 95.2
2+
Mg 22
+
Na 25.8
Alkalinity 183
-
Cl 67.8
SO42- 73
Table 2.0: Softening Input
ii. Block Diagram
Lime-Soda Ash Addition
Q Rapid Mgi
Raw Aeration Mix
Water Mgr Flow = (1-X) Q
Return Sludge
Flow Bypassed = XQ
Rapid
Mix
28
iii. Design Calculation
mg/L as
Constituent mg/L EW EW CaCO3/EWion meq/L
CaCO3
CO2 5.5 22 2.28 12.5 0.25
Ca2+ 95.2 20 2.50 238 4.76
Mg2+ 22 12.2 4.12 90.6 1.80
Na+ 25.8 23 2.18 56.2 1.12
alkalinity 183 3.66
Cl- 67.8 35.5 1.41 95.6 1.91
SO42- 73 48 1.04 76 1.52
Table 2.1: Values of the Constituents
O2 HCO 3
-
Cl - SO42-
c. Lime and soda added in the first stage to soften water to practical solubility limits
29
d. The split is calculated in terms of mg/L as CaCO3
40 10
X 0.372
90.6 10
1 0.372 0.628
Total hardness of water through the first stage is the sum of practical solubility
limits, that is
30 10 40mg / L as CaCO3
Because,
THraw water = (183+40) +90.6 = 313.6 mg/L as CaCO3
g. Excluding the extra lime to drive the reaction, the total chemical addition are in
proportion to the flow:
30
4. COAGULATION
i. Design Input
Alkalinity= 183 mg/L as CaCO3
Alum dose= 50 mg/L
d. Final Alkalinity
50
Final Alkalinity = 183 mg/L as CaCO3 – (30.81 mg/L as HCO3- )
61
Final Alkalinity = 157 mg/L as CaCO3
e. Change in pH
A carbonate buffer system is present in the solution due to the high alkalinity of
the water. The CO2 in solution is in equilibrium with atmospheric CO2(g).Any
change in the system components causes the CO2either to be released from
solution or to dissolve. The presence of this buffer system prevents any drastic
change in the pH of the water.
31
5. FLOCCULATION
i. Design Input
3
Design flowrate (Q) = 50 x103 m
day
o
Water temperature (T) = 25 C
ii. Design Criteria
a. Velocity Gradient
1
P 2
Gt
V
1
230W 2
Gt 4 3
(8.90 x10 )(382m )
Gt 26.00 s 1
b. Residence Time
V
t
Q
382m 3
t 3
3 m 1day 1hr
25 x10 x x
day 24hr 60 min
t 22.00 min
32
6. SEDIMENTATION
i. Design Input
a. Determination of JL and CL
Determine JL and CL using the figure for analysis of zone settling data, Fig6-7
Solids flux, kg/m2h
1g
Cu = 15000mg/L × = 15g/L
1000mg
To determine JL, draw a line from the x-axis at a solids concentration of 15 g/L
tangent to the solid flux curve intersecting the y-axis.
33
To determine CL, draw a vertical line from the tangent point to the x-axis
1000mg
C L 6.5g/L 6500mg/L
1g
Q i Ci
Qu = where Qi = influent flow rate to basin
Cu
Ci = solids concentrar ion
Cu = underdrain concentrat ion
(1800 m h ) 600 mg L
3
Qu =
mg
15000 L
3
Q u = 72 m h
c. Areafor thickening, A
Qi Ci
A= wher e Qi = influent flow rate to basin
JL
Ci = solids concentrat ion
C u = limiting solid flux
A=
kg 1000g
7.45 2 ×
m 1kg
A = 144.97m 2
A = 145m 2
34
7. FILTRATION
i. Design Input
Loading Rate = 216m 3 /d m 2
Specific gravity of sand = 2.65
Shape factor = 0.82
Bed porosity = 0.45
Water temperature = 10℃
Depth of the sand = 0.5m.
Uniformity 1.65a
coefficient
1.3 2.4 1.3 1.7 1.3 1.7 1.3 1.8
1.85b
Hardness, Moh 23 Very low 6.5 7.5 56 7
Porosity 0.50 0.60 0.50 0.45 58 N/A 0.40 0.47
Specific gravity 1.5 1.75 1.3 1.7 3.6 4.2 4.2 5.0 2.55 2.65
Table 2.5:Typical Properties of Filter Media
Size range, mm
3 6 50 75
512 50 75
12 20 75125
20 40 75125
40 65 125 200
Table 2.8: GLUMRB specifications for graded gravel
36
GLUMRB
Parameter Reported range Recommended
recommendation
Sand only
Effective size 0.35-0.7 mm 0.45-0.55
Uniformly
1.3-1.8 ≤ 1.65
coefficient
Shape factor(f) 0.7-0.95
Porosity 0.4-0.47
Specific gravity 2.65
Depth of
0.6-0.75 m ≥ 0.6 m ≤ 7.65 m
medium
Filtration rate 5-12 m/h ≤7.5 m/h
Backwash rate 30-60 m/h ≥ 37 m/h
Backwash
10-20 m/h ≥ 15 min
durationa
Surface wash
rate
Revolving arms 1.2-1.8 m/h ≥ 1.2 m/h
Fixed arms 4.9-10 m/h ≥ 4.9 m/h
Staged or special
Air scour
baffle
Anthracite coal
only
Effective size 0.70-0.75 mm 0.45-0.55 mm
Uniformly
1.3-1.8 ≤ 1.65
coefficient
Shape Factor(f) 0.46-0.73
Specific gravity 1.45-1.75
Porosity 0.53-0.60
Depth of
0.6-0.75 m
medium
Filtration rate 5-12 m/h ≤ 7.5 m/h
Backwash rate 37-45 m/h ≥ 24 m/h
Backwash
10-20 min ≥ 15 min
durationa
Revolving arms 1.2-1.8 m/h ≥ 1.2 m/h
Fixed arms 4.9-10 m/h ≥ 4.9 m/h
Underdrain
Pipe lateral Yes
Block Yes
Air scour No
Staged or special
Air scour
baffle
