CENTRO DE MASA Y CENTRO DE RIGIDEZ

Forma de obtencion:

Display
Show tables
ANALISYS RESULTS
Building output
Center mass rigidity

Story Diaphragm MassX MassY XCM YCM CumMassX


STORY1 D1 63.2786 63.2786 17.996 6.402 63.2786
STORY2 D2 60.2654 60.2654 17.996 6.367 60.2654
STORY3 D3 60.2654 60.2654 17.996 6.367 60.2654
STORY4 D4 60.2654 60.2654 17.996 6.367 60.2654
STORY5 D5 60.2654 60.2654 17.996 6.367 60.2654
STORY6 D6 60.2654 60.2654 17.996 6.367 60.2654
STORY7 D7 60.2654 60.2654 17.996 6.367 60.2654
STORY8 D8 51.0585 51.0585 17.995 6.232 51.0585
MASA 475.93 Tn*m/s2
PESO 4668.87 Tn

PISO PESO (Tn) PISO


para realizar la distribución de fuerzas
1 620.76 se deben voltear los pisos 8
2 591.20 7
3 591.20 6
4 591.20 5
5 591.20 4
6 591.20 3
7 591.20 2
8 500.88 1
RO DE RIGIDEZ

CENTRO DE MASA CENTRO DE RIGIDEZ EXCENTRICIDAD


CumMassY XCCM YCCM XCR YCR X Y
63.2786 17.996 6.402 18.001 7.47 0.005 1.068
60.2654 17.996 6.367 18.001 8.219 0.005 1.852
60.2654 17.996 6.367 18.001 8.672 0.005 2.305
60.2654 17.996 6.367 18 8.905 0.004 2.538
60.2654 17.996 6.367 17.999 9.031 0.003 2.664
60.2654 17.996 6.367 17.998 9.103 0.002 2.736
60.2654 17.996 6.367 17.997 9.15 0.001 2.783
51.0585 17.995 6.232 17.995 9.212 0 2.98

PESO (Tn)
500.88
591.20
591.20
591.20
591.20
591.20
591.20
620.76
FACTORES DE SISMO PERÍODO FUNDAMENTAL DE LA ES
35
ZONA Z4 0.45 Ct= 45
USO comun 1 60
S1 1
SUELO Tp 0.4 T= hn/Ct
Tl 2.5
Rxx: muros 6 hn: altura total de la estructura (sin sótanos)
Ryy: muros 6 1er piso 3.65
Cxx= 2.50 piso típico 2.75
Cyy= 2.50 # pisos 8
P (peso)= 4668.87 Tn
Txx= 0.38
COEFICIENTES ANÁLISIS SÍSMICO Tyy= 0.38
ZUCS/RX 0.19
ZUCS/RY 0.19

Fi= αi*V
DISTRIBUCIÓN DE FUERZAS EQUIVALENTES HORIZONTALES αi= (Pi*(hi)^k)/(∑(Pj*(hj)^k))
CORTANTE SÍSMICA

V=ZUCS*P/R Vxx= 875.41


Vyy= 875.41

DISTRIBUCIÓN DE FUERZAS XX k= 1 ok
fuerzas horizontales equivalentes
PISO PESO (Tn) peso acum ALTURA (m) alt acum (hi^k) Pi*hi
8 500.88 4668.87 2.75 22.9 22.9 11470.24
7 591.20 4167.98 2.75 20.15 20.15 11912.75
6 591.20 3576.78 2.75 17.4 17.4 10286.94
5 591.20 2985.58 2.75 14.65 14.65 8661.13
4 591.20 2394.37 2.75 11.9 11.9 7035.32
3 591.20 1803.17 2.75 9.15 9.15 5409.51
2 591.20 1211.97 2.75 6.4 6.4 3783.70
1 620.76 620.76 3.65 3.65 3.65 2265.79
P= 4668.87 ∑(Pj*(hj)^k) 60825.39
Factores de zona
ERÍODO FUNDAMENTAL DE LA ESTRUCTURA ZONA Z
pórticos 1 0.1
pórticos y caja de ascensor o escaleras 2 0.25
placas 3 0.35
4 0.45

