1 Manufacturing standards : IEC 60076-11 2 Type : Step down 3 Rated effective power at AN / Rated effective power at AF : 1000 / 1400 KVA 4 Rated voltages : 22.0 KV / 0.415 KV 5 Vector group : Dyn11 6 Rated frequency : 50 Hz 7 No load losses : 2.20 kW Tol acc.to IEC 8 Load losses (at 75 °C and nom. pos.) : 8.90 kW Tol acc.to IEC 9 Impedance voltage (at 75 °C and nom. pos.) : 5.00 % 10 Average Sound pressure level : 61 dB 11 Insulation System : Class F 12 Max. average Winding temperature rise : L.V.: 100 H.V.: 100 °K B- GENERAL CONDITIONS 13 Max. ambient temperature : 45 °C 14 Humidity : 100 % 15 Max. Altitude : 1000 m 16 Climate class : C2 17 Environmental class : E2 18 Fire protection : F1 19 Cooling method : ANAF 20 Short circuit withstand duration : 3 sec. - High Voltage Windings 21 Rated voltage : 22.0 kV 22 Tapping range : + 2 x 2.5 - 4 x 2.5 % 23 Insulation Class : 24 KV 24 Basic Lightning Impulse Insulation Level (BIL) : 125 KV 25 Low-Frequency Voltage Insulation Level : 50 KV 26 Conductor Material : AL 27 Type of winding insulation : encapsulated cast resin - Low Voltage Windings 28 Rated voltage at No load : 0.415 KV 29 Insulation Class : 1.1 KV 30 Basic Lightning Impulse Insulation Level (BIL) : - KV 31 Low-Frequency Voltage Insulation Level : 5 KV 32 Conductor Material : AL 33 Type of winding winding insulation : encapsulated cast resin - Enclosure 33 Degree of protection : IP 21 34 Enclosure application : indoor 35 Sheet Material : Painted metal sheet 36 Accessories 37 Temperature Indicator : NT-511 38 PT100 SENSOR 3PCS/TRANS 48 Dimensions and Weight 49 Transformer dimensions without enclosure : 1690 x 1020 x 1910 mm. 50 Total Weight without Enclosure : 3250 Kg. 51 Transformer dimensions with enclosure : 2050 x 1450 x 2450 mm. 52 Total Weight with Enclosure : 3750 Kg. Prepared by: Eng.mohamed hosney Approved by: Offer NO: 0 Checked by: eng: ashraf Eng.Enas Amer Date 10/29/2015