Table 2.11: Design criteria for single-medium filters
37
GLUMRB
Parameter Reported range Recommended
recommendation
Anthracite coal
on top
Effective size 0.9-1.4 mm 0.8-1.2 mm
Uniformly
1.3-1.8 ≤ 1.85
coefficient
Shape factor(f) 0.46-0.73
Porosity 0.53-0.60
Specific gravity 1.45-1.75
Depth of medium 0.4-0.6 m
Sand on bottom
Effective size 0.35-0.7 mm 0.45-0.55 mm
Uniformly
1.3-1.8 ≤ 1.65
coefficient
Shape Factor(f) 0.7-0.95
Specific gravity 0.4-0.47
Porosity 2.65
≥ 0.6 m and ≤
Depth of medium 0.3-0.75 m
0.76 m
Filtration rate 7-20 m/h ≤ 15 m/h
Backwash rate 30-60 m/h ≥ 24 m/h
Backwash
10-20 min ≥ 15 min
durationa
Surface wash rate
Revolving arms 1.2-1.8 m/h ≥ 1.2 m/h
Fixed arms 4.9-10 m/h ≥ 4.9 m/h
Underdrain
Pipe lateral Yes
Block Yes
No-if total depth of
Air scour
medium ≤ 0.75 m
0.6-1.5 m3/min-m2
Air scour if total medium
depth > 1 m
Table2.12:Design criteria for dual-media filters
38
Parameter Reported range Recommended
Anthracite coal
only
Effective size 0.9-1.4 mm
Uniformly 1.4-1.75
coefficient
Shape factor(f) 0.46-0.73
Porosity 0.53-0.60
Specific gravity 1.45-1.75
Depth of medium 0.4-0.5 m
Sand in middle
Effective size 0.45-0.55 mm
Uniformly 1.4-1.65
coefficient
Shape factor(f) 0.7-0.95
Porosity 0.4-0.47
Specific gravity 2.65
Depth of medium 0.15-0.3 m
Garnet on bottom
Effective size 0.20-0.35 mm
Uniformly 1.2-2.0
coefficient
Shape Factor(f) 0.6
Specific gravity 3.6-4.2
Depth of medium 0.075-0.15 m
Filtration rate 10-25 m/h ≤ 15 m/h
Backwash rate 37-45 m/h
Backwash durationa 10-20 min ≥ 15 min
Surface wash rate
Revolving arms 1.2-1.8 m/h
Fixed arms 4.9-10 m/h
Underdrain
Pipe lateral Yes
Block Yes
Air scour No-if total depth of
medium ≤ 0.75 m
Air scour 0.6-1.5 m3/min-m2 if
total medium depth > 1
m
Table 1.13: Design criteria for tri-media filters
39
Anthracite coal
Effective size 0.9-1.0 mm
Uniformly coefficient 1.4-1.7
Shape Factor(f) 0.46-0.73
Specific gravity 1.45-1.75
Porosity 0.53-0.60
Depth of medium 0.9-1.8 m
Filtration rate 10-25 m/h ≤ 15 m/h
Backwash rate 37-45 m/h
a
Backwash duration 10-20 min
Surface wash rate
Revolving arms 1.2-1.8 m/h ≥ 1.2 m/h
Fixed arms 4.9-10 m/h ≥ 4.9 m/h
Underdrain
Pipe lateral No
Block Yes
Air scour Yes
Air scour 0.6-1.5 m3/min-m2
Table 2.14:Design criteria for deep-bed monomedium filters
v. Design Procedure
40
Step 1:
Determine the effective size and
uniformity coefficient
Step 2:
Estimate clean filter headloss
Step 3:
Determine the depth of the expanded
sand filters
Step 4:
Estimate number of filters and clean
filter headloss
Step 5:
Determine the area of each individual
filter
Step 6:
Design the backwash system
Step 7:
Determine the gullet dimensions
Step 8:
Determine the depth of the filter box
41
a. Determine the effective size and uniformity coefficient
E P10
E 0.30mm
P60 0.85
U
P10 0.30
U 2 .8
Pnth percentile
216m3 / d m2
va 0.0025m / s
86400s / d
from Appendix A using water at 10C
1.307x10 -6 m2 / s
24 3
Drag coefficien t (C D ) 1/ 2 0.34
R R
7.6507 1.6938 0.34 9.6846
(0.82)(0.0 022m)(0.00 25m/s)
R 3.137
1.307 x10 6 m 2 / s
42
(C D )( f ) (9.6846)(0.053)
256.64 / m
d 0.002
f fractional mass retained
Using the procedure for the rest of the rows you will get the results.
1.067( a ) 2 D (CD)( f )
hL
( )( g )( )U dg
Where:
head loss h L , m
ν a approach v elocity, m/s
D depth of the filter, m
C D drag coefficien t
g accelerati on due to gravity, m/s 2
ε porosity
First using Fig. 11-7, find that for a 0.0126 an particle with epecific gravity of
2.65, thr thermal settling velocity is pproximtely 1cm/s (864m/d). Estimated
ν s , m/s settling velocities were found from Fig. 11-7.
43
Where:
s particle density
density of water
f
Depth of the expanded bed, m 1 - ( D)
1 e
(1 - 0.45)(0.5m)(2.53)
m 0.696 or 0.70m
De
Expansion ratio 0.40 or 40% expansion
D
44
Maximum day design flow rate 18400 m 3 / d
N 0.0195(Q) 0.5
Where:
N total number of filters
Q maximum design flowrate, m 3 / d
Q
Area of a filter beds (A)
Nq
Where:
filtration rate q 216m 3 / d m 2
18400m 3 / d
A
4 filters(21 6m 3 /d m 2 )
21.3 m 2 / filter
Redundancy capacity for the maximum day with one filter out of service must be
provided. So, the best approach is to maintain number of the beds at four but make
the area larger.
