Escolar Documentos
Profissional Documentos
Cultura Documentos
Application Guide
About the Author
Mr. Rockefeller worked for Westinghouse Electric Corporation for twenty-one years in application and
system design of protective relaying systems. He worked for Consolidated Edison Company for ten
years as a System Engineer. He has served as a private consultant since 1982.
This Guide contains a summary of information for the protection of various types of electrical
equipment. Neither Basler Electric Company nor anyone acting on its behalf makes any warranty or
representation, express or implied, as to the accuracy or completeness of the information contained
herein, nor assumes any responsibility or liability for the use or consequences of use of any of this
information.
First printing April 1994
Revision B August 2000
Generator Protection
Application Guide
Introduction The subjects covered in this guide are as
follows:
This guide was developed to assist in the
selection of relays to protect a generator. The Ground Fault Protection
purpose of each relay is described and related Phase Fault Protection
to one or more power system configurations. A Reverse Power Protection
large number of relays is available to protect for Loss of Field Protection
a wide variety of conditions. These relays Thermal Protection
protect the generator or prime mover from Voltage-Balance Relay Supervision
damage. They also protect the external power Overexcitation Protection
system or the processes it supplies. Inadvertent Energization Protection
Negative-Sequence Overcurrent
The engineer must balance the expense of Protection
applying a particular relay against the Off-Frequency Operation
consequences of losing a generator. The total Integrated Application Examples
loss of a generator may not be catastrophic if it
represents a small percentage of the The references listed on Page 14 provide more
investment in an installation. However, the background on this subject. These documents
impact on service reliability and upset to loads also contain Bibliographies for further study.
supplied must be considered. Damage to and
loss of product in continuous processes can Table 1 provides Basler model, function,
represent the dominating concern rather than description and style number. It also references
the generator unit. Accordingly, there is no the figures where the relays are indicated by
standard solution based on the MW rating. their ANSI designation.
1
The location of the ground fault within the sensitive for ground faults, then the 51N pro-
generator winding, as well as the grounding vides the primary protection for the generator.
impedance, determines the level of fault The advantage of the 87G is that it does not
current. The level is proportional to the pre- need to be delayed to coordinate with external
fault voltage to ground at the fault point: Vfg in protection; however, delay is required for the
Fig. 1. Assuming that the generated voltage 51N.
along each segment of the winding is uniform,
the current level is directly proportional to the
distance of the point from the generator neutral.
A fault 10% from neutral produces 10% of the
current that flows for a fault on the generator
terminals. While the current level drops
towards zero as the neutral is approached, the
insulation stress also drops, tending to reduce
the probability of a fault near the neutral.
FIGURE 2. GROUND-FAULT RELAYING - GENERATOR
LOW-IMPEDANCE GROUNDING.
2
during an external phase fault that produces false However, for these faults, the pre-fault third
residual current due to dissimilar CT harmonic flow in the generator ground is
saturation. disrupted, causing the 27-3N to drop out. The
27-3N performs a valuable monitoring function,
aside from its fault detection function; if the
grounding system is shorted or an open occurs,
the 27-3N drops out. The 59 overvoltage relay
in Fig. 4 supervises the 27-3N relay, so that the
86 lockout relay can be reset when the generator
is out of service; otherwise, the field could not be
applied. Once the field is applied, and the 59
operates, the 27-3N protection is enabled. The
59 relay should be set for about 90% of rated
voltage. An “a” contact of the unit breaker can be
FIGURE 4. UNIT-CONNECTED CASE WITH HIGH- used instead of the 59 relay to supervise 27-3N
RESISTANCE GROUNDING. tripping. However, use of the 59 relay allows the
Fig. 4 shows a unit-connected arrangement 27-3N to provide protection prior to synchroniza-
(generator and step-up transformer directly tion (putting the unit on line), once the field has
connected with no low-side breaker), using high- been applied.
