Você está na página 1de 19

Generator Protection

Application Guide
About the Author

George Rockefeller is President of Rockefeller Associates, Inc. He has a BS in EE from Lehigh


University; MS from New Jersey Institute of Technology and a MBA from Fairleigh Dickinson
University. Mr. Rockefeller is a Fellow of IEEE and Past Chairman of IEEE Power Systems Relaying
Committee. He holds nine U.S. Patents and is co-author of Applied Protective Relaying (1st Edition).

Mr. Rockefeller worked for Westinghouse Electric Corporation for twenty-one years in application and
system design of protective relaying systems. He worked for Consolidated Edison Company for ten
years as a System Engineer. He has served as a private consultant since 1982.

This Guide contains a summary of information for the protection of various types of electrical
equipment. Neither Basler Electric Company nor anyone acting on its behalf makes any warranty or
representation, express or implied, as to the accuracy or completeness of the information contained
herein, nor assumes any responsibility or liability for the use or consequences of use of any of this
information.
First printing April 1994
Revision B August 2000
Generator Protection
Application Guide
Introduction The subjects covered in this guide are as
follows:
This guide was developed to assist in the
selection of relays to protect a generator. The Ground Fault Protection
purpose of each relay is described and related Phase Fault Protection
to one or more power system configurations. A Reverse Power Protection
large number of relays is available to protect for Loss of Field Protection
a wide variety of conditions. These relays Thermal Protection
protect the generator or prime mover from Voltage-Balance Relay Supervision
damage. They also protect the external power Overexcitation Protection
system or the processes it supplies. Inadvertent Energization Protection
Negative-Sequence Overcurrent
The engineer must balance the expense of Protection
applying a particular relay against the Off-Frequency Operation
consequences of losing a generator. The total Integrated Application Examples
loss of a generator may not be catastrophic if it
represents a small percentage of the The references listed on Page 14 provide more
investment in an installation. However, the background on this subject. These documents
impact on service reliability and upset to loads also contain Bibliographies for further study.
supplied must be considered. Damage to and
loss of product in continuous processes can Table 1 provides Basler model, function,
represent the dominating concern rather than description and style number. It also references
the generator unit. Accordingly, there is no the figures where the relays are indicated by
standard solution based on the MW rating. their ANSI designation.

This guide simplifies the process of selecting Ground Fault Protection


relays by describing how to protect against each
type of fault or abnormal condition. Then, The following information and examples cover
suggestions are made for what is considered to three impedance levels of grounding: low,
be minimum protection as a baseline. After medium and high. The impedance values are
establishing the baseline, additional relays, as specifically defined for each application. The
described in the section on Extended location of the grounding—generator neutral(s)
Protection, may be added. or transformer also influence the protection
approach.

1
The location of the ground fault within the sensitive for ground faults, then the 51N pro-
generator winding, as well as the grounding vides the primary protection for the generator.
impedance, determines the level of fault The advantage of the 87G is that it does not
current. The level is proportional to the pre- need to be delayed to coordinate with external
fault voltage to ground at the fault point: Vfg in protection; however, delay is required for the
Fig. 1. Assuming that the generated voltage 51N.
along each segment of the winding is uniform,
the current level is directly proportional to the
distance of the point from the generator neutral.
A fault 10% from neutral produces 10% of the
current that flows for a fault on the generator
terminals. While the current level drops
towards zero as the neutral is approached, the
insulation stress also drops, tending to reduce
the probability of a fault near the neutral.
FIGURE 2. GROUND-FAULT RELAYING - GENERATOR
LOW-IMPEDANCE GROUNDING.

The neutral CT should be selected to produce a


secondary current of at least 5A for a solid
generator terminal fault, providing sufficient
current for a fault near the generator neutral. For
example, if a terminal fault produces 1000A in
the generator ground source, the neutral CT
ratio should not exceed 1000/5. For a fault 10%
from the neutral, the 51N current will be 0.5A,
with a 1000/5 CT.

Fig. 3 shows multiple generators with the


transformer providing the system grounding.
This arrangement applies if the generators will
FIGURE 1. FAULT LOCATION WITHIN GENERATOR not be operated with the transformer out of
WINDING FIXES CURRENT LEVEL. service. The transformer could serve as a
step-up as well as a grounding transformer
function. An overcurrent relay 50/51N or an 87G
The generator differential relay (87G) may be differential relay provides the protection for each
sensitive enough to detect winding ground faults generator. The transformer should produce a
with low-impedance grounding per Fig. 2. This ground current of at least 50% of generator
would be the case if a solid generator-terminal rated to provide about 95% or more winding
fault produces at least 100% of rated current. coverage. A relatively high instantaneous setting
The Basler BE1-87G variable percentage prevents incorrect operation
differential relay pickup settings range from 0.1-
1.6A; the lower pickup settings are recom-
mended only with high-quality CTs (e.g. C400)
and a good CT match (e.g. identical accuracy
class and equal burden). A representative
recommended setting for small generators is
0.4A. See this relay’s instruction manual for
specific setting recommendations.

If 87G relaying is provided per Fig. 2, relay 51N


backs up the 87G, as well as external relays. If FIGURE 3. SYSTEM GROUNDED EXTERNALLY WITH
an 87G is not provided or is not sufficiently MULTIPLE GENERATORS.