Thus, 1/3 increase in area
18400m 3 / d
q
2(1.333)( 21.3m 2 )
216m 3 / d m 2
For trial,
A 1.333(21.3m 2 )
A 28.4m 2
width of two cells= 5.2m
45
A
Length of each all (L)
W
28.4m 2
2(2.6m)
5.5m
vB 0.01m / s 36m / h
maximum flowrate of backwash water per troughs
36m / h(2.6m)(1.1m 0.8m)
177.8 or 180m3 / h
basing from figure 11-13
vB 180m3 / h
w 30cm
y 23.5cm
depth of trough
23.5cm 30cm 5cm
43.5cm
height to the weir edge above undisturbed media
De D depth of trough 0.15m
0.7m 0.5m 0.435m 0.15m
0.785 or 0.8m
volume of backwash water for 15 min(0.25h)
36m / h(2 cells )( 2.6m)(5.5m)(0.25h)
257.4m3
privided two times of this volume
520m3
backwash tank should be 11m above the of the wash troughs
v2
velocity head
2g
Where:
46
v= water velocity, m/s
(1.8m/s) 2
velocity head
2(9.81m/s 2 )
0.165 or 0.17m
velocity plus entry head loss
v2
1.7
2g
(1.8m / s ) 2
1.7
2(9.81m / s 2 )
0.28m
where:
Qww=wash water discharge, m3/s
b= width of the gullet, m
1/ 2
2(0.286m 3 / s) 2
H (0.73) 2 2 2
(9.81m / s )(0.6m) (0.73m)
0.7548 or 0.8m
47
Depth of the gravel = 0.3m
Elevation head at point 1 = water depth + depth of sand, gravel and underdrain
= 3.6m
v2
Velocity headloss 0.17m
2g
p v2
pressure 2 z1 hL
2g
3.6m - 0.17m - 0.76m
2.7m
hL 3.43m (negative pressure)
p2
3.6m 0.17m hL
3.43m hL
D box depth of water depth of media depth of underdrain factor of safety freeboard
48
8. DISINFECTION
A. Selection of Disinfectants
49
a
Ct values to achieve > 2.0 log inactivation are very high at common water
temperatures.
For groundwater, the TOC, Bromine, Turbidity, Giardia cysts, Wires and
cryptosporidium cysts concentration are given in Table 1.2.
A. Constituent Concentration
TOC 0.7 mg/L
Bromide 0.5 mg/L
Turbidity 10-30 NTU
Giardia cysts <0.25/100 L
Virus <1/1000 L
Cryptosporidium Oocysts 0.3 / 100 L
Table 2.19:Groundwater Analysis
50
a) Selection of Primary Disinfectant
Yes
High AOC?
No
Biological Treatment
BAF or GAC
No Yes
High DBPFP?
Extended
Treatment to
Distribution
reduce DBPFP
Time
Yes No
Chlorine
Chlorine Chlorine Dioxide
Chloramine Chloramine Figure 2.7: Selection of Secondary
Disinfectant
51
a) The concentration of TOC is less than 2 mg/L so it is considered low. Bromide
concentration in the water is low. From Figure 1.0, the primary disinfectants are
chlorine dioxide, chlorine, ozone, and UV.
b) Comparison of chlorine dioxide, chlorine, ozone and UV in Table 1.0 reveals the
following highlights:
Chlorine dioxide, ozone, and chlorine are not clearly superior with respect to the
production of byproducts (THM, oxidized organic matter, halogenated organic
matter, inorganic byproducts, and BOM). UV is clearly superior.
Ozone and UV do not have MRDLs (Maximum Residual Disinfectant Level) while
chlorine and chlorine dioxide does.
Ozone, UV, and chlorine dioxide can achieve >2.0 log Giardia inactivation while
chlorine cannot. All of them can achieve >2.0 log virus inactivation. The required
log removal for Giardia Cysts with a concentration of <0.25/100 L is 3 log while
the virus with a concentration of <1/100 L, the required log removal is 4 log. The
conventional filtration credit for Giardia Cysts removal is 2.5 and 2 for viruses.
Therefore, all can meet the additional disinfection required.
For the concentration of Cryptosporidium Oocysts, 1 log treatment is required for
the additional conventional filtration treatment requirements including softening and
for additional direct requirements 1.5 log treatment is required.
c) From table 1.0, with the exception of safety concerns, ozone, chlorine, chlorine
dioxide are very comparable. UV has a moderate safety concerns and moderate
equipment reliability concerns.
d) Based on this analysis, ozone is selected as the primary disinfectant with the
understanding that flow will be no residual and that AOC will be a problem.
e) From Figure 1.0, the flow path leads to a requirements for biological treatment and
high DBPFP.
f) The secondary disinfectant choices are UV, chlorine dioxide, and chorine. Because
chlorine dioxide is rated s (sometimes), UV is rated as n (No), and Chlorine is rated as
y (Yes) in Table 1.0, Chlorine is selected as secondary disinfectant.
52
C. Ozonation
i. Design Input
pH = 7.5
T = 5ºC
Second order rate constant = 3.5 L/mol.s
Transferred dose = 2.00 mg/L.
c. Determine the required Ct to achieve the required log inactivation for each
constituent at a temperature of 5 ºC.
