Você está na página 1de 1

ILUMINAÇÃO CHUV EIRO AR AUTOCLAVE ESTUFA DESTILADOR MUFLA DIGESTOR POTÊNCIA SECÇÃO

TOMADAS (W) TENSÃO DISJUNTOR BALANCEAMENTO (W)


CIRC. FLUORESCENTE (W) COND. (W) (W) (W) (W) (W) INSTALADA CONDUTOR
(V) TERMOMAG.
30 40 100 600 4500 1600 6000 1600 3500 4000 1600 (W) (mm²) AN. BN CN AB BC CA
1 3 32 1370 127 2,5 20 1370
2 22 880 127 2,5 20 880
3 2 20 860 127 2,5 20 860
4 32 1280 127 2,5 20 1280
5 1 4500 220 6,0 40 4500
6 1 4500 220 6,0 40 4500
7 1 1600 220 2,5 20 1600
8 1 1600 220 2,5 20 1600
9 1 1600 220 2,5 20 1600
10 1 1600 220 2,5 20 1600
11 1 1600 220 2,5 20 1600
12 1 6000 220 10,0 50 6000
13 1 1600 220 2,5 20 1600
14 1 1600 220 2,5 20 1600
15 1 3500 220 4,0 30 3500
16 1 3500 220 4,0 30 3500
17 1 4000 220 4,0 30 4000
18 1 1600 220 2,5 20 1600
19 20 1 2600 127 6,0 40 2600
20 1 3 1900 127 4,0 30 3100
21 13 2 2500 127 6,0 40 3100
22 8 800 127 2,5 20 800
23 9 1 1500 220 2,5 20 1500
24 24 2400 220 4,0 30 2400
TOTAL 5 106 75 7 2 5 1 2 2 1 1 54890 220 - - 4830 4780 4380 13600 14300 14800

CARGA INSTALADA: 54,89 KW CALCULO DEMANDA (D)


RAMAL DE LIGAÇÃO: SUBTERRÂNEO D=A+B+C+D+E+F+G+I
CONDUTORES: 4X70mm² - TERRA: 35mm² A=12790X,072 5755,50 ILUMINAÇÃO+TUG
DISJUNTOR: TERMOMAGNÉTICO TRIPOLAR, 150 A B=9000X0,92 8280,00 CHUVEIROS
ELETRODUTO: 60mm - PVC C=8000X0,76 6080,00 AR COND.
D=6000X1 6000,00 AUTOCLAVE
E=3600X0,92 3312,00 ESTUFA
F=7000X0,92 6440,00 DESTILADOR
G=4000X1 4000,00 MUFLA
H=1600X1 1600,00 DIGESTOR
I=2000 2000,00 DEMAIS EQUIP.
D= 43,47 KW