A Comparative Study of Retrofitting Of R.C.

Building
Using Steel Bracing And Infill Walls
www.engineeringcivil.com/a-comparative-study-of-retrofitting-of-r-c-building-using-steel-bracing-and-infill-walls.html

By
Prof. Pravin B. Waghmare
Acharya Shrimannarayan Polytechnic Pipri (M)- Wardha-Maharashtra

Abstract
The objective of this study is to identify an efficient retrofitting method for existing open
ground story reinforced concrete frame buildings. Failure of several soft-stored buildings
in the past earthquakes underscores the need to retrofit existing soft-story buildings. A
common cause for the collapse of multi-storied buildings is the occurrence of soft story in
the ground floor due to the presence of infill walls in the upper story. During the Bhuj
(Gujarat) earthquake of 6thJanuary 2001 several soft storied building failed there by
confirming the vulnerability of such buildings to earthquake loading. This underscores the
need to retrofit existing soft story buildings to prevent their total collapse. The existing
building structures, which were designed and constructed according to early codal
provisions, do not satisfy requirements of current seismic code and design practices. A
two dimensional R.C. frame designed with linear elastic dynamic analysis using response
spectrum method. The computer software package STAAD Pro–2005 is used for
dynamics analysis technique is used to assess the performance of a (G + 4) reinforced
concrete buildings, of which the ground storey is a parking facility the ground storey is
3.5m high while the upper stories giving a total height of 15.5 m. the building is located in
Seismic Zone IV.

The RC frame is retrofitted by three methods namely,


1) Brick masonry infill in the ground story.

2) Steel braces in the ground story.

3) R.C. Structural wall in the ground story.

The study concludes that the building designed as per provisions of IS: 456:2000 using
limit state method of design, and analyzed as per existing seismic code IS: 1893-2000 of
all these three methods studied the use of structural wall in the ground story panel gave
the maximum strength and ductility.

Keywords: Open ground storey, brick infill, RC wall Infill and Steel Bracing.

INTRODUCTION
The objective of this study is to identify an efficient retrofitting method for existing open
ground storey reinforced concrete frame buildings. A two dimensional RC frame,
designed with non-ductile detailing, is subjected to non-linear static pushover analysis
with code specified design shear distribution. The RC frame is retrofitted by three
Methods, namely (1) RC structural wall in the ground storey panel.2) brick masonry infill

1/7
in the ground storey and 3) steel bracing in the ground storey. Of all three methods
studied, the use of structural wall in the ground storey panel gives maximum strength and
ductility.

Reinforced Concrete (RC) is the popular material for building construction in India. Also
construction in RC is considered to be labour intensive and supposedly requires lesser
high tech tools, infrastructure and skills, than those in structural steel. Low and medium
rise RC frame buildings with masonary infill are very common in urban India (fig 1). The
2001 Bhuj earthquake is the first significant One in the past five decades to have struck
the urban constructions of India in big way, and to have provided revealing evaluation of
the seismic resistance of engineered Buildings. Numerous RC frame buildings collapsed
during the 2001 Bhuj earthquake proving that the surge of construction over the last
decade has not adequately addressed their seismic safety. Most affected multi storey
buildings are 5 storeys high (Ground+ 4 storeys), and many up to11 storeys (Ground
+10); the basement storeys are additional. Typical storey height varies from 2.6m to 3.2
m. in most of the buildings; the ground storey is left open to accommodate the parking.
Some of the buildings have partially filled ground storeys. In contrast to the infilled upper
storeys, the open ground storey may cause; (a) soft storey effect: the open storey may
have smaller stiffness and cause increased deformation demand in the frame members
of the storey; and (b) Weak storey effect: the open ground storey may have lower lateral
strength and cause a discontinuity in flow of lateral seismic shear in that storey.

Advertisements

Retrofitting of buildings is required to overcome the seismic deficiency:


Three levels of improvement of existing RC frame buildings are possible, namely (a)
Repair: only cosmetic modifications are made, (b) Restore: structural modifications are
made such that the original seismic performance of the building is restored, and (c)
Strengthen: structural modifications are made such that a higher seismic performance of
the building is achieved than that of the original undamaged structure.
The paper presents an overview of some of the retrofitting measures of RC frame
buildings. A reduced scale of a (G+3) double bay storied brick infilled RC frame with open
storey is analyzed till failure. Then three retrofitting methods re applied on the frame in
the open ground storey, namely (a) open ground storey (b) infilling with brick masonary
(specimen BMI), and (c) introduction to RC structural walls (specimen SW)(d) steel
bracing (specimen SB). The results are compared to estimate the efficiency of these
three methods.
RETROFIT SCHEMES
Strengthening schemes are implemented as part of either post earthquake Restoration of
buildings or as pre-earthquake preparedness. The aims of strengthening measures are
to provide increased ductility to structures. In Indian scenario, the relevant retrofitting
schemes are (a) open ground storey (b) masonry infilling in RC frame, (c) RC structural
wall, considering cost and feasibility of schemes. RC walls and steel bracings (e.g.,
Jordan, 1990; Pincheira and Jirsa, 1995; Ghogarah andYoussef, 2000).

During the 1985 Mexico City earthquake [Bertero et al. 1995], unreinforced masonry
2/7
infills performed favorably well as poorly in a large number of medium- rise RC frame
buildings in Mexico City. RC buildings with indiscriminate use of brick infills sustained
severe structural damage during 1997 Jabalpur earthquake. Good quality masonry
construction brought out the desired performance of low-rise buildings with masonry infill
walls in 1992 Cairo earthquake and in Uttarkashi Earthquake. Medium rise RC frame
buildings with structural walls performed commendably in 1985 Chile earthquake [Chile,
1986]. Although there were instances of failure of RC walls in san Salvador earthquake
[San Salvador, 1986] and Armenia earthquake [Armenia, 1988], the walls prevented
collapse of entire buildings.