resistance grounding. The resistor and voltage
Where wye-wye voltage transformers (vts) are
relays connect to the secondary of a distribution
connected to the machine terminals, the
transformer. The resistor is normally sized to
secondary vt neutral should not be grounded in
produce a terminal-fault current about equal to
order to avoid operation of 59N for a secondary
the fault current flow in the capacitance of the
ground fault. Instead, one of the phase leads
circuit—on the order of 5-10A primary. Sufficient
should be grounded. This connection eliminates
resistor damping prevents ratcheting up of the
any voltage across the 59N relay for a secondary
sound-phase voltages in the presence of an
ground fault. An isolation vt is required if the
intermittent ground. The ground fault elevates the
generator vts would otherwise be galvanically
sound phase voltages to a nominal 173% of
connected to a set of neutral-grounded vts. Three
rated. On the other hand, the low current level
wye vts should be applied where an iso-phase
minimizes the possibility of sufficient iron damage
bus (phase conductors separately enclosed) is
to require re-stacking. Because of the low current
used to protect against phase-phase faults on the
level, the 87G relay will not operate for single-
generator terminals.
phase ground faults.
The 59N relay in Fig. 4 is subject to operation for
a ground fault on the wye side of any power
transformer connected to the generator. This
voltage is developed even though the generator
connects to a delta winding, because of the
transformer inter-winding capacitance. This
coupling is so small that its effect can ordinarily
be ignored; however, this is not the case with the
FIGURE 5. GROUND FAULT NEAR GENERATOR 59N application because of the very high ground-
NEUTRAL REDUCES THIRD-HARMONIC CURRENT
ing resistance. The 59N overvoltage element
FLOW IN GENERATOR GROUND, DROPPING OUT 27-3N.
time delay allows the relay to override external-
Protection in Fig. 4 consists of a 59N overvolt- fault clearing.
age relay and a 27-3N third-harmonic
undervoltage relay. The 59N relay does not The Basler BE1-59N relay contains the overvolt-
respond to third harmonic voltage produced age (59N), undervoltage (27-3N) and 59 units.
during normal operation (see Fig. 5). The 59N It has a continuous rating of 360V and its filters
will not operate for faults near neutral because provide a 40 dB (100/1) minimum rejection of 3rd
of the reduced fault current level, per Fig. 1. harmonic for the overvoltage (59N) function.
3
The filter prevents tripping due to 3rd harmonic provide for a relay current about equal to the
current flow in the capacitances of the generator generator neutral current. In either position, the
and associated bus and transformers. Thus, a relay pickup should be above the harmonic
relay set for 1V, 60 Hz pickup will require at least current flow during normal operation; this will be
100V third harmonic to operate; the 100V level is approximately 1A. Assuming a maximum fault
sufficient to prevent incorrect operation. current of 8A in the neutral and a pickup of 1A,
88% of the stator winding is covered. As with the
The Basler BE1-59N third harmonic 59N relay, the 51GN delay will allow it to over-
undervoltage element (27-3N) protects for faults ride clearing of a high-side ground fault. An
near the neutral end of the generator stator instantaneous overcurrent element can also be
winding. Fundamental frequency rejection for this employed, set at about three times the time-
element is at least 40dB (100/1). overcurrent element pickup, although it may not
coordinate with primary vt fuses that are con-
In order to provide 100% stator winding cover- nected to the generator terminals.
age, the undervoltage (27-3N) and overvoltage
(59N) settings should overlap. For example, if a
generator-terminal fault produces 240V, 60 Hz
across the voltage relay (59N), a 1V 60 Hz
pickup setting would allow all but the last
(1/240)*100 = 0.416% of the winding to be
covered by the overvoltage function. If 20V, third
harmonic is developed across the relay prior to a
fault, a 1V third-harmonic drop-out setting would
provide dropout for a fault up to (1/20)*100= 5%
from the neutral.
4
generator 51N relay sees 2*10/(50/5) = 2A. about 175% of rated current to override swings
Then the relay protects down to (0.1/2)*100 = due to a slow-clearing external fault, the starting
5% from the neutral. of a large motor, or the re-acceleration current of
a group of motors. Energization of a transformer
When feeder cables are connected to the may also subject the generator to higher than
generator bus, the additional capacitance rated current flow.
dictates a much lower level of grounding resis-
tance than achieved with a unit-connected case.
