Escolar Documentos
Profissional Documentos
Cultura Documentos
Abstract
The use of Dissolved Gas Analysis (DGA) is widely known for transformers and more
recently tapchangers. DGA has been used in assessing the condition of bushings in
Europe for several years. National Grid of the United Kingdom has approximately 4000
samples taken from high voltage bushings. This paper will discuss Altalink’s experiences
with DGA analysis of bushing oil and some of the weaknesses and the strengths of
applying this condition assessment tool to bushings.
Introduction
Typically, bushing condition has been assessed by visual inspections, infrared scanning
(thermovision), and the most popular power factor and capacitance measurement.
Bushings have posed several problems when considering DGA as an assessment tool.
They are:
• Bushings are hermetically sealed and have been considered as maintenance free
devices similar to instrument transformers
• They have small volumes of oil so sample rates must be limited.
• It is not possible to inspect the primary components of a bushing. There failures
can be very damaging to the units they are mounted to.
• Old school says we should not disturb the seal.
• Some statistics indicate 80% of bushing failures occur between 12-20 years (mid
life of our transformer population).
• Bushing failures initiate 30% of transformer failures
Useful Life
Time
1
Wear-out Region
• Time.
• Material quality.
• Workmanship.
• Family of components show wear at the same rate.
Partial Discharge
• Inadequate impregnation of paper by oil
• Deteriorated oil
• Porcelain contaminated with semi-conducting sediment
• Discharge at foil ends
2
safety of our employees. I am sure we would all sacrifice some longevity of life to
prevent a catastrophic failure of a bushing that could cause a transformer fire.
Since bushings are hermetically sealed at the factory; intrusive maintenance tasks such as
DGA must be performed with consideration to external contamination entering the oil
chamber while sampling. During the process of performing condition based testing we do
not want to introduce additional failure mechanisms through improper maintenance
methods. The most predominant non-intrusive condition tests now performed on
bushings are the power factor test and infrared scanning. These tests are effective for
several of the failure mechanisms identified above; however, neither is very effective in
determining a partial discharge condition. Since the presence of hydrogen is an indicator
of corona or partial discharge DGA would be an effective tool to determine any failure
mechanism producing hydrogen.
Due to the fact bushings have no movable parts and are very simple devices the
question is: are the majority of failures (80%) during the twelve to twenty year period
random failures or is this the actual wear out region for bushings? If this is so, then if we
have transformers lasting thirty to forty years we should expect to replace the bushing
once during the lifetime of the transformer. Another observation form the Europeans is
that manufacture defects are the main cause of bushing failures, that would indicate most
bushing failure are random. If in fact bushing failures are random then knowing and
understanding the condition of all bushings in your system is critical to preventing
failures.
The condition of the bushings on the Altalink system in the past have been
assessed primarily through the analysis of the power factor, capacitance readings and
infrared scanning. We now have some limited experience with DGA analysis to confirm
both power factor and capacitance readings, which have indicated serious problems. We
have also had success in determining test instrument deficiencies and human error in test
procedures.
Infrared Scanning
• Difficult to pick up internal problems below flange.
• Load and weather condition effect readings.
• Bright sun inhibits effectiveness.
3
• Partial discharge within the bushing is difficult to pick up.
DGA
• Limited amount of oil.
• Secondary failure mode can be introduced during sampling.
• Not a lot of data to compare readings.
Infrared Scanning
• In most cases results are very definitive and can pin point problem areas above
flange.
• Non-intrusive unit in service while assessment is being made.
DGA
• Test is performed under repeatable conditions (laboratory).
• Sampling is quite simple as long as precautions are taken.
• Done in conjunction with PPM of H2O all types of failure mechanisms are
identified (partial discharge, carbon tracking, water ingress).
Component Gas Serial # 25610 Serial # 25600 Serial # 15940 Serial # 19147
4
Serial # 25600 Nameplate 1979 1989 1991
• Large region of severe carbon tracking observed lower end of bushing core.
• Inner surface of lower porcelain weathershed showed carbon tracking.
• Small amount of carbon tracking had penetrated to within 1 turn of potential tap
layer.
• Considering the condition, it was extremely fortunate that this bushing had not
failed in service.
• Overall test (GST-Ground) at 10 kV was 8.80% power factor.
• Water content was measured at 6 PPM.
• Odor of burnt oil and paper was noticed approximately half way to the core
during the unwrapping process.
• Paper was of a lighter color as we moved inward to the core and did not appear to
be saturated with oil as in the outer wrappings.
• X-wax was observed on the copper draw lead tube.
• Power factor improved after removal from unit
Bushing serial number 15940 was not disassembled due to time constraints.
5
500 KV CGE Type U Bushing Results
Hydrogen 31 25 16 140
Methane 4 12 6 40
Ethane 3 3 0 70
Ethylene 0 0 0 30
Acetylene 0 0 0 2
The above units are mounted on 3 single-phase reactors used for voltage control on our
500 KV system. You can see consistent results across all 3 bushings and the results are
well below the IEC standard for maximum normal limits for key fault gases.
The above 240 KV bushing was sampled after inconsistent power factor readings were
obtained. Some of our test crews now take samples when power factor readings show
suspicious result.
Summary