2
during an external phase fault that produces false However, for these faults, the pre-fault third
residual current due to dissimilar CT harmonic flow in the generator ground is
saturation. disrupted, causing the 27-3N to drop out. The
27-3N performs a valuable monitoring function,
aside from its fault detection function; if the
grounding system is shorted or an open occurs,
the 27-3N drops out. The 59 overvoltage relay
in Fig. 4 supervises the 27-3N relay, so that the
86 lockout relay can be reset when the generator
is out of service; otherwise, the field could not be
applied. Once the field is applied, and the 59
operates, the 27-3N protection is enabled. The
59 relay should be set for about 90% of rated
voltage. An “a” contact of the unit breaker can be
FIGURE 4. UNIT-CONNECTED CASE WITH HIGH- used instead of the 59 relay to supervise 27-3N
RESISTANCE GROUNDING. tripping. However, use of the 59 relay allows the
Fig. 4 shows a unit-connected arrangement 27-3N to provide protection prior to synchroniza-
(generator and step-up transformer directly tion (putting the unit on line), once the field has
connected with no low-side breaker), using high- been applied.
resistance grounding. The resistor and voltage
Where wye-wye voltage transformers (vts) are
relays connect to the secondary of a distribution
connected to the machine terminals, the
transformer. The resistor is normally sized to
secondary vt neutral should not be grounded in
produce a terminal-fault current about equal to
order to avoid operation of 59N for a secondary
the fault current flow in the capacitance of the
ground fault. Instead, one of the phase leads
circuit—on the order of 5-10A primary. Sufficient
should be grounded. This connection eliminates
resistor damping prevents ratcheting up of the
any voltage across the 59N relay for a secondary
sound-phase voltages in the presence of an
ground fault. An isolation vt is required if the
intermittent ground. The ground fault elevates the
generator vts would otherwise be galvanically
sound phase voltages to a nominal 173% of
connected to a set of neutral-grounded vts. Three
rated. On the other hand, the low current level
wye vts should be applied where an iso-phase
minimizes the possibility of sufficient iron damage
bus (phase conductors separately enclosed) is
to require re-stacking. Because of the low current
used to protect against phase-phase faults on the
level, the 87G relay will not operate for single-
generator terminals.
phase ground faults.
The 59N relay in Fig. 4 is subject to operation for
a ground fault on the wye side of any power
transformer connected to the generator. This
voltage is developed even though the generator
connects to a delta winding, because of the
transformer inter-winding capacitance. This
coupling is so small that its effect can ordinarily
be ignored; however, this is not the case with the
FIGURE 5. GROUND FAULT NEAR GENERATOR 59N application because of the very high ground-
NEUTRAL REDUCES THIRD-HARMONIC CURRENT
ing resistance. The 59N overvoltage element
FLOW IN GENERATOR GROUND, DROPPING OUT 27-3N.
time delay allows the relay to override external-
Protection in Fig. 4 consists of a 59N overvolt- fault clearing.
age relay and a 27-3N third-harmonic
undervoltage relay. The 59N relay does not The Basler BE1-59N relay contains the overvolt-
respond to third harmonic voltage produced age (59N), undervoltage (27-3N) and 59 units.
during normal operation (see Fig. 5). The 59N It has a continuous rating of 360V and its filters
will not operate for faults near neutral because provide a 40 dB (100/1) minimum rejection of 3rd
of the reduced fault current level, per Fig. 1. harmonic for the overvoltage (59N) function.

3
The filter prevents tripping due to 3rd harmonic provide for a relay current about equal to the
current flow in the capacitances of the generator generator neutral current. In either position, the
and associated bus and transformers. Thus, a relay pickup should be above the harmonic
relay set for 1V, 60 Hz pickup will require at least current flow during normal operation; this will be
100V third harmonic to operate; the 100V level is approximately 1A. Assuming a maximum fault
sufficient to prevent incorrect operation. current of 8A in the neutral and a pickup of 1A,
88% of the stator winding is covered. As with the
The Basler BE1-59N third harmonic 59N relay, the 51GN delay will allow it to over-
undervoltage element (27-3N) protects for faults ride clearing of a high-side ground fault. An
near the neutral end of the generator stator instantaneous overcurrent element can also be
winding. Fundamental frequency rejection for this employed, set at about three times the time-
element is at least 40dB (100/1). overcurrent element pickup, although it may not
coordinate with primary vt fuses that are con-
In order to provide 100% stator winding cover- nected to the generator terminals.
age, the undervoltage (27-3N) and overvoltage
(59N) settings should overlap. For example, if a
generator-terminal fault produces 240V, 60 Hz
across the voltage relay (59N), a 1V 60 Hz
pickup setting would allow all but the last
(1/240)*100 = 0.416% of the winding to be
covered by the overvoltage function. If 20V, third
harmonic is developed across the relay prior to a
fault, a 1V third-harmonic drop-out setting would
provide dropout for a fault up to (1/20)*100= 5%
from the neutral.