53
d. Determine the required hydraulic residence time with the bench-scale best dose of
2.0 mg/L, transferred dose, the required is
32mg min/ L
16 min
C 2.0mg / L
If the ozone concentration remains constant throughout the contact chamber, the
theoretical hydraulic detention time with the consumed t10 / t0 of 7 is
t10 16 min
0.7
t0 t0
16 min
t0 22.86 min
0.7
e. Because ozone generating capacity is expensive and the energy assumption is high,
Rakness (2005) recommend an optimized designs that makes the decay into
account by numerical integration. To perform the numerical integration, the
concentration leaving each chamber must be estimated. This requires the decay
rate constant is compatible units for Ct calculations the conversion is
L 48,000mg
3.5 x 7.29 x10 5 L / mg s or 4.38x10 - 3 L / mg s
mol s male of ozone
54
D. Chlorination
i. Design Input
Chlorine demand = 2 mg L
b.Detention Time
Lowest Operating Volume
Total Detention Time
Peak flow
77,164.64 gal
250 gal mij
308.66 min
c. Contact time
Contact Time = Total Detention Time x Baffling factor
ContactTime 308.66 x0.7
216.06 min
Ct calc. = Residual chlorine concentration x contact time
mg
Ct 0.1 x 216.06
L
mg
21.60
L. min
d.Chlorine Dose
Chlorine dose = Chlorine demand + chlorine residual
Chlorine Dose 2.0 1
mg
2.1
L
55
VI. Equipment Design
1. INTAKE WELL
A. Design Basis
i. Input
𝑚3
Design Flow Rate = 190 𝑑
56
iv. Pumping test results
𝑚3
Drawdown at observation well 300.0m from test well pumped at 0.035 𝑠
Time, min Drawdown, m
100 3.10
500 4.70
1,700 5.90
Table 3.2: Pumping Data Results
B. Design Criteria
Pump
Maximum Efficiency 32 m3/h
Total Dynamic Head 62.15 m
Nominal size of pump bowls 102mm-508mm
Upflow Velocity Less than 1.5m/s
Upper Well casing and Pump Housing
Diameter 100mm larger than the pump diameter
Vertical velocity Less than 1.5 m/s
Anticipated Well yield Less than 545 m3/d – 32,700 m3/d
Optimum size of well casing 152mm-305mm ID
Smallest size of well casing 127mm-305 ID
Well Screen
Aquifer thickness Greater than 16m
Screen length 80% of aquifer thickness
Diameter 0.05m-0.15m
Screen entrance velocity Maximum of 0.03m/s
Screen slot size 40%-60% passing value
Table 3.3: Well and Pump Design Criteria
C. Design Specifications
Design Specs Values
Number of wells 2
Well Diameter 0.15 m
Total drawdown 12 m
Well depth 189.5 m
Screen slot size 2.83
Screen diameter 0.15 m
Screen length 9.16 m
Hydraulic conductivity 6.29 m/d
Entrance velocity 0.003 m/s
Total dynamic head 62.15 m
Number of stages 20
Table 3.4: Design Specifications of Intake Well
57
D. Design Procedure Step 1:
Estimate number of wells
Step 2:
Calculate pump size
Step 3:
Assume well diameter
Step 4:
Calculate
1. Transmissivity
2. Storage Coefficient
3. Dragdown
Step 5:
Assume well depth
Step 6:
Calculate slot size
Step 7:
Select screen diameter
Step 8:
Calculate screen length
Step 9:
Calculate Hydraulic conductivity
Step 10:
Check screen entrance and entrance
velocity
Step 11:
Selection of pump
Step 12:
Obtain pump intake elevation
58
E. Design Calculation
Based on the rule of thumb for a small system, 6 hours pumping time is
selected daily.
𝒎 𝟑
Expected well yield, 𝒅 Well casing ID, mm
<500 150
400-1000 200
800-2000 250
2000-3500 300
3000-5000 350
4500-7000 400
6500-10000 500
8500-17000 600
Table 3.5:Recommended well casing diameter
From the recommended well casing diameter if Q<500 the trial diameter is 15
cm.
𝐷 = 15 𝑐𝑚
1. Transmissivity
Transmissivity can be obtained from the pumping test data in table 2.3.
𝑄′ 𝑡2
𝑇= ln( )
4𝜋(𝑆2 − 𝑆1 ) 𝑡1
59
where: 𝑇 = 𝑡𝑟𝑎𝑛𝑠𝑚𝑖𝑠𝑠𝑖𝑣𝑖𝑡𝑦
𝑄 ′ = 𝑟𝑎𝑡𝑒 𝑓𝑟𝑜𝑚 𝑝𝑢𝑚𝑝𝑖𝑛𝑔 𝑡𝑒𝑠𝑡
𝑆2 = 𝑑𝑟𝑎𝑤𝑑𝑜𝑤𝑛 𝑓𝑖𝑛𝑎𝑙
𝑆1 = 𝑑𝑟𝑎𝑤𝑑𝑜𝑤𝑛 𝑖𝑛𝑖𝑡𝑖𝑎𝑙
𝑡2 = 𝑓𝑖𝑛𝑎𝑙 𝑡𝑖𝑚𝑒
𝑡1 = 𝑖𝑛𝑖𝑡𝑖𝑎𝑙 𝑡𝑖𝑚𝑒
𝑚3
𝑄0.035 1700 𝑚𝑖𝑛
𝑠
𝑇= ln( )
4𝜋(5.9 𝑚 − 3.1 𝑚) 100𝑚𝑖𝑛
𝑚2
𝑇 = 2.818 × 10−3
𝑠
2. Storage Coefficient
In Figure 1 , extrapolate the straight line portion of the graph to the virtual
starting elevation of 0.0 m to find the virtual time: t 0= 4.2 min.
