Escolar Documentos
Profissional Documentos
Cultura Documentos
Number : 215/A/BINA/VIII/2017
Description of Sample Test : Sample Test was taken by Binalab Packaging 2L,
500, 350, 100, 200ml (polyethylene, jerry can & Glass
Bottle with Preservation)
Amount of Sample :2
Head of Laboratory
F.19-T
Page 1 of 3
ANALYSIS RESULT
Certificate Number : 215/Ala1/BINA/VIII/2017
Name of applicant : PT. HUTAMA KARYA (Persero)
th
Address : Aneka Tambang Building, Tower B Floor 19 ,
Jl. TB Simatupang No. 1 Tanjung Barat, Jakarta 12530
Location of sampling : PLTGU MUARA TAWAR
Type of sample : Sea Water Quality
th
Date of sampling : August 15 2017
Test Sampling Point : ALa – 1 Water Intake
(06°05’06,5”LS; 106°59’88,1”BT)
Quality
No. Parameter Unit Test Result Methods
standards
1 Odor* - Odorless Odorless MP-K A28 (Kebauan)
2 Turbidity * NTU 4,64 - APHA 2130 B-2012
IK – SA17 Penetuan
3 Brightness* m 2,00 >3
Kecerahan
4 Total Suspended Solid (TSS)* mg/L 2,40 80 APHA 2540 D-2012
5 Temperature* °C 31,8 Nature APHA 2550 B-2012
6 Trash - Nothing Nothing Visual
7 Oil Coating Nothing Nothing Visual
8 pH* - 7,6 6,5 – 8,5 APHA 4500 H+ B 2012
9 Salinity* ‰ <0,17 Alami IK – S1 (Salt meter)
10 Ammonia (NH3-N)* mg/L 0,18 0,3 SNI 19-6964.3-2003
11 Sulphide (H2S)* mg/L <0,006 0,03 SNI 19-6964.4-2003
12 Hydrocarbon Total* mg/L <1,0 1 US EPA 5030 & 5035 2003
13 Total Phenol mg/L <0,001 0,002 SNI 06-6989.21-2004
14 Surfactan* mg/L 0,05 1 SNI 06-6989.51-2005
15 Oil ang grease mg/L 4,03 5 SNI 06-6989.10-2011
16 Mercury (Hg) mg/L <0,0008 0,003 IK-L 42 – MP - AES
17 Cadmium ( Cd) mg/L <0,0006 0,01 IK-L 42 – MP - AES
18 Copper ( Cu) mg/L <0,006 0,05 IK-L 42 – MP - AES
19 Lead ( Pb) mg/L 0,01 0,05 IK-L 42 – MP - AES
20 Zinc (Zn) mg/L 0,01 0,1 IK-L 42 – MP - AES
21 Calcium (Ca) mg/L 5,42 - IK-L 42 – MP - AES
22 Magnesium (Mg) mg/L 224,33 - IK-L 42 – MP - AES
23 Sulphate (SO4) mg/L 2.167 - SNI 06-6989.20-2009
24 Sodium (Na) mg/L 20.104 - IK-L 42 – MP - AES
25 Chloride (Cl) mg/L 17.899 - SNI 06-6989.19-2009
26 Bicarbonate mg/L 73,98 - Titrimetry
27 Density g/mL 1,04 - Picnometer
MICROBIOLOGY
28 Total Coliform* CFU/100 mL 4.400 1000 APHA 9222 B 2012
Description Sampling Test
1 Air Condition - Sunny - -
2 Air Temperature °C 31,6 - Thermometer
3 Humidity % 56,6 - Hygrometer
Information
- Sea Water Quality Standard for Port Waters, KepMen LH. 51 of 2004 attachment I
- * Already accredited KAN
- The < mark shows the result below the detection limit
F.19.4-T
Page 2 of 3
ANALYSIS RESULT
Certificate Number : 215/Ala2/BINA/VIII/2017
Name of applicant : PT. HUTAMA KARYA (Persero)
th
Address : Aneka Tambang Building, Tower B Floor 19 ,
Jl. TB Simatupang No. 1 Tanjung Barat, Jakarta 12530
Location of sampling : PLTGU MUARA TAWAR
Type of sample : Sea Water Quality
th
Date of sampling : August 15 2017
Test Sampling Point : ALa – 2 Outfall Blok 1
(06°05’07,6”LS; 107°00’02,2”BT)
Quality
No. Parameter Unit Test Result Methods
standards
1 Odor* - Odorless Odorless MP-K A28 (Kebauan)
IK – SA17 Penetuan
2 Brightness* m 1,00 >3
Kecerahan
Total Suspended Solis
3 mg/L 9,60 80 APHA 2540 D-2012
(TSS)*
4 Temperature* °C 38,3 Nature APHA 2550 B-2012
5 Trash - Nothing Nothing Visual
6 Oil Coating Nothing Nothing Visual
7 pH* - 7,1 6,5 – 8,5 APHA 4500 H+ B 2012
8 Salinity* ‰ <0,17 Nature IK – S1 (Salt meter)
9 Ammonia (NH3-N)* mg/L 0,14 0,3 SNI 19-6964.3-2003
10 Sulphide (H2S)* mg/L 0,01 0,03 SNI 19-6964.4-2003
11 Hydrocarbon Total* mg/L <1,0 1 US EPA 5030 & 5035 2003
12 Total Phenol mg/L 0,02 0,002 SNI 06-6989.21-2004
13 Surfactan* mg/L 0,04 1 SNI 06-6989.51-2005
14 Oil and grease mg/L 4,20 5 SNI 06-6989.10-2011
15 Mercury (Hg) mg/L <0,0008 0,003 IK-L 42 – MP - AES
16 Cadmium ( Cd) mg/L <0,0006 0,01 IK-L 42 – MP - AES
17 Copper ( Cu) mg/L <0,006 0,05 IK-L 42 – MP - AES
18 Lead ( Pb) mg/L <0,006 0,05 IK-L 42 – MP - AES
19 Zinc (Zn) mg/L <0,02 0,1 IK-L 42 – MP - AES
MICROBIOLOGY
20 Total Coliform* CFU/100 mL 690 1000 APHA 9222 B 2012
Description Sampling Test
1 Air Condition - Sunny - -
2 Air Temperature °C 32,8 - Thermometer
3 Humidity % 54,3 - Hygrometer
Information
- Sea Water Quality Standard for Port Waters, KepMen LH. 51 of 2004 attachment I
- * Already accredited KAN
- The < mark shows the result below the detection limit
F.19.4-T