If the 59N relay is only used for alarming, the


distribution transformer voltage ratio should be
selected to limit the secondary voltage to the
maximum continuous rating of the relay. If the FIGURE 6. 59N RELAY OPERATION WITH MULTIPLE
relay is used for tripping, the secondary voltage UNITS WILL NOT BE SELECTIVE; 51N RELAYS
PROVIDE SELECTIVE PROTECTION IF AT LEAST
could be as high as the relay’s ten-second THREE GENERATORS ARE IN SERVICE.
voltage rating. Tripping is recommended to
minimize iron damage for a winding fault as well Multiple generators, per Fig. 6, can be high-
as minimizing the possibility of a multi-phase resistance grounded, but the 59N relays will not
fault. be selective. A ground fault anywhere at the
generation voltage level will be seen by all 59N
Fig. 4 shows a 51GN relay as a second means of relays and the tendency will be for all generators
detecting a stator ground fault. The use of a to trip. The 51N relay, when connected to a
51GN in addition to the 59N and 27-3N is readily zero-flux CT, will provide selective tripping if at
justified, since the most likely fault is a stator least three generators are in service. In this
ground fault. An undetected stator ground fault case, the faulted generator 51N relay will then
would be catastrophic, eventually resulting in a see more current than the other 51N relays. The
multiphase fault with high current flow, which proper 51N will operate before the others
persists until the field flux decays (e.g. for 1 to because of the inverse characteristic of the
2s). The CT shown in Fig. 4 could be replaced relays. Use of the zero-flux transformer is limited
with a CT in the secondary of the distribution to those cases where the CT window can
transformer, allowing use of a CT with a lower accommodate the three cables. With a 50 to 5A
voltage rating. However, the 51GN relay would CT, a 51N pickup of 0.1A should be used. With
then be inoperative if the distribution transformer two generators, each contributing 10A to a
primary becomes shorted. The CT ratio for the terminal fault in a third generator, the faulted-
secondary-connected configuration should

4
generator 51N relay sees 2*10/(50/5) = 2A. about 175% of rated current to override swings
Then the relay protects down to (0.1/2)*100 = due to a slow-clearing external fault, the starting
5% from the neutral. of a large motor, or the re-acceleration current of
a group of motors. Energization of a transformer
When feeder cables are connected to the may also subject the generator to higher than
generator bus, the additional capacitance rated current flow.
dictates a much lower level of grounding resis-
tance than achieved with a unit-connected case.
A lower resistance is required to minimize
transient overvoltages during an arcing fault.

FIGURE 8. PHASE-OVERCURRENT PROTECTION (51)


MUST BE DELAYED TO COORDINATE WITH EXTERNAL
RELAYS.

Fig. 9 shows an example of generator current


decay for a 3 phase fault and a phase-phase
fault. For a 3 phase fault, the fault current
decays below the pickup level of the 51 relay in
approximately one second. If the time delay of
FIGURE 7. MEDIUM-LEVEL GROUNDING WITH 87N the 51 can be selectively set to operate before
GROUND DIFFERENTIAL PROTECTION. the current drops to pickup, the relay will

Fig. 7 shows an application where the


grounding resistor current is at least 5% of rated
current for a terminal fault. The function is
labeled 87N, but the Basler BE1-67N is applied.
For the maximum fault, the neutral CT should
produce a secondary current of at least 2.5A;
the 87N pickup should be set at 0.25A. The
auxiliary CT (ACT) ratio should produce a match
with the neutral CT current. During external
phase faults, considerable operating current can
result when there is dissimilar saturation of the
phase CTs. For this case the 60 Hz generator
neutral current will be zero assuming balanced
conductor impedances to the fault. The time
overcurrent element should have sufficient delay
to ride through external high-current two-phase-
ground faults. (The current-polarizing threshold
for time tripping is fixed at 0.2A in the Basler
BE1-67N).

FIGURE 9. GENERATOR FAULT CURRENT DECAY


Phase-Fault Protection EXAMPLE FOR 3 PHASE AND PHASE-PHASE FAULTS
AT GENERATOR TERMINALS - WITH NO REGULATOR
BOOSTING.
Fig. 8 shows a simple means of detecting
phase faults, but clearing is delayed, since the
51 relay must be delayed to coordinate with
external devices. Its pickup should be set at

5
provide 3 phase fault protection. The current Voltage-restrained or voltage-controlled time-
does not decay as fast for a phase-phase fault, overcurrent relays (51V) may be used as shown
and thereby allows the 51 relay more time to trip in Fig. 11 to remove any concerns about ability
before current drops below pickup. Fig. 9 to operate before the generator current drops
assumes no voltage regulator boosting, al- too low. The voltage feature allows the relays
though the excitation system response time is to be set below rated current. The Basler
unlikely to provide significant fault current BE1-51/27R voltage restrained type causes the
boosting in the first second of the fault. If the pickup to decrease with decreasing voltage. For
generator is loaded prior to the fault, the super- example, the relay can be set for 175% of
position of the fault current in Fig. 9 and the generator rated current with rated voltage
prefault load current will provide the relay with a
higher level of current than indicated by the Fig.
9 curves. For example, at one second, the 3
phase fault value would be 2.4 times rated,
assuming a pre-fault rated load at 30 degree
lag, rather than 1.75 times rated. Under these
circumstances, the 51 relay has more time to
operate before current decays below pickup.