A lower resistance is required to minimize
transient overvoltages during an arcing fault.
5
provide 3 phase fault protection. The current Voltage-restrained or voltage-controlled time-
does not decay as fast for a phase-phase fault, overcurrent relays (51V) may be used as shown
and thereby allows the 51 relay more time to trip in Fig. 11 to remove any concerns about ability
before current drops below pickup. Fig. 9 to operate before the generator current drops
assumes no voltage regulator boosting, al- too low. The voltage feature allows the relays
though the excitation system response time is to be set below rated current. The Basler
unlikely to provide significant fault current BE1-51/27R voltage restrained type causes the
boosting in the first second of the fault. If the pickup to decrease with decreasing voltage. For
generator is loaded prior to the fault, the super- example, the relay can be set for 175% of
position of the fault current in Fig. 9 and the generator rated current with rated voltage
prefault load current will provide the relay with a
higher level of current than indicated by the Fig.
9 curves. For example, at one second, the 3
phase fault value would be 2.4 times rated,
assuming a pre-fault rated load at 30 degree
lag, rather than 1.75 times rated. Under these
circumstances, the 51 relay has more time to
operate before current decays below pickup.
6
Therefore, anti-motoring protection is recom-
mended whenever the unit may be connected to
a source of motoring power. Where a non-
electrical type of protection is available, as may
be the case with a steam turbine unit, the 32
relay provides a second means of detecting this
condition. Time delay should be set for about 15
seconds. This will provide time for the controls
to pick up load upon synchronizing when the
generator is initially slower than the system.
7
Loss-of-Field Protection due to other transient conditions. The Basler
BE1-40Q relay is equipped with a timer for this
purpose.
Thermal Protection
8
Overexcitation relay (24) does not need to be
blocked, since it will not see overvoltage when a
fuse blows.
9
induction motor with excessive current flow in independent of the plant is desired. In this case
the rotor. Both Fig. 19 and 20 schemes will the 67 relays would be placed in the switchyard
function properly with the vt fuses at the genera- rather than in the control room. While directional
tor terminal removed. With the generator off line, overcurrent relay (67) should be delayed to ride
safety requirements may dictate the removal of through generator swings, it can still provide
these vt fuses. In the case of Fig. 19, the faster backup for generator faults than provided
overcurrent protection is enabled by by 51 or 51V type relays, since the 67 relays
undervoltage units. In Fig. 20 the potential is need not be coordinated with external protec-
taken from bus vts, rather than unit vts, so the tion. Fig. 20 shows the operating range for
scheme will function even if the vt fuses were phase A current (Ia) with respect to phase b to c
removed during unit maintenance. voltage (VBC). This range is fixed by the 60
degree characteristic angle and the ±45 degree
In Fig. 19 the terminal voltage will be zero prior limits set on the operating zone.
to energization, so the 27 relay contacts will be
closed to energize the timer (62). The
instantaneous overcurrent relay (50) trip circuit
is established, after timer 62 operates. Upon
generator energization, the undervoltage units
may operate due to voltage transients, but the
delayed dropout of 62 allows relay 50 to initiate
tripping. The use of two 27 relays on separate vt
circuits avoids tripping for a vt fuse failure.
Alternatively, a voltage-balance relay (60) could
be used in conjunction with a single 27 relay to
block tripping.
10
and design of the generator. These values can Relays and Typical Settings
be exceeded with an open phase on a heavily-
loaded generator. The Basler BE1-46N relay Table 1 lists the applicable relays keyed to the
protects against this condition. various functional one-line figures. The third
column lists the Basler model and the sixth
column, the Basler style number. These style
numbers apply for 60 Hz relays. The style
numbers also apply for open delta vts, 120V line-
line. Where applicable, other Basler relay styles
are available for wye vts. The right column
provides typical settings for use as a starting
point in the setting determination procedure. The
proper settings are heavily influenced by the
FIGURE 21. NEGATIVE-SEQUENCE RELAY (46) specifics of each application. Typical settings are
PROTECTS AGAINST ROTOR OVERHEATING DUE TO also used as an aid in selecting the relay range
A SERIES UNBALANCE OR PROTRACTED EXTERNAL
FAULT. where a choice is available.