Factor de suelo "S"


l de la estructura (sin sótanos) Tipo Descripcion
m hn= 22.9 m So Roca dura
m S1 Roca o suelos muy rígidos
S2 Suelos intermedios
S3 Suelos blandos

FACTOR DE SUELO
ZONA/SUELO So S1
Z4 0.8 1
Z3 0.8 1
Z2 0.8 1
i= (Pi*(hi)^k)/(∑(Pj*(hj)^k)) Z1 0.8 1
PERIODOS Tp Y TL
Tp (S) 0.3 0.4
TL (S) 3 2.5

DISTRIBUCIÓN DE FUERZAS YY k=
uerzas horizontales equivalentes
αi Fi= αi*V PISO PESO (Tn) peso acum ALTURA (m) alt acum
0.19 165.08 8 500.88 4668.87 2.75 22.9
0.20 171.45 7 591.20 4167.98 2.75 20.15
0.17 148.05 6 591.20 3576.78 2.75 17.4
0.14 124.65 5 591.20 2985.58 2.75 14.65
0.12 101.25 4 591.20 2394.37 2.75 11.9
0.09 77.85 3 591.20 1803.17 2.75 9.15
0.06 54.46 2 591.20 1211.97 2.75 6.4
0.04 32.61 1 620.76 620.76 3.65 3.65
875.41 P= 4668.87
Categoria de las Edificaciones
Categoria U
A Edificaciones E 1.5
B Edificaciones 1.30
C Edificaciones 1.00
D Edificaciones *

TOR DE SUELO
S2 S3
1.05 1.1
1.15 1.2
1.2 1.4
1.6 2
IODOS Tp Y TL
0.6 1
2 1.6

1.00 ok
fuerzas horizontales equivalentes
(hi^k) Pi*hi αi Fi= αi*V
22.9 11470.24 0.19 165.08
20.15 11912.75 0.20 171.45
17.4 10286.94 0.17 148.05
14.65 8661.13 0.14 124.65
11.9 7035.32 0.12 101.25
9.15 5409.51 0.09 77.85
6.4 3783.70 0.06 54.46
3.65 2265.79 0.04 32.61
∑(Pj*(hj)^k) 60825.39 875.41
SISTEMAEspeciales
Pórticos ESTRUCTURAL
Resistentes a R: estructura regular
Momentos (SMF)
Pórticos Intermedios Resistentes a 8
Momentos (IMF) 7
Pórticos Ordinarios Resistentes a Mom 6
ACERO
Pórticos Especiales Concéntricamente A 8
PórticosOrdinarios Concéntricamente A 6
Pórticos Excéntricamente Arriostrados ( 8
Pórticos 8
CONCRETO Dual 7
ARMADO De muros estructurales 6
Muros de ductilidad limitada 4
ALBALIÑERÍA ARMADA O CONFINADA 3
MADERA (esfuerzos admisibles) 7
SX SY
PISO FX FY ex ey MZ MZ
8 165.08 165.08 0.01 1.07 176.31 0.83
7 171.45 171.45 0.01 1.85 317.53 0.86
6 148.05 148.05 0.01 2.31 341.26 0.74
5 124.65 124.65 0.00 2.54 316.37 0.50
4 101.25 101.25 0.00 2.66 269.74 0.30
3 77.85 77.85 0.00 2.74 213.01 0.16
2 54.46 54.46 0.00 2.78 151.55 0.05
1 32.61 32.61 0.00 2.98 97.18 0.00
FACTORES DE SISMO PERÍODO FUNDAMENTAL DE LA ES
35
ZONA Z4 0.45 Ct= 45
USO comun 1 60
S1 1
SUELO Tp 0.4 T= hn/Ct
Tl 2.5
Rxx: muros 6 hn: altura total de la estructura (sin sótanos)
Ryy: muros 6 1er piso 3.65
Cxx= 1.47 piso típico 2.75
Cyy= 2.44 # pisos 8
P (peso)= 4668.87 Tn
Txx= 0.68
COEFICIENTES ANÁLISIS SÍSMICO Tyy= 0.41
ZUCS/RX 0.11
ZUCS/RY 0.18