2.25 𝑇𝑡𝑜
𝑆=
𝑟2
Where: 𝑟 = 𝑑𝑖𝑠𝑡𝑎𝑛𝑐𝑒 𝑓𝑟𝑜𝑚 𝑡ℎ𝑒 𝑤𝑒𝑙𝑙
𝑇 = 𝑡𝑟𝑎𝑛𝑠𝑚𝑖𝑠𝑠𝑖𝑣𝑖𝑡𝑦
𝑡𝑜 = 𝑣𝑖𝑟𝑡𝑢𝑎𝑙 𝑡𝑖𝑚𝑒
𝑚3
2.25 (2.818 × 10−3 ) (4.2min)
𝑠
𝑆=
(300 𝑚)2
−5
𝑆 = 1.775 × 10
60
3. Estimate drawdown
a. Calculate u
𝑟 2𝑆
𝑢=
4𝑇𝑡
Where: 𝑟 = 𝑡𝑟𝑖𝑎𝑙 𝑟𝑎𝑑𝑖𝑢𝑠
𝑡 = 𝑡𝑖𝑚𝑒 𝑜𝑓 𝑝𝑢𝑚𝑝𝑖𝑛𝑔 𝑡𝑒𝑠𝑡 (100 𝑑𝑎𝑦𝑠)
−3
𝑚3
𝑇 = 2.818 × 10
𝑠
𝑆 = 1.775 × 10−5
(0.075𝑚)2 (1.775×10−5 )
𝑢= 𝑚3 𝑠
4(2.818×10−3 )(100 𝑑)(86,400 )
𝑠 𝑑
𝑢 = 1.025 × 10−12
b. Calculate W(u)
𝑢2 𝑢3
𝑊(𝑢) = −0.577216 − 𝑙𝑛𝑢 + 𝑢 − + −⋯
2 × 2! 3 × 3!
c. Calculate S
𝑞
𝑆= 𝑊(𝑢)
4𝜋𝑇
𝑚3 1ℎ
(32 ) (3600𝑠)
ℎ
𝑆= 𝑚3
(27.03)
4𝜋(2.818 × 10−3 )
𝑠
𝑆 = 6.785 𝑚 𝑜𝑟 6.8 𝑚
No potential for failure of the well due to dewatering the aquifer since
the top of the artesian aquifer is 150.8 m below grade.
Figure 3.2: Grain size analysis for selection of screen slot size
𝐷40%
𝑈=
𝐷90%
0.84
𝑈=
0.297
𝑈 = 2.83
𝑇
𝐾=
𝐷
where:
62
𝐷 = 𝑡ℎ𝑖𝑐𝑘𝑛𝑒𝑠𝑠 𝑜𝑓 𝑠𝑎𝑛𝑑 𝑙𝑎𝑦𝑒𝑟
𝑇 = 𝑡𝑟𝑎𝑛𝑠𝑚𝑖𝑠𝑠𝑖𝑣𝑖𝑡𝑦
𝑚2
2.818 × 10−3 𝑠
𝐾=
38.7 𝑚
Nominal No. No. No. No. No. No. No. No. No. No.
screen 10 15 20 25 30 40 50 60 80 100
diameter, slot slot slot slot slot slot slot slot slot slot
mm 0.25 0.38 0.50 0.64 0.76 1.0 1.3 1.5 2.0 2.5
mm mm mm mm mm mm mm mm mm mm
𝑚2
Intake area, 𝑚 of screen length
150 .053 .076 .097 .116 .133 .165 .193 .214 .252 .282
200 .087 .123 .152 .182 .207 .252 .288 .320 .370 .409
250 .061 .091 .116 .142 .163 .205 .243 .275 .332 .379
300 .074 .106 .138 .167 .193 .243 .288. .326 .394 .449
350 .080 .116 .150 .182 .212 .267 .313 .358 .432 .491
400 .085 .125 .161 .195 .226 .286 .339 .387 .470 .538
450 .095 .138 .178 .216 .252 .318 .375 .428 .519 .595
500 .114 .167 .214 .260 .303 .379 .447 .508 .614 .701
600 .097 .142 .184 .226 .265 .339 .404 .466 .578 .671
660 .104 .152 .197 .241 .284 .360 .432 .497 .614 .715
760 .119 .174 .226 .277 .326 .415 .497 .572 .707 .821
900 .144 .210 .273 .332 .389 .497 .597 .688 .849 .986
Table 3.6: Representative open areas of screen
𝑠𝑙𝑜𝑡 𝑛𝑢𝑚𝑏𝑒𝑟 = 20
𝐷𝑖𝑎𝑚𝑒𝑡𝑒𝑟 𝑜𝑓 𝑤𝑒𝑙𝑙 = 15 𝑐𝑚
2
𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑜𝑝𝑒𝑛 𝑎𝑟𝑒𝑎 = 0.097 𝑚 ⁄𝑚
63
Hydraulic conductivity, m/d Optimum screen entrance velocity ,m/s
<20 0.010
20 0.015
40 0.020
80 0.030
120 0.040
160 0.045
200 0.050
240 0.055
>240 0.060
Table 3.7: Optimum screen entrance velocities
Since K<20
𝑆𝑐𝑟𝑒𝑒𝑛 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦 = 0.010 𝑚⁄𝑠
𝑞
𝑆𝐿 =
(𝐴)(𝑣)
Where:
𝑆𝐿 = 𝑅𝑒𝑐𝑜𝑚𝑚𝑒𝑛𝑑𝑒𝑑 𝑙𝑒𝑛𝑔ℎ𝑡
𝐴 = 𝐸𝑓𝑓𝑒𝑐𝑡𝑖𝑣𝑒 𝑜𝑝𝑒𝑛 𝑎𝑟𝑒
𝑞 = 𝑑𝑒𝑠𝑖𝑔𝑛𝑒𝑑 𝑝𝑢𝑚𝑝 𝑟𝑎𝑡𝑒
𝑣 = 𝑠𝑐𝑟𝑒𝑒𝑛 𝑣𝑒𝑙𝑜𝑐𝑖𝑡𝑦
𝑚3 1ℎ
(32 )(
)
ℎ 3600𝑠
𝑆𝐿 =
(0.097)(0.010 𝑚⁄𝑠)
𝑆𝐿 = 9.16 𝑚
3 1ℎ
(32 𝑚 ⁄ℎ) (3600 𝑠)
𝑣=
3.0𝑚2
𝑚
𝑣 = 0.003 ⁄𝑠
The entrance velocity criteria are met with the longer screen.