For a particular building, the performance of a specific retrofitting scheme depends on the
properties of the original building, and the characteristics of the expected ground motion
at the site. Thus a quantative comparative study of the retrofitting schemes needs to be
done for the judicious selection of the final scheme. The prescriptive methods of
strengthening of buildings being recommended lately in urban India lack the quantative
rigour. Two quantative approaches for seismic retrofitting have been elaborated [Murty,
2002], namely (a) simple approach which focuses on strength and stiffness aspects
alone, and (b) state of the art approach which addresses ductility in addition to the other
two. The following study of a two dimensional RC frame is based on the second
approach.

ANALYTICAL STUDY
A (G+3) storeyed two bay RC frame with open ground storey and brick infilled top storey
is considered with the storey heights as 3m and 3.5m for the top and the ground storeys
respectively. The bay width is taken as 5m.The frame is assumed to be fixed against
translation in all directions and rotation about all axes at the bottom nodes. The design
lateral force on the infilled frame was estimated using the Indian Seismic Code [IS: 1893,
2002]. The frame was modeled in STAAD-PRO 2005 and linear Elastic analysis was
carried out under the lateral force. The frame members were designed and detailed
(figure 3) for the corresponding stress resultants as per Indian Concrete code [IS 456,
2000]. The details of beam and column are as shown in table1. The thickness of the brick
infill is taken as 150mm to flush with the column size

Table No.1: Details of building.

Sr.No Particulars Details/values

1 Type of building Residential

2 No. of storeys G+3

3 Spacing of frames in x direction 5m

4 Spacing of frames in z direction 5m

3/7
5 Number of bays in x direction 2

6 Number of bays in z direction 1

7 Each storey height 3m

8 Size of columns 230 x 350 mm

9 Size of beams 230 x 350mm

10 Grade of concrete M20

11 Grade of Steel Fe415 and Fe250

12 Thickness of RC Wall 100mm

13 Thickness of brick infill 150mm

14 Size of steel bracing section 2 ISA 150x115x12mm

Lateral pushover analyses of specimen OGS are performed using STAAD-PRO


2005.The infill was modeled as single strut element with possibility of forming axial hinge
.the strut hinge properties were computed as per the existing model [Rein horn et al.,
1995]. For the beams, the moment (M-?) hinge and the shear hinge (V-?,) were provided,
and for the columns the moment hinge, shear hinge and axial force moment (P-M)
interaction hinge were provided. The analysis stopped when a mechanism was formed in
the frame.

Advertisements

The model OGS was strengthened by the following retrofitting schemes. Each of them
was modeled in STAAD PRO 2005 and subjected to lateral pushover analysis for
estimating their limiting characteristics.

4/7
Figure No. 1: Elevational views of specimens for analysis.

1) BRICK MASONARY INFILL:


The open ground storey panel was filled with 150mm thick brick masonary.thus in the
model BMI, an additional strut was introduced in the frame in place of ground storey
panel. The contribution of cracked concrete in the shear capacity of ground storey
columns was neglected while determining the capacity of shear hinges

2) STRUCTURAL WALL:
Basically, the structural wall was introduced in the open panel of the ground storey. A
single layer of reinforcement was provided for the 100 mm thick RC structural wall
designed as per the Indian standard for ductile detailing [IS13920, 1993].

3) STEEL BRACING
The open ground storey column beam junction were steel braced by angle sections of
size double angle ISA 150 x 115 x12mm.

5/7
RESULTS
The comparative pushover curves fig.2 (b) show that the model SW exhibits the
maximum frequency of 53.09 Hz at a time period of 0.019 sec, for mode no.06.The
6/7
model BMI with masonry infill shows brittle failure. The strength of model BMI peaks up
at 49.315hz at 0.02 sec time period shown in figure 2 (b). Similarly for steel bracing the
curve shown in fig. 2(a) with respect to open ground storey curve shown in fig. 2(d)

CONCLUSIONS:
The salient conclusions of the study are:

1) For the open ground storey frame, retrofitting by means of introducing RC structural
wall in the open ground storey, offers the maximum strength (frequency) and ductility.

2) Although the initial stiffness of the brick masonry infilled specimen is more than that of
the other specimen, at higher displacement levels, and the RC structural wall specimens
gave better stiffness.

3) Introducing the RC structural wall in the open ground storey gives the most desirable
behaviour for the two dimensional frame from the points of view of strength, stiffness
ductility and frequency profile.

Advertisements

REFERENCES
1. Armenia Earthquake Reconnaissance Team (1986),”Performance of Engineered
structures”, earthquake spectra, special supplement, august 1989 EERI, pp.70-92.
2. Chile Earthquake Reconnaissance Team,(1986),”Performance of structures”,
Earthquake Spectra, vol.2 EERI pp 293-371.
3. Ghobrah, A; and Youseef, M ;( 2000),”Rehabilation of RC Buildings using structural
Walls” 12th world conference in earthquake engineering, CDROM Paper no 0153.
4. IS 456:2000,(2000),Indian Standard code of practice for plain and reinforced concrete
,Bureau of Indian standards New Delhi.
5. IS 1893:2002(2000) Indian standard criteria for earthquake resistant design of
Structures Part 1: general provisions and buildings, Bureau of Indian Standards, New
Delhi.
We are thankful to Shri.Pravin B.Waghmare for publishing A Comparative Study of
Retrofitting Of R.C. Building Using Steel Bracing And Infill Walls. This will be of great use
to all civil engineers who are looking to understand the concept of retrofitting.