Fi= αi*V
DISTRIBUCIÓN DE FUERZAS EQUIVALENTES HORIZONTALES αi= (Pi*(hi)^k)/(∑(Pj*(hj)^k))
CORTANTE SÍSMICA

V=ZUCS*P/R Vxx= 514.95


Vyy= 854.06

DISTRIBUCIÓN DE FUERZAS XX k= 1.09 ok


fuerzas horizontales equivalentes
PISO PESO (Tn) peso acum ALTURA (m) alt acum (hi^k) Pi*hi
8 500.88 4668.87 2.75 22.9 30.3543317 15204.00
7 591.20 4167.98 2.75 20.15 26.403397 15609.78
6 591.20 3576.78 2.75 17.4 22.5008374 13302.58
5 591.20 2985.58 2.75 14.65 18.6536151 11028.08
4 591.20 2394.37 2.75 11.9 14.8712059 8791.91
3 591.20 1803.17 2.75 9.15 11.1673208 6602.16
2 591.20 1211.97 2.75 6.4 7.56373268 4471.71
1 620.76 620.76 3.65 3.65 4.10108926 2545.80
P= 4668.87 ∑(Pj*(hj)^k) 77556.02
Factores de zona
ERÍODO FUNDAMENTAL DE LA ESTRUCTURA ZONA Z
pórticos 1 0.1
pórticos y caja de ascensor o escaleras 2 0.25
placas 3 0.35
4 0.45

Factor de suelo "S"


l de la estructura (sin sótanos) Tipo Descripcion
m hn= 22.9 m So Roca dura
m S1 Roca o suelos muy rígidos
S2 Suelos intermedios
S3 Suelos blandos

FACTOR DE SUELO
ZONA/SUELO So S1
Z4 0.8 1
Z3 0.8 1
Z2 0.8 1
i= (Pi*(hi)^k)/(∑(Pj*(hj)^k)) Z1 0.8 1
PERIODOS Tp Y TL
Tp (S) 0.3 0.4
TL (S) 3 2.5

DISTRIBUCIÓN DE FUERZAS YY k=
uerzas horizontales equivalentes
αi Fi= αi*V PISO PESO (Tn) peso acum ALTURA (m) alt acum
0.20 100.95 8 500.88 4668.87 2.75 22.9
0.20 103.64 7 591.20 4167.98 2.75 20.15
0.17 88.33 6 591.20 3576.78 2.75 17.4
0.14 73.22 5 591.20 2985.58 2.75 14.65
0.11 58.38 4 591.20 2394.37 2.75 11.9
0.09 43.84 3 591.20 1803.17 2.75 9.15
0.06 29.69 2 591.20 1211.97 2.75 6.4
0.03 16.90 1 620.76 620.76 3.65 3.65
514.95 P= 4668.87
Categoria de las Edificaciones
Categoria U
A Edificaciones E 1.5
B Edificaciones 1.30
C Edificaciones 1.00
D Edificaciones *

