RULES for working in areas with high-voltage must be
• Click on the Go button. obeyed AT ALL TIMES!
A histogram will be accumulated over a specified time
period. The progress bar at the bottom will indicate NEVER touch parts which are under high-voltage!
Measuring the progress of this operation. The high-voltage set-up MUST NOT be used without being
With a right-click on the histogram a “screenshot” will earthed!
be saved as PNG file.
All of the data gathered during a measurement may be recorded for later
analysis by clicking on the button. Be sure to have enough hard disk manufactured by:
space.
OMICRON Energy Solutions - Developement Center, Berlin, Germany
info@omicron.at
distributed by:
OMICRON electronics GmbH, Klaus, Austria
info@omicron.at
A
Units and Software Accessories
• One fiber optics controller MCU 502, 504, or 550 • Fiber optic cable(s)
• One (or more) acquisition unit(s) MPD 600 with battery pack(s) • BNC cables
MPP 600
What is in
• One quadripole/measuring impedance unit CPL 542 • Battery cable(s)
the Box?
• MPD 600 software CD • USB cable
• Optional: One charge calibrator CAL 542
B
MPD600 Software - System Requirements Installation:
• PCwith Intel Pentium 4 (≥ 2.5 GHz), Pentium M (≥ 1.5 GHz), • Insert the software CD into the CD/DVD drive of the computer.
Core, Core 2 processor; or AMD Athlon 64 or Turion 64 processor
• 1 GB RAM; USB 2.0 compatible • The installation starts automatically.
Software
Setup • Microsoft Windows XP, 2000 Professional, or VISTA • Follow the instructions on the screen.
System
Setup
C NOTE:
The plugs are color-coded!
Connect the MPP 600 battery pack to the MPD 600 acquisition
unit using the battery cable. The red LED at the MPD 600 unit
starts flashing indicating that the acquisition unit is ready for
operation.
Connect the CPL 542 quadripole/measuring impedance unit.
Use two short BNC cables and connect the PD and V outputs of
the CPL 542 to the PD and V inputs of the MPD 600.
Connect the CPL 542 unit to a high voltage coupling capacitor
and earth the system. Keep the cable(s) as short as possible.
Connect the MCU unit to the Computer using the USB cable.
D
Start the PC and doubleclick on the
high voltage area
MPD software icon on the desktop.
If the software doesn’t start in Basic Mode select the main menu item Mode and choose Basic.
System • Select the Settings Tab.
Calibration • Select unit 1.1 in the Trigger source box. (If you are performing a calibration you may also select “line” as trigger source. The system then
uses a light-sensitive sensor to synchronize itself to fluorescent light sources. Do not forget to change the trigger source back to unit 1.1
before performing the actual measurement)
• Enter 350 kHz into the fCenter box.
• Select 300 kHZ in the Bandwidth box.
This configuration sets up the system for an IEC60270-compliant measurement.
The option High Sensitivity Mode should be unchecked to prevent the MPD unit from damage.