www.siemens.com/busbar
Contents
Totally Integrated Power 2
Introduction to the LI system 3
Applications of the LI system 4 – 5
Advantages of the LI system 6 – 9
SIVACON 8PS – LI system 10
Body sizes 11
Conductor configuration 12 – 13
Power transmission 14 –15
Power distribution 16 – 17
Installation 18 – 20
Fire barriers 21
Type code 22 – 23
Technical data 24 – 25
Support 26 – 27
Our products, systems, and solutions for low- As part of the Totally Integrated Power concept, the
and medium-voltage make power distribution LI system from the SIVACON 8PS busbar trunking system
efficient, reliable, and safe – in cities, infra- portfolio embodies the motto “We bring power to the
point”. Power is delivered safely and reliably to the loads –
structure, buildings, and industrial plants.
and in a flexible and efficient way. For power transmission
They can be linked to industrial and building and power distribution in infrastructure and industrial
automation, and are rounded out by com applications from 800 A to 6300 A, the LI system provides
prehensive support throughout the entire an integrated solution to the application requirements.
lifecycle.
2
SIVACON 8PS busbar trunking system –
LI system
An integrated solution for safe and efficient power supply
Benefits
The LI system offers a broad range of design verified trunking and tap-off units Integrated and future-
in accordance with the new IEC 61439-1/-6 standards, enabling high personnel proof at every stage
and system safety as well as improved operational availability.
Safe for people and
The fire barrier for the LI system has been tested for fire resistance classes EI90 plant
and EI1201) (category of EN 13501) in accordance with EN 1366-3 to meet
Efficient in all project
building requirements according to European Standards, providing a high degree
phases
of safety for your infrastructure.
Flexible in planning and
Furthermore today’s infrastructures require space-saving power supply. The
operation
compact design of the LI system satisfies this requirement and facilitates
integration into narrow buildings in order to achieve a cost-efficient Reliable in operation
infrastructure.
Innovative technical features such as tap-off units with measuring devices
enable a modern energy management in accordance with ISO 50001 – meeting
the latest demands for increased power efficiency and energy performance.
Let us introduce to you the advantages of an integrated system with high
flexibility and security of investment.
1) In preparation
3
Applications of the LI system
Supplying large amounts of power over long distances for infrastructure
and industry
1) In accordance with EN 50110-1 (VDE 0105-1); please always observe national regulations/standards
2) Tap-off units from 800 A up to 1250 A in preparation 5
Integrated
6
Safe
1) In preparation
7
Efficient Flexible
8
Reliable
Reliable in operation.
Benefits Secure your system availability Benefits
Economic targets go hand in hand with
Variety of feeding units and acces-
high operational reliability. Thanks to the Design verified in accordance with
sories to connect to transformers, compact sandwich design, the LI system current standard IEC 61439-1 / -6
switchboards and other power allows power transmission with a low-
High operating voltage
sources voltage drop. Furthermore, the LI system
(Ue = 1000 V)
can run at full load at high ambient
Range of conductor configurations
temperatures up to 40 °C, without High short-circuit rating
to fit grid types
derating.
High degree of protection IP55
Compact design for high current
The LI system also supports you through
ratings as double body side-by-side Full loads at high ambient
robust and error-free hook and bolt con-
for vertical runs temperature (40 °C)
nections with shear-off nuts to ensure
Quick and easy modification or
joints are adequately tightened. Long busbar runs with low-voltage
expansion with plug-on / -off tap-off drop due to sandwich design
Delivering a high level of rated data such
units up to 1250 A2) on energised3)
as short-circuit rating, operational voltage Hook and bolt connection with
runs
and degree of protection, the LI system shear-off nut for optimised connec-
Modular tap-off unit configuration
ensures system and power supply tion of the busbar trunkings
reliability for your infrastructure.
9
SIVACON 8PS – LI system
A compact system for safe and efficient power supply
2 7
6
6
4
5 2
2 3
2 Fire barrier
5 Junction unit
6 Tap-off unit
10
Body sizes
Compact dimension saves space and makes installation easier
H
100
W
11
Conductor configuration
Wide range of configurations available to fit different requirements
/ / /
/ / /
/ / /
1 3(1 3(1 3(
3( 1
Grid type / System
Electrical equipment must be selected to
fit the associated grid type / system in
order to determine the protective mea-
sures that are required (in accordance
with IEC 60364).
12
/ /
/ /
/ /
1
3(
3(
TT grid IT grid
In TT systems, one point is directly earthed; The IT system has no direct link between
the exposed parts of the electrical installation active conductors and earthed parts; the
are connected to earth electrodes which are exposed parts of the electrical installa-
isolated from the system earth electrode. tion are earthed. Today’s IT systems
feature protective measures in the form
of a protective conductor system.
Conductor configuration1)
1 2 3 4 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 7
1 2 3 4 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 6 7
L1 L2 L3 PEhsg PENbar L1 L2 L3 PEhsg2) N L1 L2 L3 PEN50 %2) or 100 % N N L1 L2 L3 CPE PEhsg2)
+ hsg bar + hsg
1 2 3 4 5 1 2 3 4 5 6
N L1 L2 L3 PEhsg N N L1 L2 L3 PEhsg2)
1 2 3 4 5 6
N L1 L2 L3 CPE PEhsg2)
1) The 50 % and 100 % PE bar cross-sections are defined as two different conductor configurations
13
2) In preparation
Power transmission
Safe, flexible and efficient solution
14
Junction units Connection LI system / SIVACON S8
Elbow
Knee
Powermanager –
power monitoring software
7KM PAC4200
measuring device
Molded Fuse-switch-
case disconnector
circuit-
breakers
16
Modular tap-off units
1 2
Align the trunking ends with hook and bolt. Tighten the self-torque bolt until the outer head of
Join and connect the busbar elements. the nut shears off. This indicates a correct torque
level of 40 Nm.