TOR DE SUELO
S2 S3
1.05 1.1
1.15 1.2
1.2 1.4
1.6 2
IODOS Tp Y TL
0.6 1
2 1.6

1.00 ok
fuerzas horizontales equivalentes
(hi^k) Pi*hi αi Fi= αi*V
30.3543317 15204.00 0.20 167.43
26.403397 15609.78 0.20 171.90
22.5008374 13302.58 0.17 146.49
18.6536151 11028.08 0.14 121.44
14.8712059 8791.91 0.11 96.82
11.1673208 6602.16 0.09 72.70
7.56373268 4471.71 0.06 49.24
4.10108926 2545.80 0.03 28.03
∑(Pj*(hj)^k) 77556.02 854.06
SISTEMAEspeciales
Pórticos ESTRUCTURAL
Resistentes a R: estructura regular
Momentos (SMF)
Pórticos Intermedios Resistentes a 8
Momentos (IMF) 7
Pórticos Ordinarios Resistentes a Mom 6
ACERO
Pórticos Especiales Concéntricamente A 8
PórticosOrdinarios Concéntricamente A 6
Pórticos Excéntricamente Arriostrados ( 8
Pórticos 8
CONCRETO Dual 7
ARMADO De muros estructurales 6
Muros de ductilidad limitada 4
ALBALIÑERÍA ARMADA O CONFINADA 3
MADERA (esfuerzos admisibles) 7
SX SY
PISO FX FY ex ey MZ MZ
8 100.95 167.43 0.01 1.07 107.81 0.84
7 103.64 171.90 0.01 1.85 191.95 0.86
6 88.33 146.49 0.01 2.31 203.59 0.73
5 73.22 121.44 0.00 2.54 185.84 0.49
4 58.38 96.82 0.00 2.66 155.51 0.29
3 43.84 72.70 0.00 2.74 119.94 0.15
2 29.69 49.24 0.00 2.78 82.63 0.05
1 16.90 28.03 0.00 2.98 50.37 0.00
FACTORES DE SISMO PERÍODO FUNDAMENTAL DE LA ES
35
ZONA Z4 0.45 Ct= 45
USO comun 1 60
S1 1
SUELO Tp 0.4 T= hn/Ct
Tl 2.5
Rxx: muros 5.4 hn: altura total de la estructura (sin sótanos)
Ryy: muros 4.5 1er piso 3.65
Cxx= 1.47 piso típico 2.75
Cyy= 2.44 # pisos 8
P (peso)= 4668.87 Tn
Txx= 0.68
COEFICIENTES ANÁLISIS SÍSMICO Tyy= 0.41
ZUCS/RX 0.12
ZUCS/RY 0.24

Fi= αi*V
DISTRIBUCIÓN DE FUERZAS EQUIVALENTES HORIZONTALES αi= (Pi*(hi)^k)/(∑(Pj*(hj)^k))
CORTANTE SÍSMICA

V=ZUCS*P/R Vxx= 371.50


Vyy= 371.50

DISTRIBUCIÓN DE FUERZAS XX k= 1 ok
fuerzas horizontales equivalentes
PISO PESO (Tn) peso acum ALTURA (m) alt acum (hi^k) Pi*hi
8 276.57 2953.55 2.75 22.9 22.9 6333.48
7 380.36 2676.98 2.75 20.15 20.15 7664.35
6 380.36 2296.61 2.75 17.4 17.4 6618.35
5 380.36 1916.25 2.75 14.65 14.65 5572.34
4 380.36 1535.88 2.75 11.9 11.9 4526.34
3 380.36 1155.52 2.75 9.15 9.15 3480.34
2 380.36 775.15 2.75 6.4 6.4 2434.33
1 394.79 394.79 3.65 3.65 3.65 1440.97
P= 2953.55 ∑(Pj*(hj)^k) 38070.50
Factores de zona
ERÍODO FUNDAMENTAL DE LA ESTRUCTURA ZONA Z
pórticos 1 0.1
pórticos y caja de ascensor o escaleras 2 0.25
placas 3 0.35
4 0.45

Factor de suelo "S"


l de la estructura (sin sótanos) Tipo Descripcion
m hn= 22.9 m So Roca dura
m S1 Roca o suelos muy rígidos
S2 Suelos intermedios
S3 Suelos blandos

FACTOR DE SUELO
ZONA/SUELO So S1
Z4 0.8 1
Z3 0.8 1
Z2 0.8 1
i= (Pi*(hi)^k)/(∑(Pj*(hj)^k)) Z1 0.8 1
PERIODOS Tp Y TL
Tp (S) 0.3 0.4
TL (S) 3 2.5

