Model KSS/KSP

Specific-Breaker Rated ATS

MPACt 1500 Controller


Standard Features
D Microprocessor-based controller
D Environmentally sealed user interface
D LCD display, 4 lines x 20 characters, backlit
D Dynamic function keypad with tactile feedback pushbuttons
allows complete programming and viewing capability at the
door
D LED indicators: Source available, transfer switch position,
service required (fault), and “not in auto”
D Broadrange voltage sensing (208--600 VAC) on all phases
D Phase-to-phase sensing and monitoring with 0.5% accuracy
on both sources
D Frequency sensing with 0.5% accuracy on both sources
D Anti-single phasing protection
D Phase rotation sensing for three-phase systems
D Real-time clock with automatic adjust for daylight saving time
and leap year
D Time-stamped event log
D Fail-safe transfer for loaded test and exercise functions
D DIP switches: password disable and maintenance
D Modbusr RTU and Modbusr TCP/IP protocols
Ratings (Modbusr register map available)
D RJ45 connector for 10/100 ethernet connection
Voltage: 208--480 VAC 50/60 Hz
D USB port with read/write compatibility
Current: 40--1000 Amps (standard transition) D Isolated RS-485 ports
100--600 Amps (programmed transition) D One-year limited warranty

Transfer Switch Standard Features Programmable Features


D Programming and monitoring methods:
D UL 1008 listed at 208--480 VAC
file # E58962 (automatic), # E86894 (nonautomatic) d Monitoring and password-protected programming at the
door using the keypad and display
D CSA certification available
d Program and monitor using a PC with Monitor III
D Available with either automatic or non-automatic control
integrated generator set and ATS monitoring software
D Available in 2, 3, or 4 pole configurations
d Transfer files through the USB port
D High withstand/closing ratings, for use with specific breakers
D System voltage and frequency
only
D Voltage unbalance
D Electrically operated, mechanically held mechanism
D Over/undervoltage and over/underfrequency for all phases of
D Double-throw, mechanically interlocked design
the normal and emergency sources
(break-before-make power contacts)
D Time delays
D Enclosed arc chambers with arc chutes
D Load/no load/auto-load test and load/no-load exercise
D Standard-transition model KSS and programmed-transition
functions
KSP model available
D Programmable inputs and outputs
D Silver tungsten alloy contacts on 400--600 amp models
(Model KSS) D Load control outputs (load stepping)
D Silver alloy main contacts (Model KSP) D Selectable operating modes: utility-generator,
generator-generator, or utility-utility
D Front-accessible contacts for easy inspection
D Load bank control for exercise or test
D Programmed-transition operation provides a center OFF
position that allows residual voltages in the load circuits to D Pre/post-transfer, nine individual time delays for selected loads
decay (Model KSP) D ABC/BAC/none phase rotation selection with error detection
D Main shaft auxiliary position-indicating contacts, one set D Resettable historical data
Normal and one set Emergency D In-phase monitor
D Password protection, three security levels
G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 1
MPACt 1500 Controller Features
User Interface LED Indicators Communications
D Contactor position: source N and source E D USB port with read/write capability
D Source available: source N and source E D Isolated RS-485 ports
D Service required (fault indication) D RJ-45 connector for 10/100 ethernet connection
D Not in automatic mode D Modbusr RTU and Modbusr TCP/IP protocols
(Modbusr register map available)
LCD Display
D USB Port. Upload or download files from a PC or a memory
D System status device through the USB port.
D Line-to-line voltage d Application software
D Line-to-neutral voltage d Event history files
D Active time delays d Language files
D Source frequency d Parameter settings
D Preferred source selection d Usage reports
D System settings d Feature configuration
D Common alarms
Programmable Features
D Load current, each phase (requires optional current
transformers) D System voltage, 208--600 VAC *
D Inputs and outputs D System frequency, 50/60 Hz *
D Faults D Single/three-phase operation *
D Time/date D Standard/programmed-transition operation *
D Address D Preferred source selection
D Event history D Phase rotation: ABC/BAC/none selection with error
detection
D Maintenance records
D Voltage and frequency pickup and dropout settings
D Exerciser schedule
D Voltage unbalance, enable/disable
D Exerciser mode
D In-phase monitor: enable/disable and phase angle
D Time remaining on active exercise
D Transfer commit/no commit
Dynamic Function Tactile Keypad Operations D Source/source mode: utility/gen, gen/gen, utility/utility
D Scroll up/down/forward/back D Passwords, system and test
D Increase/decrease/save settings D Time, date, automatic daylight saving time enable/disable
D End time delay D Time delays (see table)
D Start/end test D Exerciser: calendar mode, loaded/unloaded up to 21 events
D Reset fault D Test: loaded/unloaded/auto load (1--60 minutes)
D Lamp test D External test: loaded/unloaded
Main Logic Board Inputs and Outputs D Automatic override on generator failure
(loaded test and exercise)
D Two (2) programmable inputs
D Peak shave delay enable/disable
D Two (2) programmable outputs, isolated form C (SPDT)
contacts rated 1 amp @ 30 VDC, 500 mA @120 VAC D Current monitoring (requires optional current transformers)
D Pre/post-transfer, nine individual time delays for selected
DIP Switches loads
D Maintenance mode D Resettable historical data
D Password disable

