4 Short Circuit Current Calculation

ISC ( KA ) =
R X RT XT
Uo / ( √3 * √ ( R2T +X2T))

HV network = 1.5 * X =U2o / Psc Psc (MVA) / √3 * (KVA)


0.052 0.344 =
Psc ( MVA) 500 0.052 0.344 26.2

Transformer =Pcu * 1000/3 * In √ Z2tr-R2tr In *100/ 1000*Usc


In = (Pn *1000) / Ztr=U2o*Usc /
(√3* Uo ) ( Pn * 100) =

primary (KV) 11
uo (V) 415 11.50 32.83
Pn (KVA) 200
Usc (%) 4 11.45 32.49 7.0
Pcu ( Watt ) 2,660
In 278
Ztr 34.45

cable =(22.5/CSA)*L =0.08 * L

35.19 40.8 4.4


CSA 95
23.68 8
Cable Length: L 100

Main C.B RD = 0 XD = 0.15


35.14 40.64
0 0.15

Bus Bars RB = 0 XB =0.15*L


35.14 40.94 4.4
LENGTH 2 0 0.3

cable =(22.5/CSA)*L =0.08 * L

41.89 42.14 4.0


CSA 50
6.75 1.2
Cable Length: L 15

cable =(22.5/CSA)*L =0.08 * L

86.89 43.74 2.5


CSA 10
45.00 1.6
Cable Length: L 20
Cable Sizing
1 Cable from SMDB to FDB(G1)
Input Data system 3
( Uo ) No Load Voltage = 415
( P.F ) Power Factor = 0.80
( Vn ) Rated Voltage = 400
Ambient Temperature = 45
Max.conductor Temperature = 90
( L) Route length of Cable. = 190
( PL ) Load Power = 74,800

( IL ) Rated Current = PL / ( √3 x Vn x PF ) =

Cable selection is 1 x ( 4 x 150

Iz = 344 A

INSTALLATION METHOD INSTALLATION DETAILS


Multi-Core Cable 3 Adjacent Circuit

In The Ground Dry Soil

Construction cavities and closed cable trenchs

Calculation & formula


Air Temperature factor = 0.80
Grouping Factor = 0.62
Rated current of Cable = 344
O.CF = 1.25
De- rated current of Cable
= Air Temp. factor x Grouping Factor x Rated current of Cable
= 170 A
De-rated current of cable > Rated Current ( I L ) x O.C.F

170 A > 169 A


2 Voltage Drop Calculations

( RAC ) AC Resistance of Cable = 0.150


(X) inductance of Cable = 0.08
P.F = cos(φ) = 0.80 Sin (φ) = 0.600

(VD) Voltage drop of cable ( L ) per Amp. Per legnth


= √3 × ( R (AC)90°×cos(φ) + X × sin(φ) )
= 0.29 V/Amp/Km

(VD Cable) Voltage drop of cable ( L ) = (V D x I L x L)


= 7.46

( V D% ) = (V D cable *100 / V n) = 1.87

( V D % ) total

1.87 % < 2.5 % (2)

3 C.B selection
Three pole
rated current = 250 A (3)

Warrning Rating Of C.B is High check Cable Size


phase
V

V


m
Watt

134.96

mm² )

(1)
Ω/Km
Ω/Km

× sin(φ) )
Amp/Km

V D x I L x L)
V
S. No Cross Section Current

1 1.5 19.5
2 2.5 27
3 4 36
4 6 48
5 10 63
6 16 85
7 25 112
8 35 138
9 50 168
10 70 213
11 95 258
12 120 299
13 150 344
14 185 392
15 240 461
16 300 530
S. No Temperatures derating factor

1 10 1.15
2 15 1.12
3 20 1.08
4 25 1.04
5 30 1
6 35 0.96
7 40 0.91
8 45 0.87
9 50 0.82
10 55 0.76

Unburid Circuit

S. No Temperatures derating factor

1 10 1.07
2 15 1.04
3 20 1
4 25 0.96
5 30 0.93
6 35 0.89
7 40 0.85
8 45 0.8
9 50 0.76
10 55 0.71
1 Insaultated Conductor
2 Single-Core Cable
3 Multi-Core Cable

1 Embedded in structure
2 In Accessible Building Void
3 In Cable Chanel
4 In not Accessible Building Void
5 In The Ground
6 Overhead
7 Surface Mounted

S. No Method of Installation derating factor

1 In Conduit 0.9
2 Conduit installed in thermal installation material 0.77
3 Cables Installed directly in thermal installation materials 0.7
4 Construction cavities and closed cable trenchs 0.95
5 Surface Mounted on Ceiling 0.95
6 placed in earthenware ducts; in conduits or in decorative Moulding 0.8
7 On Cable Ladder Or Perforated Cable Tray 1
8 1

S. No Method of Installation derating factor

1 Unburied Circuit 1
2 Very wet soil 1.21
3 Wet Soil 1.13
4 Damp Soil 1.05
5 Dry Soil 1
6 Very Dry Soil 0.86
1 Cables Insta 0.7
S. No Method of Installation derating factor

1 No Adjacent Circuit 1
2 1 Adjacent Circuit 0.8
3 2 Adjacent Circuit 0.7
4 3 Adjacent Circuit 0.65
5 4 Adjacent Circuit 0.6
6 5 Adjacent Circuit 0.57
7 6 Adjacent Circuit 0.54
8 13 5 4 4 5 14 3
Temp CSA Ins Meth 1 Ins Meth 2 Ins Det1 Ins Det2 C.B

S. No rating amp

1 10
2 16
3 20
4 25
5 30
6 40
7 50
8 60
9 80
10 100
11 125
12 160
13 200
14 250
15 320
16 400
17 500
18 630
19 800