Off-Frequency Operation
Diesel engines can be safely operated off FIGURE 22. EXAMPLE OF BARE-MINIMUM PROTECTION
(LOW-IMPEDANCE GROUNDING).
normal frequency and no protection is required.
Gas turbine controls generally provide Fig. 22 represents bare-minimum protection, with
protection for off frequency conditions and only fault protection. It may appear to be a
separate relays are not required. In contrast, disadvantage to use CTs on the neutral side as
frequency relays are sometimes applied with shown, since the relays may operate faster with
steam-turbine units, particularly to minimize CTs on the terminal side. The increase in speed
turbine blade fatiguing. Ref. 3 specifically would result with a larger current contribution
addresses abnormal frequency operation. Fig. 5 from external sources. However, if the CTs are
of Ref. 3 shows frequency operating limits located on the terminal side of the generator,
specified by various generator manufacturers. there will be no protection prior to putting the
The simplest relay application would be a single machine on line. This is not recommended
underfrequency stage (e.g. BE1-81). The Basler because a generator with an internal fault
BE1-81 O/U relay can be provided with up to could be destroyed when the field is applied.
four setting stages, each with a time-delay
setting of up to 99 seconds. Each setpoint may
be set to recognize either overfrequency or
underfrequency.
11
quality of differential relay protection. A defi-
ciency in the CT circuits is unlikely to disable
both the 87G and 51V relays. Rather, a shorted
CT or defective connection will unbalance the
differential circuit and cause the 87G to trip.
Independent CTs could be used to provide
improved back-up protection, although this
seems to be a minimal advantage here. How-
ever, a separate CT is used for the 51N relay
that provides protection for the most likely type
of fault.
Fig. 23 shows three relays sharing the same Fig. 24 differs from Fig. 23 only in the use of a
CTs with a differential relay. This is practical ground differential relay (87N). This protection
with solid state relays because of their low provides faster clearing of ground faults where
burden and will not significantly degrade the the grounding impedance is too high to sense
12
ground faults with the phase differential relay Fig. 26 shows the application of additional relays
(87G). The auxiliary CT (ACT) is used to step up for extended protection: overexcitation relay
the current from the phase CTs by 10:1. The (24), negative-sequence overcurrent relay (46),
51N relay provides backup for the ground ground-overcurrent relay (51GN), voltage-
differential (87N) and for external faults. The balance relay (60), field-ground relay (64F),
Basler BE1-67N relay functions as the 87N frequency relay (81) and the 27/50/62 relay
relay, using the current polarizing mode. The combination for inadvertent energization protec-
polarizing winding measures the neutral current. tion. Relay 51GN provides a second means of
detecting stator ground faults or faults in the
generator connections or faults in the delta
transformer windings. Differential relay 87T and
sudden-pressure relay 63 protect the unit step-
up transformer. Relay 51N provides backup for
external ground faults and for faults in the high-
voltage transformer windings and leads. This
relay may also respond to an open phase
condition or a breaker-interrupter flashover that
energizes the generator. The 51N relay will be
very slow for the flashover case, since it must
be set to coordinate with external relays and is a
last-resort backup for external faults.
13
FIGURE 26. EXTENDED PROTECTION EXAMPLE (HIGH-RESISTANCE GROUNDING).
Bibliography
1. IEEE C37.101-1993, IEEE Guide
for Generator Ground Protection
2. IEEE C37.102-1995, IEEE Guide
for AC Generator Protection
3. IEEE C37.106-1987, IEEE Guide
for Abnormal Frequency Protection for
Generating Plants
4. J. Lewis Blackburn, “Protective Relay
ing: Principles and Applications”, 2nd
Edition, Marcel Dekker, Inc., 1998.
5. S. Horowitz and A. Phadke, “Power
System Relaying”, John Wiley & Sons,
Inc., 1992.