If an external source contributes more current


than does the generator, using CTs on the
generator terminals, rather than neutral-side FIGURE 11. VOLTAGE-RESTRAINED OR VOLTAGE-
CTs, will increase 51 relay sensitivity to internal CONTROLLED TIME-OVERCURRENT PHASE FAULT
PROTECTION.
faults due to higher current contribution from the
external source; however, the generator is applied; at 25% voltage the relay picks up at
unprotected should a fault occur prior to syn- 25% of the relay setting (1.75*0.25=0.44 times
chronizing. rated). The Basler BE1-51/27C voltage
controlled type inhibits operation until the
Fig. 10 eliminates concerns about the decay voltage drops below a preset voltage. It should
rate of the generator current by using an instan- be set to function below 80% of rated voltage,
taneous overcurrent relay (50) on a zero-flux with a current pickup of about 50% of generator
CT, where the CT window can accommodate rated. Since the voltage-controlled type has a
cable from both sides of the generator. The fixed pickup, it can be more readily coordinated
relay does not respond to generator load with external relays than can the voltage-
current, nor to external fault conditions. The restrained type. The voltage-controlled type is
instantaneous overcurrent relay (50) provides recommended since it is easier to coordinate.
high-speed sensitive protection. The 51 relay However, the voltage-restrained type will be less
shown in Fig. 10 is applied for back-up of susceptible to operation on swings or motor
external relays and as back-up for the 50 relay. starting conditions that depress the voltage
below the voltage-controlled undervoltage unit
dropout point.

The 87G relays in Fig. 12 are connected to


respond to differential currents. In contrast to a
51 or 51V relay, the 87G relay responds to both
the generator and external contributions to a
generator fault. Because of the differential
connection, the relays are immune to operation
due to generator load flow or external faults and,
therefore, can provide sensitive, high speed
FIGURE 10. ZERO-FLUX RELAY (50) PROVIDES protection. While the CTs must be of the same
SENSITIVE, HIGH-SPEED, SELECTIVE PROTECTION. ratio, they do not need to be matched in

6
Therefore, anti-motoring protection is recom-
mended whenever the unit may be connected to
a source of motoring power. Where a non-
electrical type of protection is available, as may
be the case with a steam turbine unit, the 32
relay provides a second means of detecting this
condition. Time delay should be set for about 15
seconds. This will provide time for the controls
to pick up load upon synchronizing when the
generator is initially slower than the system.

Since motoring can occur during a large


FIGURE 12. 87G PROVIDES SENSITIVE, HIGH-SPEED reactive-power flow, the real power component
COVERAGE; 51V PROVIDES BACK-UP FOR 87G AND
FOR EXTERNAL RELAYS. needs to be measured at low power factors. The
BE1-32R measures real power down to 0.1 pf.
performance, but the pickup of the Basler BE1-
87G must be raised as the degree of
performance mismatch increases. (See the
BE1-87G instruction manual for specifics on
settings.) A 0.4A pickup is representative of a
recommended setting for a moderate mismatch
in CT quality and burden. Fig. 12 also shows
51V relays to back up the 87G and external
relays and breakers.

Reverse Power Protection

The reverse-power relay (32) in Fig. 13 senses


real power flow into the generator, which will
occur if the generator loses its prime-mover
input. Since the generator is not faulted, CTs on
either side of the generator would provide the
same measured current.

FIGURE 14. REVERSE-POWER RELAY 32-1 PREVENTS


LOAD REJECTION FOR SELECTED TRIPS; RELAY 32-2
OPERATES IF MOTORING IS NOT ACCOMPANIED BY
AN 86NE OPERATION.

Fig. 14 shows the use of two reverse-power


relays 32-1 and 32-2. The 32-1 relay supervises
the generator tripping of devices that can wait
until the unit begins to motor. Overspeeding on
large steam-turbine units can be prevented by
delaying main and field breaker tripping until
FIGURE 13. OVEREXCITATION (24), ANTI-MOTORING
(32), LOSS-OF-FIELD (40), PROTECTION. motoring occurs for non-electrical and selected
electrical conditions (e.g. loss-of-field and
In a steam-turbine, the low pressure blades will overtemperature). Relay 32-1 should be delayed
overheat with the lack of steam flow. Diesel and about 3 seconds, while relay 32-2 should be
gas-turbine units draw large amounts of motor- delayed by about 30 seconds. Relay 32-2 trips
ing power, with possible mechanical problems. directly for cases of motoring that were not
In the case of diesels, the hazard of a fire initiated by lockout relay 86NE —e.g. governor
and/or explosion may occur due to unburnt fuel. control malfunction.

7
Loss-of-Field Protection due to other transient conditions. The Basler
BE1-40Q relay is equipped with a timer for this
purpose.

Fig. 13 shows the connection of the loss-of-field


relay (40).

Thermal Protection

FIGURE 15. FOR LOSS OF FIELD THE POWER


TRAJECTORY MOVES FROM POINT A INTO THE
FOURTH QUADRANT.