64
TDH = static lit to ground level + static lift to the top of the reservoir + minor
losses + hf + hv
Where:
ℎ𝑓 + ℎ𝑣 + 𝑚𝑖𝑛𝑜𝑟 𝑙𝑜𝑠𝑠𝑒𝑠 = 0.15 𝑚
𝑠𝑡𝑎𝑡𝑖𝑐 𝑙𝑖𝑡 𝑡𝑜 𝑔𝑟𝑜𝑢𝑛𝑑 𝑙𝑒𝑣𝑒𝑙 = 12𝑚
𝑠𝑡𝑎𝑡𝑖𝑐 𝑙𝑖𝑓𝑡 𝑡𝑜 𝑡ℎ𝑒 𝑡𝑜𝑝 𝑜𝑓 𝑡ℎ𝑒 𝑟𝑒𝑠𝑒𝑟𝑣𝑜𝑖𝑟 = 50𝑚
𝑇𝐷𝐻 = 12 + 50 + 0.15
𝑇𝐷𝐻 = 62.15𝑚
From the pump given, the maximum number of stages is 35. Therefore this is
acceptable.
Therefore, the pump intake is set 1.0m below the maximum 100 day
drawdown to meet both requirements.
65
F. Design Figure
Static nonpumping
water level
NPSHA=9.6m
6.8m
well screen
38.7m Sand aquifer
66
2. SURFACE AERATOR
A. Design Basis
i. Input
hp req 0.3839 hp
B. Design Criteria
Different KASCO Surface Aerators
Model Size, hp Min. Depth, inch Voltage, V Running Amps
2400AF ½ 15 120 5.0
3400AF ¾ 18 120 6.7
3400HAF ¾ 18 240 3.4
4400AF 1 19 120 11.3
4400HAF 1 19 240 5.7
8400AF 2 20 240 9.0
2.3AF 2 20 230V 3 4.5
3.1AF 3 24 240 10.7
3.3AF 3 24 230V 3 8.2
5.1AF 5 26 240 18
5.3AF 5 26 230V 3 13
Table 3.8: Different KASCO Surface Aerators
C. Design Specification
Based on KASCO MODEL floating aerator:
Design Value
Model type 2400AF
Motor power 0.5 hp
Voltage 115V
Running Amps 5.0 ampere
Float width (A) 28 inches
Unit height (B) 15 inches
Minimum operating
15 inches
depth (C)
Table 3.9: Design Specs of KASCO MODEL floating aerator
For the tank dimension (using typical size required for groundwater):
Design Value
Water depth 6 meters
Tank diameter 18 meters
Total height of tank w/
6.6 meters
10% excess
Table 3.10: Tank dimensions
67
D. Design Figure
TOP VIEW
ISOMETRIC VIEW:
68
3. SOFTENING
A. Design Basis
i. Input
Design Flow rate = 7,400 m3/d
Weirs = 8
B. Design Criteria
C. Design Specification
69
D. Design Procedure
Select Tank
Diameter
Is the unit
acceptable for
the detention
time?
Change volume
Calculate volume and
of basin.
detention time of the
truncated cone.
Is the detention
time greater
than or equal
to 30 minutes?
Select volume of Select volume of
truncated cone truncated cone.
a. Trial selection of 12 m diameter tank to check the overflow rate using the
separation zone area.
Q
v
As
7,400m 3 / d
v
100m 2
v 74m / d
v 3.08m / h
The GLUMRB design guidance is less than 4.2 m/h. Therefore, the unit is
acceptable for overflow rate.
b. Detention time for softening using the volume of the basin.
t
Q
580m 3
t
7,400m 3 / d
t 0.078d
t 1.88h
The GLUMRB design guidance is one to two hours. Therefore, the unit is
acceptable for the detention time.
c. Checking of mixing time by calculating the volume of the truncated cone and
calculating the detention time in the cone. The volume of the cone is
h
3
r1 2 r1r2 r2 2
Where h = height of the truncated cone
r1= radius of the bottom of cone
r2 = radius at top of cone
For the trial tank values of h, r1, and r2are taken from Table 7-4.
3.6m
3
6.52 6.5m2m 2m2
223.4m 3
The mixing time in the cone is
223.4m 3
t
7,400m 3 / day
t 0.030day
t 43.46 min
The GLUMRB design guidance is a minimum of 30 minutes. Therefore, the unit
is acceptable for mixing time.
d. Checking weir length by computing the length of the weir taking into account that
there are eight weirs and that water enters both sides of each weir.
71
12m 1.3m
L 8weirs 2sides / weir
2
L 85.6m
With a flow rate of 7,400 m3/d, the weir hydraulic loading is
7,400m 3 / day
WL
85.6m
WL 86.45m 3 / day m
WL 0.06m 3 / min m
The GLUMRB design guidance is a maximum of 0.240 m3/min m of weir length.
Therefore the unit is acceptable for weir loading.
F. Design Figure
72
A. Design Basis
i. Input
Flow Rate (Q): 383 m3/hr
Viscosity (μ): 1.081x10-3 Pa-s
Water Temperature: 17°C
B. Design Criteria
Root Mean Square of Velocity Gradient (G): 3000 to 5000 s-1
Detention Time (t): Approximately 5 seconds
Head Loss: 0.3 to 0.9 m
C. Design Specification
1. Manufacturer Model: AZ-6
Chamber Diameter: 36 cm
Length: 60 cm
Power: 1500 W
2. Water Power: 80% of motor power
D. Design Procedure
Step 1:
Selection of Mixing Method
Step 2:
Specify the conditions of the input stream
Step 3:
Specify the design criteria
Step 4:
Assume a manufacturer mixed for the mixer
Step 5:
Calculate the velocity gradient and detention time
No
Step 6: Stop
73
E. Design Calculation
61,072cm3
t
Q
Where: = Volume
Q = Flow Rate
t = Detention Time
(61,072cm3 )(10 6 m 3 / cm3 )
t
383m3 / hr
t 1.5946 x10 4 hr
t 0.57s
The calculated value of RMS of velocity gradient (G) and detention time (t) have
met the design criteria recommended for adsorption/destabilization reactions.