18
3 4
Install side covers followed by top and bottom covers. Final hook and bolt connection
Then, fasten screws. with degree of protection IP55.
19
Fixing brackets
Simple fixing accessories to fit a range of building structures
20
Fire barriers
Built-in prevention for a safe infrastructure
European building regulations The LI system fire barrier has been tested
Benefits
prescribe that buildings must for fire resistance classes EI90 and EI1201
be designed in such a way that (category acc. to EN 13501) in accor- High degree of person-
dance with EN 1366-3 to meet European
“fire and smoke are prevented nel and infrastructure
building requirements. safety
from starting and spreading
and that, if there is a fire, effec- In accordance with different national Tested in accordance
tive fire fighting and the saving requirements, various approval kits are with EN 1366-3
also available on request2).
of human and animal life is Flexible with kit solution
possible”. This means that no for fire barriers
fire or fumes are permitted to
spread from one floor or fire
section to another.
1) In preparation
2) “ Fire test passed” approval for various countries in preparation 21
Type code
Selection and ordering data
Conductor material
Al A
Cu C
Insulation material
Mylar® film M
Epoxy coating and Mylar® film E
None (where feature not relevant) N
22
Type code for tap-off units LI - T - .... - .. - .. - . - . - .. - . - . . - . .
23
Technical data
Standards and regulations IEC 61439-1/-6, EN 61439-1/-6
Ambient temperature (min. / max. / 24-hour average)1) °C –5 / +50 / +40
Degree of protection IP55
Mounting positions Horizontal edgewise, horizontal flat2), vertical
Busbar surface treatment At the current transitions: LI-A nickel-coated
and tin-plated, LI-C tin-plated
Insulation Mylar®, epoxy coating with additional Mylar®3)
Class of protection against external mech. loads IK08
Trunking unit material Aluminium, powder-coated
Tap-off unit material Steel sheet, powder-coated
Colour of trunking unit, tap-off unit RAL 7035 (light grey)
Rated insulation voltage in acc. with IEC 61439-1 V AC 1,000
Rated operating voltage (transmission) V AC 1,000
for overvoltage category III/3
Rated operating voltage (energy distribution with V AC 690
tap-off units) for overvoltage category III/3
Frequency Hz 50 / 604)
1) Temperature factor k1 for min. and max. ambient temperature on request
2) Mounting factor k2 for mounting positions
3) In preparation
4) In accordance with IEC 61439, a reduction to 95 % is required for currents > 800 A at 60 Hz frequency
LI-A
Rated current InA A 800 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000
Conductor material Aluminium
Short-circuit rating
Rated short-time Icw kA 35 50 60 65 80 100 120 150 150
withstand current (1s)
Rated peak Ipk kA 77 110 132 143 176 220 264 330 330
withstand current
LI-C
Rated current InA A 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000 6,300
Conductor material Copper
Short-circuit rating
Rated short-time Icw kA 43 60 65 80 100 1001) 150 150 150
withstand current (1s)
Rated peak Ipk kA 94.6 132 143 176 220 2201) 330 330 330
withstand current
1) For PE conductor (100 %) Icw = 120 kA, Ipk = 264 kA
24
Tap-off units
Installation with circuit-breaker1) 3VL1 3VL2 3VL3 3VL4 3VL5
Rated current Ie2) A 50 – 160 50 – 160 200 – 250 315 – 400 500 – 630
Rated conditional short-circuit current (Icc) kA 55 55 55 55 55
with switching capacity N
Rated conditional short-circuit current (Icc) kA 70 70 70 70 70
with switching capacity H
Rated conditional short-circuit current (Icc) kA – 100 100 100 100
with switching capacity L
25
Support
Optimize your time with Siemens as a competent partner at your side
Our website offers you SIVACON 8PS busbar trunking systems Convenient electrical planning with
a broad range of pro- on the Internet SIMARIS software tools
Visit us online. You can obtain additional Planning electric power distribution for
motional and technical
information on our SIVACON 8PS busbar industrial plants, infrastructure and
information such as trunking systems, for example the buildings is becoming more and more
helpful tools for our SIVACON 8PS overview brochure, along complex. To help electrical planning
SIVACON 8PS busbar with links to technical materials at: engineers to work faster and better under
trunking systems. www.siemens.com/busbar existing conditions, the innovative
SIMARIS software tools effectively
Tender specification texts
support the planning process.
We offer a comprehensive range of
specification texts to support you: SIMARIS design
www.siemens.com/specifications For network calculations and dimension-
ing, SIMARIS design offers a secure solu-
Reliable local support
tion from the broad product portfolio
Our local experts are there for you
of power distribution, according to reco-
around the world, helping you to develop
gnised rules and standards (VDE, IEC),
solutions for your energy supply, and
and specific requirements. The specific
providing you with specific expertise on
components that are required are
project management and financial
selected automatically on the basis of
services for your projects. Important
the given project structure and the basic
aspects of safety, logistics, and environ-
data collected.
mental protection are considered.
Advanced users can buy the SIMARIS
We will gladly advise you as an end user
design professional version which pro-
or planner. In the planning phase espe-
vides additional functions: Display and
cially, our experts from Totally Integrated
dimensioning of networks with parallel
Power (TIP) will provide you with profes-
network operation, automatic selectivity
sional consulting, software tools, specifi-
evaluation, export of the created project
cation texts, and planning manuals.
for further processing in SIMARIS project,
creation of active and passive emergency
power supply systems.
26
Technical documentation on the internet Training offer
www.siemens.com/lowvoltage/product-support www.siemens.com/lowvoltage/training
27