The power diagram (P-Q) of Fig. 15 shows the


Basler BE1-40Q characteristic with a represen-
tative setting, a representative generator thermal
capability curve and an example of the trajectory
following a loss of excitation. The first quadrant
of the diagram applies for lagging pf operation. FIGURE 16. STATOR TEMPERATURE PROTECTION.
The trajectory starts at point A and moves into
the leading pf zone (4th quadrant) and can Fig. 16 shows the Basler BE1-49 relay
readily exceed the thermal capability of the unit. connected to a resistance-temperature detector,
embedded in a stator slot. Relay models are
With complete loss of excitation, the unit will available for either a copper or platinum RTD.
eventually operate as an induction generator The relay provides a constant-current source to
with a positive slip. Because the unit is running produce a voltage across the RTD and includes
above synchronous speed, excessive currents the means to measure that voltage (proportional
can flow in the rotor, resulting in overheating of to temperature) using separate leads.
elements not designed for such conditions. This
heating cannot be detected by thermal relay 49, The relay provides outputs at two temperature
which is used to detect stator overloads. levels over a 60° to 150° C range. The lower
level can be used for alarming and the upper
Rotor thermal capability can also be exceeded level for tripping.
for a partial reduction in excitation due to an
operator error or regulator malfunction. If a unit Voltage-Balance Relay Supervision
is initially generating reactive power and then
draws reactive power upon loss of excitation, Fig. 17 shows the use of two sets of vts on the
the reactive swings can significantly depress the generator terminals. One set supplies the
voltage. In addition, the voltage will oscillate and voltage regulator, the other, the relays. If the
adversely impact sensitive loads. If the unit is potential decreases or is lost from vt #1, the
large compared to the external reactive sources, Basler BE1-60 disables the voltage regulator; if
system instability can result. source #2 fails, the Basler BE1-60 blocks relay
tripping. Since both the 40 and 51V relay
The Basler BE1-40Q relay provides loss-of-field functions in Fig. 17 are time delayed, the 60
protection. A trip delay of about 0.2 seconds is relay does not need to operate at high speed.
recommended to prevent unwanted operation

8
Overexcitation relay (24) does not need to be
blocked, since it will not see overvoltage when a
fuse blows.

FIGURE 18. COMBINED GENERATOR/TRANSFORMER


FIGURE 17. VOLTAGE-BALANCE RELAY (60) DETECTS OVEREXCITATION PROTECTION USING BOTH THE
POTENTIAL SUPPLY FAILURE TO BLOCK EITHER THE INVERSE SQUARED AND “ALARM” UNITS FOR
VOLTAGE REGULATOR OR INCORRECT TRIPPING. TRIPPING. EQUIPMENT WITHSTAND CURVES ARE
EXAMPLES ONLY.
Overexcitation Protection
Fig. 18 shows the relation between the Basler
Overexcitation can occur due to higher than BE1-24 relay characteristics and an example of
rated voltage, or rated or lower voltage at less a generator and transformer withstand capabil-
than rated frequency. A volts/hertz relay (24) ity. The generator and transformer manufactur-
responds to excitation level as it affects thermal ers should supply the specific capabilities of
stress to the generator (and to any transformer these units.
tied to that generator). IEEE C50.13 specifies
that a generator should continuously withstand Inadvertent Energization Protection
105% of rated excitation at full load.
Inadvertent energization can result from a
With the unit off line, and with voltage-regulator breaker interrupter flashover or a breaker close
control at reduced frequency, the generator can initiation while the unit is at standstill or at low
be overexcited if the regulator does not include speed. The rapid acceleration can do extensive
an overexcitation limiter. Overexcitation can also damage, particularly if the generator is not
occur, particularly with the unit off line, if the promptly de-energized. While relays applied for
regulator is out of service or defective. If volt- other purposes may eventually respond, they
age-balance supervision (60) is not provided are not generally considered dependable for
and a fuse blows on the regulator ac potential responding to such an energization.
input, the regulator would cause overexcitation.
Loss of ac potential may also fool the operator Figs. 19 and 20 show two methods of detecting
into developing excessive excitation. The 24 the energization of a machine at standstill or at a
relay can only protect for overexcitation resulting speed significantly lower than rated. This could
from an erroneous voltage indication if the 24 be caused by single-phase energization due to
relay is connected to an ac potential source breaker-interrupter flashover or 3 phase
different than that used for the regulator. energization due to breaker closure. The unit,
without excitation, will accelerate as an

9
induction motor with excessive current flow in independent of the plant is desired. In this case
the rotor. Both Fig. 19 and 20 schemes will the 67 relays would be placed in the switchyard
function properly with the vt fuses at the genera- rather than in the control room. While directional
tor terminal removed. With the generator off line, overcurrent relay (67) should be delayed to ride
safety requirements may dictate the removal of through generator swings, it can still provide
these vt fuses. In the case of Fig. 19, the faster backup for generator faults than provided
overcurrent protection is enabled by by 51 or 51V type relays, since the 67 relays
undervoltage units. In Fig. 20 the potential is need not be coordinated with external protec-
taken from bus vts, rather than unit vts, so the tion. Fig. 20 shows the operating range for
scheme will function even if the vt fuses were phase A current (Ia) with respect to phase b to c
removed during unit maintenance. voltage (VBC). This range is fixed by the 60
degree characteristic angle and the ±45 degree
In Fig. 19 the terminal voltage will be zero prior limits set on the operating zone.
to energization, so the 27 relay contacts will be
closed to energize the timer (62). The
instantaneous overcurrent relay (50) trip circuit
is established, after timer 62 operates. Upon
generator energization, the undervoltage units
may operate due to voltage transients, but the
delayed dropout of 62 allows relay 50 to initiate
tripping. The use of two 27 relays on separate vt
circuits avoids tripping for a vt fuse failure.
Alternatively, a voltage-balance relay (60) could
be used in conjunction with a single 27 relay to
block tripping.