14
Table 1 Relays and Typical Settings for 60 Hz Models
IEEE Basler Model/
No. Qty Function Description Basler Style No. Typical Settings & Remarks Figure No.
32 1 BE1-32R 2 elem.; open delta vts; E1XE1XX0SXX 12W; 15s 13, 23, 24,
Reverse power 1.5-60W; def. time; 25, 26
120V ac
32-1, 2 BE1-32R 2 elem.; open delta vts; E1XE1XX0SXX 12W; 32-1: 3s; 32-2: 30s 14
32-2 Reverse power 1.5-60W; def. time
40 1 BE1-40Q 25-1000 var. 120V, F3XE1XX1SXX 100 vars; 0.2s 13, 17, 23,
Loss-of-field open-delta vts 24, 25, 26
46 1 BE1-46N with external monitor G1XB8XX3XXX Alarm p.u.: 3%; Trip p.u.: 21, 26
Neg. sequence 10%; K=10; max. time=200s
overcurrent
49 1 BE1-49 60-190 degrees C PXXA1XX0SXX Lower: 95; upper: 105 16, 23, 24,
Stator 25, 26
temperature
51 3 BE1-50/51B 0.5-15.9A, 1 phase 50/51B-1XX P.U.: 7A; TD: 0.8 8, 10, 22,
Stator phase Curve: VI; inst. reset 24
51N 1 BE1-50/51B 0.1-3.18A, 1 phase 50/51B-1XX P.U.: 0.25A; TD: 4 (VI); 2, 6, 22,
Stator ground Inst. reset 23, 24
51V 1 BE1-51/27C 3 ph., open delta vts, A1XZ1XX0CXX P.U.: 2A; TD=30; VI; 11, 12, 17,
Ph. b.u. o.c. 0.5-12A, 3 ph. volt. UV=80%; also avail. with 23, 24, 25,
controlled grd. unit (non-controlled) 26
15
Table 1 Relays and Typical Settings for 60 Hz Models
IEEE Basler Model/
No. Qty Function Description Basler Style No. Typical Settings & Remarks Figure No.
51V 1 BE1-51/27C 3 ph., open delta vts, A1XZ1XX0CXX P.U.: 2A; TD=30; VI; 11, 12, 17,
Ph. b.u. o.c. 0.5-12A, 3 ph. volt. UV=80%; also avail. with 23, 24, 25,
controlled grd. unit (non-controlled) 26
59N, 1 BE1-59N 59N: 1-20V; inverse A5XF6XX2SXX 59N: 1V, TD=20; 27-3N: 1V, 4, 6, 25,
27- Ground 27-3N:0.1-2.5V; def time 3rd harm., 10s; 40 db 26
3N, overvoltage 59: 40-120V rejection of 3rd harm. by ov
59 unit and 40 db rejection of
fund. by uv unit; 59: 90V
63 1 --- 26
Sudden-pressure
64 1 --- 26
Field ground
67 1 BE1-67 0.5-12A, inst. 1-40 times B1XZ2XX3C6X Time: 3A, TD=01 Inst.: 10 20
Directional 3 phase times (30A); def. time
Overcurrent
86 2 --- 4, 14, 19
Lockout auxiliary
87N 1 BE1-67N 0.2-6A, 2-100A inst. A4XZ2XX3CXX Current polar.; time: 0.25A; 7
Ground TD: 02 (VI) Inst: Disconnect
differential
NOTE: All of the above functions may be found in Basler Electric numerical multifunction relays. Consult product
bulletins for the BE1-GPS, BE1-CDS, BE1-951, and BE1-851.
16
Revision B August 2000
If you have any questions or need Basler Electric Headquarters Basler Electric International
additional information, please contact Route 143, Box 269, P.A.E. Les Pins, 67319
Basler Electric Company. Highland Illinois USA 62249 Wasselonne Cedex FRANCE
Our web site is located at: Phone 618/654-2341 Phone (33-3-88) 87-1010
http://www.basler.com Fax 618-654-2351 Fax (33-3-88) 87-0808
e-mail: info@basler.com