Event History
View up to 99 time and date-stamped events on the display or
on a personal computer equipped with optional Monitor III
software. Download up to 2000 events with Monitor III software
or download complete event history file to a PC or a memory * System parameters factory-set per order
device connected to the USB port. Modbusr is a registered trademark of Schneider Electric.

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 2


MPACt 1500 Controller Features, continued
Programmable Inputs Voltage and Frequency Sensing
D External time delay input
Adjustment
D External battery fault Parameter Default Range
D External common fault Undervoltage dropout 90% of pickup 75%--98%
D Inhibit transfer
Undervoltage pickup 90% of nominal 85%--100%
D Load shed to force transfer to OFF (programmed- transition
models only; requires optional load shed kit) Overvoltage dropout * 115% of nominal* 106%--135%
D Peak shave/area protection input Overvoltage pickup 95% of dropout 95%--100%
D External test Unbalance enable Disable Enable/Disable
D Three-source system disable Unbalance dropout 20% 5%--20%
D Bypass disable
Unbalance pickup 10% 3%--18%
Programmable Outputs Voltage dropout time 0.5 sec. 0.1--9.9 sec.
D Chicago alarm control
Underfrequency dropout 99% of pickup 95%--99%
D Common alarm events
Underfrequency pickup 90% of nominal 80%--95%
D Contactor position
Overfrequency dropout 101% of pickup 101%--115%
D Exercise active
D Failure to acquire standby source Overfrequency pickup 110% of nominal 105%--120%
D Failure to transfer Frequency dropout time 3 sec. 0.1--15 sec.
D Generator engine start, source N and E * 690 volts, maximum. Default = 110% for 600 volt applications.
D I/O module faults
D Load bank control
Adjustable Time Delays
D Load control active (pre/post transfer delay, up to 9 outputs)
Adjustment
D Loss of phase fault, source N and E Time Delay Default Range
D External battery fault
Emergency source engine start 3 sec. 0--6 sec.[
D Non-emergency transfer
Normal source engine start
D Not in automatic mode 3 sec. 0--6 sec. [
(gen/gen mode)
D Over/underfrequency faults, source N and E (generator)
Emergency source engine cooldown 5 sec.
D Over/undervoltage faults, source N and E
Normal source engine cooldown
D Peak shave/area protection active 2 sec.
(gen/gen mode)
D Phase rotation error, source N and E
Failure to acquire standby source 1 min.
D Preferred source supplying load
D Software-controlled relay outputs (four maximum) Preferred to standby 3 sec.

D Source available, preferred and standby Standby to preferred 15 min.


D Standby source supplying load Pretransfer to preferred signal 0 sec.
D Synchronizing output Post-transfer to preferred signal 0 sec. 0--60 min. [
D Test active
Pretransfer to standby signal 0 sec.
D Transfer switch auxiliary contact fault
Post-transfer to standby signal 0 sec.
D Transfer switch auxiliary contact open
Failure to synchronize 30 sec.
D Voltage unbalance
Off (preferred to standby,
1 sec.
programmed-transition only)
Off (standby to preferred,
1 sec.
programmed-transition only)
Auto load test duration 30 min. 1--60 min. ]
[ Adjustable in 1 second increments. Engine start can be extended to
60 minutes with an External Battery Supply Module Kit.
] 1 minute increments.