FIGURE 20. BE1-67 DIRECTIONAL OVERCURRENT


RELAYS DETECT INADVERTENT ENERGIZATION.

Negative-Sequence Overcurrent Protection

Negative-sequence stator currents, caused by


FIGURE 19. INADVERTENT ENERGIZATION fault or load unbalance, induce double-
PROTECTION USING INSTANTANEOUS frequency currents into the rotor, that may
OVERCURRENT RELAY (50). eventually overheat elements not designed to be
subjected to such currents. Series unbalances,
In Fig. 19 the 5 sec pickup delay on timer 62 such as untransposed lines, produce some
prevents tripping for external disturbances that negative-sequence current (I2) flow. The most
allow dropout of the 27 relays. The 27 relays serious series unbalance is an open phase,
should be set at 85% voltage (below the operat- such as an open breaker pole. ANSI C50.13-
ing level under emergency conditions). The Fig. 1977 specifies a continuous I2 withstand of 5 to
20 scheme could be employed where protection 10% of rated current, depending upon the size

10
and design of the generator. These values can Relays and Typical Settings
be exceeded with an open phase on a heavily-
loaded generator. The Basler BE1-46N relay Table 1 lists the applicable relays keyed to the
protects against this condition. various functional one-line figures. The third
column lists the Basler model and the sixth
column, the Basler style number. These style
numbers apply for 60 Hz relays. The style
numbers also apply for open delta vts, 120V line-
line. Where applicable, other Basler relay styles
are available for wye vts. The right column
provides typical settings for use as a starting
point in the setting determination procedure. The
proper settings are heavily influenced by the
FIGURE 21. NEGATIVE-SEQUENCE RELAY (46) specifics of each application. Typical settings are
PROTECTS AGAINST ROTOR OVERHEATING DUE TO also used as an aid in selecting the relay range
A SERIES UNBALANCE OR PROTRACTED EXTERNAL
FAULT. where a choice is available.

Fig. 21 shows the 46 relay connection. CTs on Integrated Application Examples


either side of the generator can be used, since
the relay protects for events external to the Figs. 22 through 26 show examples of
generator. The Basler BE1-46N alarm unit will protection packages.
alert the operator to the existence of a danger-
ous condition. This relay also provides negative
sequence inverse-time protection shaped to
match the short-time withstand capability of the
generator should a protracted fault occur. This is
an unlikely event, because other fault sensing
relaying tends to clear faults faster, even if
primary protection fails.

Off-Frequency Operation

Diesel engines can be safely operated off FIGURE 22. EXAMPLE OF BARE-MINIMUM PROTECTION
(LOW-IMPEDANCE GROUNDING).
normal frequency and no protection is required.
Gas turbine controls generally provide Fig. 22 represents bare-minimum protection, with
protection for off frequency conditions and only fault protection. It may appear to be a
separate relays are not required. In contrast, disadvantage to use CTs on the neutral side as
frequency relays are sometimes applied with shown, since the relays may operate faster with
steam-turbine units, particularly to minimize CTs on the terminal side. The increase in speed
turbine blade fatiguing. Ref. 3 specifically would result with a larger current contribution
addresses abnormal frequency operation. Fig. 5 from external sources. However, if the CTs are
of Ref. 3 shows frequency operating limits located on the terminal side of the generator,
specified by various generator manufacturers. there will be no protection prior to putting the
The simplest relay application would be a single machine on line. This is not recommended
underfrequency stage (e.g. BE1-81). The Basler because a generator with an internal fault
BE1-81 O/U relay can be provided with up to could be destroyed when the field is applied.
four setting stages, each with a time-delay
setting of up to 99 seconds. Each setpoint may
be set to recognize either overfrequency or
underfrequency.

11
quality of differential relay protection. A defi-
ciency in the CT circuits is unlikely to disable
both the 87G and 51V relays. Rather, a shorted
CT or defective connection will unbalance the
differential circuit and cause the 87G to trip.
Independent CTs could be used to provide
improved back-up protection, although this
seems to be a minimal advantage here. How-
ever, a separate CT is used for the 51N relay
that provides protection for the most likely type
of fault.

The reverse power relay (32) in Fig. 23 protects


the prime mover against forces from a motored
FIGURE 23. SUGGESTED MINIMUM PROTECTION generator and could provide important protec-
EXAMPLE (LOW-IMPEDANCE GROUNDING). tion for the external system if the motoring
power significantly reduces voltage or overloads
Fig. 23 shows the suggested minimum protec- equipment. Likewise, the loss-of-field relay (40)
tion with low-resistance grounding. It includes has dual protection benefits—against rotor
differential protection, which provides fast, overheating and against depressed system
selective response. Note that the differential voltage due to excessive generator reactive
relay responds to both generator and external absorption. Thermal relay (49) protects against
source current contributions. While the differen- stator overheating due to protracted heavy
tial relay is fast, the slow decay of the generator reactive power demands. Even if the excitation
field will cause the generator to continue feeding system is equipped with a maximum excitation
current into a fault. However, fast relay opera- limiter, a failure of the voltage regulator or a
tion will interrupt the external-source contribu- faulty manual control could cause excessive
tion, which may be greater than the generator reactive power output.
contribution. Fast disconnection from the
external source allows prompt restoration of
normal voltage to loads and may reduce dam-
age and cost of repairs.

