Você está na página 1de 1

boundary walls to match house & to be

maintanance free on neighbours side


various handrails available
and fixed by specialist
GUTTERS & DOWN PIPES TO BE UNOBSTRUCTIVE
Concrete Roof Tiles
CHROMADEK "KLIP-LOK 700" METAL ROOF ROOF COVERING @
CHROMADECK ROOFING SHEETS plaster & paint colour plaster & paint colour
finish floor level to client's choice to client's choice

concrete slab 1400mm C/C ON ROOF TRUSSES @ 1.2m C/C MAX ON


220mm Wall 114x38mm TIMBER WALL PLATE.
DESIGNED AND SUPPLIED BY SPECIALIST
CHIMNEY/COWL -1000mm
ABOVE HIGHEST PITCH
TO COMPLY WITH NBR CEMENT / EQUALLY APPROAVED
PART V V1-4 CAPPING & WATER PROOFING
satellite dish
-CONCRETE ROOF TO ENGINEER'S DETAIL WITH MINIMUM 50mm THICKNESS
220mm BRICK WALL PAINTED & PLASTERED -VERMICULITE SCREED GRADED TO 1:50 FALL TO 100m DIAMETER BILD IN DOWNPIPES
EXTERIOR WALL INTERIOR TO CLIENT'S COLOUR & CHOICE
TO BE EXTERIOR WALL TO BE MAINTENACE FREE
-WATERPROOFING BY SPECIALIST WITH A TEN YEAR GUARANTEE AS PER SPECIFICATION
CHROMADECK ROOFING SHEETS MAINTENACE FREE
440x440mm BRICK PIER
CHROMADECK ROOFING SHEETS
WOODEN -GROUND FLOOR SLAB=85mm THICK 20mpa CONCRETE PERFECTLY LEVEL AND AT
110mm BRICK WALL PAINTED & PLASTERED
440x440mm 440x440mm 440x440mm TO CLIENT'S COLOUR & CHOICE MINIMUM 150mm ABOVE GROUND LEVEL ON PROPERLY COMPACTED HARDCORE FILL
BRICK PIER BRICK PIER BRICK PIER
-25mm THICK SCREED AND FINISHES AS INDICATED
-SUSPENDED CONCRETE FLOOR SLABS TO ENGINEER'S DETAIL AND SPECIFICATIONS
-DPC UNDER ALL WALLS (EXCEPT FREE STANDING), FLOORS AND WINDOW SILLS
STEEL FRAME AND TO ALL VERTICAL CHANGES IN FLOOR LEVELS
600x230mm CONC FOOTING
-FLUSHINGS TO ALL PARAPETS AND CHANGES IN ROOF LEVELS
WOODEN

900
FROM CATCHPIT FITTED WITH GRATING AND SILT TRAP
-PLANTERS TO BE WATERPROOFED AND DRAINAGE INSTALLED
20mm vertical Planks fixed to be
steel frame gate hinges fixed 1549
to vertical supports built into
CHROMADECK ROOFING SHEETS CHROMADECK ROOFING SHEETS brick side wall -ALL FOUNDATIONS TO BE 25mpa CONCRETE , AT LEAST 200x700mm. MINIMUM
200mm UNDER GROUND TO ENGINEER'S DETAILS AND SPECIFICATIONS
-BOUNDARY WALLS' FOUNDATION MUST NOT ENCROACH ON BOUNDARY AND WALLS
ARE TO BE PLASTERED AND PAINTED ON THEW INNER WALL

VISIBLE OR AUDIBLE AND POSITIONED SO AS NOT TO NEGATIVELY AFFECT THE NEIGHBOURS


-PARAPET WALLS TO BE ATLEAST 300mmHIGH AND MAXIMUM 500mm WITH BRICKFORCE
IN EVERY COURSE
CHROMADECK ROOFING SHEETS HOUSE NUMBER AND LETTERING SIZE NOT

PUMPS AND FILTERS MUST BE ENCLOSED AND SCREENED SO AS TO BE NOT TO BE


I.E -ALL SCREEN WALLS TO BE AT LEAST 1800mm HIGH ABOVE GROUND LEVEL
LESS THAN 100mm AND NOT LARGER THAN 300mm
R.E 1:40 FALL CONNECTING TO MUNICIPAL SEWER
I.E
-LINTOLS TO BE SUPPORTED MINIMUM 150mm FOR OPENINGS UPTO 4800mm.BRICKFORCE
I.E R.E
1550 TO BE BUILT IN EVERY COURSE BELOW FLOOR LEVEL AND ABOVE WINDOW LEVEL, EVERY
THIRD COURSE BETWEEN BETWEEN IN CONTINOUS BANDS
-NO TEETHING OR BLOCK BONDING WILL BE ALLOWED UNDER ANY CIRCUMSTANCES
-ANY PARTITION TO BE RODENT PROOF