Therefore, the manufacture model AZ-6 is satisfactory for the process.
74
F. Design Figure
75
5. PADDLE FLOCCULATOR
A. Design Basis
i. Input
t = 22 min
B. Design Criteria
Parameter Value
Detention time 30 min
Flocculation At least 3 compartments
Flow velocities 0.15-0.45 m/s
Water depth 3-5 m
Baffle wall:
1-2 cm (slightly submerged)
Top of baffle
2-3 cm (above floor
Bottom of baffle
Table 3.12: Design Criteria of Paddle Flocculator
76
C. Design Specification
77
D. Design Procedure
78
E. Design Calculation
To provide redundancy, the flow will be divided into two flocculation basins
79
STEP 6: Minimum length of stage
80
STEP 11: Orientation of paddle boards
Placing three paddle boards on each of four paddle arms with leading edge at
1/3 points,
1.5m
0.5m
3
Dimensions of each paddle board
15 cm x 3.18 m
81
STEP 12: Power required
C D AP
P [(V at r1 ) 3 (Vat r2 ) 3 (V at r3 ) 3 ]
2
C D AP
P [2 (0.75)n] 3 [( r1 ) 3 (r2 ) 3 (r3 ) 3 ]
2
Area of paddle blade
AP 1.15m(3.18m)
AP 0.477m 2
82
0.15m
r1 0.5m ( ) 0.425m
2
0.15m
r2 1.0m ( ) 0.925m
2
0.15m
r3 1.5m ( ) 1.425m
2
Solving rotational speed
1
2P 3
n 3
C D AP [2 (0.75)] [( r1 ) (r2 ) (r3 ) ]
3 3 3
1
2(232.04W ) 3
n
(1000 kg m )(1.5)(0.477m )(104.65)[( 0.425 ) (0.925 ) (1.425 )]
3 2 3 3 3
1
464.08 3
n
(78877.07)(3.762)
60 s
n 0.116rpsx ( )
1 min
n 6.96rpm
n 7rpm
83
F. Design Figure
Influent from
coagulation
Drive Paddle
motor wheel mixer
Section A-A
84
6. SEDIMENTATION BASIN
A. Design Basis
i. Input
3
Design Flow = 0.5 m s
B. Design Criteria
85
C. Design Specification
86
D. Design Procedure Step 1:
Determine the number of basin
Step 2:
Calculate the basin area
Step 3:
Select a trial width
Step 4:
Check L:W ratio
Step 5:
Assume a trial depth, SWD (side
water depth), sludge depth,
freeboard depth
Step 6:
Calculate the total depth of the
tank
Step 7:
Check the L:D ratio
Step 8:
Determine and check the
horizontal mean velocity
Step 9:
Determine and check the
hydraulic detention time
Step 10:
Calculate the hydraulic radius
Step 11:
Determine and check Reynolds
and Froude number
Step 12:
Assume launder length based
from and design criteria
Step 13:
Determine the number of
launders
Step 14:
Calculate the weir loading rate
Figure 3.14: Design Procedure of Sedimentation Basin
87
E. Design Calculation
n t = 6 tanks
3
Q = (0.5 m s )(86,400 s day)
3
= 43,200 m day
Q
ν OF = ; wh ere Q = process flow rate
As
ν OF = overflow rate
A s = basin area on settling zone
Q
As =
ν OF
m3
43,200
day
As = 6tanks
m3
32.5
day • m 2
m2
A s = 222
tank
Assume,
w=4m
88
STEP 4: Length-To-Width Ratio (L:W)
As
L = width/tank
w
m2
222
tank
m
4 tank
L=
4m
L = 13.8 or 13.8 : 1 ; This is larger tha n the ratio of 6 : 1 and is ACCEPTABLE
STEP 5: Assume,
Sludge depth = 1m
As
L/D = width/tank
trial depth
m2
222
tank
4 m tank
L/D =
2m
L/D = 27.75 or 28 : 1 ; ACCEPTABLE
89
STEP 8: Horizontal Mean Velocity
Design flow
vf = ; whe re A = (n t )(trial depth)(tri al width)
A
m3
0.5
vf = s
(6 tanks)(2 m depth)(4 m width)
v f = 0.0104 m s ; ACCEPTABLE within th e range of 0.005 - 0.018 m s
V
τ= ; wher e V(volume of the basin) = (A s )(trial depth of water) \
Q
m2 m
(222 )(4 )
τ= tank tank
m3 1day
43,200 ×
day 24h
τ = 0.5 hr
Ax
RH =
Pw
depth × width
RH =
2depth × width
(2 m deep)(4 m wide)
RH =
2m + 4m + 2m
R H = 1.0m
Reynolds Number
vf R H
R= ; where R = Reynolds number
υ
R H = hydraulic radius
v f = horizontal mean velocity
υ = kinematic viscosity
90
m
(0.0104 )(1.0m)
R= s
2
1.307 ×10 - 6 m
s
R = 7,957.15 or 8000 ; ACCEPTABLE
Froude Number
(v f ) 2
Fr = ; wher e Fr = Froude number
gR H
v f = horizontal mean veloc ity
g = accelerati on due to gravity, 9.81 m s
R H = hydraulic radius
2
(0.0104 m)
Fr =
m
(9.81 2 )(1.0m)
s
Fr = 1.1 × 10 5 ; ACCEPTABLE
As
n
L launder = t
3
55.5m
L launder =
3
L launder = 18.5m
Place the 18.5 m length of launder at 1 m intervals on center so that there are
91
STEP 14: Weir Loading Rate
Q
WL =
(n t )(n launder )(L launder )(no. of sides )
m3