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 3


Application Data Codes and Standards
UL-Listed Solderless Screw-Type Terminals The ATS meets or exceeds the requirements of the following
for External Power Connections specifications:
Normal, Emergency, and Load Terminals D Underwriters Laboratories UL 508, Standard for Industrial
Control Equipment
Switch
Rating, Cables per Range of Wire Sizes, D Underwriters Laboratories UL 1008, Standard for Automatic
Model amps Pole Copper or Aluminum* Transfer Switches for Use in Emergency Standby Systems
40--150 1 #8 to 3/0 AWG
file # E58962 (automatic), # E86894 (nonautomatic)
D CSA C22.2 No. 178 certification available, file # LR58301
200--225 1 #6 AWG to 250 MCM
D NFPA 70, National Electrical Code
260 1 #6 AWG to 350 MCM
D NFPA 99, Essential Electrical Systems for Health Care
1 #4 AWG to 600 MCM
KSS 400 Facilities
2 #1/0 AWG to 250 MCM
D NFPA 110, Emergency and Standby Power Systems
600 2 #2 AWG to 600 MCM
D IEEE Standard 446, IEEE Recommended Practice for
800 2 #1/0 AWG to 750 MCM Emergency and Standby Power Systems for Commercial
and Industrial Applications
1000 4 #2 AWG to 600 MCM
D NEMA Standard ICS 10--2005, Electromechanical AC
100 1 #14 to 1/0 AWG
Transfer Switch Equipment
200 1 #6 AWG to 250 MCM
D EN61000-4-4 Fast Transient Immunity Severity Level 4
KSP 2 1/0 AWG to 250 MCM
400 D IEC 60947-6-1, Low Voltage Switchgear and Control Gear;
1 #4 AWG to 600 MCM Multifunction Equipment; Automatic Transfer Switching
Equipment
600 2 #2 AWG to 600 MCM
D EN61000-4-5 Surge Immunity Class 4
* Use 60°C minimum wire for #14 to #1 AWG. Use 75°C minimum
wire for 1/0 AWG and larger. (voltage sensing and programmable inputs only)
D IEC Specifications for EMI/EMC Immunity:

Environmental Specifications d CISPR 11, Radiated Emissions


d IEC 1000-4-2, Electrostatic Discharge
Operating Temperature --20°C to 70°C (--4°F to 158°F)
d IEC 1000-4-3, Radiated Electromagnetic Fields
Storage Temperature --40°C to 85°C (--40°F to 185°F)
d IEC 1000-4-4, Electrical Fast Transients (Bursts)
Humidity 5% to 95% noncondensing
d IEC 1000-4-5, Surge Voltage
d IEC 1000-4-6, Conducted RF Disturbances
Input and Output Connection Specifications d IEC 1000-4-8, Magnetic Fields
Component Wire Size Range d IEC 1000-4-11, Voltage Dips and Interruptions
Main board I/O terminals #12--24 AWG D IEEE 472 (ANSI C37.90A) Ring Wave Test
I/O module terminals #14--24 AWG

Contact Ratings
Motor Load
Resistive Load Inductive Load NC NO
Engine Start Contacts 2 A @ 30 VDC N/A N/A N/A
Auxiliary Contacts, KSS (40--600A) 15 A @ 250 VAC N/A N/A N/A
Auxiliary Contacts, KSS (800--1000A) 15 A @ 480 VAC 15 A @ 250 VAC; 5 A @ 125 VAC; 2.5 A @ 125 VAC;
6 A @ 500 VAC 3 A @ 250 VAC; 1.5 A @ 250 VAC;
1.5 A @ 500 VAC 0.75 A @ 500 VAC
Auxiliary Contacts, KSP 15 A @ 480 VAC 15 A @ 250 VAC; 5 A @ 125 VAC; 2.5 A @ 125 VAC;
6 A @ 500 VAC 3 A @ 250 VAC; 1.5 A @ 250 VAC;
1.5 A @ 500 VAC 0.75 A @ 500 VAC

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 4


Weights and Dimensions
Weights and dimensions are shown for transfer switches in NEMA type 1 enclosures, type 3R enclosures, and open units. Consult
the factory for NEMA type 12, 4, and 4X enclosures.
Note: Weights and dimensions are provided for reference only and should not be used for planning installation. See your local
distributor for submittal drawings.

