Engineering Units : Flow : Liquid - M3 / Hr, Steam- Kg / Hr, Pressure -Kg / cm2 ,
SHEET 1 of 1
Differential Pressure : mmWc, Temperature : Deg C, Level : mm
Type ELECTRONIC MICROPROCESSOR TYPE TRANSMITTER
Make/ Model No. As per Approved Vendor list
Service -Fluid As per Annexure-III
Location As per Annexure-III
GENERAL
Certification ATEX
Communication Protocol HART
Zero Adjustment Required
Connection Location Side
Page 1 of 3
Name/Tag Plate Required
DATASHEET FOR DP FLOW TRANSMITTER REV. 0
DP Type Flow Transmitter
Annexure - III
1 2
Service or Location At Cooling water Inlet of Heat Exchanger From Caustic Header to UASB Mixing Tank
Line MOC CS CS
Manufacturer & Model No As per Approved Vendor List As per Approved Vendor List
Page 2 of 3
3 4
Service or Location Inlet of Bio gas Liquid ring Pump from Seal Inlet of Bio gas Liquid ring Pump from Seal
Flush Cooler Flush Cooler
Manufacturer & Model No As per Approved Vendor List As per Approved Vendor List
2. Orifice plate sizing shall be as per ISO 5167 & tender document.
3 Orifice Plate shall be provided with complete assemby including flanges etc.