43,200
day
WL =
(6tanks)(3 launders/t ank)(18.5 m/launder) (2 sides)
m3 m3
WL = 64.86 or 65 : This is well below the limit of 250 ,
day • m day • m
so it is ACCEPTABLE )
F. Design Figure
PLAN VIEW
Walkway Effluent
Influent
Launder length = 18.5
Lc of chain & tee rails
Equipment
tank width
w=4m
Diffusser Wall = 2m
Tank depth = 2m
Influent
Effluent
Sludge
92
settling zone
sludge zone
sludge
raw water clarified water
Q
sludge zone
sludge
settling zone
settling zone
Q
Q sludge zone
sludge zone
93
7. RAPID SAND FILTER
A. Design Basis
i. Input
porosity 0.50
attachment efficiency 1.0
temperatur e T 20C (293K)
particle density 1050kg/m 3
filtration rate v F 15m / h
bed depth L 1.0m
Hamaker constant H a 10 -20 J
Boltzman constant K g 1.381x10 -23 J / K
B. Design Specification
Design Specs Values
Filter media Anthracite and sand
Maximum flow rate 18,400 m3/day
Total number of filters 4
2
Total filter area 28.4 m per filter
Depth of trough 0.435 m
Depth of gullet 1.25 m
Depth of sand 0.6 m
Depth of anthracite 0.3 m
Depth of underdrain block 0.3 m
94
C. Design Procedure
Calculate and As
Get NRfor dc
CalculateNV
Get Pe for dc
CalculateND
CalculateNG
Calculate G
CalculateNA
CalculateN
Calculate Yes
No
Calculate C/Co, log removal Repeat for
new dc? End
value (LRV)
95
D. Design Calculation
1 1/ 3
1 0.5
1/ 3
0.7937
As
1 5
2 3 3 5 2 6
2 1 0.7937
5
2 3(0.7937) 3(0.7935) 5 2(0.7937) 6
21.46
STEP 3: Calculate NV
Ha 1x1020 kgm2 / s 2
Nv 2.47
kgT 1.381x1020 kgm2 / s 2 293.15K
STEP 5: Calculate ND
96
STEP 6: Calculate NG
Density of water at 20C is w 998kg / m3
g ( p w )d 2
NG
18vF
(9.81m/s 2 )(1050 998kg / m3 )(1x10 -7 m 2 )(3600s/h)
18(1x10 3 kg / m s)(15m / h)
6.76x10 -8
STEP 7: Calculate G
STEP 8: Calculate NA
Ha
NA
3 ( )( dp 2 )(vF )
(1x10 -20 kgm 2 /s 2 )(3600s/h)
3 (1x10 -3 kg/m s)(1x10 -7 m 2 )(15m/h)
2.54x10 -2
STEP 9: Calculate N
97
STEP 12: Computation table for other diameters
Media diameter C/CO Log removal
0.4 0.074 1.13
0.6 0.262 0.58
0.8 0.434 0.36
1.0 0.560 0.25
1.2 0.650 0.19
1.4 0.716 0.15
1.6 0.764 0.12
1.8 0.801 1.10
2.0 0.830 0.08
Table 3.17: Other Diameters
E. Design Figure
5.5000
0.5000
influent 0.4000
0.4000
2.5000
sand 0.6000
athracite 0.3000
underdrain block 0.3000
effluent
98
2.6 2.6
1.1
wash trough
1.6
Gullet
wash trough
5.5
1.6
wash trough
1.1
0.6
99
8. CONTACT CHAMBER
A. Design Basis
i. Input
Water temperature = 5 ºC
t10
Performance ratio 0.7
t0
Second order rate constant = 3.5 L
mol.s
mg
Transferred dose = 2
L
3
Flow rate = 18400 m
day
B. Design Criteria
Baffle Classifications
Performance t10/t0 Baffling Description
Unbaffled (mixed flow), agitated, very low length-
Very poor 0.1
to-width ratio, high inlet and outlet flow velocities.
Single or multiple unbaffled inlets and outlets, no
Poor 0.3
intrabasin baffles.
Perforated inlet or outlet with some intrabasin
Average 0.5
baffles.
Perforated inlet baffle, serpentine or perforated
Superior 0.7 intrabasin baffles, outlet weir or perforated
launders.
Very high length-to-width ratio (pipeline flow),
Perfect 1.0
perforated inlet, outlet, and intrabasin baffles.
Table 3.18:Baffle Classifications
C. Design Specification
Design Specs Calculated Values
Contact Time (Ct ) 31.846 mg.min/L
Hydraulic residence time 16 min.
Theoretical hydraulic residence time (t0) 22.86 min.
Volume of the chamber 292.1 m3
Contact Chamber
Depth 6 m.
Length 16.5 m.
Width 3.25 m.
Tabl.e 3.19: Design Specification of the contact Chamber
100
D. Design Calculation
a. Assume 10 cells
concentration of cell inf luent
C
1 (order rake cons tan t ) ( HDT ) (concentration of cell inf luent )
18400m3 1day
V to Q (22.86)min x x 292.1 m3
day 1440 min
Using Henry and Freeman (1996)
L : W = 1 :1 assume H 6
H : L = 4 :1 H 4L
H 6
L 1.5m / cell
4 4
292.1 m3 (6m) (1.5 m/cell) (10cell) (width)
Width = 3.25 m
1.5 m
L (10 cell) 15 m 1.5 16.5
cell 101
Depth = 6 m
E. Design Figure
Off –gas to ozone
destruct units
Influent
1.5 m
water
6m
3.25 m Effluent
water
102