The differential relay (87G) may protect for


ground faults, depending upon the grounding
impedance. The 51N relay in Fig. 23 provides
back-up protection for the 87G or will be the
primary protection if the differential relay (87G)
is not sufficiently sensitive to the ground current
level.

The 51V voltage-controlled or voltage-


restrained time overcurrent relay in Fig. 23
provides back-up for the differential relay (87G)
and for external relays and breakers. It will not
provide any back-up coverage prior to having
the unit on line. If there is no external source, FIGURE 24. SUGGESTED MINIMUM PROTECTION
connect the 51V to neutral-side CTs. EXAMPLE (MEDIUM-IMPEDANCE GROUNDED)

Fig. 23 shows three relays sharing the same Fig. 24 differs from Fig. 23 only in the use of a
CTs with a differential relay. This is practical ground differential relay (87N). This protection
with solid state relays because of their low provides faster clearing of ground faults where
burden and will not significantly degrade the the grounding impedance is too high to sense

12
ground faults with the phase differential relay Fig. 26 shows the application of additional relays
(87G). The auxiliary CT (ACT) is used to step up for extended protection: overexcitation relay
the current from the phase CTs by 10:1. The (24), negative-sequence overcurrent relay (46),
51N relay provides backup for the ground ground-overcurrent relay (51GN), voltage-
differential (87N) and for external faults. The balance relay (60), field-ground relay (64F),
Basler BE1-67N relay functions as the 87N frequency relay (81) and the 27/50/62 relay
relay, using the current polarizing mode. The combination for inadvertent energization protec-
polarizing winding measures the neutral current. tion. Relay 51GN provides a second means of
detecting stator ground faults or faults in the
generator connections or faults in the delta
transformer windings. Differential relay 87T and
sudden-pressure relay 63 protect the unit step-
up transformer. Relay 51N provides backup for
external ground faults and for faults in the high-
voltage transformer windings and leads. This
relay may also respond to an open phase
condition or a breaker-interrupter flashover that
energizes the generator. The 51N relay will be
very slow for the flashover case, since it must
be set to coordinate with external relays and is a
last-resort backup for external faults.

FIGURE 25. SUGGESTED MINIMUM PROTECTION


EXAMPLE (HIGH-RESISTANCE GROUNDING).

Fig. 25 differs from Fig. 23 only in the ground


relay protection and the method of grounding.
The voltage units 59N/27-3N provide the only
ground protection, since the ground fault current
is too small for phase differential relay (87G)
operation. The 59N relay will not be selective if
other generators are in parallel, since all the
59N relays will see a ground fault and nominally
operate at the same time.

The Basler BE1-59N package includes a third


harmonic undervoltage function (27-3N), which
provides supervision of the grounding system
and protects for faults near the generator
neutral. Its most important function is to detect a
shorted or open connection in the generator
ground connection or in the distribution trans-
former secondary circuit. The 59 overvoltage
relay opens the 27-3N break-contact connection
to allow lockout-relay reset following unit shut-
down. Otherwise the field could not be reap-
plied.

13
FIGURE 26. EXTENDED PROTECTION EXAMPLE (HIGH-RESISTANCE GROUNDING).

Fig. 26 shows wye-connected vts, appropriate


with an isolated-phase bus. This calls for a
different style number for some of the Table 1
relays.

Bibliography
1. IEEE C37.101-1993, IEEE Guide
for Generator Ground Protection
2. IEEE C37.102-1995, IEEE Guide
for AC Generator Protection
3. IEEE C37.106-1987, IEEE Guide
for Abnormal Frequency Protection for
Generating Plants
4. J. Lewis Blackburn, “Protective Relay
ing: Principles and Applications”, 2nd
Edition, Marcel Dekker, Inc., 1998.
5. S. Horowitz and A. Phadke, “Power
System Relaying”, John Wiley & Sons,
Inc., 1992.

14
Table 1 Relays and Typical Settings for 60 Hz Models
IEEE Basler Model/
No. Qty Function Description Basler Style No. Typical Settings & Remarks Figure No.

24 1 BE1-24 No instantaneous ACXF1XX0SXX P.U.: 1.1*Vrated/60 17, 13, 26


Overexcitation TD: 0.3; reset: 5
alarm P.U.: 1.18*Vrated/60
alarm delay: 2.5s

27 2 BE1-27 120V nominal, inst. A3EA1XX0BXX 85% rated 19, 26


Undervoltage for one phase
Inadvertent Ener.