Standard-Transition Models
Dimensions mm (in.) Weight kg (lb.)
Amps NEMA Type Height Width Depth * 2-Pole 3-Pole 4-Pole
40--225 1, 3R 791 (31.1) 450 (17.7) 316 (12.5) 28 (62) 30 (65) 31 (68)
260--400 1, 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131)
600 1, 3R 1702 (67.0) 610 (24.0) 514 (20.2) 179 (395) 183 (403) 186 ( 410)
800 1, 3R 1932 (76.1) 864 (34.0) 515 (20.3) N/A 226 (498) 236 (520)
1000 1, 3R 1932 (76.1) 864 (34.0) 515 (20.3) N/A 231 (509) 241 ( 531)
* Allow enough room to fully open the door for inspection and service per NEC and local codes. The NEMA type 3R enclosures have a security cover
on the controller that extends 54 mm (2.1 in.) beyond the door.

Programmed-Transition Models
Dimensions mm (in.) Weight kg (lb.)
Amps NEMA Type Height Width Depth * 2-Pole 3-Pole 4-Pole
100--200 1, 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131)
400 1, 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131)
600 1, 3R 1702 (67.0) 610 (24.0) 514 (20.2) 179 (395) 183 (403) 186 ( 410)
* Allow enough room to fully open the door for inspection and service per NEC and local codes. The NEMA type 3R enclosures have a security cover
on the controller that extends 54 mm (2.1 in.) beyond the door.

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 5


Withstand and Close-On Ratings (WCR), Standard-Transition Models
Ratings Summary
The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes listed at the
specified maximum voltage below, but no greater than the interrupting capacity of the selected circuit breaker or fuse. Circuit
breakers and fuses are supplied by the customer.

Certified Withstand Current Ratings in RMS Symmetrical Amperes (480 V maximum) *

Specific Coordinated Breaker Rating,


With Current-Limiting Fuses per the following tables
Switch Rating, Maximum Fuse Maximum Circuit Amps at Maximum Circuit Amps at
amps Size, amps Fuse Class 480 VAC Maximum Voltage 480 VAC
40 50
80 100
100 125
J 200,000 480 V / 60 Hz 30,000
150 200
200 300
225 300
260 N/A N/A N/A 480 V / 60 Hz 35,000
J 200,000
400 600
RK5, RK1 100,000 480 V / 60 Hz 50,000
600 N/A N/A N/A
800 1000
L 200,000 480 V / 60 Hz 65,000
1000 1250
* All values are available symmetrical RMS amperes and tested in accordance with the withstand/closing requirements of UL 1008.

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 6


Ratings with Specific Manufacturers’ Circuit Breakers, Standard-Transition Models
Withstand and close-on ratings (WCR) in RMS symmetrical amperes for specific manufacturers’ circuit breakers.

Molded-Case Circuit Breakers


Switch WCR,
Rating, amps Voltage, Max. Size,
amps RMS Max. Manufacturer Type amps
FDC, HFD 150
Cutler-Hammer HJD, JDC 250
HKD, KD, KDB, KDC, LA TRI--PAC, LCL 400
FC, FI 100
Square D KC, KH, KI 250
40
LA, LC, LE, LH, LI, LX, LXI 400
80
100 CED6, HED4, HED6 125
30,000 480
150 ITE/Siemens CFD6, FD6, FXD6, HFD6 250
200 CJD6, HJD6, HHJD6, HHJXD6, JD6, JXD6, SCJD6, SHJD6, SJD6 400
225
TB1 100
SEL, SEP, TEL, THLC1 150
GE TFL, THLC2 225
SFL, SFP 250
SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 400
FDC, HFD 150
Cutler-Hammer HJD, JDC 250
HKD, KD, KDB, KDC, LA TRI--PAC, LCL 400
FC, FI 100
Square D KC, KH, KI 250
LA, LC, LE, LH, LI, LX, LXI 400
CED6, HED4, HED6 125
260 35,000 480
ITE/Siemens CFD6, FD6, FXD6, HFD6 250
CJD6, HJD6, HHJD6, HHJXD6, JD6, JXD6, SCJD6, SHJD6, SJD6 400
TB1 100
SEL, SEP, TEL, THLC1 150
GE TFL, THLC2 225
SFL, SFP 250
SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 400