-STAIRS TO BE 750mm MIN WIDTH, TREADS 300mm , RISERS 170mm WITH 6mm MAX DEVIATION
-1000mm HIGH BALUSTRADES TO ALL STAIRS AND BALCONIES
a)The installation must be installed in compliance with SANS 100400,10087:1 I.E I.E
R.E
R.E -MAX 3000mm VERTICAL RISE PER FLIGHT , WINDERS WHERE SHOWN ,TO BE AT LEAST 250mm
b)One 9kg dry chemical power BC type fire extinguisher must be provided per installation.
WIDE, 450mm FROM THE NARROW END AND ANGLE BETWEEN THE RISERS TO BE CONSTANT
c)SABS approved symbolic
-MINIMUM HEADROOM TO BE 2100mm MEASURED FROM PICHLINE
1.no smoking
-GLASS BALUSTRADES (IF SHOWN ) TO BE SAFETY GLASS
2.no open fires
3.no unauthorized person
I.E
4.no littering at cage- signs must be provided
d.gas cage must be provided with locks for protection.
e.No cylinders are allowed to be stored outside an approved LPG cage
f.LPG signs to be displayed on front of the entrance of the premises -BATHROOM WINDOWS TO BE FROSTED GLASS
g.Should have adequate ventilation -ALL GLAZING ON DOORS TO BE SATETY GLASS

1:40 FALL CONNECTING TO MUNICIPAL SEWER


1:40 FALL CONNECTING TO MUNICIPAL SEWER
h.Atest certificate must be provided by the installer. -ALL GLAZED AREA LESS THAN 300MM ABOVE FFL TO BE COVERED WITH SATETY GLASS
I.E
i.All electrical cables must be a minimum of 150mm from any gas pipes,exepted electric
gulley
cables in appliances.
j.Gas piping shall not be used as an earth for circuits
k.All buried steel pipes must be corrosion protected in an approved manner.
l.Schedule 40 steel pipes and wrought steel fittings comply with SANS62-1 to be used or FIRST FLOOR PLAN (without open balconies)
copper tubing complying with SANS 460
m.All underground pipes must be placed a minimum of 50mm below top of the concrete.
n.Pipes that are to be embedded in a concrete must be tested before the completing of the
floor. SITE COVERAGE =42%
o.Pipes lines to be tested prior to completions of the installation
55x55mm cobble
FIRST FLOOR PLAN COVERS 69% OF THE GROUND FLOOR
STONE PAVING
p.however,kitchen must be adequately ventilated by Extrata Canopy. 1551
I.E I.E
q.A test certificate must be provided before any product is supplied.
r.Gas supply line must be tamper proof. R.E SEE SCHEDULE DRAWINGS OF DOORS AND WINDOWS
s.The user must be ensure that appliances,components of a systems be inspected at regular 55x55mm cobble R.E
intervals not exceeding 5 years.
STONE PAVING DO NOT SCALE THE DRAWINGS

t. all hoses used on outdoor installation must be replaced after 5 years.


u.Gas cage to be protected from moving vehicles by boallards.
plaster&paint
v.Gas piping in critical locations shall be SCH40 piping and welded to
not screwed
owner's choice
REV DATE DETAILS BY
GAS FIREPLACE
TO COMPLY WITH NBR
PART V V1-4 A XX/XX/XX XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX XX

plaster&paint to
owner's choice

ROOF NOTES
CHROMADEK "KLIP-LOK 700" METAL ROOF ROOF COVERING @

1400mm C/C ON ROOF TRUSSES @ 1.2m C/C MAX ON


114x38mm TIMBER WALL PLATE.
DESIGNED AND SUPPLIED BY SPECIALIST

*NB: ANY WOOD USED TO COMPLY WITH


WOOD SANS 10163
6.4mm GYPSUM CEILING BOARD
FIXED ON 38x38mm BRANDERING
SPACED AT 450x900mm C/C ON
PROPOSED NEW HOUSE FOR
52 x152mm CEILING JOIST/TIE BEAM KHUMALO OF ERF 31
THE HILLS
plaster&paint to

PRECAST CONCRETE LINTOL / BEAM


owner's choice

STORM WATER MUST FLOW WHERE THE


DIRECTION OF THE SLOPE FLOWS

SIDEWALK
170mm REINFORCED CONC SIDEWALK
SLAB TO ENGI'S DETAIL
precast
concrete
lintol SCALE DATE DESIGNED BY DRAWN BY CHECKED BY
220mm SOLID BRICK WALL PLASTERED NO boundary wall side AS SHOWN /2016 M.E.M M.O.N M.E.M
& PAINTED INTERIOR & EXTERIOR
of the street and
plaster&paint to
owner's choice
street to be DRAWING
COMPLETELY open TITLE
30mm THICK SCREED LAYED ON
85mm THICK CONC SURFACE BED ENGINEER'S
600x230mm
concrete footing
SIGNATURE
600x230mm CONC FOOTING 600x230mm
floor finish on 30mm screed on 85mm floor finish on 30mm screed on 85mm to engineer detail
600x230mm concrete concrete concrete footing floor finish on 30mm screed on 85mm
concrete ENGINEER'S
150mm WELL COMPACTED HARDCORE 600x230mm slab or on approved damp proof 600x230mm to engineer detail
600x230mm concrete footing concrete footing slab or on approved damp proof slab or on approved damp proof
UNDERNEATH THE SUFACE BED concrete footing to engineer detail to engineer detail
course
on 20mm sand blinding on 200mm course concrete footing course REF Number
to engineer detail on 20mm sand blinding on 200mm to engineer detail on 20mm sand blinding on 200mm
well well well
compacted hardcoreon shelldrite CLIENT'S
termiteprufe compacted hardcoreon shelldrite compacted hardcoreon shelldrite DATE
soil poisoner treated soil termiteprufe termiteprufe
soil poisoner treated soil soil poisoner treated soil SIGNATURE