32 1 BE1-32R 2 elem.; open delta vts; E1XE1XX0SXX 12W; 15s 13, 23, 24,
Reverse power 1.5-60W; def. time; 25, 26
120V ac

32-1, 2 BE1-32R 2 elem.; open delta vts; E1XE1XX0SXX 12W; 32-1: 3s; 32-2: 30s 14
32-2 Reverse power 1.5-60W; def. time

40 1 BE1-40Q 25-1000 var. 120V, F3XE1XX1SXX 100 vars; 0.2s 13, 17, 23,
Loss-of-field open-delta vts 24, 25, 26

46 1 BE1-46N with external monitor G1XB8XX3XXX Alarm p.u.: 3%; Trip p.u.: 21, 26
Neg. sequence 10%; K=10; max. time=200s
overcurrent

49 1 BE1-49 60-190 degrees C PXXA1XX0SXX Lower: 95; upper: 105 16, 23, 24,
Stator 25, 26
temperature

50 1 BE1-50 zero-flux cts G2XA1XX1N6X 0.25A 10, 26


Differential separate pwr. supp.
0.25-2A, 3 phase

50 1 BE1-50 separate pwr. supp. G2XA1XX1N6X 0.25A 19


Inadvertent 0.25-2A, 3 phase
energiz.
overcurrent

50/ 1 BE1-50/51B 0.1-3.18A 50/51B-1XX Time: 0.1A; TD: 3(EI) 3


51N Stator ground Inst: 10A

51 3 BE1-50/51B 0.5-15.9A, 1 phase 50/51B-1XX P.U.: 7A; TD: 0.8 8, 10, 22,
Stator phase Curve: VI; inst. reset 24

51N 1 BE1-50/51B 0.1-3.18A, 1 phase 50/51B-1XX P.U.: 0.25A; TD: 4 (VI); 2, 6, 22,
Stator ground Inst. reset 23, 24

51N 1 BE1-50/51B 0.1-3.18A, 1 phase 50/51B-1XX P.U.: 2A; TD: 4 (VI); 26


Unit step-up inst. reset
transformer
neutral

51G 1 BE1-50/51B 0.1-3.18A, 1 phase 50/51B-1XX P.U.: 1A; TD: 4 (VI); 4, 26


Stator ground Inst.: 3A; inst. reset

51V 1 BE1-51/27C 3 ph., open delta vts, A1XZ1XX0CXX P.U.: 2A; TD=30; VI; 11, 12, 17,
Ph. b.u. o.c. 0.5-12A, 3 ph. volt. UV=80%; also avail. with 23, 24, 25,
controlled grd. unit (non-controlled) 26

15
Table 1 Relays and Typical Settings for 60 Hz Models
IEEE Basler Model/
No. Qty Function Description Basler Style No. Typical Settings & Remarks Figure No.

51V 1 BE1-51/27C 3 ph., open delta vts, A1XZ1XX0CXX P.U.: 2A; TD=30; VI; 11, 12, 17,
Ph. b.u. o.c. 0.5-12A, 3 ph. volt. UV=80%; also avail. with 23, 24, 25,
controlled grd. unit (non-controlled) 26
59N, 1 BE1-59N 59N: 1-20V; inverse A5XF6XX2SXX 59N: 1V, TD=20; 27-3N: 1V, 4, 6, 25,
27- Ground 27-3N:0.1-2.5V; def time 3rd harm., 10s; 40 db 26
3N, overvoltage 59: 40-120V rejection of 3rd harm. by ov
59 unit and 40 db rejection of
fund. by uv unit; 59: 90V

60 1 BE1-60 3 phase, 120V rated C1XA1XX1CXX p.u.: 5% 17, 26


Voltage balance 5-50% difference p.u.;
open-delta vts

62 1 --- adjustable pickup, 5s pickup delay 19, 26


Timer min. delayed dropout
of 0.05s

63 1 --- 26
Sudden-pressure

64 1 --- 26
Field ground

67 1 BE1-67 0.5-12A, inst. 1-40 times B1XZ2XX3C6X Time: 3A, TD=01 Inst.: 10 20
Directional 3 phase times (30A); def. time
Overcurrent

81 1 BE1-81O/U Over or under, 40-70 Hz, T3XE2XX7SXX 58 and 62 Hz; 99s 26


Frequency two setpoints

86 2 --- 4, 14, 19
Lockout auxiliary

87G 1 BE1-87G 0.1-1.6A, 3 phase G1XA1XX0C6X 0.4A 2, 12,


Differential 23, 24,
25, 26

87N 1 BE1-67N 0.2-6A, 2-100A inst. A4XZ2XX3CXX Current polar.; time: 0.25A; 7
Ground TD: 02 (VI) Inst: Disconnect
differential

87T 1 BE1-87T 3 Ph., 3 input, 2.0-8.9A G1EA1XX0S0X 26


Transformer
differential

NOTE: All of the above functions may be found in Basler Electric numerical multifunction relays. Consult product
bulletins for the BE1-GPS, BE1-CDS, BE1-951, and BE1-851.

16
Revision B August 2000

If you have any questions or need Basler Electric Headquarters Basler Electric International
additional information, please contact Route 143, Box 269, P.A.E. Les Pins, 67319
Basler Electric Company. Highland Illinois USA 62249 Wasselonne Cedex FRANCE
Our web site is located at: Phone 618/654-2341 Phone (33-3-88) 87-1010
http://www.basler.com Fax 618-654-2351 Fax (33-3-88) 87-0808
e-mail: info@basler.com

Você também pode gostar