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 7


Ratings with Specific Manufacturers’ Circuit Breakers, Standard-Transition, continued
Molded-Case Circuit Breakers
Switch WCR,
Rating, amps Voltage, Max. Size,
amps RMS Max. Manufacturer Type amps
HJD, JDC 250
HKD, CHKD, KDC, LCL, LA TRIPAC 400
Cutler-Hammer
HLD, CHLD, LDC, CLDC 300--600
NB TRI--PAC 300--800
KI, KC 250
Square D LI, LXI, LX, LE, LC 600
MX, ME, MH 800
CFD6, HFD6 250
CJD6, SCJD6, HHJD6, HHJXD6, SHJD6, HJD6 400
ITE/Siemens
400 50,000 480 CLD6, SCLD6, HHLD6, HHLXD6, SHLD6, HLD6 600
CMD6, SCMD6, HMD6, SHMD6, HMXD6, MD6, MXD6, SMD6 800
SFL, SFP, TFL, THLC2 250
SGL4, SGP4, TB4, THLC4, TLB4 400
GE
SGL6, SGP6, TB6, TJL4V, TKL4V, TJL1S--6S 600
SKL8, SKP8, TB8, SKH8 800
CF250L, CF250H 250
CJ400L, CK400H, CJ400H, CK400N 400
Merlin Gerin
CJ600H 600
CK800H, CK800N 800
ABB JHB 400
FDC, HFD 150
HJD, JDC 250
Cutler-Hammer CHKD, HKD, KDC, LA TRIPAC, LCL 400
HLD, CHLD, LDC, CLDC 300--600
NB TRIPAC 300--800
KI, KC 250
LC, LE, LI, LX, LXI 400
Square D
LC, LE, LI, LX, LXI 600
ME, MH, MX 800
CFD6, HFD6 250
600 50,000 480 CJD6, HJD6, HHJD6, HHJXD6, SCJD6, SHJD6 400
ITE/Siemens
CLD6, HLD6, HHLD6, HHLXD6, SCLD6, SHLD6 600
CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 800
SEL, SEP, THLC1 150
SFL, SFP, TFL, THLC2 250
GE SGL4, SGP4, TB4, THLC4, TJL, TLB4 400
SGL6, SGP6, TB6, TJL1S--6S, TJL4V, TKL4V 600
TB8, SKL8, SKP8, SKH8 800
CF250L, CF250H 250
CJ400L, CK400H, CJ400H, CK400N 400
Merlin Gerin
CJ600H 600
CK800H, CK800N 800
TRI-PAC NB, CHMDL, HMDL, CHND, HND, NDC, CNDC 800
Cutler-Hammer
TRI-PAC NB, CNDC, NDC, CRDC, TRI-PAC PB, RDC, CHND, HND 1200
MH, MH SERIES 2 800
Square D
MH SERIES 2 1000
800
65,000 480 CMD6, HMD6, SCMD6, SHMD6, CND6, HND6, SCND6, SHND6, CPD6 800
1000 ITE/Siemens
CND6, HND6, SCND6, CPD6, SHND6 1200
TB8, TC, THC, THP, TKL85, SKL8, SKP8, MICROVERSA TKL 12S,
800
GE SKL12, SKP12
THC, THP, SKP12, TRP, MICROVERSA TKL, SKL12 1200

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 8


Withstand and Close-On Ratings (WCR), Programmed-Transition Models
Suitable for emergency and standby applications on all classes of load, 30% tungsten rated on all amperages. The transfer switch
is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes listed at 480 volts maximum, but no
greater than the interrupting capacity of the selected circuit breaker. Circuit breakers are supplied by the customer. All WCR
values are available symmetrical RMS amperes and tested in accordance with the withstand/closing requirements of UL 1008.