DISTRIBUCIÓN DE FUERZAS YY k=
uerzas horizontales equivalentes
αi Fi= αi*V PISO PESO (Tn) peso acum ALTURA (m) alt acum
0.17 61.80 8 276.57 2953.55 2.75 22.9
0.20 74.79 7 380.36 2676.98 2.75 20.15
0.17 64.58 6 380.36 2296.61 2.75 17.4
0.15 54.38 5 380.36 1916.25 2.75 14.65
0.12 44.17 4 380.36 1535.88 2.75 11.9
0.09 33.96 3 380.36 1155.52 2.75 9.15
0.06 23.75 2 380.36 775.15 2.75 6.4
0.04 14.06 1 394.79 394.79 3.65 3.65
371.50 P= 2953.55
Categoria de las Edificaciones
Categoria U
A Edificaciones E 1.5
B Edificaciones 1.30
C Edificaciones 1.00
D Edificaciones *

TOR DE SUELO
S2 S3
1.05 1.1
1.15 1.2
1.2 1.4
1.6 2
IODOS Tp Y TL
0.6 1
2 1.6

1.00 ok
fuerzas horizontales equivalentes
(hi^k) Pi*hi αi Fi= αi*V
22.9 6333.48 0.17 61.80
20.15 7664.35 0.20 74.79
17.4 6618.35 0.17 64.58
14.65 5572.34 0.15 54.38
11.9 4526.34 0.12 44.17
9.15 3480.34 0.09 33.96
6.4 2434.33 0.06 23.75
3.65 1440.97 0.04 14.06
∑(Pj*(hj)^k) 38070.50 371.50
SISTEMAEspeciales
Pórticos ESTRUCTURAL
Resistentes a R: estructura regular
Momentos (SMF)
Pórticos Intermedios Resistentes a 8
Momentos (IMF) 7
Pórticos Ordinarios Resistentes a Mom 6
ACERO
Pórticos Especiales Concéntricamente A 8
PórticosOrdinarios Concéntricamente A 6
Pórticos Excéntricamente Arriostrados ( 8
Pórticos 8
CONCRETO Dual 7
ARMADO De muros estructurales 6
Muros de ductilidad limitada 4
ALBALIÑERÍA ARMADA O CONFINADA 3
MADERA (esfuerzos admisibles) 7

IRREGULARIDAD EN ALTURA
Ia presenta
PISO BLANDO 0.75
PISO DÉBIL 0.75
PISO BLANDO EXTREMO 0.5
PISO DÉBIL EXTREMO 0.5
MASA O PESO 0.9
GEOMÉTRICA VERTICAL 0.9
DISCONTINUIDAD EN LOS SISTEMAS RESISTENTES 0.8
DISCONTINUIDAD EXTREMA EN LOS SISTEMAS RESISTENTES 0.8

Ia= 1

IRREGULARIDAD EN PLANTA presenta


Ip= En eje X
IRREGULARIDAD TORSIONAL 0.75
IRREGULARIDAD TORSIONAL EXTREMA 0.6
ESQUINAS ENTRANTES 0.9 x
DISCONTINUIDAD DEL DIFRAGMA 0.85
SISTEMAS NO PARALELOS 0.9

Ip= 0.9
no existe irregularidad

presenta
En eje Y
x
tomaremos en cuenta a modo de modificar el R, en
un calculo real no se toma en cuenta por lo
x explicado (50% de deriv máxima)

0.75
SX SY
PISO FX FY ex ey MZ MZ
8 61.80 61.80 0.01 1.07 66.01 0.31
7 74.79 74.79 0.01 1.85 138.51 0.37
6 64.58 64.58 0.01 2.31 148.86 0.32
5 54.38 54.38 0.00 2.54 138.01 0.22
4 44.17 44.17 0.00 2.66 117.67 0.13
3 33.96 33.96 0.00 2.74 92.92 0.07
2 23.75 23.75 0.00 2.78 66.11 0.02
1 14.06 14.06 0.00 2.98 41.90 0.00