Ratings with Specific Manufacturers’ Circuit Breakers, 480 Volts


Molded-Case Circuit Breakers
Switch WCR, Voltage,
Rating, amps amps RMS Max. Manufacturer Type Max. Size, amps
FCL, FB TRI-PAC 100
FD, FDC, HFD 150
Cutler-Hammer
HJD, JD, JDB, JDC 250
HKD, KD, KDB, KDC, LA TRI--PAC, LCL, DK, CHKD 400
HLA 70, 100
FC, FH, FI 100
Square D
KA, KC, KH, KI 250
LA, LC, LE, LH, LI, LX, LXI 400
CED6, ED6, HED4, HED6, ED4 125
ITE/Siemens CFD6, FD6, FXD6, HFD6 250
100
30,000 480 CJD6, HJD6, HHJD6, HHJXD6, SCJD6, SHJD6, SJD6 400
200
TB1 100
SEL, SEP, TEL, THED, THLC1 150
GE TFL, THFK, THLC2 225
SFL, SFP, TFL 250
SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 400
CF250L, CF250H 250
CJ400L, CK400H, CJ400H, CK400N 400
Merlin Gerin
CJ600H 600
CK800H, CK800N 800
ABB JHB 400
FCL, FB TRI-PAC 100
FD, FDC, HFD 150
HJD, JD, JDB, JDC 250
Cutler-Hammer
HKD, KD, KDB, KDC, LA TRIPAC, LCL, DK, CHKD 400
HLD, CHLD, LDC, CLDC 300--600
NB TRI--PAC 300--800
FC, FH, FI 100
KA, KC, KH, KI 250
Square D LA, LC, LE, LH, LI, LX, LXI 400
LC, LE, LI, LXI, LX 600
400 MX, ME, MH 800
65,000 480
600 CED6, ED6, HED4, HED6, ED4 125
CFD6, HFD6, FD6, FXD6 250
ITE/Siemens CJD6, SCJD6, HHJD6, HHJXD6, SHJD6, HJD6, SJD6 400
CLD6, SCLD6, HHLD6, HHLXD6, SHLD6, HLD6 600
CMD6, SCMD6, HMD6, SHMD6, HMXD6, MD6, MXD6, SMD6 800
CF250L, CF250H 250
CJ400L, CK400H, CJ400H, CK400N 400
Merlin Gerin
CJ600H 600
CK800H, CK800N 800
JHB 400
ABB
S6 800

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 9


Accessories
Accessories are available either factory-installed or as loose - Alarm Module
kits, unless otherwise noted.
D 90 dB Audible alarm
Accessory Modules D Any alarm function can be programmed to trigger the
audible alarm
The mounting kit holds up to five optional modules. The
maximum total current draw is 300 mA. If an External Battery D Chicago alarm function
Module is installed, there is no current restriction. D Preferred source selection
D Supervised transfer control (supervised transfer control
Module Current Draw Specifications, mA switch required)
Alarm Module 75 D Connection for external alarm
Standard I/O Module 75
External Alarm Connection Specifications
High Power I/O Module 100
Wire Size #12--22 AWG Cu
500 mA @ 120 VAC
- Standard Input/Output Module Contact Voltage Rating
250 mA @ 240 VAC
Inputs
Available Inputs 2
- External Battery Supply Module
Input Definition Contact closure
D Energizes the ATS controls using an external battery
Current 5 mA Max when no source power is available
Connection Type Terminal Strip D Allows extended engine start time delays
Wire Size #14--24 AWG D Allows the use of any combination of accessory modules
Max Distance 700 feet (no current draw restriction, maximum of five modules
Outputs total)
Outputs Available 6 D Connects to one or two batteries, 12 VDC or 24 VDC
system
Contact Type Form C (SPDT)
D Current draw, 140 mA @ 12 VDC, 86 mA @ 24 VDC
2 A @ 30 VDC
Contact Voltage Rating
500 mA @ 125 VAC D Provides low external battery voltage indication to the
transfer switch controller
Connection Type Terminal Strip
D Reverse-polarity protected
Wire Size #14--24 AWG
- Battery Charger
- High-Power Input/Output Module D Three-stage (bulk, absorption, and float) electronic battery
charger
Inputs
D Red and green LEDs indicate the charge rate
Available Inputs 2
D Designed for 12 or 24 VDC battery electrical systems
Input Definition Contact closure
D Charge lead-acid or gel cell batteries
Current 5 mA Max
D Sealed and potted design is rainproof, lightweight, silent,
Connection Type Terminal Strip
and completely automatic
Wire Size #14--24 AWG
D Internal short-circuit protection for the outputs
Max Distance 700 feet
D Fuses for reverse-polarity protection
Outputs
D Available only as a loose kit for field installation
Outputs Available 3
Contact Type Form C (SPDT) Battery Charger Specifications
12 A @ 24 VDC Output
12 A @ 250 VAC
Contact Voltage Rating 12 VDC (min.) at 6 amps
10 A @ 277 VAC Charging
2 A @ 480 VAC 24 VDC (min.) at 3 amps
Connection Type Terminal Strip Maintaining 13.30 VDC at 0.1 amps
Wire Size #14--24 AWG Circuit Protection (2) 10 amp fuses (AGC-10)
Environmental Specifications
Recommended Maximum Battery Size
Temperature --40°C to 85°C (--40°F to 185°F)
Recharging 150 amp--hours
Humidity 35% to 85% noncondensing
Maintaining only 300 amp--hours
Current Draw @ 50/60 Hz, 0.7 amps maximum

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 10


Accessories, continued
Other Accessories - Monitor III Software
D Monitor and control the power system’s generator sets
- CSA Certification and transfer switches from a personal computer using a
single software package
D Monitor and control systems through a Windowsr-based
- Current Sensing Kit graphical user interface
D Monitor current on all phases with 1% accuracy
D Monitor and control systems over a local area network,
remotely via a modem connection, or through an Ethernet
- Digital Meter connection
D Measure and display for both sources: D Password-protected data access: Guest, User, and
d Voltage Supervisor levels
d Current D Ethernet capability
d Frequency D Start or stop a test from a remote PC
d Power D View and adjust trip points, time delays, and system
D Programmable visual alarms: parameters
d High voltage D Assign inputs and outputs
d Low voltage D Available as loose kits:
d High current d Software kit with serial cable
D Serial port for optional network connections d Software kit with device modem and cables
D Password-protected programming menus
D Available factory-installed - Padlockable User Interface Cover
D See TT-1506, Digital Power Meters D With or without window
D Cover without window standard on NEMA 3R enclosures
- Line-to-Neutral Voltage Monitoring
D Monitors all line-to-neutral voltages - Supervised Transfer Control Switch
D Auto, Manual, and Transfer positions
- Load Shed Kit D Automatic and non-automatic modes
D Forced transfer from Emergency to OFF D Alarm module required
D Available for 600 Amp programmed-transition models only
D External hardware is required for the forced transfer to - Literature Kits
OFF function
D Production literature kit
D Factory-installed (one kit is included with each transfer switch)
D Overhaul literature kit
- Logic Disconnect Switch
D Disconnects power to controller without disconnecting - Extended Warranties
load
D 2-year basic
D Mounts inside the enclosure
D 5-year basic
D 5-year comprehensive
- Neutral Assembly
D 10-year major components
D Available as loose kit for open units

- Export Packaging

G11-108 (Model KSS/KSP Transfer Switch) 12/09f Page 11


KOHLER CO., Kohler, Wisconsin 53044 USA Kohler Power Systems
Phone 920-565-3381, Fax 920-459-1646 Asia Pacific Headquarters
For the nearest sales and service outlet in the 7 Jurong Pier Road
US and Canada, phone 1-800-544-2444 Singapore 619159
KohlerPower.com Phone (65) 6264-6422, Fax (65) 6264-6455

Model Designation
Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Miscellaneous

Record the transfer switch model designation in the boxes. The transfer switch model designation defines
characteristics and ratings as explained below.

Sample Model Designation: KSP-DCTA-0100S


Model Number of Poles/Wires
K: Kohler Transfer Switch N: 2-pole, 3-wire, solid neutral
T: 3-pole, 4-wire, solid neutral
Mechanism V: 4-pole, 4-wire, switched neutral
S: Specific-Breaker Rated
Enclosure
Transition A: NEMA 1[ D: NEMA 4
S: Standard B: NEMA 12 F: NEMA 4X
P: Programmed C: NEMA 3R G: Open unit
Controls [ NEMA 1 enclosure is standard. Other types are
D: MPACt 1500 available to order.
Microprocessor Controls, Automatic
F: MPACt 1500 Current Rating: Numbers indicate the current
Microprocessor Controls, Non-Automatic rating of the switch in amperes:
0040 ] 0200 0600
Voltage/Frequency 0080 ] 0225 ] 0800]
C: 208 Volts/60 Hz 0100 0260 ] 1000]
D: 220 Volts/50 Hz 0150 ] 0400
F: 240 Volts/60 Hz
G: 380 Volts/50 Hz ] Standard--transition models only.
H: 400 Volts/50 Hz
J: 416 Volts/50 Hz
K: 440 Volts/60 Hz
M: 480 Volts/60 Hz Miscellaneous
P: 380 Volts/60 Hz S: Standard Connections
R: 220 Volts/60 Hz

DISTRIBUTED BY:

Availability is subject to change without notice. Kohler Co. reserves the


right to change the design or specifications without notice and without
any obligation or liability whatsoever. Contact your local Kohlerr Power
Systems distributor for availability.